Laserfiche WebLink
System Installation <br /> General Information Important: Notify the appropriate personnel(building occupants,fire <br /> department,monitoring facility,etc.)of the installation. <br /> The following paragraphs contain material which is applicable to all 4009 IDNet <br /> systems. Be sure that you are thoroughly familiar with this material before <br /> installing your 4009 IDNet. <br /> To help you with installation of this and other Simplex Fire Alarm equipment, <br /> the following publication is available for general reference: How to Wire a <br /> Building for a Fire Alarm System(FA2-91-001 or 575-892). <br /> Tools and Equipment The following tools and equipment are required to install the 4009 IDNet: <br /> Required . 1/4-inch flat-tip screwdriver,8-inches long <br /> • 1/8-inch flat-tip screwdriver,4-inches long <br /> • Volt-Ohmmeter <br /> • Diagonal cutting pliers <br /> • Wire strippers <br /> • Listed end-of-line resistors(ordered seperately) <br /> 10K resistor(733-804) <br /> • Field Wiring Diagram 842-068. <br /> General Notes 1. All wiring must be installed in accordance with local codes. <br /> 2. A minimum of 6 inches of free conductor is required at each electrical box <br /> to facilitate terminations. <br /> 3. A 12-inch service loop of cable is required for all continuous pulls through <br /> an electrical box. <br /> 4. All system wiring subject to physical damage must be mechanically <br /> protected based on the environment to which the cable is subjected. <br /> 5. A neatly wired system helps assure an accurate inspection of all connections <br /> and simplify troubleshooting. <br /> Continued on next page <br /> 11 <br /> Technical Manuals Online! - http://www.tech-man.com <br />