System Installation, Continued <br /> Mounting the 4009 IDNet, 5. Mount back box to wall. Back box must be level and plumb. For surface <br /> continued mounting use the teardrop and clearance holes located in the rear of the box <br /> and screw to wall. <br /> 6. Wire Non-Power-Limited wiring in the shaded areas only(see Figure 6), <br /> this includes AC input and battery connections. All other wiring is Power- <br /> Limited. Maintain at least 1/4-inch spacing between all Power-Limited and <br /> Non-Power-Limited wiring. <br /> 7. Connect the AC wiring harness and install the electronic card cage assembly <br /> to the 4009 IDNet cabinet. <br /> Wiring the 4009 IDNet When wiring the 4009 IDNet,refer to the 842-068 Field Wiring Diagram,the <br /> 4009 IDNet NAC Extender Connection Diagram(Figure 7),and the following <br /> system wiring requirements. <br /> • All wiring,except incoming power and ground connecting wires,must be <br /> free from grounds or shorts and have a resistance of one megohm,or higher, <br /> to EARTH. <br /> • All wires are to be copper conductors only,except fiber cables. All <br /> equipment must be installed in accordance with the manufacturer's <br /> recommendations and the specifications and standards of the Authority <br /> Having Jurisdiction(AHJ). The installation of all wiring,cable,and <br /> equipment must be in accordance with NFPA 70. <br /> • If shielded wire is used,the metallic continuity of the shield must be <br /> maintained and insulated throughout the entire length of the cable. The <br /> entire length of the cable must have a resistance of one megohm to earth. <br /> • Splicing is permitted in accordance with NFPA 70. All wiring must be <br /> terminated with UL listed devices(e.g.,wire nuts,pressure connectors). <br /> Wiring terminated with only electrical tape is not permitted. All splicing <br /> (free ends of conductors)must be covered with an insulation equivalent to <br /> that of the conductors. <br /> • An appropriate system ground must be provided for earth detection and <br /> lighting protection devices. This connection shall be made to an approved <br /> dedicated earth connection per NFPA 70. <br /> • When running wires to the 4009 IDNet,identify the wires appropriately: <br /> Only system wiring can be run in the same conduit which includes dedicated <br /> NAC wiring,IDNet wiring,24V AUX wiring,and the four NAC circuits(an <br /> additional four NAC circuits are available as a field-installed option). <br /> Input power and external battery power are Non-Power-limited and <br /> cannot be run with Power-Limited system wiring. <br /> Continued on next page <br /> 13 <br /> Technical Manuals Online! - http://www.tech-man.com <br />