Laserfiche WebLink
System Installation, Continued <br /> Mounting and Wiring Refer to the 842-068 Field Wiring Diagram for detailed information,and the <br /> Peripheral Devices procedure listed below when installing the 4009 IDNet peripheral devices. <br /> 1. Determine the mounting locations of the peripheral devices and install <br /> system wires from the mounting location of each peripheral device to the <br /> 4009 system board. All wiring to be minimum 18 AWG,supervised,and <br /> Power-Limited. <br /> 2. Install all peripheral devices and connect them to appropriate wires. (Refer <br /> to the installation instructions packed with the devices.) <br /> 3. For 2-wire Class B/Style Y and 4-wire Class A/Style Z devices,a 10K, 1/2 <br /> W(Brown/Black/Orange)End-of-Line Resistor(EOLR)is provided. Refer <br /> to Field Wiring Diagram 842-068. <br /> System Wiring Configurations The base 4009 IDNet NAC Extender has the following system wiring <br /> configurations: <br /> • 2-wire Class B/Style Y NAC(reverse polarity) <br /> • 4-wire Class A/Style Z NAC(reverse polarity) <br /> • Hardwired NAC Control Inputs from host FACP(Class A/Style Z& <br /> Class B/Style Y) <br /> • Addressable IDNet Slave Interface(Class B/Style 4 and Class A/Style 6) <br /> • Addressable IDNet Repeater Interface(Class B/Style 4 and Class A/Style 6) <br /> • Addressable IDNet Fiber Receiver/Transmitter Interface(Class B/Style 4 <br /> and Class A/Style 6) <br /> 15 <br /> Technical Manuals Online! - http://wvm.tech-man.com <br />