<br />ELECTRICAL NOTES:
<br />1. ALL WORK SHALL BE DONE IN A NEAT AND WORKMAN LIKE MANNER
<br />AND SHALL CONFORM TO THE 2005 NATIONAL ELECTRICAL CODE.
<br />2. ALL NEW WORK MAY BE INSPECTED BY THE OWNER.
<br />3. UPON COMPLETION OF THE WORK. THE ELECTRICAL CONTRACTOR SHALL
<br />DEMONSTRATE THAT THE INSTALLATIONS ARE COMPLETE AND IN
<br />PERFECT OPERATING ORDER WITH WIRING FREE FROM GROUNDS OR
<br />SHORTS AND WITH EQUIPMENT AND RACEWAYS PROPERLY GROUNDED.
<br />4. ALL MATERIAL SHALL BE NEW AND U.L. OR EQUALLY APPROVED.
<br />5. THE ELECTRICAL CONTRACTOR SHALL TEST ALL EQUIPMENT AND DEVICES
<br />INSTALLED TO THE SATISFACTION OF THE OWNER. RESPONSIBILITY AS TO
<br />THE OPERATION OF EQUIPMENT SHALL APPLY ONLY TO THOSE ITEMS
<br />FURNISHED BY THE ELECTRICAL CONTRACTOR, BUT THE CONTRACTOR
<br />ASSUMES ALL RESPONSIBILITY FOR ACCURATE WIRING AND FOR
<br />THE CORRECT CONTROL OF ALL DEVICES.
<br />6. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR AND TEST
<br />INSTRUMENTS REQUIRED FOR TESTING ELECTRICAL WORK.
<br />7. PROVIDE NAMEPLATES ON CONTROL DEVICES WHICH SHOW THE
<br />EQUIPMENT SERVED, VOLTAGE, PHASE AND CIRCUIT NUMBERS.
<br />8. CABLE TO BE THHN/THWN COPPER, 60OV, 1/C, #12 AWG (MINIMUM) FOR
<br />POWER, #14 AWG FOR 120V. CONTROL UNLESS OTHERWISE NOTED.
<br />9. UNDERGROUND CONDUIT MAY BE SCHEDULE 40 PVC. ALL FEEDERS TO
<br />PANELS AND EQUIPMENT SHALL BE IN ELECTRICAL METALLIC TUBING (E.M.T.).
<br />10. CONTRACTOR SHALL INSTALL EQUIPMENT GROUNDING SYSTEM
<br />CONNECTING NON -CURRENT CARRYING METAL PARTS OF WIRING
<br />SYSTEM TO THE GROUND.
<br />11. TAG ALL WIRES AT PANEL BOARDS AND JUNCTION BOXES WITH FIBER
<br />OR PLASTIC TAGS.
<br />12. ALL GROUNDING SHALL BE IN STRICT COMPLIANCE WITH THE LATEST
<br />OSHA AND NEC REQUIREMENTS. ALL CONDUIT CONNECTIONS
<br />MUST BE TIGHT TO MAINTAIN A GROUND PATH.
<br />13. ALL CIRCUITS FOR POWER AND LIGHTING SHALL HAVE GROUND
<br />CONDUCTOR FOR EQUIPMENT GROUNDING.
<br />14. ELECTRICAL SHALL SUBMIT SHOP DRAWINGS ON ALL
<br />FIXTURES AND EQUIPMENT.
<br />15. SUBMIT TO THE OWNER, CERTIFICATES OF FINAL INSPECTION AND
<br />APPROVAL IN DUPLICATE FROM APPROVED INSPECTION AGENCY
<br />UPON COMPLETION OF THE WORK.
<br />16. PRIOR TO THE FINAL ACCEPTANCE F THE WORK, SUBMIT A WRITTEN
<br />STATEMENT TO THE OWNER GUARANTEEING ALL EQUIPMENT AND
<br />SYSTEMS AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FOR
<br />ONE YEAR FROM DATE OF ACCEPTANCE. UPON WRITTEN NOTICE AND
<br />AT NO EXPENSE TO THE OWNER, PROMPTLY REPAIR AND/OR REPLACE
<br />ALL DEFECTIVE MATERIALS.
<br />17. CONTRACT DRAWINGS ARE ESSENTIALLY SCHEMATIC. CONTRACTOR
<br />SHALL VERIFY LOCATION AND DETAIL INFORMATION PRIOR TO
<br />ROUGHING IN.
<br />18. VERIFY ALL CEILING CONSTRUCTION PRIOR TO ROUGHING IN.
<br />19. CONTRACTOR SHALL VERIFY EXACT ELECTRICAL CHARACTERISTICS
<br />OF ALL EQUIPMENT TO BE WIRED.
<br />20. ON LIGHTING AND RECEPTACLE CIRCUITS, CONTRACTOR MAY USE
<br />METAL CLAD CABLE TYPE 'MC' WHERE ALLOWED BY APPLICABLE
<br />CODES LIVING UNIT WIRING FROM ITS LOCAL PANEL MAY BE TYPE 'NM'
<br />SUBJECT TO LOCAL AUTHORITY APPROVAL.
<br />21. PROVIDE TELEPHONE JACK AND CONDUIT TO ABOVE CEILING FOR
<br />TELEPHONE ROUGH -IN. MINIMUM CONDUIT SIZE TO BE 3/4".
<br />22. CONTRACTOR SHALL OBSERVE OSHA SAFETY STANDARDS AND
<br />MAINTAIN AREA CLEAN DAILY.
<br />23. ALL WALL AND ROOF PENETRATIONS BY THIS CONTRACTOR.
<br />OPENINGS SHALL BE FLASHED, COUNTER FLASHED AND SEALED
<br />WEATHER TIGHT AND WATER PROOF.
<br />24. PROVIDE A COMPLETE AND OPERATING FIRE ALARM AND FIRE
<br />DETECTION SYSTEM IN ACCORDANCE WITH THE LATEST BOCA
<br />AND/OR NFPA 101 REQUIREMENTS FOR THE SPECIFIC TYPE OF
<br />BUILDING AND USE.
<br />25. PROVIDE ALL REQUIRED MOTOR STARTING, DISCONNECTING AND
<br />CONTROL EQUIPMENT FOR EACH ITEM OF MOTOR OPERATED
<br />MECHANICAL SYSTEM EQUIPMENT COMPLETE WITH NECESSARY
<br />SHORT CIRCUIT AND OVERLOAD PROTECTION. THE CONTRACTOR
<br />SHALL COORDINATE WITH THE MECHANICAL CONTRACTORS FOR
<br />SCOPE OF WORK INVOLVED.
<br />26. PROVIDE ALL NECESSARY ELECTRICAL WORK FOR EACH ITEM
<br />OF ELECTRICALLY OPERATED EQUIPMENT FURNISHED BY THE
<br />OWNER OR OTHER CONTRACTS. VERIFY ELECTRICAL
<br />CHARACTERISTICS PRIOR TO INSTALLATION.
<br />27. ALL SAFETY AND DISCONNECT SWITCHES SHALL BE HEAVY DUTY
<br />CONSTRUCTION AND OF VOLTAGE AND AMPERE RATING TO SUIT
<br />EACH FUNCTION.
<br />28. ALL PANELBOARDS TO BE CIRCUIT BREAKER TYPE OF VOLTAGE
<br />CHARACTERISTICS AND AMPACITY RATING TO SUIT EACH
<br />APPLICATION. MINIMUM SERIES SHORT CIRCUIT RATING TO BE
<br />10,000 AMPERES, RMS, U.L. SYMMETRICAL. ALL BUS BARS ARE
<br />TO BE COPPER. ALL CIRCUIT BREAKERS TO BE BOLT -ON.
<br />29. FIRE ALARM SYSTEM DESIGN TO BE BY AN APPROVED AND CERTIFIED
<br />SYSTEM VENDOR OR CONTRACTOR AND INSTALLED IN ACCORDANCE
<br />WITH N.F.P.A. REGULATIONS AND LOCAL FIRE MARSHALL'S OFFICE.
<br />30. CONTRACTOR TO SUBMIT SYSTEM DESIGN TO FIRE MARSHALL'S OFFICE
<br />FOR APPROVAL UTILIZING THE SYSTEM EQUIPMENT SHOWN AS A GUIDE
<br />ONLY. ALL MODIFICATIONS AND/OR ADDITIONS TO THE SYSTEM
<br />REQUIRED BY THE FIRE MARSHALL'S OFFICE SHALL BE A PART OF THIS
<br />CONTRACT.
<br />31. LOCATE ALL SYSTEM DETECTORS TO SUIT LIGHTING FIXTURES,
<br />MECHANICAL SYSTEMS EQUIPMENT AND AIR DIFFUSERS.
<br />32. ALL SYSTEM WIRING SHALL BE TYPE APPROVED FOR APPLICATION.
<br />ALL SYSTEM WIRING NOT CONCEALED IN BUILDING CONSTRUCTION
<br />SHALL BE INSTALLED IN SPECIFIED ELECTRICAL RACEWAYS.
<br />33. SEE FP DRAWINGS FOR EXTENT OF WORK.
<br />34. PROVIDE FIRE STOPPING AT ALL FIRE WALL PENETRATIONS. SEE
<br />ARCHITECTURAL DRAWINGS FOR FIRE WALL LOCATIONS.
<br />35. ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE LOCAL UTILITY
<br />COMPANY FOR THE TYPE OF ELECTRIC SERVICE TO SERVE THIS PROJECT
<br />INCLUDING THE LOCATION OF ENERGY RECORDING EQUIPMENT. ALL
<br />CHARGES BY THE UTILITY COMPANY TO THE OWNER SHALL BE INCLUDED
<br />INTO THE ELECTRICAL CONTRACT. ANY AND ALL DISCREPANCIES BETWEEN
<br />THE CONTRACT DESIGN AND THE UTILITY COMPANY'S REQUIREMENTS SHALL
<br />BE REPORTED TO THE ARCHITECT FOR CLARIFICATION AND NECESSARY
<br />ADDENDUMS DURING THE PROJECT BIDDING PERIOD.
<br />36. ALL APPURTENANCES REQUIRED FOR A COMPLETE AND OPERATING
<br />SYSTEM ARE NOT SHOWN. CONTRACTOR TO PROVIDE ALL
<br />APPURTENANCES NECESSARY FOR A COMPLETE OPERATING SYSTEM.
<br />CONTRACTOR TO CONTACT ARCHITECT/ENGINEER IN WRITING, PRIOR
<br />TO BIDDING, FOR CLARIFICATION DISCREPANCIES OR OMISSIONS IN
<br />DESIGN DOCUMENTS.
<br />ELECTRICAL AB13REVIATIONS:
<br />A
<br />AMP
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />AFG
<br />ABOVE FINISHED GRADE
<br />A/C
<br />AIR CONDITIONING
<br />AC
<br />ALTERNATING CURRENT
<br />C/B(CB)
<br />CIRCUIT BLEAKER
<br />C
<br />CONDUIT
<br />CU
<br />COPPER
<br />EC
<br />ELECTRICAL CONTRACTOR
<br />EMT
<br />ELECTRICAL METALLIC TUBING
<br />GC
<br />GENERAL CONTRACTOR
<br />GFI
<br />GROUND FAULT INTERRUPTER
<br />GND
<br />GROUND
<br />HOA
<br />HANDS OFF AUTO
<br />HP
<br />HORSEPOWER
<br />JB
<br />JUNCTION BOX
<br />KW
<br />KILOWATT
<br />KV
<br />KILOVOLT
<br />KV-A
<br />KILOVOLT -AMPERE
<br />MCC
<br />MOTOR CONTROL CENTER
<br />N
<br />NEUTRAL
<br />NIC
<br />NOT IN CONTRACT
<br />NTS
<br />NOT TO SCALE
<br />PB
<br />PUSH BUTTON
<br />PNL
<br />PANEL
<br />RCPT
<br />RECEPTACLE
<br />UON
<br />UNLESS OTHERWISE NOTED
<br />V
<br />VOLT
<br />WP
<br />WEATHERPROOF
<br />XFMR
<br />TRANSFORMER
<br />2
<br />3
<br />FIRE ALARM AND SMOKE DETECTION SYSTEM NOTES:
<br />1. PROVIDE APPROVED EARTH GROUND AT THE FIRE ALARM CONTROL PANEL.
<br />CHASSIS OR CONDUIT GROUND IS NOT ACCEPTABLE.
<br />2. ALL INSTALLATIONS MUST BE IN ACCORDANCE WITH ARTICLE 760 OF THE
<br />NATIONAL ELECTRICAL CODE. FIRE ALARM CABLE MUST BE MARKED TYPE
<br />FPL (NON -PLENUM) OR FPLP (PLENUM) AS DETERMINED BY TYPE(S) OF
<br />CEILING IN THE BUILDING.
<br />3. AUXILIARY ALARM RELAY MUST BE WITHIN 3 FEET OF DEVICE IF IT IS TO
<br />CONTROL AS PER NFPA 72, CHAPTER 3.9.2.1 LATEST EDITION.
<br />4. NO A.C. CARRYING CONDUCTORS ARE ALLOWED TO SHARE RACEWAYS WITH
<br />FIRE ALARM SYSTEM WIRING.
<br />S. ALL SMOKE DETECTORS SHALL BE LOCATED 3 OR MORE FEET FROM ANY
<br />SUPPLY OR RETURN AIR REGISTER. DETECTORS SHALL BE AT LEAST
<br />12 INCHES FROM ANY PART OF ANY LIGHTING FIXTURE.
<br />6. 110 VAC CIRCUIT FEEDING THE FIRE ALARM CONTROL PANEL(S) SHALL
<br />BE DEDICATED EQUIPPED WITH BREAKER LOCK IN ACCORDANCE WITH
<br />NFPA 72 LATEST EDITION.
<br />7. THIS SYSTEM SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH NFPA 72.
<br />S. MOUNTING HEIGHTS ARE AS FOLLOWS:
<br />• PULL STATION: 48" AFF TO HANDLE
<br />• HORN STROBE: V-8" AFF OR 6" BELOW CEILING
<br />WHICHEVER IS LOWER
<br />- STROBE: 6'-8" AFF OR 6" BELOW CEILING
<br />WHICHEVER IS LOWER
<br />9. DUST COVERS FURNISHED WITH DETECTORS MUST BE INSTALLED WITH EVERY
<br />DETECTOR UNTIL FINAL CHECKOUT.
<br />10. ANY CABLE OTHER THAN THAT SPECIFIED ABOVE SHALL BE SUBMITTED TO
<br />AND APPROVED IN WRITING PRIOR TO PURCHASE.
<br />11. SMOKE AND HEAT DETECTORS SHALL BE MOUNTED ON THE CEILING, UNLESS
<br />NOTED OTHERWISE. IT IS NOT PERMISSIBLE TO INSTALL DETECTORS ON THE
<br />BOTTOM OF OPEN WEB JOISTS, OR ANY BEAM EXCEEDING 12" IN DEPTH
<br />FROM CEILING. SMOKE/NEAT DETECTORS CAN BE MOUNTED ON THE BOTTOM
<br />OF A SOLID BEAM IF IT MEASURES 12" OR LESS IN DEPTH, PROVIDED THE
<br />CEILING IS LESS THAN 10 FEET AFF.
<br />12. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR METERING ALL WIRES
<br />TO ENSURE THAT THEY ARE FREE AND CLEAR OF GROUNDS AND THE PROPER
<br />END -OF -LINE RESISTANCE IS READ. IF GROUNDS AND SHORTS ARE FOUND
<br />ON THE SYSTEM WIRING ALL WIRING SHALL BE CORRECTED.
<br />13. PROVIDE FIRE STOPPING AT ALL FIRE WALL PENETRATIONS. SEE
<br />ARCHITECTURAL DRAWINGS FOR FIRE WALL LOCATIONS.
<br />14. ALL APPURTENANCES REQUIRED FOR A COMPLETE AND OPERATING SYSTEM
<br />ARE NOT SHOWN. CONTRACTOR TO PROVIDE ALL APPURTENANCES
<br />NECESSARY FOR A COMPLETE OPERATING SYSTEM. CONTRACTOR TO
<br />CONTACT ARCHITECT/ENGINEER IN WRITING, PRIOR TO BIDDING, FOR
<br />CLARIFICATION OF DISCREPANCIES OR OMISSIONS IN DESIGN DOCUMENTS.
<br />ELECTRICAL SYMBOLS:
<br />2'x4' FLUORESCENT FIXTURE
<br />0 Vx4' FLUORESCENT FIXTURE
<br />2'x2' FLUORESCENT FIXTURE
<br />EXPOSED STRIP LIGHT
<br />® EXIT LIGHT
<br />EXIT LIGHT WITH DIRECTIONAL ARROW (1 SIDE)
<br />1e, EXIT LIGHT WITH DIRECTIONAL ARROW (2 SIDE)
<br />FA LIGHTING FIXTURE ON EMERGENCY CIRCUIT
<br />NL
<br />EMERGENCY LIGHT/BATTERY
<br />0
<br />FLUORESCENT WALL SLOT FIXTURE
<br />0
<br />RECESSED LIGHTING FIXTURE
<br />1_0
<br />WALL -MOUNTED FIXTURE
<br />S SWITCH
<br />S3 SWITCH - 3 WAY
<br />S4 SWITCH - 4 WAY
<br />SD SWITCH - DIMMER
<br />SA SINGLE POLE SWITCH CONTROLLING LIGHTING FIXTURE
<br />SM MANUAL MOTOR STARTER
<br />SO OCCUPANCY SENSOR - WALL MOUNTED
<br />ST MANUAL MOTOR STARTER SWITCH
<br />OS OCCUPANCY SENSOR - CEILING MOUNTED
<br />RECEPTACLE - DUPLEX
<br />0
<br />ELECTRICAL DEVICE MOUNTING HEIGHTS:
<br />9" BELOW CEILING- CLOCKS, PROGRAM LIGHTS, FIRE ALARM GONGS
<br />1 & - BATTERY LIGHT UNITS & REMOTE WALL MOUNTED LIGHT
<br />HEADS OR V-0" BELOW CEILING.
<br />8%6" - PENDANT HUNG INCANDESCENT & STRIP LIGHT FIXTURES,
<br />OR SEE ARCH DWGS.
<br />6" BELOW CEILING- TOP OF BACK MOUNTED WALL EXIT FIXTURES (NOT ABOVE DO
<br />g ABOVE DOOR - WARNING & SIGNALING FIXTURES/SIGNS
<br />V-8" - ILLUMINATED FIRE SIGNALS
<br />V-6" - TOP OF FLUSH & SURFACE MOUNTED ELECTRICAL LIGHTING 8
<br />PANELBOARDS & TELEPHONE CABINETS
<br />V-O" - TOP OF HIGHEST ELECTRICAL SAFETY DISCONNECT SWITCH, N
<br />STARTERS,CONTACTORS
<br />- WALL MOUNTED ELECTRICAL DEVICE LIGHTING SWITCHES, MA
<br />4%0" MOTOR STARTERS, THERMOSTATS & FIRE ALARM PULL STATII
<br />- WALL MOUNTED WIRE MOLD
<br />- ELECTRICAL RECEPTACLES WITHIN MECHANICAL SPACES, ELE
<br />& ELEVATOR ROOMS
<br />V-6" - ELECTRICAL RECEPTACLES
<br />- TELEPHONE OUTLETS (NON-PUBLIC)
<br />- VOICE DATA OUTLETS
<br />NOTES:
<br />1. MOUNTING HEIGHTS TO CENTER OF OUTLETS UNLESS NOTED
<br />2. + INDICATES SPECIAL MOUNTING HEIGHTS
<br />3. AC INDICATES ABOVE COUNTER
<br />="FI
<br />RECEPTACLE - DUPLEX - GROUND FAULT INTERRUPTER
<br />=QNP
<br />RECEPTACLE - DUPLEX - WEATHERPROOF
<br />RECEPTACLE - DUPLEX - SWITCHED ON ONE SIDE
<br />SPECIAL RECEPTACLE -RATING AS NOTED
<br />®
<br />FLOOR MOUNTED DUPLEX RECEPTACLE
<br />�J
<br />JUNCTION BOX
<br />TELEPHONE OUTLET -WALL MOUNTED
<br />q
<br />HOUSE TELEPHONE/DATA
<br />TELEPHONE VERIZON
<br />-
<br />PANEL BOARD
<br />MOTOR
<br />UNFUSED SAFETY SWITCH
<br />❑F FIRE ALARM PULL STATION
<br />FIRE ALARM AUDIOVISUAL ALARM
<br />-6 0- CIRCUIT BREAKER
<br />TR TRANSFORMER
<br />11. GROUND
<br />GFCI GROUND FAULT CIRCUIT INTERRUPTER
<br />NL NIGHT LIGHT
<br />WP WEATHER PROOF
<br />2IL 26 HOME RUN TO PANEL & CIRCUIT NOTED
<br />�+ CABLE TELEVISION OUTLET
<br />® CARD READER
<br />WIRE SIZE CHART
<br />(FOR 3% VOLTAGE DROP)
<br />BREAKER SIZE
<br />0'-50,
<br />51'-100,
<br />101'-150'
<br />151'-200'
<br />201'-250'
<br />120V
<br />20A
<br />12
<br />10
<br />8
<br />6
<br />4
<br />30A
<br />10
<br />8
<br />6
<br />4
<br />3
<br />40A
<br />8
<br />6
<br />4
<br />3
<br />2
<br />50A
<br />6
<br />4
<br />3
<br />2
<br />1
<br />NOTE:
<br />WIRE SIZES FOR CIRCUITS SHALL BE #12 UNLESS CIRCUIT WIRE
<br />LENGTH EXCEEDS 50' (FOR 20A). OTHER SIZES SHALL BE AS SHOWN
<br />BY THE CHART ABOVE.
<br />5
<br />A
<br />SCIBMI`f U11) ,A1N(S) HAVE BEEN R VIEWET�
<br />8* 20ftyt+ L nARS S OFFICE
<br />i
<br />be anted this revie of Phn aftftdis a
<br />Devi -to assist theycontra in cow4arm ro
<br />*12fic-aWlim, safety codes. This, rem is not inwrded
<br />te, k aiaat apprmval of the submit plans.. it is,
<br />WdT8ctpr*sek responsibility to ensure that the plans are in
<br />WnPlefe;Lopliance with att applicabl&NFPA codes ffid
<br />I al or iinarlces, in tt event that fuirther examination,or
<br />site, Inspectw-rt reveals areas of norl-compliance, if shalt be
<br />the cpntrecWs sple responsibility. at theicsole expense 1
<br />bn%, those areas. it) compliance, The. Cityassumes no)
<br />Wwp sibillty .for the. contractor's failure. to, be-ia compii
<br />04,4111 applicable NFPA_Godes,and local:ordbarx=.
<br />VA
<br />A4*WWUWWLYW1THALL
<br />A00 MM. FLORIDA BUILDING
<br />XPWAL��,EGMC CODE AND
<br />0 4MYROW ORDINANCES
<br />REVIEW DATE
<br />P17'y
<br />LAM
<br />OF ZE H
<br />EN
<br />U
<br />N
<br />z
<br />O
<br />F-'
<br />O
<br />�
<br />E~
<br />Con
<br />U
<br />a
<br />Cn
<br />O
<br />a
<br />U
<br />o
<br />O
<br />Q
<br />0)
<br />�
<br />Gn
<br />Un
<br />CA
<br />6
<br />N
<br />c
<br />o
<br />0
<br />4-1
<br />a
<br />ROBERT MUNROE PE #33868
<br />J
<br />Q
<br />W
<br />rn
<br />project no.
<br />drawn by:
<br />2006-068.00
<br />date:
<br />checked by:
<br />NOV , 2006
<br />scale:
<br />approved by:
<br />sheet no.
<br />El
<br />A mO
<br />
|