2 <br />3 <br />5 <br />I� <br />10'-St. TRIAD ELEC. SERVICE GROUNDING <br />SYSTEM - BUILDING EXTERIOR <br />3/4"0 x 10'.0" DRIVEN GND ROD - SET TOP -6" 12" ID x 24" LONG VITRIFIED CLAY SEWER TILE <br />BELOW FINISHED GRADE WITH REMOVABLE -- -- WITH REMOVABLE CAST CONCRETE COVER WITH <br />CLAMPS FOR TESTING RECESSED LIFT HANDLE - (TYP 3) <br />I <br />NOTE: <br />1. AVAILABLE FAULT CURRENT AT MAIN DISTRIBUTION SWITCHBOARD <br />FROM POWER Co's OUTDOOR 30,750 KA, DISTRIBUTION <br />TRANSFORMER WILL BE 47.85 KA - SWITCHBOARD TO BE DESIGNED <br />TO WITHSTAND 50.0 KAIC AT 240 VOLT, UL, RMS, SYM <br />UNDERGROUNS #4/0 GND CONDUCTOT (TYP) <br />�I <br />GROUND TO BLDG MAIN STEEL STRUCTURAL COLUMN <br />AT 1 st FLOOR LEVEL - USE CADWELD CONNECTION <br />INDOOR FLOOR MOUNTED ON CONCRETE PAD ELEC. SERVICE <br />1 ENTRANCE & DISTRIBUTION SWITCHBOARD MDPA <br />BLDG COLD WATER SERVICEGROUND (1st FLR ELEC. DISTRIB RM -Left Side) <br />(S ) ISCA - 50 KA AT 240 VOLT, UL, RMS, SYM <br />PROVIDE BONDING JUMPER(S) AROUND <br />EACH WATER METER 3/4" R.G. CONDUIT _ 114" x 2" COPPER GROUND BUS BAR ON WALL BEHIND <br />SWITCHBOARD ON STAND-OFF BRACKETS <br />#4/0 GND CONDUCTOR MAIN MAIN <br />CABLE BREAKER BREAKER <br />1 IFENTRANCE SECTION SECTION <br />SECTION SERVICE #1 SERVIDE #2 <br />(3) 4" EMPTY PVC CONDUITS, CAP UNDERGROUND AS DIRECTED <br />r BY POWER Co. FOR POWER Co's INCOMING PRIMARY SERVICE <br />I CONDUCTORS Ik <br />U <br />PRIMARY SERVICE LA's _�" <br />BY POWER Co. <br />IV" <br />�I <br />LINK <br />FEEDER CIRCUIT BREAKERS #6 thru #17 - EA. 125/2P <br />(TYP (17) BREAKERS) <br />2000 AMP MAIN BUSES <br />2000 AMP NEUT BUS <br />r 225 AMP EQ GND BAR <br />FEEDER CIRCUIT BREAKERS #18 thru #24 - EA. 125/2P <br />(TYP (7) BREAKERS) <br />SWITCHBOARD CABLE ENTRANCE TERMINALS <br />i 2 3 4 5 6 7 8 9 10 11 12 13 14 20 21 22 23 24 <br />4) <br />100/3P 600/3P 125/3P STO 1000/3P 401 125) 125) 125) 125) 125/2P <br />125/2P' 125/2P <br />125/2P <br />125/2P) 12512P) 125/2P) 125/2P) 125/2P J 125/2P� <br />POWER Co's PRIMARY LOAD BREAK ) ) ) ) / �� / // / �� / <br />ELBOWS WITH GND SHIELDS O <br />SWITCHBOARD 1 SPA <br />CABLE ENTRANCE <br />CABLE SECTION 1 a <br />208Y/120V, 30, 4W <br />3/4"0 x 10'-0" COPPERWELD 4" SWITCHBOARD CONCRETE PAD g <br />DRIVEN GND ROD BY ELEC. CONTR. ANCHOR INTO 1 st FLR CONC. SLAB <br />d <br />POWER Co's OUTDOOR PAD MOUNTED <br />DISTRIBUTION TRANSFORMER EQUIPMENT _______ �- 750 KVA, 30 DISTRIB TRANSFORMER <br />GROUNDING BY POWER Co. i AVAILABLE FAULT CURRENT 47.948 AMPS <br />POWER Cos METERING C.T. s INSIDE TRANSFORMER <br />LOW VOLTAGE COMPT. - ARRANGE CABLES AS ------ 1 <br />DIRECTED BY POWER Co. i i WP HOUSING BY ELEC. CONTR. <br />TERMINATE PRIMARY & SECONDARY SERVICE <br />CONDUITS AT DISTRIBUTION TRANSFORMER J <br />AS DIRECTED BY POWER Co. (TYP) <br />(9) ACTIVE CONDUITS <br />WALL MOUNTED BREAK GLASS <br />STATION OUTSIDE ELECTRICAL — <br />DISTRIBUTION ROOM <br />GENERATOR NEUTRAL EXTENDED TO GND <br />BUS ON WALL INSIDE ELEC. DISTRIB. RM. <br />OUTDOOR CONCRETE PAD MOUNTED _ <br />208Y/120V, 30, 4W, DIESEL FUEL <br />OPERATED, RADIATOR WATER COOLED, <br />WEATHERPROOF CONSTRUCTION, 750 GAL. <br />SUB -BASE OIL TANK, START BATTERY WITH <br />MOUNTING CABINET, ENGINE ELECTRIC <br />1 i 1 FOR POWER Co. METERS) <br />1 GALVANIZED STEEL 1 <br />s >�~ EQUIPMENT FRAME <br />k9 <br />2=.. n FINISH GRADE <br />t4 <br />12 S x 48I <br />DEEP UNDERGROUND w� 6 <br />CONCRETE ENCASEMENT FOR AFT <br />p <br />METER GALVANIZED STEEL FRAME <br />" ;, "� " <br />(9) ACTIVE CONDUITS <br />UNDERGROUND 1.1/2" R.G. METER CONDUIT <br />FOR POWER Co's METER WIRING <br />(9) 4" PVC EA. 4.1/C, 600 KCMIL (AL) THWN <br />TERMINATE CONDUITS INSIDE <br />SERVICE ENTRANCE CABLE COMPT <br />SWITCHBOARD MAIN ELECTRONIC CIRCUIT BREAKER <br />SECTION, EACH BREAKER TO BE FULL FUNCTION WITH <br />GENERATOR LOAD CIRCUIT BREAKER SETTINGS LONGTIME, SHORT TIME, INSTANT & <br />AT UNIT CONTROL PANEL GROUND FAULT TRIP <br />_ GENERATOR ENGINE <br />START-UP CONTACT MAIN CIRCUIT BREAKER FULL FUNCTION TRIP SYSTEM <br />MONITORING & OPERATIONS PANEL WITH FACTORY <br />WIRING TO EACH BREAKER UNIT <br />RADIATOR WATER HEATER, ENGINE ELECTRIC GENERATOR CAPACITY <br />CRANK GAS HEATER, REINFORCED CONCRETE 110 KW / 137.5 KVA - PRIME <br />PAD WITH CONCRETE FOOTER, GENERATOR 600/3P 125 KW / 156.25 KVA STANDBY <br />VIBRATION ISOLATORS, ETC. STO GENERATOR SYSTEM OPERATION <br />MONITOR / CONTROL PANEL INSIDE <br />FIN. GRADE I� GENERATOR <br />77 <br />3/4'0 x 10'-O" LONG GND ROD WITH #1/0 <br />GND CABLE CONNECTION TO <br />GENERATOR FRAME <br />L 1 "C, 3 #10 <br />— 1"C, WITH GENERATOR SET SYSTEM MONITOR WIRING <br />(2) WC, EA. 4.1/C, 350 KCMIL + #1/0 GND <br />1600/3P <br />UNDERGROUND TO SUB -DISTRIBUTION SWITCHBOARD MDPB <br />(5) 4" PVC CONDUITS EA. 4.1/C, 600 KCMIL + #4/0 GND + (1) 4" <br />EMPTY SPARE CONDUIT RACK CONDUITS UNDERGROUND <br />STO <br />2000/3P <br />TVSS UNIT <br />208/12OV, <br />30, 4W <br />MOUNTED INSIDE <br />SWITCHBOARD <br />COMPARTMENT <br />SWITCHBOARD <br />SERVICE <br />PROTECTION <br />P <br />z' <br />S <br />Gy <br />z <br />t7 <br />0 <br />WALL MOUNTED BREAK GLASS % <br />STATION OUTSIDE ELECTRICAL + <br />J <br />DISTRIBUTION ROOM <br />O <br />ENGINE START-UP 4, <br />CONTACT <br />(E) <br />R1 <br />r <br />Re <br />1.1 /2"C, 3 #1 + #6 <br />(TYP (2) FEEDERS) <br />1.1 /4"C, 3 #2 + #6 GND <br />TO FIRE ALARM SYSTEM CONTROL <br />PANEL - 3/4"C, WITH SYSTEM WIRING <br />FOR ELEVATOR RECALL & SHUTDOWN <br />2"C, 3 #1/0 + #6 GND, (TYP (15) FEEDERS) <br />(17) 10, 3W + EQ GND FEEDERS SERVICE APT PANELS Ist, 2nd & 3rd FLOORS <br />SEE ELECTRICAL FLOOR PLANS, TYP PANEL FEEDER RISER DIAGRAMS <br />EA. 4.1/C. 400 KCMIL + #2/0 GND <br />FUSED SAF SWT <br />(ELEV. MACH RM) <br />211C, 3 #1/0 + #6 GND, (TYP (17) FEEDERS) <br />(7) 10, 3W + EQ GND FEEDERS SERVICE APT <br />PANELS 2nd & 3rd FLOORS <br />SEE ELECTRICAL FLOOR PANS, TYP PANEL <br />FEEDER RISER DIAGRAMS <br />+3 S <br />HOUSE SERVICE DISTRIBUTION PANEL HSPA <br />208Y120V, 30, 4W + EQ GND BUS <br />(LEFT SIDE ELECTRIC DISTRIBUTION RM - 1 st FLR) <br />ISCA - 50 KA AT 240 VAC, UL, RMS, SYM <br />IDCA - 50 KA AT 240 VOLT, UL, EMS, SYM 1 <br />(N) 1 20OA/3P <br />1 a <br />a <br />600 AMP, 3P + SN EMERG SYS. AUTO-TRANSF 125 AMP <br />SWT WITH OVERLAP NEUTRAL NEMA t ENCLOSURE, TDDE <br />(N/E) EXERCISE CLOCK, OPERATION & CONTROL RELAYS, <br />5 SYSTEM METERS '.`""" � 1 2 3 4 1.15 6 7 8 11� <br />1-1 /4"C, 3 #2 + \\ \\ <br />AUTO-TRANSF SWT #6 GND 225/3P) 100/3P) 150/3 P 100/3P) 100/3P) 400/3P) 100/3PJ 600/3P) 100/3P) <br />MONITORING PANEL <br />ELEV. CONTROLLER 4 <br />ELEV. MACH RM) R <br />) <br />Z <br />a <br />p <br />Z <br />Z <br />z <br />Z <br />Z <br />#6 GND <br />a <br />Z <br />p <br />Z <br />Z <br />cs <br />TO EMERGENCY POWER SYSTEM REMOTE <br />4 <br />a <br />W <br />ao <br />aD <br />v <br />ao <br />v <br />ao <br />MONITORING PANEL IN 1 st FLOOR RECEPTION + <br />+ <br />+ <br />+ <br />v g <br />+ <br />+ <br />AREA (2) 1"C, WITH SYSTEM WIRING o <br />ELEV. #1 <br />+ <br />O <br />N + <br />r <br />+ <br />a J <br />C <br />v <br />N O <br />30 HP, <br />92 <br />q <br />208V, 30 <br />tj <br />v <br />v <br />v <br />v <br />N <br />r <br />T <br />:■: <br />T <br />� <br />q <br />� <br />N� <br />r <br />N <br />r <br />N <br />r <br />r <br />r <br />r <br />W <br />EMERGENCY DISTRIBUTION PANEL LSMP <br />208Y/12OV, 30, 4W + EQ GND BUS <br />ti <br />(LEFT SIDE ELECTRIC DISTRIBUTION RM - 1st FLR) <br />FISCA <br />h <br />- 50 KA AT 240 VOLT, UL, RMS, SYM <br />600/3P J MAIN <br />BRKR <br />150 AMP EQ GND BUS <br />600 AMP NEUT BUS <br />600 AMP MAIN BUSES <br />i <br />2 <br />1.3 <br />4 1,15 6 <br />GENERAL NOTES: <br />1. ALL UNDERGROUND ELECTRIC RACEWAYS UNDER BUILDING <br />1 400/3P) <br />150/3P) <br />)// <br />150/3P J <br />\ I <br />100/3P) 100/3P) 100/3PJ <br />/ <br />O O <br />CONSTRUCTION TO BE SCHEDULE 40 PVC WITH SOLVENT <br />SPACE SPACE <br />WELDED JOINTS AND FITTINGS <br />Z <br />Z <br />+ <br />c� <br />Jp <br />W <br />W <br />O Q <br />O 01 <br />+ <br />O <br />+ <br />O <br />to <br />f <br />SEE LSMP PANEL SCHEDULE ON <br />DRAWING E1.3.0 FOR ADDITIONAL <br />S/L ELECTRIC DISTRIBUTION DIAGRAM <br />(Left <br />Side) <br />le <br />!V <br />tV <br />CIRCUITS <br />SCALE: NONE <br />NOTE: <br />OUTDOOR ENGINE GENERATOR SET AND AUTOMATIC TRANSFER SWITCH. <br />1. UNIT DESIGN IS BASED ON KATOLIGHT - MODEL #D125FPA4, 120/208V, 30, 4W, 60 Hz. <br />125 KW /156.25 KVA STANDBY RATINGS. 110 KW /137.5 KVA PRIME RATING. CONTROL PANEL, <br />ENGINE, GENERATOR, VOLTAGE REGULATOR, STANDARD EQUIPMENT - MODEL #50 SERIES <br />CONTROL PANEL, HIGH AMBIENT RADIATOR, FUEL/WATER SEPARATOR, 750 GAL., DOUBLE WALL <br />SUB -BASE MOUNTED FUEL OIL TANK, UL LISTED, CRITICAL GRADE MUFFLER, RAIN CAP, <br />LOAD ACID BATTERY & BATTERY RACK, AUTO -BATTERY CHARGER, MAIN LINE CIRCUIT WITH <br />SHUNT TRIP, SPRING VIBRATION ISOLATORS, OIL DRAIN EXTENSION, WEATHERPROOF <br />ENCLOSURE, JACKET WATER HEATER, CRANKCASE OIL HEATER, FLUSH MOUNTED (12) LIGHT <br />ANNUNCIATOR WITH (4) ADDITIONAL LIGHTS, 2 YEAR WARRANTY, OPERATING INSTRUCTIONS <br />UNDER PLEXIGLAS, SERVICE INDICATOR LIGHT, LOW FUEL INDICATOR LIGHT, FUEL SYSTEM <br />PIPING, CLEAN RADIATOR WATER WITH PERMANENT ANTI -FREEZE, OIL TANK FILLED WITH #2 <br />DIESEL FUEL, EXHAUST SYSTEM PIPING WITH FLEX CONNECTION. <br />2. AUTOMATIC TRANSFER SWITCH TO BE ASCO SERIES #300 MICROPROCESSOR CONTROLLER, <br />INDOOR CONSTRUCTION WITH ALL STANDARD FEATURES PLUS OPTIONAL ACCESSORIES <br />1311G, 14AA/140A, ASCO PULSAR #450 - ASSEMBLY CAT. No. 300+13+3 - 600 +C+1+X - <br />E - 11 BG/14AA/14BA/2 EXW300, 20SY/I20V, 30, 4W, 60 Hz, NRG BATTERY CHARGER, <br />42.0 KAIC <br />3. EMERGENCY SYSTEM TO BE COMPLETE IN ALL RESPECTS AND PLACED IN FIRST <br />CLASS OPERATING CONDITION. <br />J <br />J <br />C! <br />g <br />� <br />� <br />� <br />� <br />o <br />� <br />r <br />� <br />PANEL LS2A PANEL KP2 PANEL LS2B <br />2nd FLR <br />Kitchen <br />2nd FLR <br />Left Side <br />Left Side <br />Right Side <br />20BY/I20V, <br />208Y/120V, <br />208Y/12OV, <br />30, 4W + <br />30, 4W + <br />30, 4W + <br />EQ GND BAR <br />EQ GND BAR <br />EQ GND BAR <br />22.0 KAIC <br />22.0 KAIC <br />22.0 KAIC <br />a <br />a <br />4 <br />a <br />a <br />4 <br />a <br />4 <br />a <br />N <br />O <br />N <br />O <br />O <br />0 <br />O <br />PANEL KP <br />PANEL HP1A <br />PANEL HP1C <br />PANEL HP2A <br />PANEL HP3An42.OKAIC <br />R <br />PANEL HP1E <br />PANEL HPR2 <br />PANEL SLP <br />Kitchen <br />1 st FLR <br />1st FLR <br />2nd FLR <br />3rd FLR1 <br />st FLR <br />3rd FLR <br />1 st FLR <br />Left Side <br />Left Side <br />Left Side <br />Left Side <br />Left Side <br />Left Side <br />Left Side <br />ELEC. RM <br />20BY/12OV, <br />208Y/12OV, <br />208Y/12OV, <br />208Y/12OV, <br />208Y/12OV,, <br />208Y/12OV, <br />208Y/12OV, <br />LEFT SIDE <br />30, 4W + <br />30, 4W + <br />30, 4W + <br />30, 4W + <br />30, 4W + <br />30, 4W + <br />30, 4W + <br />208Y/12OV, <br />EQ GND BAR <br />EQ GND BAR <br />EQ GND BAR <br />EQ GND BAR <br />EQ GND BAR <br />EQ GND BAR <br />EQ GND BAR <br />30, 4W + <br />22.0 KAIC <br />22.0 KAIC <br />50.0 KAIC <br />42.0 KAIC <br />22.0 KAIC <br />50.0 KAIC <br />22.0 KAIC <br />EQ GND BAR <br />50.0 KAIC <br />225 AMP EQ GND BUS <br />1000 AMP NEUT BUS <br />1000 AMP MAIN BUSES <br />v <br />t <br />U <br />z <br />O <br />2n <br />Z <br />O <br />U <br />on <br />00 <br />Cn <br />C <br />O <br />O <br />O <br />a <br />�L <br />U <br />o <br />N <br />c <br />1 <br />o <br />0 <br />- <br />O <br />N <br />�I <br />ROBERT MUNROE PE #33868 <br />a <br />w <br />N - <br />project no. <br />drawn by: <br />2006-068.00 <br />date: <br />checked by: <br />NOV , 2006 <br />scale: <br />approved by: <br />sheet no. <br />E I m5mO <br />L_ <br />r <br />C C <br />ro <br />0 L <br />(D N <br />C 0 <br />2) L <br />0 <br />3 <br />0 0 <br />�t <br />N W <br />-C C <br />*' O <br />M <br />L. C <br />0 U <br />C <br />�c <br />0 ro <br />-C m <br />3C <br />0 <br />� N <br />o .E <br />C� <br />,L <br />0 .0 <br />.Ft E <br />C 00 <br />0 C <br />0 t�C <br />Q �L <br />ro <br />to � <br />fl C <br />�, ro <br />0 0 <br />c <br />ro .� <br />E <br />0 <br />c c <br />ro tU <br />Jto <br />J 7 <br />w a� <br />Q� <br />U 0 <br />0-C <br />Q� <br />ro <br />Y -fl <br />� o <br />2� <br />J C <br />U- O <br />0 <br />(n C <br />4- 0 <br />0 U <br />c <br />to <br />ro <br />2 C <br />21.E <br />.0 C <br />2U <br />N <br />N � <br />to O <br />Ln <br />to <br />CO <br />c <br />22 <br />0 <br />N � <br />C <br />. N <br />0 C <br />U ro <br />c� <br />ro <br />E� <br />mC <br />2A <br />0 L <br />c o <br />ro U <br />ro <br />N � <br />0 0 <br />�U <br />0 C <br />0 <br />0 <br />N -0 <br />N <br />N ro <br />C U <br />0 2n <br />0 <br />O U <br />C 0 <br />ro� <br />❑ U <br />z <br />2U <br />N -CM> <br />�? c <br />0) <br />L <br />Q� <br />2v <br />LO <br />0)0 <br />T- 2n <br />d. C <br />N <br />L6C <br />N E <br />N � <br />Z c <br />E 2v <br />=0 <br />C U <br />.0 J m <br />21 J 429 <br />00Ujt <br />a) <br />T- Q <br />C <br />1L 0 <br />�m U <br />0¢ a <br />U W <br />z� o <br />J= ro <br />(1) IJi O <br />0. <br />Hg a <br />QQ ro <br />L <br />0 <br />U)O� <br />Q 00 <br />0 <br />N <br />Y N 'E <br />I- E - <br />L <br />Q fl 41 <br />0 <br />= C tU <br />u- � E <br />a 'C � <br />QNrn <br />m <br />Nb <br />CL <br />0 <br />O N <br />N <br />L ._ 22 <br />0 <br />Cr <br />L rn <br />U o. Q <br />