<br />1 Smoke Evacuation Schematic Diagram
<br />Scale: NTS
<br />SMOKE CONTROL SYSTEM VERIFICATION
<br />INSPECTION PROCEDURES FOR SMOKE CONTROL
<br />1 SCOPE
<br />THE INSPECTION PROCEDURES DESCRIBED APPLY TO SMOKE CONTROL SYSTEMS THAT ARE DEDICATED
<br />TO CONTROLLING SMOKE IN BUILDING ATRIUM FIRES. THESE PROCEDURES ADDRESS THE MAJOR
<br />COMPONENTS OF SMOKE CONTROL SYSTEMS. THE PHRASE AS SPECIFIED IS USED TO MEAN AS
<br />SPECIFIED IN ACCORDANCE WITH CONTRACT DOCUMENTS, THE FLORIDA BUILDING, NFPA 92B SMOKE
<br />MANAGEMENT SYSTEMS IN MALLS, ATRIA AND LARGE SPACES, LATEST EDITION.
<br />2 BARRIERS
<br />a. CHECK WALLS, PARTITIONS, FLOORS, AND CEILINGS OF BARRIERS OF SMOKE CONTROL
<br />SYSTEMS FOR OBVIOUS AND UNUSUAL OPENINGS THAT COULD ADVERSELY AFFECT SMOKE CONTROL
<br />PERFORMANCE.
<br />b. CHECK THAT GAPS AROUND DOORS DO NOT EXCEED THE LIMITS SPECIFIED. IF GASKETING IS
<br />REQUIRED, CHECK THAT IT IS AS SPECIFIED.
<br />G. CHECK THAT AUTOMATIC DOOR CLOSERS IN BARRIERS OF SMOKE CONTROL SYSTEMS ARE AS
<br />SPECIFIED.
<br />3 AIR -MOVING EQUIPMENT
<br />A. CHECK DUCTS TO VERIFY THAT DUCT MATERIAL AND CONSTRUCTION ARE AS SPECIFIED,
<br />B. CHECK DUCT INSTALLATION. DUCT INSTALLATION, INCLUDING THE HANGERS, MUST NOT REDUCE
<br />THE FIRE -RESISTIVE RATING OF STRUCTURAL MEMBERS AND ASSEMBLIES. FREQUENTLY,
<br />STRUCTURAL MEMBERS AND ASSEMBLIES HAVE FIRE -PROTECTIVE COVERINGS, SUCH AS DRY WALL
<br />CONSTRUCTION OR SPRAYED -ON LAYER. CHECK THAT DUCTS ARE INSTALLED IN SUCH A MANNER
<br />THAT THESE PROTECTIVE COVERINGS ARE NOT DAMAGED. CHECK THAT CLEARANCE FROM DUCTS
<br />TO COMBUSTIBLE CONSTRUCTION IS AS SPECIFIED. IN ADDITION, CHECK THAT WHERE DUCTS PASS
<br />THROUGH WALLS, FLOORS, OR PARTITIONS, THE OPENINGS IN CONSTRUCTION AROUND THE DUCTS ARE
<br />AS SPECIFIED.
<br />C. CHECK DUCT COVERINGS AND LININGS TO VERIFY THAT THEIR FIRE SAFETY REQUIREMENTS ARE
<br />AS SPECIFIED. CHECK THAT DUCT COVERINGS DO NOT CONCEAL ANY SERVICE OPENING.
<br />D. CHECK DIRECT ACCESS AND INSPECTION PROVISIONS. SERVICE OPENINGS AND TELESCOPING OR
<br />REMOVABLE DUCT SECTIONS ARE USED FOR DIRECT ACCESS AND INSPECTION. CHECK THAT A
<br />SERVICE OPENING ACCESS DOOR IS PROVIDED IN DUCTS AS SPECIFIED ADJACENT TO FIRE
<br />DAMPERS, SMOKE DAMPERS, AND SMOKE DETECTORS, CHECK THAT THESE ACCESS OPENINGS
<br />ARE IDENTIFIED WITH LETTERS AS SPECIFIED. CHECK THAT SERVICE OPENINGS ARE PROVIDED IN
<br />HORIZONTAL DUCTS AND PLENUMS WHERE SPECIFIED.
<br />E. CHECK AIR FILTERS TO VERIFY THAT THEY HAVE THE CLASSIFICATION SPECIFIED.
<br />F. CHECK THAT THE LOCATION, FIRE PROTECTION RATING, AND INSTALLATION OF FIRE, CEILING, AND
<br />SMOKE DAMPERS ARE AS SPECIFIED. GENERALLY, FIRE, CEILING, AND SMOKE DAMPERS SHOULD
<br />BE INSTALLED IN ACCORDANCE WITH THE CONDITIONS OF THEIR LISTING AND THE
<br />MANUFACTURER'S INSTALLATION INSTRUCTIONS THAT ARE SUPPLIED WITH THE DAMPER.
<br />FURTHER CHECK INSTALLATION BY REMOVING THE FUSIBLE LINK (WHERE APPLICABLE) AND
<br />OPERATE THE DAMPER TO VERIFY THAT IT FULLY CLOSES. IT IS DESIRABLE TO OPERATE DAMPERS
<br />WITH NORMAL AIR FLOW TO ENSURE THAT THEY ARE NOT HELD OPEN BY THE AIRSTREAM.
<br />REMEMBER TO REINSTALL ALL FUSIBLE LINKS THAT HAVE BEEN REMOVED DURING INSPECTION.
<br />4 CONTROLS
<br />a. CHECK MANUAL CONTROLS. CHECK THAT DEVICES FOR MANUAL ACTIVATION AND DEACTIVATION
<br />OF THE SMOKE CONTROL SYSTEM ARE OF MATERIALS AND INSTALLATION AS SPECIFIED.
<br />b. CHECK AUTOMATIC CONTROLS. CHECK THAT DEVICES FOR AUTOMATIC ACTIVATION AND
<br />DEACTIVATION AND CONTROL OF THE SMOKE CONTROL SYSTEM ARE OF MATERIALS AND
<br />INSTALLATION AS SPECIFIED.
<br />PROCEDURES FOR SMOKE -CONTROL SYSTEM TESTING
<br />1. BEFORE TESTING SMOKE -CONTROL SYSTEMS, VERIFY THAT CONSTRUCTION IS COMPLETE AND VERIFY HE
<br />INTEGRITY OF EACH SMOKE -CONTROL ZONE BOUNDARY. VERIFY THAT WINDOWS AND DOORS ARE
<br />CLOSED AND THAT APPLICABLE SAFING, GASKET, AND SEALANTS ARE INSTALLED. REPORT DEFICIENCIES
<br />AND POSTPONE TESTING UNTIL AFTER THE REPORTED DEFICIENCIES ARE CORRECTED. REFERTO
<br />INSPECTION PROCEDURES FOR SMOKE CONTROL.
<br />2. MEASURE AND RECORD WIND SPEED AND DIRECTION, OUTSIDE -AIR TEMPERATURE, AND RELATIVE
<br />HUMIDITY ON EACH TEST DAY.
<br />3. MEASURE, ADJUST, AND RECORD AIRFLOW OF EACH SMOKE -CONTROL FAN WITH ALL FANS THAT ARE A PART
<br />OF THE SYSTEM OPERATING AS INTENDED BY THE DESIGN.
<br />4. MEASURE, ADJUST, AND RECORD THE AIRFLOW OF EACH FAN. FOR DUCTED SYSTEMS, MEASURE THE FAN
<br />AIRFLOW BY DUCT PITOT-TUBE TRAVERSE.
<br />5. MEASURE AND RECORD THE AIR FLOW VELOCITY THROUGH THE ATRIUM OUTSIDE DOORS.
<br />6. AFTER AIR BALANCING IS COMPLETE, PERFORM THE FOLLOWING PRESSURIZATION TESTING:
<br />a. VERIFY THE BOUNDARIES OF SMOKE -CONTROL ATRIUM ZONE.
<br />b. WITH THE HVAC SYSTEMS IN THEIR NORMAL MODE OF OPERATION AND SMOKE CONTROL NOT
<br />OPERATING, MEASURE AND RECORD THE PRESSURE DIFFERENCE ACROSS EACH SMOKE -CONTROL
<br />ARE OF THE ATRIUM. MAKE MEASUREMENTS AFTER CLOSING DOORS THAT SEPARATE THE AREAS.
<br />MAKE ONE MEASUREMENT ACROSS EACH DOOR. CLEARLY INDICATE THE HIGH AND LOW
<br />PRESSURE SIDE OF EACH DOOR.
<br />C. WITH THE SYSTEM OPERATING IN THE SMOKE -CONTROL MODE PERFORM THE FOLLOWING:
<br />1. MEASURE AND RECORD THE PRESSURE DIFFERENCE ACROSS EACH DOOR THAT SEPARATES THE
<br />SMOKE AREA FROM ADJACENT AREAS. MAKE MEASUREMENTS WITH DOORS THAT SEPARATE THE
<br />ATRIUM SMOKE ZONE FROM THE OTHER AREAS CLOSED. CLEARLY INDICATE THE HIGH AND LOW
<br />PRESSURE SIDE OF THE DOOR. DOORS THAT HAVE A TENDENCY TO OPEN SLIGHTLY DUE TO THE
<br />PRESSURE DIFFERENCE SHOULD HAVE ONE PRESSURE MEASUREMENT MADE WHILE HELD CLOSED
<br />AND ANOTHER MEASUREMENT MADE WITH THE DOOR OPEN.
<br />2. THE ATRIUM AREA PRESSURE SHOULD BE LOWER (NEGATIVE) WITH RESPECT TO EACH DOOR ON THE
<br />SMOKE AREA BOUNDARY.
<br />7. OPERATIONAL TESTS:
<br />a. CHECK THE PROPER ACTIVATION OF ATRIUM SMOKE -CONTROL SYSTEM IN RESPONSE TO ALL MEANS OF
<br />ACTIVATION, BOTH AUTOMATIC AND MANUAL.
<br />b. CHECK AND RECORD THE PROPER OPERATION OF FANS, DAMPERS, AND RELATED EQUIPMENT AS
<br />OUTLINED BELOW FOR THE ATRIUM SMOKE -CONTROL SYSTEM.
<br />1. SMOKE -CONTROL SYSTEM AUTOMATIC ACTIVATION.
<br />2. TYPE OF SIGNAL THAT ACTIVATES A SMOKE -CONTROL SYSTEM I.E. SMOKE DETECTOR.
<br />3. FANS "ON" AS REQUIRED TO IMPLEMENT THE SMOKE -CONTROL SYSTEM.
<br />4. FAN(S) "OFF" AS REQUIRED TO IMPLEMENT THE SMOKE CONTROL SYSTEM.
<br />5. DAMPERS "OPEN" WHERE MAXIMUM AIRFLOW MUST BE ACHIEVED.
<br />6. DAMPER(S) "CLOSED" WHERE NO AIRFLOW SHOULD TAKE PLACE,
<br />7. AUXILIARY FUNCTIONS TO ACHIEVE THE SMOKE -CONTROL SYSTEM CONFIGURATION SUCH AS
<br />CHANGES OR OVERRIDE OF NORMAL OPERATING PRESSURE AND TEMPERATURE -CONTROL SET
<br />POINTS.
<br />8. IF STANDBY POWER IS PROVIDED FOR THE SMOKE -CONTROL SYSTEM, TEST TO VERIFY THAT THE
<br />SYSTEM FUNCTIONS WHILE OPERATING UNDER BOTH NORMAL AND STANDBY POWER.
<br />9. CONDUCT ADDITIONAL TEST REQUIRED BY AUTHORITIES HAVING JURISDICTION. UNLESS REQUIRED
<br />BY AUTHORITIES HAVING JURISDICTION, PERFORM TESTING WITHOUT THE USE OF MOKE OR
<br />PRODUCTS THAT SIMULATE SMOKE.
<br />10. PREPARE A COMPLETE REPORT OF OBSERVATIONS, MEASUREMENTS, AND DEFICIENCIES.
<br />SMOKE SYSTEM CONTROL VERIFICATION
<br />1. CHECK FREE TRAVEL AND PROPER OPERATION OF CONTROL DEVICES SUCH AS DAMPER OPERATORS.
<br />2. CHECK THE SEQUENCE OF OPERATION OF CONTROL DEVICES. NOTE AIR PRESSURES AND DEVICE
<br />OSITIONS AND CORRELATE WITH AIRFLOW MEASUREMENTS. NOTE THE SPEED OF RESPONSE TO INPUT
<br />HANGES.
<br />3. CHECK THE INTERACTION OF ELECTRICALLY OPERATED SWITCH TRANSDUCERS.
<br />4. CHECK THE INTERACTION OF INTERLOCK AND LOCKOUT SYSTEMS,
<br />5. RECORD VOLTAGES OF POWER SUPPLY AND CONTROLLER OUTPUT. DETERMINE WHETHER THE SYSTEM
<br />OPERATES ON A GROUNDED OR NONGROUNDED POWER SUPPLY.
<br />6. NOTE OPERATION OF ELECTRIC ACTUATORS USING SPRING RETURN FOR PROPER FAIL-SAFE OPERATIONS.
<br />TOLERANCES
<br />1 SET HVAC SYSTEM AIRFLOW RATES WITHIN THE FOLLOWING TOLERANCES:
<br />a. FANS: 0 TO PLUS 10 PERCENT
<br />INSPECTIONS
<br />2 FINAL INSPECTION
<br />a. AFTER INITIAL INSPECTION IS COMPLETE AND CHECKS VERIFIES THAT TESTING AND
<br />BALANCING ARE COMPLETE AND ACCURATELY DOCUMENTED IN THE FINAL REPORT,
<br />REQUEST THAT A FINAL INSPECTION BE MADE BY THE OWNER.
<br />b. SMOKE TESTING FIRM TEST AND BALANCE ENGINEER SHALL CONDUCT THE INSPECTION
<br />IN THE PRESENCE OF THE OWNER AND THE ARCHITECT AND CODE OFFICIALS.
<br />C. SMOKE TESTING FIRM SHALL RECHECK ALL MEASUREMENTS AND MAKE
<br />ADJUSTMENTS. REVISE THE FINAL REPORT AND BALANCING DEVICE SETTINGS TO
<br />INCLUDE ALL CHANGES AND RESUBMIT THE FINAL REPORT.
<br />FINAL REPORT
<br />1 GENERAL: TYPEWRITTEN, OR COMPUTER PRINTOUT IN LETTER -QUALITY FONT, ON STANDARD BOND
<br />PAPER, IN THREE-RING BINDER, TABULATED AND DIVIDED INTO SECTIONS BY TESTING AND BALANCED
<br />SYSTEMS.
<br />2 INCLUDE A CERTIFICATION SHEET IN FRONT OF BINDER SIGNED AND SEALED BY THE CERTIFIED TESTING
<br />NO BALANCING ENGINEER.
<br />a. NCLUDE A LIST OF INSTRUMENTS USED FOR PROCEDURES, ALONG WITH PROOF OF
<br />CALIBRATION.
<br />3 FINAL REPORT CONTENTS: IN ADDITION TO CERTIFIED FIELD REPORT DATA, INCLUDE THE FOLLOWING:
<br />a. FAN CURVES
<br />b. MANUFACTURER'S TEST DATA.
<br />C. FIELD TEST REPORTS PREPARED BY SYSTEM AND EQUIPMENT INSTALLERS.
<br />d. OTHER INFORMATION RELATIVE TO EQUIPMENT PERFORMANCE, BUT DO NOT
<br />INCLUDE SHOP DRAWINGS AND PRODUCT DATA.
<br />4 GENERAL REPORT DATA: IN ADDITION TO FORM TITLES AND ENTRIES, INCLUDE THE FOLLOWING DATA IN
<br />HE FINAL REPORT, AS APPLICABLE:
<br />a. TITLE PAGE
<br />b. NAME AND ADDRESS OF TAB FIRM
<br />C. PROJECT NAME
<br />d. PROJECT LOCATION
<br />e. ARCHITECT'S NAME AND ADDRESS
<br />f. ENGINEER'S NAME AND ADDRESS
<br />9. CONTRACTOR'S NAME AND ADDRESS
<br />h. REPORT DATE
<br />i. SIGNATURE OF TAB FIRM WHO CERTIFIES THE REPORT
<br />j. TABLE OF CONTENTS WITH THE TOTAL NUMBER OF PAGES DEFINED FOR EACH
<br />SECTION OF THE REPORT. NUMBER EACH PAGE IN THE REPORT.
<br />k. SUMMARY OF CONTENTS INCLUDING THE FOLLOWING:
<br />1 INDICATED VERSUS FINAL PERFORMANCE
<br />2 NOTABLE CHARACTERISTICS OF SYSTEMS
<br />3 DESCRIPTION OF SYSTEM OPERATION SEQUENCE IF IT VARIES FROM THE
<br />CONTRACT DOCUMENTS
<br />I. NOMENCLATURE SHEETS FOR EACH ITEM OF EQUIPMENT
<br />M. DATA FOR TERMINAL UNITS, INCLUDING MANUFACTURER, TYPE SIZE, AND FITTINGS
<br />n. NOTES TO EXPLAIN WHY CERTAIN FINAL DATA IN THE BODY OF REPORTS VARIES FROM
<br />INDICATED VALUES
<br />o. TEST CONDITIONS FOR FANS INCLUDING THE FOLLOWING:
<br />1 SETTINGS FOR OUTSIDE AIR AND SMOKE DAMPERS
<br />2 FAN DRIVE SETTINGS INCLUDING SETTINGS AND PERCENTAGE OF MAXIMUM PITCH
<br />DIAMETER
<br />5 OTHER SYSTEMS OPERATING CONDITIONS THAT AFFECT PERFORMANCE
<br />6 FAN TEST REPORTS: INCLUDE THE FOLLOWING:
<br />a. FAN DATA:
<br />1 SYSTEM IDENTIFICATION
<br />2 LOCATION
<br />3 MAKE AND TYPE
<br />4 MODEL NUMBER AND SIZE
<br />5 MANUFACTURER'S SERIAL NUMBER
<br />6 ARRANGEMENT AND CLASS
<br />7 SHEAVE MAKE, SIZE IN INCHES, AND BORE
<br />8 SHEAVE DIMENSIONS, CENTER -TO -CENTER, AND AMOUNT OF ADJUSTMENTS IN
<br />INCHES
<br />b. MOTOR DATA:
<br />1 MAKE AND FRAME TYPE AND SIZE
<br />2 HORSEPOWER AND RPM
<br />3 VOLTS, PHASE, AND HERTZ
<br />4 FULL -LOAD AMPERAGE AND SERVICE FACTOR
<br />5 SHEAVE MAKE, SIZE IN INCHES, AND BORE
<br />6 SHEAVE DIMENSIONS, CENTER -TO -CENTER, AND AMOUNT OF ADJUSTMENTS IN
<br />INCHES
<br />7 NUMBER OF BELTS, MAKE, AND SIZE
<br />C. TEST DATA (INDICATED AND ACTUAL VALUES):
<br />1 TOTAL AIRFLOW RATE IN CFM
<br />2 TOTAL SYSTEM STATIC PRESSURE IN INCHES WG
<br />3 FAN RPM
<br />4 DISCHARGE STATIC PRESSURE IN INCHES WG
<br />5 SUCTION STATIC PRESSURE IN INCHES WG
<br />SMOKE REMOVAL SEQUENCE:
<br />1. ATRIUM SMOKE DETECTOR DETECTS SMOKE.
<br />2. FIRST FLOOR LOBBY DOORS C109, C109A, C10913, C109C, C100, C100A AND
<br />Cl 10 OPEN.
<br />3. MAKE-UP AIR UNIT (MUA-1) SHUTS DOWN AND MOTORIZED AIR DAMPER
<br />CLOSES. RELIEF VENT (RV-1)MOTORIZED DDAMPER CLOSES.
<br />4, KITCHEN SUPPLY FAN (KSF-1) SHUTS DOWN.
<br />5. KITCHEN EXHAUST FAN (KEF/1) REMAINS ON. UNIT SHALL SHUT DOWN VIA
<br />EMERGENCY CUT-OUT SWITCH IN KITCHEN,
<br />6. SMOKE REMOVAL FANS (SEF-1 AND SEF-2) MOTORIZED DAMPERS OPEN.
<br />PROVIDE END SWITCH TO INDICATE DAMPER OPEN POSITION FOR SMOKE
<br />FAN START.
<br />7. SMOKE REMOVAL FANS (SEF-1 AND SEF-2) ARE ACTIVATED. SMOKE
<br />REMOVAL FANS SHALL OPERATE UNTILL SHUT DOWN BY THE FIRE
<br />DEPARTMENT.
<br />8. THE FIRE ALARM PANEL SHALL HAVE A SMOKE OVERRIDE COMMAND TO
<br />ACTIVATE THE SMOKE REMOVAL SEQUENCE MANUALLY. THE FIRE ALARM
<br />PANEL SHALL DEACTIVATE THE SMOKE REMOVAL SYSTEM AND SET THE
<br />HVAC CONTROLS TO NORMAL OPERATION.
<br />PROVIDE CONTROLS, RELAYS, SWITCHES, POWER AND ACCESSORIES FOR
<br />AN OPERATIONAL SMOKE CONTROL SYSTEM, COORDINATE WITH F.A.
<br />CONTRACTOR FOR INTERFACE COMPONENTS.
<br />FREDERICK MUSCATELLO, PE
<br />FL. PE # 62451
<br />PO Box 941168
<br />MAITLAND, FL 32794-1168
<br />PH. 407-748-4348
<br />EMAIL: frecIftmengineering.com
<br />t
<br />U
<br />V)
<br />z
<br />0
<br />V)
<br />5
<br />w
<br />Irf
<br />0
<br />z
<br />o
<br />P4
<br />o
<br />,2
<br />O
<br />O
<br />�
<br />A
<br />A
<br />U
<br />�
<br />�
<br />O
<br />N
<br />c
<br />00
<br />oo
<br />�D
<br />0
<br />I
<br />o
<br />�
<br />w
<br />a
<br />J
<br />U
<br />le
<br />U
<br />••
<br />w
<br />J
<br />0
<br />W
<br />Q
<br />W
<br />N
<br />A��18.
<br />drawn by:
<br />00
<br />dfte: �'S, tDA
<br />checked by:
<br />z9!
<br />Qx
<br />sca
<br />pproved by:
<br />sheet no.
<br />`f$
<br />Ml m3m
<br />
|