FEEDER SCHEDULE
<br />WIRE SIZES
<br />CONDUIT
<br />30/TVSS
<br />4#10, #10 GND
<br />1 /2"
<br />60/TVSS
<br />4#6, #6 GND
<br />1"
<br />100
<br />3#2, #8 GND, CU OR
<br />1 1 /4"
<br />3#3/0 AL MC W/GND
<br />1 1/2"
<br />125
<br />4#1, #6 GND
<br />150
<br />4#1 /0, #6 GND , CU
<br />1 1 /2"
<br />OR 4#3/0, #4 GND AL
<br />2 1 /2"
<br />175
<br />4#2/0, #6 GND, CU
<br />2"
<br />OR 4#4/0, #4 GND AL
<br />2 1/2"
<br />200
<br />4#3/0, #6 GND, CU
<br />206
<br />OR 4-250KCMIL, #4 GND, AL
<br />3"
<br />225
<br />4#4/0, #4 GND, CU
<br />2 1 /2"
<br />OR 4-300KCMIL, #2, AL
<br />300
<br />4-300MCM, #4 GND, CU
<br />3"
<br />OR 4-500KCMIL, #2 GND, AL
<br />4"
<br />350
<br />2 SETS 4#2/0, #3 GND, CU
<br />(2) 2"
<br />OR 4#4/0, #4 GND , AL
<br />(2) 2 1 /2"
<br />400
<br />2 SETS 4#3/0, #3 GND, CU
<br />(2) 2"
<br />OR 4-250KCMIL, #1 GND, AL
<br />(2) 2 1 /2"
<br />600
<br />2 SETS 4-350MCM, #3/0 GND
<br />(2) 3"
<br />1200
<br />4 SETS 4-350MCM, #3/0 GND
<br />(4) 3"
<br />1600
<br />5 SETS 4-400MCM, #4/0 GND
<br />(5) 3 1 /2"
<br />2500S
<br />7 SETS 4-500MCM, #4/0 GND & SPARE
<br />(8) 4"
<br />4" CONDUIT
<br />NEUTRAL WIRES NOT REO'D FOR TRANSFORMER PRIMARIES.
<br />SEE RISER DIAGRAM FOR SERVICE GROUNDING ELECTRODE
<br />CONDUCTOR SIZING IN LIEU OF GROUND INDICATED.
<br />30 KVA (OR LESS), 480-120/208V XFMR #8 AWG
<br />45 KVA, 480-120/208V XFMR #6 AWG
<br />75 KVA, 480-120/208V XFMR #2 AWG
<br />112.5 KVA, 480-120/208V XFMR #1 /0 AWG
<br />150 KVA, 480-120/208V XFMR #1 /0 AWG
<br />225 KVA, 480-120/208V XFMR #2/0 AWG
<br />300 KVA (OR MORE), 480-120/208V XFMR #3/0 AWG
<br />PARTIAL ELECTRICAL RISER
<br />SCALE: NONE
<br />MEMORY UNIT SERVICE
<br />CALCULATION
<br />AREA = 300
<br />LOAD
<br />GENERAL LIGHTING LOAD = 3VA/SF X AREA
<br />SMALL APPLIANCES
<br />TOTAL "OTHER LOAD"
<br />APPLICATION OF DEMAND FACTORS
<br />FIRST 10kW OF "OTHER LOAD" @ 100%
<br />REMAINDER @ 40%
<br />COMBI. HP/AHU = 920 VA
<br />TOTAL HVAC
<br />SERVICE DEMAND LOAD
<br />SERVICE AMPS @ 120/208V, 1 e
<br />TOTAL CONNECTED LOAD
<br />VOLT -AMPS
<br />900 VA
<br />0 VA
<br />900 VA
<br />900 VA
<br />0 VA
<br />920 VA
<br />1820 VA
<br />9 AMPS
<br />1820 VA
<br />(2) MEMORY UNIT SERVICE
<br />CALCULATION
<br />AREA = 600
<br />LOAD
<br />GENERAL LIGHTING LOAD = 3VA/SF X AREA
<br />SMALL APPLIANCES
<br />TOTAL"OTHER LOAD"
<br />APPLICATION OF DEMAND FACTORS
<br />FIRST 10kW OF "OTHER LOAD" @ 100%
<br />REMAINDER @ 40%
<br />COMBI. HP/AHU_ (2) = 1840 VA
<br />TOTAL HVAC
<br />SERVICE DEMAND LOAD
<br />SERVICE AMPS @ 120/208V, 1 e
<br />TOTAL CONNECTED LOAD
<br />VOLT -AMPS
<br />1800 VA
<br />0 VA
<br />1800 VA
<br />1800 VA
<br />0 VA
<br />1840 VA
<br />3640 VA
<br />18 AMPS
<br />3640 VA
<br />PANELS MAY REQUIRE
<br />HIN APARTMENT BASED ON
<br />,NS. FIELD COORDINATE.
<br />NG 100A PANELS IN
<br />ITS PROVIDED POWER TO
<br />OKING APPLIANCES, THESE
<br />:MAIN TO SERVE RECEPTACLE
<br />IT APT. UNITS.
<br />cVEIGH & MANGUM
<br />ENGINFER ING•INC
<br />340 Interstate North Parkway, Suite 360
<br />Atlanta - Georgia 30339
<br />Ph: (678)213-1616 Fax: (678)213-1617
<br />email: mail@MeVeighMangum.com
<br />of Record: Tony G. Fernandez License No.: 60754
<br />FOUSE
<br />ARCHITECTURE
<br />& INTERIORS, P.C.
<br />3201 S. Cherokee Lane Suite 340
<br />Woodstock, Georgia 30188
<br />Voice 678-391-5365
<br />Fax 678-391-5362
<br />email: rlf@fousearchitecture.com
<br />OC Copyright 2011 Fouse Architecture & Interiors, P.C.
<br />Seal
<br />,o still //4I
<br />♦`♦ C,. F ER&
<br />�1 •��CENg�•�Y� i
<br />• �0 ••� w
<br />O 0754
<br />w S ATE OF •:i� `
<br />w �
<br />.,� �oNA ;'
<br />Consultants: CIVIL ENGINEER:
<br />STRUCTURAL ENGINEER:
<br />McVeigh & Mangum Engineering Inc
<br />340 N Interstate Parkway, Suite 360
<br />Atlanta, GA 30339
<br />Contact: Chad McDonald, P.E.
<br />678.213.1616
<br />MEP ENGINEER:
<br />McVeigh & Mangum Engineering Inc
<br />340 N Interstate Parkway, Suite 360
<br />Atlanta, GA 30339
<br />Contact: Tony G. Fernandez, P.E.
<br />678.213.1616
<br />r� Job Title:
<br />V1 ��
<br />C
<br />Z �A
<br />0 C 20 a ao
<br />r w
<br />p4 �
<br />a
<br />a�
<br />w oldx
<br />�a
<br />� as
<br />AN
<br />Sheet Information:
<br />Job Number 11002
<br />Original Issue Date 08-31-2012
<br />Issue Dates:
<br />No. ISSUE DATE
<br />PERMIT/CONSTRUCTION 08-31-2012
<br />Sheet Title:
<br />PARTIAL
<br />ELECTRICAL
<br />RISER
<br />E-004
<br />FOR CONSTRUCTION
<br />
|