FEEDER SCHEDULE <br />WIRE SIZES <br />CONDUIT <br />30/TVSS <br />4#10, #10 GND <br />1 /2" <br />60/TVSS <br />4#6, #6 GND <br />1" <br />100 <br />3#2, #8 GND, CU OR <br />1 1 /4" <br />3#3/0 AL MC W/GND <br />1 1/2" <br />125 <br />4#1, #6 GND <br />150 <br />4#1 /0, #6 GND , CU <br />1 1 /2" <br />OR 4#3/0, #4 GND AL <br />2 1 /2" <br />175 <br />4#2/0, #6 GND, CU <br />2" <br />OR 4#4/0, #4 GND AL <br />2 1/2" <br />200 <br />4#3/0, #6 GND, CU <br />206 <br />OR 4-250KCMIL, #4 GND, AL <br />3" <br />225 <br />4#4/0, #4 GND, CU <br />2 1 /2" <br />OR 4-300KCMIL, #2, AL <br />300 <br />4-300MCM, #4 GND, CU <br />3" <br />OR 4-500KCMIL, #2 GND, AL <br />4" <br />350 <br />2 SETS 4#2/0, #3 GND, CU <br />(2) 2" <br />OR 4#4/0, #4 GND , AL <br />(2) 2 1 /2" <br />400 <br />2 SETS 4#3/0, #3 GND, CU <br />(2) 2" <br />OR 4-250KCMIL, #1 GND, AL <br />(2) 2 1 /2" <br />600 <br />2 SETS 4-350MCM, #3/0 GND <br />(2) 3" <br />1200 <br />4 SETS 4-350MCM, #3/0 GND <br />(4) 3" <br />1600 <br />5 SETS 4-400MCM, #4/0 GND <br />(5) 3 1 /2" <br />2500S <br />7 SETS 4-500MCM, #4/0 GND & SPARE <br />(8) 4" <br />4" CONDUIT <br />NEUTRAL WIRES NOT REO'D FOR TRANSFORMER PRIMARIES. <br />SEE RISER DIAGRAM FOR SERVICE GROUNDING ELECTRODE <br />CONDUCTOR SIZING IN LIEU OF GROUND INDICATED. <br />30 KVA (OR LESS), 480-120/208V XFMR #8 AWG <br />45 KVA, 480-120/208V XFMR #6 AWG <br />75 KVA, 480-120/208V XFMR #2 AWG <br />112.5 KVA, 480-120/208V XFMR #1 /0 AWG <br />150 KVA, 480-120/208V XFMR #1 /0 AWG <br />225 KVA, 480-120/208V XFMR #2/0 AWG <br />300 KVA (OR MORE), 480-120/208V XFMR #3/0 AWG <br />PARTIAL ELECTRICAL RISER <br />SCALE: NONE <br />MEMORY UNIT SERVICE <br />CALCULATION <br />AREA = 300 <br />LOAD <br />GENERAL LIGHTING LOAD = 3VA/SF X AREA <br />SMALL APPLIANCES <br />TOTAL "OTHER LOAD" <br />APPLICATION OF DEMAND FACTORS <br />FIRST 10kW OF "OTHER LOAD" @ 100% <br />REMAINDER @ 40% <br />COMBI. HP/AHU = 920 VA <br />TOTAL HVAC <br />SERVICE DEMAND LOAD <br />SERVICE AMPS @ 120/208V, 1 e <br />TOTAL CONNECTED LOAD <br />VOLT -AMPS <br />900 VA <br />0 VA <br />900 VA <br />900 VA <br />0 VA <br />920 VA <br />1820 VA <br />9 AMPS <br />1820 VA <br />(2) MEMORY UNIT SERVICE <br />CALCULATION <br />AREA = 600 <br />LOAD <br />GENERAL LIGHTING LOAD = 3VA/SF X AREA <br />SMALL APPLIANCES <br />TOTAL"OTHER LOAD" <br />APPLICATION OF DEMAND FACTORS <br />FIRST 10kW OF "OTHER LOAD" @ 100% <br />REMAINDER @ 40% <br />COMBI. HP/AHU_ (2) = 1840 VA <br />TOTAL HVAC <br />SERVICE DEMAND LOAD <br />SERVICE AMPS @ 120/208V, 1 e <br />TOTAL CONNECTED LOAD <br />VOLT -AMPS <br />1800 VA <br />0 VA <br />1800 VA <br />1800 VA <br />0 VA <br />1840 VA <br />3640 VA <br />18 AMPS <br />3640 VA <br />PANELS MAY REQUIRE <br />HIN APARTMENT BASED ON <br />,NS. FIELD COORDINATE. <br />NG 100A PANELS IN <br />ITS PROVIDED POWER TO <br />OKING APPLIANCES, THESE <br />:MAIN TO SERVE RECEPTACLE <br />IT APT. UNITS. <br />cVEIGH & MANGUM <br />ENGINFER ING•INC <br />340 Interstate North Parkway, Suite 360 <br />Atlanta - Georgia 30339 <br />Ph: (678)213-1616 Fax: (678)213-1617 <br />email: mail@MeVeighMangum.com <br />of Record: Tony G. Fernandez License No.: 60754 <br />FOUSE <br />ARCHITECTURE <br />& INTERIORS, P.C. <br />3201 S. Cherokee Lane Suite 340 <br />Woodstock, Georgia 30188 <br />Voice 678-391-5365 <br />Fax 678-391-5362 <br />email: rlf@fousearchitecture.com <br />OC Copyright 2011 Fouse Architecture & Interiors, P.C. <br />Seal <br />,o still //4I <br />♦`♦ C,. F ER& <br />�1 •��CENg�•�Y� i <br />• �0 ••� w <br />O 0754 <br />w S ATE OF •:i� ` <br />w � <br />.,� �oNA ;' <br />Consultants: CIVIL ENGINEER: <br />STRUCTURAL ENGINEER: <br />McVeigh & Mangum Engineering Inc <br />340 N Interstate Parkway, Suite 360 <br />Atlanta, GA 30339 <br />Contact: Chad McDonald, P.E. <br />678.213.1616 <br />MEP ENGINEER: <br />McVeigh & Mangum Engineering Inc <br />340 N Interstate Parkway, Suite 360 <br />Atlanta, GA 30339 <br />Contact: Tony G. Fernandez, P.E. <br />678.213.1616 <br />r� Job Title: <br />V1 �� <br />C <br />Z �A <br />0 C 20 a ao <br />r w <br />p4 � <br />a <br />a� <br />w oldx <br />�a <br />� as <br />AN <br />Sheet Information: <br />Job Number 11002 <br />Original Issue Date 08-31-2012 <br />Issue Dates: <br />No. ISSUE DATE <br />PERMIT/CONSTRUCTION 08-31-2012 <br />Sheet Title: <br />PARTIAL <br />ELECTRICAL <br />RISER <br />E-004 <br />FOR CONSTRUCTION <br />