SERVICE MAIN DISCONNECT <br />N EQUIPMENT <br />GROUND BAR <br />BONDED TO <br />PANELBOARD <br />CABINET <br />NEUTRAL <br />BAR <br />�— MAIN <br />BONDING <br />JUMPER <br />ISOLATED GROUND <br />PANELBOARD (NOTE 6) <br />GC <br />EGC <br />IG N EQUIPMENT —1 <br />GROUND BAR <br />BONDED TO <br />PANELBOARD <br />CABINET <br />(NOTE 1) <br />INSULATED <br />NEUTRALBAR <br />(NOTE 2) <br />NOTE 4 <br />I> <br />ISOLATED GROUND <br />RECEPTACLE <br />MOUNTING SCREWS BOND <br />ONLY THE RECEPTACLE FRAME <br />TO METALLIC OUTLET BOX <br />ISOLATED GROUND TERMINAL <br />IS NOT CONNECTED TO THE <br />RECEPTACLE FRAME AND IS <br />THEREFORE INSULATED <br />FROM THE OUTLET BOX <br />GROUNDING PATH <br />OUTLET BOX EQUIPMENT <br />GROUND TERMINAL <br />METALLIC OUTLET BOX <br />SILVER GROUNDED <br />(NEUTRAL) TERMINAL <br />ORANGE COLOR FACE <br />IDENTIFIES ISOLATED <br />GROUND NOT CONNECTED <br />GROUND ISOLATED GROUND BAR NOT BONDED TO TO RECEPTACLE FRAME <br />(INSULATED FROM) PANELBOARD CABINET <br />(NOTE 3) <br />GENERAL NOTES: <br />A. THIS DETAIL IS DIAGRAMMATIC IN NATURE AND IS NOT INTENDED TO INDICATE PROPOSED CIRCUIT <br />ROUTING. PHASE CONDUCTORS AND RACEWAYS ARE NOT SHOWN FOR CLARITY. ALL RACEWAYS SHALL CONDUCTOR LEGEND <br />BE SECURELY BONDED TO THE ENCLOSURES THE RACEWAYS CONNECT. — GC — GROUNDED (NEUTRAL) CONDUCTOR <br />B. A GREEN EQUIPMENT GROUNDING CONDUCTOR IS REQUIRED IN ADDITION TO THE ISOLATED GROUNDING <br />CONDUCTOR FOR BONDING METALLIC RACEWAY AND ENCLOSURES. UNDER NO CIRCUMSTANCES WILL A —EGC— EQUIPMENT GROUNDING CONDUCTOR <br />METALLIC RACEWAY SYSTEM BE ACCEPTED AS THE SOLE MEANS OF EQUIPMENT GROUNDING. — IG — IsoLATED GRouNDwG CONDUCTOR <br />C. GROUNDED (NEUTRAL) CONDUCTORS ARE ONLY REQUIRED FOR 120V LOADS OR POLYPHASE LOADS THAT —GEC— GROUNDING ELECTRODE CONDUCTOR <br />REQUIRE 120V POWER. <br />D. REFERENCE PLAN DRAWINGS FOR ACTUAL RECEPTACLE TYPE AND NEMA CONFIGURATION. <br />NOTES: <br />1. EGC BUS BAR: ONLY EQUIPMENT GROUNDING CONDUCTORS SHALL TERMINATE ON THIS EQUIPMENT GROUND BAR. <br />2. NEUTRAL BUS BAR: ONLY GROUNDED (NEUTRAL) CONDUCTORS SHALL TERMINATE ON THIS NEUTRAL BAR. <br />3. IG BUS BAR: ONLY ISOLATED GROUNDING CONDUCTORS SHALL TERMINATE ON THIS ISOLATED GROUND BAR. <br />4. SIZED PER NEC TABLE 250.122 BASED ON CONTIN <br />UOUS CURRENT RATING OF UPSTREAM OCPD (BREAKER/FUSE) PROTECTING ISOLATED GROUND PANELBOARD.ISOLATED <br />GROUNDING CONDUCTORS ARE PERMITTED TO PASS THROUGH ONE OR MORE PANELBOARDS WITHOUT A CONNECTION TO THE INTERMEDIATE PANELBOARD GROUNDING <br />TERMINALS. ISOLATED GROUNDING CONDUCTORS SHALL BE ROUTED BACK TO THE SERVICE EQUIPMENT FOR CONNECTION TO THE SERVICE EQUIPMENT GROUNDING <br />TERMINAL WHERE THE NEUTRAL -GROUND CONNECTION IS MADE. <br />5. SIZED PER NEC TABLE 250.122 BASED ON CONTINUOUS CURRENT RATING OF BRANCH CIRCUIT OCPD (BREAKER/FUSE) PROTECTING ISOLATED GROUND RECEPTACLE. <br />6. ISOLATED GROUND CIRCUITS SHALL BE ROUTED IN DEDICATED RACEWAYS AND SHALL NOT BE COMBINED IN THE SAME RACEWAY WITH NON -ISOLATED GROUND CIRCUITS. <br />EGC <br />GC <br />IG <br />NOTE 5 <br />ISOLATED GROUND DETAIL SCALE 1 <br />N.T.S. <br />NOT ALL DETAILS ON THIS SHEET ARE APPLICABLE <br />TO THIS PROJECT. REFER TO PLAN DRAWINGS FOR <br />SPECIFIC REQUIREMENTS. <br />EXISTING iC3 NOTE: <br />BEFORE THE START OF CONSTRUCTION, EC SHALL CONTACT iC3 <br />REPRESENTATIVE FOR ALL MODIFICATIONS TO EXISTING iC3 SYSTEM OR TO <br />DETERMINE IF SITES WITHOUT AN EXISTING iC3 ARE TO BE RETROFITTED WITH <br />AN iC3 CONTROL PANEL. <br />iC3 CONTRACT INFORMATION: <br />PONCELL BROWN: IC3_OPERATIONS@BANKOFAMERICA.COM <br />WITH A COPY TO: PONCELL.BROWN@AM.JLL.COM <br />SENSOR SCHEDULE <br />TYPE <br />DESCRIPTION <br />MANUFACTURER <br />MODEL NUMBER <br />MOUNTING <br />NOTES <br />Os <br />os <br />OCCUPANCY SENSOR - CORNER MOUNT <br />WATTSTOPPER <br />LMDX-100 <br />CORNER CEILING <br />DUAL TECHNOLOGY <br />NOTE 5 <br />OCCUPANCY SENSOR - 360 DEGREE <br />DUAL TECHNOLOGY <br />os B <br />(LOW VOLTAGE) <br />WATTSTOPPER <br />LMDC-100 <br />CEILING <br />NOTE 5 <br />DUAL TECHNOLOGY WALL SWITCH <br />WATTSTOPPER <br />DSW-301 <br />WALL <br />GM <br />VS: VACANCY SENSOR (AUTO'ON' / AUTO'OFF) <br />LINE VOLTAGE <br />SENSOR SWITCH <br />WSD-PDT <br />WALL <br />NOTES 1,2 <br />OS: OCCUPANCY SENSOR (MANUAL 'ON' / AUTO 'OFF') <br />os <br />DIMMING PHOTO SENSOR <br />WATTSTOPPER <br />LMLS-400 <br />CEILING <br />NOTES 1,2 <br />D <br />LOW VOLTAGE DIGITAL WALL SWITCH, DIMMING <br />WATTSTOPPER <br />LMDM-101 <br />WALL <br />NOTES 1,2 <br />Rc <br />DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROLLER, <br />WATTSTOPPER <br />LMRC-211 <br />ABOVE CEILING <br />0-10V <br />t <br />SINGLE CONTACT <br />NOTES 1,2,3,4 <br />GDIGITAL <br />Rc <br />ON/OFF/0-10V DIMMING ROOM CONTROLLER, <br />WATTSTOPPER <br />LMRC-212 <br />ABOVE CEILING <br />0-10V <br />2 <br />DUAL CONTACT <br />NOTES 1,2,3,4 <br />Rc <br />E)WATTSTOPPER <br />DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROLLER, <br />LMRC-213 <br />ABOVE CEILING <br />3 <br />TRIPLE CONTACT <br />EPc <br />AUTOMATIC EMERGENCY POWER TRANSFER <br />WATTSTOPPER <br />ELCU-200 <br />WALL MOUNT <br />NOTE 2 <br />CONTROL <br />GENERAL NOTES: <br />A. REFER TO ELECTRICAL SPECIFICATIONS AND ADDITIONAL REQUIREMENTS WHICH MAY NOT NECESSARILY BE REFLECTED IN CATALOG NUMBER AND/OR DESCRIPTION IN <br />THE SCHEDULE. <br />NOTES: <br />1. CONTRACTOR SHALL PROVIDE THE APPROPRIATE NUMBER OF ROOM CONTROLLERS AND OCCUPANCY SENSORS FOR THE PROJECT. COORDINATE WITH THE <br />MANUFACTURER FOR THE CORRECT QUANTITY. <br />2. CONTRACTOR SHALL PROVIDE 4"x4" JUNCTION BOX AS REQUIRED. <br />3. ROOM CONTROLLER SHALL BE CONNECTED TO UNSWITCHED HOT. <br />4. MOUNT ROOM CONTROLLER ABOVE ACOUSTICAL CEILING TILE IN AN ACCESSIBLE LOCATION. <br />5. MULTIPLE OCCUPANCY SENSORS CONTROLLING A SINGLE SPACE SHALL BE WIRED IN PARALLEL. <br />6. ADD'ADCX' TO END OF NCM PDT 9 OR NCM PDT 10 FOR A COMBO SENSOR. <br />I <br />Emergency Light Fixture(s) <br />Unswitched Hot <br />Emergency <br />Ballast <br />I <br />witched Hot 0-10V <br />I <br />Neutral Dimming <br />H <br />Ballast mii I <br />I <br />---/ <br />Lj>l <br />INTEGRAL EMERGENCY BACK-UP APPLICATIONS <br />W <br />W <br />BALLAST W/INTEGRAL BATTERY PACK <br />Refer to Lighting Plan. <br />—_�--� <br />Wall Switch Under Cabinet Light Fixture(s) <br />pplicable. <br />Ff <br />ed Hot <br />H Non -Dimmable <br />N Ballast <br />_ — — —Ngutral— <br />— — <br />Normal Light Fixture(s) <br />Hot <br />Switched Ho[ H 0-10V <br />Unswitched <br />To DLM Lighting Control Panel for time control <br />(Omit for areas not requiring time control). <br />Daylight Harvesting Zones Only: Photosensor <br />Provide photosensor for light o <br />fixtures within 15ft of an exterior <br />fenestration. Refer to Lighting Plan. ® c <br />WIRING DIAGRAM IS TYPICAL. REFER TO <br />LIGHTING PLAN FOR ROOM SPECIFIC <br />CONTROLS AND PROVIDE ACCORDINGLY. <br />Dimming Room Controller 0 <br />Corner or 360 degree Os <br />DLM Occupancy Sensor A <br />mounted on ceiling. <br />Refer to plans. <br />Os <br />B <br />RJ45 Port <br />(Typical) <br />Class 2 0-10 Volt <br />Control Wiring <br />— Pre -Terminated <br />Cables or CAT5e. <br />LV Dimming Switch $L <br />0 <br />RJ45 <br />Connector <br />(Typical) <br />DLM ROOM CONTROLLER SCALE L1 <br />WIRING DIAGRAM N.T.S. <br />WALL SWITCH os <br />OCCUPANCY SENSOR <br />LINE VOLTAGE OCCUPANCY SENSOR SCALE L2 <br />WIRING DIAGRAM N.T.S. <br />DEDICATED EXHAUST FAN SCALE L3 <br />WIRING DIAGRAM N.T.S. <br />I Emergency Light Fixture(s) I <br />Unswitc of H <br />Emergency <br />IN Ballast <br />Switched Hot 0H Non -Dimmable I <br />Neutral N Ballast <br />I [Men's RR] I <br />INTEGRAL EMERGENCY BACK-UP <br />APPLICATIQNS: <br />BALLAST W/INTEGRAL BATTERY PACK — — -- — -- — — — — — —. — <br />Normal Light Fixture(s) <br />Switched Hot #1 H Non -Dimmable <br />Neutral N Ballast <br />[Men's RR] <br />IN <br />lh�sffi <br />UN <br />I� <br />I <br />I <br />INTEGRAL EMERGENCY BACK-UP <br />APPLICATIONS: <br />BALLAST W/ INTEGRAL BATTERY PACK — <br />If applicable. Refer to Lighting Plan. <br />I <br />l___ <br />Emergency Light Fiai..re(s) <br />Itched Hot <br />H Emergency <br />N <br />Ballast <br />H <br />Non -Dimmable <br />N <br />Ballast <br />[Women's RR] <br />— — — — — — — <br />_j <br />Normal Light Fixture(s) <br />hed Hot #2 <br />H Non -Dimmable <br />at <br />Ballast N t <br />[Women's RR] <br />— Normal Light Fixture(s) <br />#3 <br />N Non -Dimmable <br />al <br />Ballast <br />I <br />— — — — — — — — [Janitor's Closet] — <br />I <br />Non -Dimming Room Rc <br />Controller <br />Unswitched (2 or 3 relay 2s applicable) <br />For applications that do not U U U U <br />include a Janitor's Closet, <br />provide two relay room <br />controller. <br />Janitor's Closet <br />Men's RR Women's RR (When applicable) <br />Corner or 360 degree DLM Occupancy os os <br />Sensor mounted on ceiling. Refer to plans. A B <br />LV On/Off Switch <br />Janitor's Closet <br />Men's RR Women's RR (When applicable) <br />0 0 0 <br />$L <br />Switched <br />Neutral <br />Non -Dimming <br />Room Controller RC <br />RJ45 <br />Connector <br />(Typical) <br />Unswitched <br />RJ45 Port <br />(Typical) <br />Pre -Terminated <br />Cables or CAT5e. <br />D <br />Common <br />EF Exhaust <br />Fan <br />RJ45 Port <br />(Typical) <br />COMMON EXHAUST FAN SCALE L4 <br />WIRING DIAGRAM N.T.S. <br />FURNISH ONE WATTSTOPPER LMCT-100 DIGITAL WIRELESS <br />CONFIGURATION TOOL FOR OWNER'S USE WHEN PROJECT <br />SCOPE INCLUDES THE INSTALLATION OF NEW WATTSTOPPER <br />ROOM CONTROLLER. <br />Bank of Amenca,4w <br />ADA- ZEPHYRHILLS <br />5632 GALL BOULEVARD <br />ZEPHYRHILLS, FL 33542 <br />SERIAL NUM./MANH. ID: FL2-019 <br />Nelco Architecture, Inc. <br />a licensed affiliate <br />Florida Certificate of Authorization Number. W6000525 <br />Architect: Client Representative: <br />Firm Name: NELSON Firm Name: ILL <br />Attn: Mark Schroeder Attn: David Berrios <br />T: 404.881.1811 Tel.: 813.245.0909 <br />e-mail: mschroeder@nelsononline.com e-mail: David.Berrios@am.jll.com <br />Engineer: <br />Firm Name: Infinity Engineering Group, LLC. <br />Attn: Brett Nevaril <br />1208 E Kennedy Blvd, STE 230 <br />Tampa, FL 33602 <br />T:813.434-4770 <br />e-mail: brett@iegroup.net <br />Certification of Authorization #27889 <br />General Contractor: <br />Firm Name: Spartan Contracting Corporation <br />Attn: Scott Kramer <br />T: 813.481.5778 <br />e-mail: skramer@spartancc.com <br />IIssue Date & Issue Description By Check <br />1 04/23/18 Issue For Review KL CV <br />2 04/27/18 Issue For Permit KL CV <br />Seal/Signature <br />NISIT SAPPARKHAO, P.E. <br />FL REG. NO. 64085 <br />No 6 t 85 <br />'e-!3 STAT OF <br />s�QT� O R n <br />DATE <br />IProiect Name <br />Bank of America <br />Zephyrhills <br />NELSON Project Number <br />18.00358.00 / 10-65. <br />IDescription <br />ELECTRICAL DETAILS AND SCHEDULES <br />IScale & Sheet Number <br />AS INDICATED <br />E0101 <br />