GENERAL PLUMBING NOTES <br />ill <br />1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS. IT IS INTENDED THAT A <br />COMPLETE PLUMBING AND FIRE PROTECTION SYSTEM BE PROVIDED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS <br />COMPLETELY COORDINATED WITH ALL DISCIPLINES. ALL PARAMETERS GIVEN IN THESE DOCUMENTS SHALL BE STRICTLY CONFORMED TO. ANY <br />ITEMS AND LABOR REQUIRED FOR A COMPLETE PLUMBING AND FIRE PROTECTION SYSTEM IN ACCORDANCE WITH ALL APPLICABLE CODES, <br />STANDARDS, LOCAL AUTHORITIES AND THESE CONTRACT DOCUMENTS SHALL BE FURNISHED WITHOUT INCURRING ANY ADDITIONAL COST TO <br />THE OWNER. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS. <br />2. COORDINATE ALL WORK WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL TRADES. PIPE ROUTING SHOWN IS <br />DIAGRAMMATIC. PROVIDE ALL OFFSETS, ETC. TO AVOID INTERFERENCES WITH EQUIPMENT, PIPING, DUCT WORK, LIGHTS, CONDUITS, AND <br />STRUCTURAL ITEMS, ETC... <br />3. ALL DRAINAGE PIPING AND POTABLE WATER PIPING SHALL BE CONCEALED INSIDE WALLS AND PIPE CHASES OR ABOVE CEILINGS AS HIGH AS <br />POSSIBLE. <br />4. EXPOSED PIPING AT FIXTURES SHALL BE SECURED TO WALLS CONSTRAINED AGAINST ANY FREE -MOVEMENT OF PIPING. <br />5. CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL DOMESTIC WATER, SANITARY SEWERS, STORM DRAINS, FIRE SUPPLY AND GAS <br />SERVICES AT APPROXIMATELY 5'-0" FROM BUILDING STRUCTURE UNLESS OTHERWISE NOTED. <br />6. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR LOCATION OF ALL PLUMBING FIXTURES. EXACT LOCATION OF ALL PLUMBING <br />FIXTURES MUST BE VERIFIED IN FIELD PRIOR TO INSTALLATION. FINAL LOCATIONS AND HEIGHTS SHALL BE AS DIRECTED BY ARCHITECT. <br />7. PLUMBING CONTRACTOR SHALL MAKE FINAL CONNECTION TO ALL EQUIPMENT INDICATED ON DRAWINGS INCLUDING KITCHEN AND LAUNDRY <br />EQUIPMENT PER MANUFACTURER'S SPECIFIC INSTALLATION INSTRUCTIONS. FINAL CONNECTION SHALL INCLUDE ANY ADAPTERS, NIPPLES <br />SHUTOFF VALVES, PRESSURE REGULATING VALVES, SHOCK ABSORBERS, BACKFLOW PREVENTION DEVICES, ETC. CONTRACTOR SHALL <br />COMPLETELY REVIEW EACH EQUIPMENT ITEM'S INSTALLATION INSTRUCTIONS PRIOR TO COMMENCEMENT OF WORK. ALL ITEMS REQUIRED FOR <br />INSTALLATION ARE INCLUDED IN THE PLUMBING CONTRACTOR'S SCOPE. <br />8. DO NOT RUN PLUMBING OR FIRE PROTECTION PIPING THROUGH TRANSFORMER VAULTS, ELECTRICAL CLOSETS, ELECTRICAL SWITCHGEAR <br />ROOMS, ELEVATOR EQUIPMENT ROOMS, COMPUTER ROOMS OR TELEPHONE ROOMS. DO NOT RUN ANY PIPING ABOVE ELECTRICAL PANELS OR <br />OTHER ELECTRICAL/CONTROLS COMPONENTS. <br />9. ALL COMMERCIAL FIXTURES SPECIFIED BY AN EQUIPMENT PROVIDER SHALL OVERRIDE ANY SPECIFIED PLUMBING FIXTURES ON THIS PLAN. THE <br />PLUMBER SHALL COORDINATE FINAL REQUIRED FIXTURES WITH OWNER/EQUIPMENT SUPPLIER. VERIFY CONNECTION SIZE AND LOCATION OF <br />ALL ITEMS WITH KITCHEN EQUIPMENT DRAWINGS. <br />10.PROVIDE AN EXPANSION JOINT ON ALL PIPING SYSTEMS THAT CROSS BUILDING EXPANSION JOINTS. <br />11.PROVIDE CONNECTION TO EXISTING WATER SERVICE WHERE AVAILABLE. PROVIDE WATER METER, PRV STATION WITH FULL SIZE BYPASS, AND <br />RPZ VALVE. COORDINATE METER AND BACKFLOW REQUIREMENTS WITH LOCAL AUTHORITY AND UTILITY COMPANIES. CONNECT TO EXISTING <br />SANITARY AND KITCHEN WASTE STUB WHERE AVAIALBLE. CONNECTIONS TO EXISTING UTILITIES SHALL BE COORDINATED IN THE FIELD FOR <br />EXACT LOCATION AND INVERT AVAILABILITY. <br />12.PROVIDE GAS CONNECTION TO EXISTING METER WHERE POSSIBLE. PROVIDE CONNECTION TO ROOF MOUNTED EQUIPMENT AND TO KITCHEN <br />EQUIPMENT AS INDICATED ON KITCHEN EQUIPMENT DRAWING. PROVIDE SHUT-OFF VALVES AT ALL POINTS OF CONNECTION. PROVIDE <br />SOLENOID SHUT-OFF VALVE FOR GAS ITEMS UNDER KITCHEN HOODS. INTERLOCK SOLENOID WITH HOOD FIRE PROTECTION SYSTEM. GAS <br />PIPING SHALL NOT BE ROUTED BELOW FLOORS. PIPING INDICATED AS BELOW SLAB SHALL BE PROVIDED IN A PREFABRICATED MODULAR <br />STAINLESS STEEL UTILITY TRENCH. <br />13.ALL PLUMBING FIXTURES, PIPING, AND MATERIALS SHALL BE LISTED OR LABELED AND INSTALLED AS PER A RECOGNIZED APPROVAL AGENCY. <br />14.ALL WORK WITHIN THIS SCOPE OF WORK SHALL COMPLY WITH ALL CITY, STATE AND NATIONAL PLUMBING CODES. ALL WORK SHALL CONFORM <br />TO BUILDING STANDARDS. <br />15.PLUMBING CONTRACTOR SHALL VERIFY VOLTAGE, PHASE AND WIRE SIZE OF PLUMBING EQUIPMENT REQUIRING ELECTRICAL CONNECTION <br />WITH ELECTRICAL CONTRACTOR PRIOR TO PURCHASE OF EQUIPMENT <br />16.COORDINATE ALL FLOOR PENETRATIONS WITH STRUCTURAL DRAWINGS. THE PLUMBER SHALL SET SLEEVES IN FLOORS AND WALLS AND <br />ATTACHMENTS FOR HANGERS AS CONSTRUCTION PROGRESSES. COORDINATE THE EXACT SIZE AND LOCATION OF ALL SLEEVES WITH <br />STRUCTURAL ENGINEER. ALL PENETRATIONS MUST BE SEALED AND HELD AS TIGHT TO COLUMNS OR WALLS AS POSSIBLE. <br />17.COORDINATE ALL UNDERGROUND PIPING WITH GRADE BEAMS, WALL FOOTINGS, COLUMN FOUNDATIONS AND OTHER STRUCTURAL <br />CONDITIONS. <br />18.ALL DRAINAGE PIPING AND VENT PIPING SHALL SLOPE AT 1/8 INCH PER FOOT UNLESS OTHERWISE NOTED. <br />19.EXACT LOCATION OF ALL CLEANOUTS MUST BE COORDINATED AND APPROVED BY ARCHITECT PRIOR TO INSTALLATION. <br />20. SANITARY VENTS MUST TERMINATE A MINIMUM OF 10 FT. FROM OR 2 FT. ABOVE AIR INTAKES, WINDOWS OR VENT SHAFTS. <br />21. ALL HOSE BIBBS AND WASHDOWN FAUCETS ARE REQUIRED TO HAVE PROPER BACKFLOW PREVENTERS WHERE HOSES ARE ATTACHED AND <br />LEFT UNATTENDED. CHEMICAL FEED SYSTEMS AT COMMERCIAL KITCHENS SHALL HAVE DEDICATED BACKFLOW PREVENTERS SEPARATE FROM <br />WASHO-DOWN OR HOSE BIB FIXTURES. <br />22. PROVIDE 12" x 12" ACCESS PANELS FOR SHOCK ABSORBERS, TRAP PRIMERS AND ALL VALVES LOCATED ABOVE NON -ACCESSIBLE CEILINGS <br />AND INSIDE PIPE CHASES. EXACT LOCATION MUST BE COORDINATED WITH ARCHITECTURAL DRAWINGS AND APPROVED BY ARCHITECT PRIOR <br />TO INSTALLATION. ALL ACCESS PANELS SHALL BE LOCATED SO THAT THEY ARE NOT VISIBLE TO PUBLIC VIEW. <br />23. WALL HYDRANTS AND HOSE BIBBS SHALL BE MOUNTED 1' - 6" ABOVE GRADE OR FLOOR LEVELS. <br />24. PIPING INSULATION SHALL BE PROVIDED WITH CONTINUOUS AIR -TIGHT VAPOR BARRIER WITH NO LOOSE TAPE OR EXPOSED INSULATION <br />MATERIAL. CONDENSATE PIPING SHALL BE PROVIDED WITH ELECTROMETRIC INSULATION. ALL INSULATION AND WRAPPING JOINTS AND SEEMS <br />SHALL BE PROVIDED WITH 1 OVERLAP AND MANUFACTURER RECOMMENDED, AIR-TIGH MASTIC AT ANY INSULATION OR VAPOR BARRIER JOINTS. <br />INSULATION SHALL BE INSTALLED WITH FULL THICKNESS, FREE OF ANY INSULATION COMPRESSION, PROVIDE RIGID INSULATION SECTION AT <br />ALL PIPING HANGERS. <br />25. PROVIDE A VALVE BYPASS AT ALL EQUIPMENT INCLUDING WATER HEATERS, STORAGE TANKS WATER SOFTENERS, BOOSTER PUMPS, FIRE <br />PUMPS, ETCO FOR MAINTENANCE OF EQUIPMENT. <br />26. PROVIDE BALL VALVES AT ALL BRANCH LINES SERVING MULTIPLE FIXTURES. PROVIDE ACCESSIBLE BALL VALVE AT EACH FIXTURE <br />CONNECTION (IN ADDITION TO ANY EXPOSED STOPS) OR FIXTURE HEADER BRANCH CONNECTION. <br />27. ALL HAND -WASHING BASINS AND LAVATORIES INSTALLED SHALL BE EQUIPPED WITH HOT AND COLD WATER THROUGH A MIXING VALVE <br />UNLESS A TEMPERED WATER SUPPLY IS INDICATED. <br />28. INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF A FIXTURE SERVED WITH NO SHUT-OFF DEVICES BEYOND THE <br />DISCHARGE OF THE VACUUM BREAKER. <br />29. THE USE OF RISER CLAMPS TO SUPPORT VERTICAL PIPE ALONG WALLS, OR COLUMNS IS PROHIBITED. PROVIDE B-LINE 22 STRUT & B-2000 PIPE <br />CLAMPS <br />30. CONTRACTOR SHALL HANG ALL PIPING FROM THE STRUCTURAL MEMBERS (W-SHAPES, BAR JOISTS) WITH CLAMP -TYPE CONNECTIONS. PIPING <br />SHALL NOT BE SUPPORTED FROM THE METAL DECK. STRUCTURAL MEMBERS SHALL NOT BE CUT OR DRILLED. <br />31. ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS FOR FOOD <br />SERVICE AREAS. <br />32. ALL ANNULAR SPACES ARE TO BE CLOSED AND ESCUTCHEON PLATES AT HAND WASHING AREAS MUST BE SECURED. <br />33. INSTALL VACUUM BREAKERS A MINIMUM OF 6" ABOVE THE FLOOD LEVEL RIM OF THE FIXTURE SERVED WITH NO SHUT-OFF DEVICES BEYOND <br />THE DISCHARGE OF THE VACUUM BREAKER. <br />34, ALL JOINTS, ANNULAR SPACES, OR OPENINGS INTO HOLLOW OR INACCESSIBLE AREAS ARE TO BE CLOSED TO 1/32" OR LESS FOR FOOD <br />SERVICE AREAS. <br />CHROME WALLCI <br />AND SCREW <br />PLUGGED TEE <br />W/CLEANOUT <br />MAY EXTEND AS A <br />WASTE OR VENT <br />WALL <br />FLOOR LINE <br />WALL CLEAN OUT DETAIL <br />SCALE: NONE <br />BRASS FLOOR <br />� DRAIN COVER <br />I 1 12"X12" WHITE ENAMEL, <br />I I CAST IRON 3/4 GRATE FINISH FLOOR <br />I I DRAIN COVER <br />I <br />EQUIPMENT DRAIN 1 I <br />1 I •,!'r <br />1 I DOMED GRATE ; �.:• . <br />LJ <br />04 <br />CONCRETE SLAB <br />CONCRETE SLAB ALL FLOOR SINKS MUST BE DEEP SEAL <br />FLUSH WITH THE CONCRETE SLAB TRAP <br />FLOOR DRAIN <br />SCALE: NONE <br />LAP SEALANT <br />S/S CLAMPING RING <br />PRE -MOLDED PIPE <br />FLASHING BOOT.- , <br />ATTACH BOOT TO ROOF <br />PER ROOF MFR --s <br />RECOMMENDATIONS. <br />TO INDOOR GAS <br />EQUIPMENT <br />PRESSURE REGULATOR <br />WITH INTERNAL VENT. <br />STEEL SLEEVE WELD TO <br />STRUCTURE AND FILL WITH <br />WATER PROOF MASTIC <br />GAS PIPING RUN TIGHT TO <br />BOTTOM OF STRUCTURE <br />GROUND JOINT UNION <br />GAS COCK WITH PLUGGED 1/8" <br />NPT TEST GAUGE CONNECTION <br />DRIP/DIRT POCKET <br />2" MIN, TYP <br />ROOF <br />GAS PIPING DETAIL- ROOF INSTALLATION <br />GAS PIPING ON ROOF. SEE <br />P200 FOR ROUTING. <br />GAS PIPE ADJUSTMENT AT <br />ROOF OBSTRUCTIONS <br />TYPICAL <br />PILLOW BLOCK MODEL 3-R <br />SHOWN. MODEL 1.5 MAY BE <br />USED FOR SMALLER <br />PIPING. <br />BACKFLOW PREVENTER MATRIX <br />MODEL <br />SERVES <br />TYPE <br />IPC LISTING <br />WATTS 009 <br />WATER SERVICE OUTDOOR <br />RPZ <br />ASSE 1013 <br />WATTS SD-3 <br />CARBONATOR <br />CO2 CHECK <br />ASSE 1022 <br />WATTS 7 <br />FOOD SERVICE WATER FILTER <br />DOUBLE CHECK <br />ASSE 1024 <br />WATTS 7 <br />RINSE FAUCETS MULTI COMP SINK <br />DOUBLE CHECK <br />ASSE 1024 <br />INTEGRAL TO FIXTURE <br />HOSE BIB <br />DOUBLE CHECK <br />ASSE 1052 <br />WATTS 7 <br />CHEMICALS DISP. <br />DOUBLE CHECK <br />ASSE 1024 <br />WATTS SD-3 <br />CARBONATED DRINK DISPENSER <br />CO2 CHECK <br />ASSE 1022 <br />WATTS 7 <br />ICE MAKER <br />DOUBLE CHECK <br />ASSE 1024 <br />WATTS 7 <br />NON -GARB DRINK DISPENSER <br />DOUBLE CHECK <br />ASSE 1024 <br />WATTS 288A <br />WATER HEATER VACUUM BREAKER <br />VACUUM BREAKER <br />ASSE 1001 <br />NOTES: <br />1. PROVIDE HANGING ALUMINUM TAG FOR EACH BFP WITH THE BFP DESIGNATOR AND LISTING ETCHED IN AS INDICATED ABOVE. <br />2. TENANT SHALL PROVIDE TESTING FOR EACH BFP AT THE TIME OF ISNTALLATION/RELOCATION AND ANNUALLY THEREAFTER <br />3. TESTING PROCEDURES TO BE PERFOMED PER LOCAL CODE <br />4. MOUNT WITH BFP ACCESSIBLE FOR TESTING/REPAIR AT A MINIMUM 1" ABOVE FLLOR AND MAXIMUMS ABOVE FLOOR <br />5. PROVIDE ACCESS PANELS FOR BFP THAT ARE INSTALLED WITHIN WALLS WHERE SURFACE MOUNTING IS NOT POSSIBLE. <br />6. PROVIDE IN ACCORDANCE WITH THE REQUIREMENTS OF LOCAL CODE. <br />7. ALL BFP MUST BE LEAD FREE ASSEMBLY <br />END <br />PLUMBING FIXTURE SCHEDULE <br />FIXTURE TAG <br />DRAIN <br />VENT <br />CW <br />HW <br />GAS <br />FIXTURE DESCRIPTION <br />FIXTURE SPECIFICATION <br />VALVE/FACUET SPECIFICATION <br />WC-1 <br />3 <br />1-1/2" <br />1-1/4" <br />SLOAN <br />VITREOUS CHINA, FLOOR MOUNTED SIPHON JET, 1-1/2" TOP SPUD; CENTOCO 500 STSCCSS, EXTRA HEAVY DUTY <br />INTEGRAL PRESSURE ASSIST <br />ADA FLOOR WATER CLOSET <br />1" CON. <br />ST-2003-1.6 <br />SOLID PLASTIC, ELONGATED OPEN FRONT SEAT, WHITE, INSTALLED PER ADA REQUIREMENTS <br />LV-1 <br />1-1/2" <br />1-1/4" <br />1/2" <br />1/2" <br />KOHLER GREENWICH <br />VITREOUS CHINA, 20"X18" WALL HUNG 4" CENTERS, WITH OVERFLOW AND GRID DRAIN, JAY R. SMITH 0700-M31 <br />DELTA 2529 LF <br />WALL LAVATORY <br />K-2030 <br />SERIES CARRIER. PROVIDE CHROME PLATED LOOSE KEY ANGLE STOP, ESCUTCHEON, P-TRAP AND SUPPLIES. <br />0.5GPM VANDAL RESISTANt AERATOR <br />INSTALLED PER ADA ACCESSIBILITY; TRUEBRO LAV GUARD UNDERSINK PROTECTIVE COVERS FOR P-TRAP AND <br />ANGLE VALVE ASSEMBLIES MODEL 102 <br />MS-1 <br />3" <br />1-1/2" <br />3/4" <br />3/4" <br />FIAT <br />ONE PIECE SERVICE BASIN; AND 3.0 GPM FLOW RESTRICTOR; DELTA 28T910 STAINLESS STEEL MOP HOLDER; <br />DELTA 28T9 <br />MOP SERVICE BASIN <br />MSB-2424 <br />28T911 HEAVY DUTY 31" LONG REINFORCED HOSE, BRASS COUPLING, STAINLESS STEEL HANGER BRACKET, <br />WITH INTERGRAL VACUUM BREAKER <br />FD-1 <br />3" <br />1-1/2" <br />JAY R. SMITH <br />CAST IRON BODY WITH NICKEL BRONZE GRATE, 8-1/2" ROUND GRATE; SEDIMENT BUCKET; VANDLE PROOF GRATE; <br />FLOOR DRAIN <br />2210.00 <br />P050 TRAP PRIMER OPTION. CAST IRON GRATES NOT PERMITTED. <br />FS-1 <br />3" <br />JAY R. SMITH <br />CAST IRON FLANGED RECEPTOR WITH SEEPAGE HOLES; ACID RESISTANT COATED INTERIOR; 8-1/2" NICKEL BRONZE <br />FLOOR SINK <br />3100.00 <br />RIM AND SECURED GRATE; SEDIMENT BUCKET; P-050 TRAP PRIMER OPTION. CAST IRON GRATES NOT PERMITTED. <br />FCO <br />4" <br />JAY R. SMITH <br />CAST IRON CLEANOUT; NICKEL BRONZE 6" ROUND ADJUSTABLE SCORIATED VANDAL PROOF TOP; GASKET SEAL <br />FLOOR CLEAN OUT <br />4020S <br />ABS THREADED PLUG WITH SLOT TO RECEIVE 1/2" BAR STOCK. ARFCO- ACID RESITANT OPTION. <br />WCO <br />4" <br />JAY R. SMITH <br />CAST IRON SPIGOT FERRULE; CAST BRONZE TAPER THREADED COUNTERSUNK PLUG WITH SLOT TO RECEIVE 1/2" <br />WALL CLEAN OUT <br />4420.00 <br />BAR STOCK <br />UR-1 <br />2 <br />1-1/4" <br />3/4" <br />SLOAN <br />VITREOUS CHINA, WALL HUNG SIPHON JET WITH FLUSHING RIM, 3/4" TOP SPUD; JAY R. SMITH 0644 FLOOR CARRIER. <br />URINAL <br />SU-1005-.5 <br />MOUNT UR-2 AT HANDICAP HEIGHT. <br />GCO <br />4" <br />JAY R. SMITH <br />CAST IRON SPIGOT FERRULE; CAST BRONZE TAPER THREADED COUNTERSUNK PLUG WITH SLOT TO RECEIVE 1/2" <br />GRADE CLEAN OUT <br />4261L <br />WHA <br />JAY R. SMITH 5000 SERIES <br />STAINLESS STEEL PRESSURIZED COMPRESSION CHAMBER; THREADED NIPPLE CONNECTION; SIZE AS INDICATED <br />WATER HAMMER ARRESTOR <br />MXV-1 <br />1/2" <br />POWERS <br />MIXING VALVE, SOLID BRASS WITH INTEGRAL CHECK. THREADED UNION CONNECTIONS. ASSE1017 <br />MIXING VALVE <br />LM495- SINGLE FIXTURE <br />MXV-2 <br />3/4" <br />POWERS <br />MIXING VALVE, SOLID BRASS WITH INTEGRAL CHECK. THREADED UNION CONNECTIONS. ASSE1017 <br />MIXING VALVE <br />LM491 MULTI -FIXTURE VALVE <br />1. ALL FIXTURES, EQUIPMENT, TRIM, FITTINGS, ETC. SHALL COMPLY WITH LOCAL, STATE AND/OR FEDERAL REGULATIONS AND CODES, INCLUDING BUT NOT LIMITED TO WATER AND ENERGY CONSERVATION CODES, AND THE AMERICANS WITH DISABILITIES ACT (ADA). THE SCHEDULE REFLECTS <br />FIXTURES AND EQUIPMENT WHICH ARE MINIMUM CRITERIA AND SHALL BE THE BASIS FOR CONTRACTORS BASE BID. WHERE SPECIFIED FIXTURES AND/OR EQUIPMENT ARE NOT IN COMPLIANCE WITH GOVERNING CODES AND REGULATIONS, THE CONTRACTOR SHALL PROVIDE AN ALTERNATE BID FOR <br />THE SUBSTITUTIONS OF COMPLYING FIXTURES EQUIPMENT FITTINGS ETC. THE ABSENCE OF AN ALTERNATE BID SHALL BE CONSTRUED TO MEAN THAT THE CONTRACTORS BASE BID INCLUDES ALL COSTS NECCESSARY TO MEET ALL REGULATIONS AND CODES. <br />WALL PLATE <br />1/4" CLOSE NIPPLE HINGED <br />---- -- / / FPIPE GER <br />OR 1i" PPE <br />u <br />1 1/4" MAX UNDER HOOD <br />PIPE SUPPORT DETAIL <br />SCALE: NONE <br />AVOID DIRECT INSTALLATION <br />TO PREVENT FOREIGN <br />MATERIAL FROM ENTERING <br />DIRECTLY INTO PRIMER <br />-TRAP PRIMER VALVE <br />-BACK FLOW PREVENTER <br />VACUUM BREAKER PORTS <br />PETERSON PLUMBING <br />PRODUCTS P2-500 TRAP SEWER <br />PRIMER OR EQUAL <br />TRAP PRIMER VALVE SHOULD ATER <br />BE MOUNTED V ABOVE THE <br />FINISHED FLOOR FOR EVERY <br />20' OR PRIMER LINE. <br />TRAP PRIMER DETAIL <br />SCALE: NONE <br />WATER HEATER SCHEDULE <br />LAYOUT <br />STORAGE <br />GAS INPUT <br />OUTPUT <br />ELECTRICAL <br />GPH RECOVERY <br />TEMP <br />ELEC <br />EXPANSION TANK <br />MARK <br />TYPE <br />BASIS <br />GALLONS <br />MBH <br />MBH <br />CAPACITY KW <br />980 DEG RISE <br />SETTING <br />VOLT/PHASE <br />ACCPETANCE GAL <br />WH-1 <br />GAS - INSTANT <br />NORITZ MC 380 <br />-- <br />380 <br />361 <br />-- <br />173.00 <br />140 <br />120/1 <br />-- <br />1. PROVIDE CONDENSATE NUETRALIZER AND CONDENSATE TRAP FOR WATER HEATER. ROUTE CONDENSATE TO EXTERIOR OR FLOOR DRAIN. <br />2. PROVIDE REGULATOR FOR WATER HEATER SERVED BY GAS PIPING PRESSURE GREATER THAN 10" WC. PROVIDE GAS SHUTOFF AT EACH WATER HEATER <br />3. PROVIDE INDIVIDUAL FIXTURE MIXING VALVES SET TO 110 DEGREES FOR HAND WASHING FIXTURES. <br />4. PROVIDE PVC FLUE AND COMBUISTION AIR VENT ITH WITH ACCESSORY TERMINATION KIT PER <br />MFG INSTRUCTION. <br />NICKLE BRONZE ADJUSTABLE <br />SCORIATED SECURED COVER. <br />FLUSH WITH <br />FLOOR BRONZE TAPER THREAD PLUG <br />LINE r�_ WITH COUNTER SUNK HEAD <br />45° WYE AND 118TH BEND <br />FITTING OR COMBINATION <br />FITTING <br />WASTE LINE LENGTH <br />TO SUIT <br />i , 11 11 FLOW <br />NOTE: <br />CLEAN -OUT TO BE J.R. SMITH MODEL 4100-F SERIES OR EQUAL INSTALLATION SHALL BE <br />FLUSH WITH SURROUNDING FLOOR SURFACES. <br />FLOOR CLEANOUT DETAIL <br />r <br />N <br />COPPER OR LEAD SLEEVE <br />WITH FLANGE <br />I <br />18" MAX <br />r VENT PIPE CONTINUOUS CONTINUOUS <br />4" ( ROOF MASTIC WELD JOINTS _ _ WELD JOINTS <br />I <br />I <br />ROOF DECK ROOF DECK BOLTS W/NUTS- ` - - THREADED JOINT VALVE <br />I WELDED FLANGES <br />I PACK W/OAKUM OR EQUAL WALL BRACKET SUPPORT <br />i MATERIAL TO PREVENT WITHIN 12" OF FLANGES <br />ASPHALT DRAINAGE <br />GAS SHUTOFF VALVES DETAIL <br />VENT THRU ROOF (MOUNT VERTICALLY) <br />SCALE: NONE SCALE: NONE <br />&P VALVE <br />DRAIN VALVE <br />/4" GAS <br />DRAIN <br />NATURAL GAS INST. WATER HEATER DETAIL <br />�Q <br />• <br />U <br />ICI <br />V <br />0 <br />Z <br />c� <br />A <br />CV <br />Q <br />Q <br />00 <br />vc/) <br />� <br />UJ <br />.V <br />�C/) co00 <br />coz <br />r- UJ <br />U�UDa�-J <br />EW�Qr"v <br />UJ <br />�z>U>C'oU <br />I- <br />�N> <br />� <br />N <br />Q <br />ui <br />z <br />D <br />In <br />MM• <br />h� <br />• <br />I� <br />w <br />Y <br />U <br />z <br />Q <br />Do <br />LU <br />W <br />J <br />mm <br />CONTRACT DATE: 08.13.2017 <br />BUILDING TYPE: ONE-OFF <br />PLAN VERSION: <br />SITE NUMBER: <br />STORE NUMBER: <br />SUNRISE EATERY <br />5915 GALL BLVD. <br />ZEPHYRHILLS, FL <br />PLUMBING <br />SCHEDULES <br />AND DETAILS <br />Po. 1 <br />FLOOR SINK <br />SCALE: NONE <br />PLOT DATE: <br />