COMMERCIAL LOAD SUMMARY <br />BUILDING AREA: 1,829 SO. FT VOLTAGE: 208Y/120V, 3PH, 4W <br />LOAD DESCRIPTION <br />CONNECTED <br />LOAD (VA) <br />DEMAND <br />FACTOR <br />DEMAND <br />LOAD (VA) <br />LIGHTING <br />INTERIOR LIGHTING <br />1,504 <br />x <br />125% <br />= <br />0 <br />EXTERIOR LIGHTING <br />0 <br />x <br />125% <br />= <br />0 <br />SIGNAGE <br />1,200 <br />x <br />125% <br />= <br />1,500 <br />MINIMUM GENERAL LIGHTING PER NEC-220 x 125% <br />4,573 <br />MINIMUM TRACK LIGHTING/SHOW WINDOW PER NEC-220 x 125% <br />5,688 <br />POWER & HVAC <br />EXISTING <br />0 <br />x <br />100% <br />= <br />0 <br />RECEPTACLES <br />1,620 <br />x <br />100%;50% <br />= <br />1,620 <br />MISCELLANEOUS EQUIPMENT <br />11,601 <br />x <br />100% <br />= <br />11,601 <br />REFRIGERATION EQUIPMENT <br />8,575 <br />x <br />100% <br />= <br />8,575 <br />KITCHEN <br />16,364 <br />x <br />65% <br />= <br />10,637 <br />HVAC- SUMMER <br />18,157 <br />x <br />100% <br />= <br />18,157 <br />HVAC - WINTER <br />0 <br />x <br />100% <br />= <br />0 <br />SUPP, ELECTRIC HEAT <br />216 <br />x <br />100% <br />= <br />216 <br />MOTORS <br />7,849 <br />x <br />100% <br />= <br />7,849 <br />LARGEST MOTOR <br />1,224 <br />x <br />25% <br />= <br />306 <br />SUB -TOTAL (VA) 68,310 SUB -TOTAL (VA) <br />SUB -TOTAL (AMPS) 190 SUB -TOTAL (AMPS) <br />SERVICE SIZE (AMPS) <br />SPARE CAPACITY (AMPS) <br />70,721 <br />196 <br />400 <br />204 <br />REUSE EXISTING CONDUIT AND CONDUCTORS <br />FROM EXTERIOR SERVICE ENTRANCE <br />EQUIPMENT TO EXISTING PANELBOARD'A' <br />WITHIN SPACE. VERIFY THAT THE EXISTING <br />SERVICE IS 400A AT 208Y/120V, 3PH, 4W. <br />PROVIDE ISOLATED GROUND WIRE FROM <br />PANELBOARD 'B' BACK TO POINT OF <br />NEUTRAL/GROUND BOND AT SERVICE <br />ENTRANCE EQUIPMENT IF NOT CURRENTLY <br />ELECTRIC SERVICE LOAD SUMMARY 17 1 <br />HCP <br />HCP <br />HCP <br />GF <br />HCP <br />HCP <br />HCP <br />GF,HCP <br />GF <br />GF <br />GF <br />GF <br />GF <br />TS,EM <br />GF,IG <br />GF,IG <br />TS <br />PANELBOARD A (EXISTING) <br />BUS AMPS: 400A LOCATION: BACK OF HOUSE GROUND BUS: YES <br />MAIN SIZE / TYPE: MLO NEMA RATING: NEMA 1 ISOL. GROUND BUS: NO <br />VOLTS/PHASE: 208Y/120V, 3PH, 4W AFC VALUE: VERIFY FEED THRU LUGS: NO <br />MOUNTING: SURFACE AIC RATING: EXISTING SECTIONS: 1 OF 1 <br />CKT <br /># <br />CIRCUIT <br />DESCRIPTION <br />BREAKER <br />WIRE <br />SIZE <br />LOAD <br />(VA) <br />CONNECTED PER PHASE (VA) <br />LOAD <br />(VA) <br />WIRE <br />SIZE <br />BREAKER <br />CIRCUIT <br />DESCRIPTION <br />CKT <br /># <br />AMPS <br />I P <br />A B C <br />P <br />AMPS <br />1 <br />EF-1 <br />15 <br />1 <br />12 <br />1,056 <br />2,101 _ _ <br />2,2 69 <br />1,573 <br />1,825 <br />1 1,545 <br />2,293 <br />2,059 <br />2,059 <br />1 1,572 <br />4,214 <br />L4,214 _ <br />3,866 <br />4,226 <br />L4,226 <br />1 3,086 <br />3,974 <br />3,478 <br />4,238 <br />4,405 <br />5,761 <br />4,105 <br />1,045 <br />12 <br />3 <br />20 <br />WALK-IN FREEZER COND <br />(W1-004)(ICS) <br />2 <br />3 <br />SF-1 <br />20 <br />1 <br />12 <br />1,224 <br />1,045 <br />4 <br />5 <br />EF-2 <br />15 <br />1 <br />12 <br />528 <br />1,045 <br />6 <br />7 <br />VISICOOLER (R2-008) <br />20 <br />1 <br />12 <br />780 <br />1,045 <br />12 <br />3 <br />20 <br />WALK-IN COOLER COND <br />(W1-004)(ICS) <br />8 <br />9 <br />HOOD CONTROL PANEL POWER & HOOD LTS <br />15 <br />1 <br />12 <br />500 <br />1,045 <br />10 <br />11 <br />OVEN #1 (C3-015) <br />20 <br />2 <br />12 <br />1,248 <br />1,045 <br />12 <br />13 <br />1,248 <br />811 <br />12 <br />2 <br />15 <br />WALK-IN FREEZER EVAP <br />14 <br />15 <br />OVEN #2 (C3-015) <br />20 <br />2 <br />12 <br />1,248 <br />811 <br />16 <br />17 <br />1,248 <br />324 <br />12 <br />1 <br />15 <br />WALK-IN COOLER EVAP <br />18 <br />19 <br />OVEN #3 (C3-015) <br />20 <br />2 <br />12 <br />1,248 <br />2,966 <br />8 <br />3 <br />35 <br />RTU-3 <br />20 <br />21 <br />1,248 <br />2,966 <br />22 <br />23 <br />FRYER (C2-002) <br />20 <br />1 <br />12 <br />900 <br />2,966 <br />24 <br />25 <br />PROOFER (P3-003) <br />20 <br />2 <br />12 <br />1,920 <br />2,306 <br />8 <br />3 <br />35 <br />RTU-1 <br />26 <br />27 <br />1,920 <br />2,306 <br />28 <br />29 <br />VISICOOLER (R2-007) <br />20 <br />1 <br />12 <br />780 <br />2,306 <br />30 <br />31 <br />MAKETABLE (P2-001) <br />20 <br />1 <br />12 <br />1,536 <br />2,438 <br />1 10 <br />3 <br />30 <br />RTU-2 <br />32 <br />33 <br />REACH -IN FREEZER (R3-005) <br />20 <br />1 <br />12 <br />1,040 <br />2,438 <br />34 <br />35 <br />DISHWASHER (Z3-002) <br />20 <br />1 <br />12 <br />1,800 <br />2,438 <br />36 <br />37 <br />ROOF TOP RCPTS <br />20 <br />1 <br />12 <br />540 <br />3,865 <br />SR <br />3 <br />100 <br />PANELBOARD'B' <br />38 <br />39 <br />HOLDING CABINET (S15-003) <br />30 <br />1 <br />10 <br />2,316 <br />3,445 <br />40 <br />41 <br />WINGSTREET REFRIGERATOR (R4-013) <br />15 <br />1 <br />12 <br />360 <br />3,745 <br />42 <br />PER PHASE SUB -TOTALS <br />22,803 23,551 20,732 <br />LEGEND: <br />TOTAL CONNECTED PANELBOARD (VA) 67,086 TS -VIA TIME SWITCH ST - SHUNT TRIP <br />TOTAL CONNECTED PANELBOARD (AMPS) 186 GF - GROUND FAULT INTERRUPTER LCK - PAD LOCKABLE BREAKER <br />TOTAL PANELBOARD DEMAND (VA) 68,046 FA - FIRE ALARM / RED / LOCKING TAB IN OPEN POSITION <br />TOTAL PANELBOARD DEMAND (AMPS) 189 EM - EMERGENCY LTG. / LOCKING TAB IG - ISOLATED GROUND <br />HCP - ROUTE VIA HOOD CONTROL PANEL SR - RE: SERVICE RISER <br />PANELBOARD B <br />BUS AMPS: <br />MAIN SIZE / TYPE: <br />VOLTS/PHASE: <br />MOUNTING: <br />125A <br />MLO <br />208Y/120V, 3PH, 4W <br />SURFACE <br />LOCATION: <br />NEMA RATING: <br />AFC VALUE: <br />AIC RATING: <br />BACK OF HOUSE <br />NEMA 1 <br />VERIFY <br />MATCHING EXISTING <br />GROUND BUS: YES <br />ISOL. GROUND BUS: YES <br />FEED THRU LUGS: NO <br />SECTIONS: 1 OF 1 <br />CKT <br /># <br />CIRCUIT <br />DESCRIPTION <br />BREAKER <br />WIRE <br />SIZE <br />LOAD <br />(VA) <br />CONNECTED PER PHASE (VA)__]I <br />LOAD <br />(VA) <br />WIRE <br />SIZE <br />BREAKER <br />CIRCUIT <br />DESCRIPTION <br />CKT <br /># <br />AMPS <br />P <br />A B C <br />P <br />AMPS <br />1 <br />COOLER/FREEZER LIGHTS <br />20 <br />1 <br />12 <br />400 <br />609 <br />680 1 <br />L1,440 <br />1,216 <br />L614 <br />1,360 <br />0 <br />1,391 <br />0 <br />0 <br />685 <br />1,560 <br />1,000 <br />500 <br />0 <br />209 <br />12 <br />1 <br />20 <br />FRONT AREA & EM LIGHTS <br />2 <br />3 <br />BACK AREA & EM LIGHTS <br />20 <br />1 <br />12 <br />851 <br />540 <br />12 <br />1 <br />20 <br />SHOW WINDOW RCPT <br />4 <br />5 <br />COOLER/FREEZER POWER <br />20 <br />1 <br />12 <br />500 <br />185 <br />12 <br />1 <br />20 <br />CUSTOMER CASH OUT MONITOR <br />6 <br />7 <br />POS AT TELEPHONE BOARD <br />20 <br />1 <br />12 <br />180 <br />500 <br />12 <br />1 <br />20 <br />COMPUTER <br />8 <br />9 <br />(2) KMS AT MAKETABLE <br />20 <br />1 <br />12 <br />1,440 <br />0 <br />1 <br />20 <br />SPARE <br />10 <br />11 <br />FRONT SIGNAGE <br />20 <br />1 <br />1 12 <br />1,200 <br />360 <br />12 <br />1 <br />20 <br />CONVENIENCE RCPTS <br />12 <br />13 <br />WATER HEATER (Z13-003) <br />20 <br />1 <br />12 <br />216 <br />1,000 <br />12 <br />1 <br />20 <br />POS #1/#3 <br />14 <br />15 <br />RR/EF-3 & EM LIGHTS <br />20 <br />1 <br />12 <br />114 <br />500 <br />12 <br />1 <br />20 <br />POS #2 <br />16 <br />17 <br />SPARE <br />20 <br />1 <br />0 <br />1,000 <br />12 <br />1 <br />20 <br />POS #4/#5 <br />18 <br />19 <br />LIGHTING CONTROLS <br />20 <br />1 <br />12 <br />360 <br />1;000 <br />12 <br />1 <br />20 <br />POS #6/#7 <br />20 <br />21 <br />SPARE <br />20 <br />1 <br />0 <br />0 <br />1 <br />20 <br />SPARE <br />22 <br />23 <br />SPARE <br />20 <br />1 <br />0 <br />500 <br />12 <br />1 <br />20 <br />BACK CASH OUT <br />24 <br />25 <br />SPARE <br />20 <br />1 <br />0 <br />0 <br />1 <br />20 <br />SPARE <br />26 <br />27 <br />SPARE <br />20 <br />1 <br />0 <br />0 <br />1 <br />20 <br />SPARE <br />28 <br />29 <br />SPARE <br />1 20 <br />1 <br />1 <br />1 0 11 <br />0 <br />1 <br />1 20 <br />ISPARE <br />30 <br />PER PHASE SUB -TOTALS <br />3,865 <br />3,445 <br />3,745 <br />1 LEGEND: <br />TOTAL CONNECTED PANELBOARD (VA) <br />TOTAL CONNECTED PANELBOARD (AMPS) <br />TOTAL PANELBOARD DEMAND (VA) <br />TOTAL PANELBOARD DEMAND (AMPS) <br />11,054 <br />31 <br />17,435 <br />48 <br />TS - VIA TIME SWITCH ST - SHUNT TRIP <br />GF - GROUND FAULT INTERRUPTER LCK - PAD LOCKABLE BREAKER <br />FA - FIRE ALARM / RED / LOCKING TAB IN OPEN POSITION <br />EM - EMERGENCY LTG. / LOCKING TAB IG - ISOLATED GROUND <br />LC - LIGHTING CONTACTOR OL - RE: ONE -LINE DIAGRAM <br />NOTE: <br />ALL CONDUCTORS SHALL BE COPPER, WITH <br />THWN/THHN INSULATION. <br />NOTE: <br />CONTRACTOR TO VERIFY IF EXISTING PANEL WITHIN SPACE CAN BE REUSED. FIELD VERIFY PANEL SIZE AND <br />VERIFY EXISTING PANEL MATCHES INFORMATION LISTED HERE. PROVIDE ALL NEW CIRCUIT BREAKERS AS <br />SCHEDULED. CONTRACTOR IS RESPONSIBLE TO PROVIDE NEW PANEL'B' AS SHOWN ON PLANS. <br />NOTE: <br />ALL HOOD, OVEN AND FRYER CIRCUITS ARE TO BE ROUTED FROM PANELBOARD 'A', THROUGH THE HOOD <br />CONTROL PANEL, THEN TO FINAL TERMINATION POINT. REFER TO PANELBOARD SCHEDULE FOR HOOD CONTROL <br />PANEL CIRCUIT DESIGNATION. <br />TS,EM <br />IG <br />GF,IG <br />IG <br />GF,IG <br />GF,IG <br />GF,IG <br />GF,IG <br />1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC <br />CODE (NEC), THE AMERICANS WITH DISABILITIES ACT (ADA), AND ALL STATE AND LOCAL <br />REQUIREMENTS AND CODES. <br />2. REFER TO RELATED ARCHITECTURAL AND MECHANICAL DRAWINGS FOR RELATED INFORMATION <br />AND EQUIPMENT DESCRIPTIONS. <br />3. ALL LIGHTING FIXTURES AND MECHANICAL EQUIPMENT SHALL BE COMPLETELY CONNECTED BY <br />ELECTRICAL CONTRACTOR (BOTH POWER AND CONTROL WIRING). <br />4. ALL NEW LIGHTING FIXTURES SHALL BE FURNISHED WITH LAMPS. <br />5. ALL NEW TELEPHONE OUTLETS SHALL HAVE 3/4" CONDUIT WITH PULL WIRES ROUTED TO <br />TELEPHONE TERMINAL BOARD. CONDUIT SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR. <br />VERIFY TELEPHONE REQUIREMENTS WITH LOCAL TELEPHONE COMPANY. <br />6. VERIFY ALL OUTLET LOCATIONS ON THE JOB PRIOR TO ROUGH -IN. <br />7. PANELBOARDS SHALL BE U.L. LISTED FOR A MINIMUM 22,000 AIC FAULT CURRENT. CONTRACTOR <br />TO COORDINATE WITH SERVING UTILITY COMPANY AND LANDLORD TO PROVIDE PANELBOARDS <br />PROPERLY BRACED FOR AVAILABLE FAULT CURRENT. <br />8. PROVIDE TYPEWRITTEN SCHEDULE INDICATING EQUIPMENT DESCRIPTION AND/OR LOCATION FOR <br />EACH CIRCUIT IN PANEL DOOR. <br />9. SAFETY SWITCHES SHALL BE GENERAL DUTY WITH CLASS "J" FUSE CLIPS. <br />10. FUSES SHALL BE BUSSMAN LPJ OR EQUAL BY GOULD SHAWMUT OR LITTLE FUSE. <br />11. PROVIDE SWITCH DUTY BREAKERS FOR CIRCUITS BEING SWITCHED AT PANEL. <br />12. PROVIDE HACR TYPE BREAKERS FOR ALL HVAC EQUIPMENT. <br />13. ALL BREAKERS SHALL BE 1" BREAKERS. ELECTRICAL CONTRACTOR SHALL NOT PLACE (2) CIRCUIT <br />BREAKERS IN (1) CIRCUIT BREAKER SPACE (I.E. TANDEM BREAKER OR 1/2" BREAKER). <br />14. USE ONLY INSULATED COPPER CONDUCTORS IN CONDUIT. CONDUCTORS SHALL BE SIZED PER <br />DRAWINGS AND N.E.C. (MINIMUM # 12 COPPER) MINIMUM CONDUCTOR INSULATION SHALL BE TYPE <br />"THWN/THHN" FOR ALL CONDUCTORS. NO ROMEX ALLOWED. A GROUND WIRE SIZED PER N.E.C. ART, <br />250-66 (SERVICE GROUND) OR N.E.C. ART. 250-122 (EQUIPMENT GROUND) SHALL BE PULLED IN ALL <br />CONDUIT. <br />15. ALUMINUM CONDUCTORS ARE SPECIFICALLY PROHIBITED. <br />16. COMPLETE SYSTEM SHALL BE GROUNDED PER N.E.C. ARTICLE 250-66. <br />17. ISOLATED GROUND OUTLETS: CONNECT PANEL B ISOLATED GROUND BUS TO SYSTEM GROUND AT <br />PANEL A. RUN ISOLATED GROUND IN SAME CONDUIT WITH CIRCUIT CONDUCTORS. <br />18. ALL CONDUIT WILL BE INSTALLED CONCEALED IN WALLS OR ABOVE ACCESSIBLE CEILING TILES. DO <br />NOT EXPOSE CONDUIT. <br />19. PROVIDE ELECTRICAL DEVICES AND WIRING TO COMPLY WITH N.F.P.A. 96.7-3.1.3 FOR POWER <br />SHUT-OFF ON ALL ELECTRICAL EQUIPMENT UNDER OVEN HOOD. VERIFY INSTALLATION AND <br />OPERATION REQUIREMENTS WITH EXTINGUISHING SYSTEM SUPPLIER. <br />20. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS FOR CLARITY ONLY, CONTRACTOR <br />MAY GROUP SINGLE POLE BRANCH CIRCUITS IN MULTIPLE CIRCUIT HOME RUNS. (2 CIRCUITS MAX @ <br />120/240V. 30 & 10). A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL <br />POWER, RECEPTACLE, AND LIGHTING CONDUITS. <br />21. FINAL CONNECTIONS TO ALL DIRECT CONNECTED KITCHEN EQUIPMENT SHALL BE WITH U.L. <br />APPROVED LIQUIDTIGHT CONDUIT. PROVIDED WITH GROUND WIRE SIZED PER N.E.C. ART. 250-122. <br />22. PROVIDE STAINLESS STEEL COVERPLATES FOR ALL WIRING DEVICES. COVERPLATES SHALL BE <br />EQUAL TO PASS & SEYMOUR. <br />23. ALL RECEPTACLES AND SWITCHES TO BE GRAY. <br />24. ALL CONDUITS TO BE CONCEALED INCLUDING SECURITY SYSTEM CONDUITS. E.C. SHALL INSTALL <br />SECURITY SYSTEM CONDUITS AND LABEL CONDUIT FOR SECURITY USE. <br />25. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONNECTIONS FOR FIRE ALARM CONTROL PANEL <br />AND DUCT SMOKE DETECTORS AND COMPLY WITH N.F.P.A. 90A 4-4. <br />26. RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, FITTINGS, LOW VOLTAGE WIRING AND LINE <br />VOLTAGE WIRING SHALL BE SECURELY FASTENED IN PLACE TO THE ABOVE STRUCTURE. <br />ELECTRICAL DEVICES LAYING DIRECTLY ON THE CEILING GRID IS STRICTLY PROHIBITED. SUPPORT <br />WIRES THAT DO NOT PROVIDE SECURE SUPPORT SHALL NOT BE PERMITTED AS THE SOLE SUPPORT. <br />SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE SECURE SUPPORT AND THAT ARE <br />INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE PERMITTED AS THE SOLE <br />SUPPORT. WHERE INDEPENDENT SUPPORT WIRES ARE USED, THEY SHALL BE SECURED AT BOTH <br />ENDS. CABLES AND RACEWAYS SHALL NOT BE SUPPORTED BY CEILING GRIDS. <br />F.A.C.P. IS FOR MONITORING SMOKE <br />DUCT DETECTORS ONLY. E.C. SHALL <br />PROVIDE ALL CONNECTIONS TO <br />COMPLY WITH N.F.P.A 90A 4-4. <br />ELECTRICAL SERVICE RISER 1 6 1 ELECTRICAL PANELS 1 5 1 ELECTRIC GENERAL NOTES 14 1 <br />AMP.INC. <br />#558260-1 (12 PORT) CAT. 5, MINI PATCH <br />PANEL, <br />MOUNT VERTICALLY AT 6" BELOW CEILING <br />BACK WALL AT TELEPHONE BOARD <br />BACK WALL AT TELEPHONE BOARD <br />RJ45 TYPICAL <br />z <br />O <br />2 z <br />NOTES: <br />P.O.S. ORDER ENTRY STATION (FRONT COUNTER) 1 <br />w <br />_jui <br />Ww <br />z <br />1. <br />RJ45 FEMALE WALL PLATES TYPICAL AT ALL <br />P.O.S. ORDER ENTRY STATION (DISPATCH) 2 <br />� J <br />TERMINATION POINTS (CAT 5). <br />Q <br />__T_3 <br />U <br />2. <br />ALL WIRING FROM WALL PLATES TO <br />P.0 S. ORDER ENTRY STATION (FRONT COUNTER) <br />EQUIPMENT BY OWNER. <br />P.O.S. ORDER ENTRY STATION 4 <br />3. <br />ELECTRICAL CONTRACTOR TO MARK EACH <br />RJ45 WALL PLATE AND EACH DATA CABLE AT <br />PATCH PANEL TO INDICATE WHICH STATION <br />P.O.S. ORDER ENTRY STATION 5 <br />- <br />OR PIECE OF EQUIPMENT EACH WIRE RUNS. <br />P.O.S. ORDER ENTRY STATION 6 <br />4. <br />P.O.S. INSTALLATION CONTRACTOR TO VERIFY <br />QUANTITY AND LOCATION OF ALL ORDER <br />-' <br />ENTRY STATIONS, <br />P.O.S. ORDER ENTRY STATION (BACK AREA) 7 <br />z <br />I <br />a- <br />5. <br />ELECTRICAL CONTRACTOR IS RESPONSIBLE <br />(BUMP PAD/MONITOR AT CUT TABLE 8 <br />� <br />_ <br />FOR ALL POS WIRING AND ALL TELEPHONE <br />WIRING WITHIN THE SPACE. COORDINATE <br />WITH NPC CONSTRUCTION MANAGER. <br />BUMP PAD/MONITOR #1 AT MAKETABLE 9 <br />O <br />z I <br />J <br />6. <br />ELECTRICAL CONTRACTOR TO PROVIDE A SET <br />BUMP PAD/MONITOR #2 AT MAKETABLE 10 <br />z <br />OF (4) FOUR CONDUCTORS CAT 5 CABLES <br />01 <br />FROM PIZZA HUT SPACE TO INCOMING <br />w <br />PHONE PROVIDER JUNCTION POINT. <br />P.O.S. WINGSTREET LINE (FINISH STATION SIDE} 71-1 <br />w I - <br />7. <br />ELECTRICAL CONTRACTOR TO RUN A <br />WINGSTREET UPLINK (FRONT COUNTER) 12 <br />~ <br />uj <br />CONTINUITY CHECK ON EVERY DATA CABLE <br />a_ <br />AND PROVIDE DOCUMENTATION WITH NPC <br />OFFICE COMPUTER AT MANAGER'S DESK 13 <br />i <br />_ <br />CONSTRUCTION MANAGER. <br />Q <br />fr <br />8. <br />ELECTRICAL CONTRACTOR TO PUNCH DOWN <br />OFFICE PRINTER AT MANAGER'S DESK I j14 <br />Ella <br />fr <br />(B TYPE) EVERYTHING TO DATA PATCH PANEL. <br />9. <br />ELECTRICAL CONTRACTOR TO PROVIDE (2) <br />OFFICE APPLIANCE AT MANAGER'S DESK (NOT PHONE) 15 <br />I <br />L - <br />`U <br />.- <br />TWO PATCH PANELS AS SPECIFIED. <br />CUSTOMER CASH OUT MONITOR (MOUNT AT 7'-8" A.F.F.) 16 <br />(4 PAIR, 24 GA. CAT. 5 TYP.) TO <br />PATCH PANEL <br />POS WIRING DIAGRAM <br />3 <br />_ <br />n <br />v <br />N <br />INTERNET IN <br />DSL/ <br />CABLE <br />MODEM <br />ROUTER <br />PORTABLE BASE <br />CONTROLLER <br />APC 750 <br />BATTERY BACKUP <br />- - - - TELEPHONE LINES (CAT 5) <br />DATA LINES (CAT 5) <br />BACKBOARD NETWORK EQUIPMENT LAYOUT 12 <br />NOTE: <br />PER SECTION NEC, ALL 15 AND 20A, 120V RECEPTACLES IN COMMERCIAL KITCHENS REQUIRED TO <br />BE GFCI PROTECTED. <br />LEGEND <br />SYMBOL DESCRIPTION <br />DOUBLE DUPLEX GROUNDED OUTLET <br />@=GFCI <br />DUPLEX GROUNDED OUTLET (GFCI) <br />SIG <br />ISOLATED GRD.DUPLEX GROUNDED RECEPTACLE & MTG. HT. <br />@=WP <br />WEATHER PROOF <br />0=15" <br />DUPLEX GROUNDED-NEMA 5-20R (UNO) RECEPTACLE & MTG. HT. <br />& <br />SINGLE GROUNDED RECEPTACLE-NEMA 5-20R (UNO) <br />01 <br />SPECIAL OUTLET SEE SCHEDULE <br />O © <br />JUNCTION BOX <br />© <br />JUNCTION BOX WITH COAXIAL CABLE FACE PLATE <br />$ $3 $P <br />SWITCHES 1P, 3P, PILOT LT. ECT. <br />0 <br />WALL MOUNTED OCCUPANCY SENSOR <br />a,b,c <br />INDICATES SWITCH SCHEME <br />v <br />TELEPHONE <br />I-O <br />P.O.S. CASH REG. CONDUIT W/ 4 PAIR CAT. 5 CABLE <br />D <br />DIMMER SWITCH <br />® <br />FAN RHEOSTAT <br />T <br />THERMOSTAT <br />QS <br />SPEAKER IN CEILING <br />EXIT LIGHT CEILING/WALL <br />EM <br />EMERGENCY LIGHT HEADS UNIT WITH BATTERY BACK-UP <br />p1 <br />DISCONNECT SWITCH <br />60/3 = 60 AMP SWITCH, 3 POLE <br />60/3/40 = 60 AMP SWITCH, 3 POLE, 40 AMP FUSE <br />NOTE: <br />NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT, <br />SYMBOL LEGEND 11 <br />6 <br />z <br />O <br />UI <br />w <br />O <br />U. <br />I- <br />r w <br />y <br />v <br />a <br />N <br />6 <br />O <br />Z <br />Y <br />CLi z <br />C 00 <br />U <br />Q <br />or J <br />W W <br />< VJ <br />0- W <br />J 0'^6 u VJ 0 <br />U W <br />V�cf) <br />W <br />_I Q <br />ON <br />coo <br />J <br />m LL <br />J <br />J <br />Q J <br />Lc) <br />LCK <br />`n a <br />r LLI <br />cD N <br />�n <br />U10 <br />10 <br />W <br />_j10 <br />aLO <br />� <br />ILc: <br />c <br />� <br />N <br />E <br />O <br />N <br />c`' <br />o <br />COU <br />V <br />0 <br />a <br />U- <br />O <br />O <br />Illz <br />J <br />N <br />} <br />N <br />N <br />a <br />�2 <br />o, <br />ZN <br />O3: <br />a� <br />CL <br />V00 <br />q <br />```,,`,``P� <br />•�eopO 0000000 <br />.\ C E NSA 000000� <br />�r 00° No. 65765 000 <br />o * 00 � <br />0 STATE OF / o W <br />Oc� 0°o F•C R <br />SHEET NUMBER <br />El <br />