COMMERCIAL LOAD SUMMARY
<br />BUILDING AREA: 1,829 SO. FT VOLTAGE: 208Y/120V, 3PH, 4W
<br />LOAD DESCRIPTION
<br />CONNECTED
<br />LOAD (VA)
<br />DEMAND
<br />FACTOR
<br />DEMAND
<br />LOAD (VA)
<br />LIGHTING
<br />INTERIOR LIGHTING
<br />1,504
<br />x
<br />125%
<br />=
<br />0
<br />EXTERIOR LIGHTING
<br />0
<br />x
<br />125%
<br />=
<br />0
<br />SIGNAGE
<br />1,200
<br />x
<br />125%
<br />=
<br />1,500
<br />MINIMUM GENERAL LIGHTING PER NEC-220 x 125%
<br />4,573
<br />MINIMUM TRACK LIGHTING/SHOW WINDOW PER NEC-220 x 125%
<br />5,688
<br />POWER & HVAC
<br />EXISTING
<br />0
<br />x
<br />100%
<br />=
<br />0
<br />RECEPTACLES
<br />1,620
<br />x
<br />100%;50%
<br />=
<br />1,620
<br />MISCELLANEOUS EQUIPMENT
<br />11,601
<br />x
<br />100%
<br />=
<br />11,601
<br />REFRIGERATION EQUIPMENT
<br />8,575
<br />x
<br />100%
<br />=
<br />8,575
<br />KITCHEN
<br />16,364
<br />x
<br />65%
<br />=
<br />10,637
<br />HVAC- SUMMER
<br />18,157
<br />x
<br />100%
<br />=
<br />18,157
<br />HVAC - WINTER
<br />0
<br />x
<br />100%
<br />=
<br />0
<br />SUPP, ELECTRIC HEAT
<br />216
<br />x
<br />100%
<br />=
<br />216
<br />MOTORS
<br />7,849
<br />x
<br />100%
<br />=
<br />7,849
<br />LARGEST MOTOR
<br />1,224
<br />x
<br />25%
<br />=
<br />306
<br />SUB -TOTAL (VA) 68,310 SUB -TOTAL (VA)
<br />SUB -TOTAL (AMPS) 190 SUB -TOTAL (AMPS)
<br />SERVICE SIZE (AMPS)
<br />SPARE CAPACITY (AMPS)
<br />70,721
<br />196
<br />400
<br />204
<br />REUSE EXISTING CONDUIT AND CONDUCTORS
<br />FROM EXTERIOR SERVICE ENTRANCE
<br />EQUIPMENT TO EXISTING PANELBOARD'A'
<br />WITHIN SPACE. VERIFY THAT THE EXISTING
<br />SERVICE IS 400A AT 208Y/120V, 3PH, 4W.
<br />PROVIDE ISOLATED GROUND WIRE FROM
<br />PANELBOARD 'B' BACK TO POINT OF
<br />NEUTRAL/GROUND BOND AT SERVICE
<br />ENTRANCE EQUIPMENT IF NOT CURRENTLY
<br />ELECTRIC SERVICE LOAD SUMMARY 17 1
<br />HCP
<br />HCP
<br />HCP
<br />GF
<br />HCP
<br />HCP
<br />HCP
<br />GF,HCP
<br />GF
<br />GF
<br />GF
<br />GF
<br />GF
<br />TS,EM
<br />GF,IG
<br />GF,IG
<br />TS
<br />PANELBOARD A (EXISTING)
<br />BUS AMPS: 400A LOCATION: BACK OF HOUSE GROUND BUS: YES
<br />MAIN SIZE / TYPE: MLO NEMA RATING: NEMA 1 ISOL. GROUND BUS: NO
<br />VOLTS/PHASE: 208Y/120V, 3PH, 4W AFC VALUE: VERIFY FEED THRU LUGS: NO
<br />MOUNTING: SURFACE AIC RATING: EXISTING SECTIONS: 1 OF 1
<br />CKT
<br />#
<br />CIRCUIT
<br />DESCRIPTION
<br />BREAKER
<br />WIRE
<br />SIZE
<br />LOAD
<br />(VA)
<br />CONNECTED PER PHASE (VA)
<br />LOAD
<br />(VA)
<br />WIRE
<br />SIZE
<br />BREAKER
<br />CIRCUIT
<br />DESCRIPTION
<br />CKT
<br />#
<br />AMPS
<br />I P
<br />A B C
<br />P
<br />AMPS
<br />1
<br />EF-1
<br />15
<br />1
<br />12
<br />1,056
<br />2,101 _ _
<br />2,2 69
<br />1,573
<br />1,825
<br />1 1,545
<br />2,293
<br />2,059
<br />2,059
<br />1 1,572
<br />4,214
<br />L4,214 _
<br />3,866
<br />4,226
<br />L4,226
<br />1 3,086
<br />3,974
<br />3,478
<br />4,238
<br />4,405
<br />5,761
<br />4,105
<br />1,045
<br />12
<br />3
<br />20
<br />WALK-IN FREEZER COND
<br />(W1-004)(ICS)
<br />2
<br />3
<br />SF-1
<br />20
<br />1
<br />12
<br />1,224
<br />1,045
<br />4
<br />5
<br />EF-2
<br />15
<br />1
<br />12
<br />528
<br />1,045
<br />6
<br />7
<br />VISICOOLER (R2-008)
<br />20
<br />1
<br />12
<br />780
<br />1,045
<br />12
<br />3
<br />20
<br />WALK-IN COOLER COND
<br />(W1-004)(ICS)
<br />8
<br />9
<br />HOOD CONTROL PANEL POWER & HOOD LTS
<br />15
<br />1
<br />12
<br />500
<br />1,045
<br />10
<br />11
<br />OVEN #1 (C3-015)
<br />20
<br />2
<br />12
<br />1,248
<br />1,045
<br />12
<br />13
<br />1,248
<br />811
<br />12
<br />2
<br />15
<br />WALK-IN FREEZER EVAP
<br />14
<br />15
<br />OVEN #2 (C3-015)
<br />20
<br />2
<br />12
<br />1,248
<br />811
<br />16
<br />17
<br />1,248
<br />324
<br />12
<br />1
<br />15
<br />WALK-IN COOLER EVAP
<br />18
<br />19
<br />OVEN #3 (C3-015)
<br />20
<br />2
<br />12
<br />1,248
<br />2,966
<br />8
<br />3
<br />35
<br />RTU-3
<br />20
<br />21
<br />1,248
<br />2,966
<br />22
<br />23
<br />FRYER (C2-002)
<br />20
<br />1
<br />12
<br />900
<br />2,966
<br />24
<br />25
<br />PROOFER (P3-003)
<br />20
<br />2
<br />12
<br />1,920
<br />2,306
<br />8
<br />3
<br />35
<br />RTU-1
<br />26
<br />27
<br />1,920
<br />2,306
<br />28
<br />29
<br />VISICOOLER (R2-007)
<br />20
<br />1
<br />12
<br />780
<br />2,306
<br />30
<br />31
<br />MAKETABLE (P2-001)
<br />20
<br />1
<br />12
<br />1,536
<br />2,438
<br />1 10
<br />3
<br />30
<br />RTU-2
<br />32
<br />33
<br />REACH -IN FREEZER (R3-005)
<br />20
<br />1
<br />12
<br />1,040
<br />2,438
<br />34
<br />35
<br />DISHWASHER (Z3-002)
<br />20
<br />1
<br />12
<br />1,800
<br />2,438
<br />36
<br />37
<br />ROOF TOP RCPTS
<br />20
<br />1
<br />12
<br />540
<br />3,865
<br />SR
<br />3
<br />100
<br />PANELBOARD'B'
<br />38
<br />39
<br />HOLDING CABINET (S15-003)
<br />30
<br />1
<br />10
<br />2,316
<br />3,445
<br />40
<br />41
<br />WINGSTREET REFRIGERATOR (R4-013)
<br />15
<br />1
<br />12
<br />360
<br />3,745
<br />42
<br />PER PHASE SUB -TOTALS
<br />22,803 23,551 20,732
<br />LEGEND:
<br />TOTAL CONNECTED PANELBOARD (VA) 67,086 TS -VIA TIME SWITCH ST - SHUNT TRIP
<br />TOTAL CONNECTED PANELBOARD (AMPS) 186 GF - GROUND FAULT INTERRUPTER LCK - PAD LOCKABLE BREAKER
<br />TOTAL PANELBOARD DEMAND (VA) 68,046 FA - FIRE ALARM / RED / LOCKING TAB IN OPEN POSITION
<br />TOTAL PANELBOARD DEMAND (AMPS) 189 EM - EMERGENCY LTG. / LOCKING TAB IG - ISOLATED GROUND
<br />HCP - ROUTE VIA HOOD CONTROL PANEL SR - RE: SERVICE RISER
<br />PANELBOARD B
<br />BUS AMPS:
<br />MAIN SIZE / TYPE:
<br />VOLTS/PHASE:
<br />MOUNTING:
<br />125A
<br />MLO
<br />208Y/120V, 3PH, 4W
<br />SURFACE
<br />LOCATION:
<br />NEMA RATING:
<br />AFC VALUE:
<br />AIC RATING:
<br />BACK OF HOUSE
<br />NEMA 1
<br />VERIFY
<br />MATCHING EXISTING
<br />GROUND BUS: YES
<br />ISOL. GROUND BUS: YES
<br />FEED THRU LUGS: NO
<br />SECTIONS: 1 OF 1
<br />CKT
<br />#
<br />CIRCUIT
<br />DESCRIPTION
<br />BREAKER
<br />WIRE
<br />SIZE
<br />LOAD
<br />(VA)
<br />CONNECTED PER PHASE (VA)__]I
<br />LOAD
<br />(VA)
<br />WIRE
<br />SIZE
<br />BREAKER
<br />CIRCUIT
<br />DESCRIPTION
<br />CKT
<br />#
<br />AMPS
<br />P
<br />A B C
<br />P
<br />AMPS
<br />1
<br />COOLER/FREEZER LIGHTS
<br />20
<br />1
<br />12
<br />400
<br />609
<br />680 1
<br />L1,440
<br />1,216
<br />L614
<br />1,360
<br />0
<br />1,391
<br />0
<br />0
<br />685
<br />1,560
<br />1,000
<br />500
<br />0
<br />209
<br />12
<br />1
<br />20
<br />FRONT AREA & EM LIGHTS
<br />2
<br />3
<br />BACK AREA & EM LIGHTS
<br />20
<br />1
<br />12
<br />851
<br />540
<br />12
<br />1
<br />20
<br />SHOW WINDOW RCPT
<br />4
<br />5
<br />COOLER/FREEZER POWER
<br />20
<br />1
<br />12
<br />500
<br />185
<br />12
<br />1
<br />20
<br />CUSTOMER CASH OUT MONITOR
<br />6
<br />7
<br />POS AT TELEPHONE BOARD
<br />20
<br />1
<br />12
<br />180
<br />500
<br />12
<br />1
<br />20
<br />COMPUTER
<br />8
<br />9
<br />(2) KMS AT MAKETABLE
<br />20
<br />1
<br />12
<br />1,440
<br />0
<br />1
<br />20
<br />SPARE
<br />10
<br />11
<br />FRONT SIGNAGE
<br />20
<br />1
<br />1 12
<br />1,200
<br />360
<br />12
<br />1
<br />20
<br />CONVENIENCE RCPTS
<br />12
<br />13
<br />WATER HEATER (Z13-003)
<br />20
<br />1
<br />12
<br />216
<br />1,000
<br />12
<br />1
<br />20
<br />POS #1/#3
<br />14
<br />15
<br />RR/EF-3 & EM LIGHTS
<br />20
<br />1
<br />12
<br />114
<br />500
<br />12
<br />1
<br />20
<br />POS #2
<br />16
<br />17
<br />SPARE
<br />20
<br />1
<br />0
<br />1,000
<br />12
<br />1
<br />20
<br />POS #4/#5
<br />18
<br />19
<br />LIGHTING CONTROLS
<br />20
<br />1
<br />12
<br />360
<br />1;000
<br />12
<br />1
<br />20
<br />POS #6/#7
<br />20
<br />21
<br />SPARE
<br />20
<br />1
<br />0
<br />0
<br />1
<br />20
<br />SPARE
<br />22
<br />23
<br />SPARE
<br />20
<br />1
<br />0
<br />500
<br />12
<br />1
<br />20
<br />BACK CASH OUT
<br />24
<br />25
<br />SPARE
<br />20
<br />1
<br />0
<br />0
<br />1
<br />20
<br />SPARE
<br />26
<br />27
<br />SPARE
<br />20
<br />1
<br />0
<br />0
<br />1
<br />20
<br />SPARE
<br />28
<br />29
<br />SPARE
<br />1 20
<br />1
<br />1
<br />1 0 11
<br />0
<br />1
<br />1 20
<br />ISPARE
<br />30
<br />PER PHASE SUB -TOTALS
<br />3,865
<br />3,445
<br />3,745
<br />1 LEGEND:
<br />TOTAL CONNECTED PANELBOARD (VA)
<br />TOTAL CONNECTED PANELBOARD (AMPS)
<br />TOTAL PANELBOARD DEMAND (VA)
<br />TOTAL PANELBOARD DEMAND (AMPS)
<br />11,054
<br />31
<br />17,435
<br />48
<br />TS - VIA TIME SWITCH ST - SHUNT TRIP
<br />GF - GROUND FAULT INTERRUPTER LCK - PAD LOCKABLE BREAKER
<br />FA - FIRE ALARM / RED / LOCKING TAB IN OPEN POSITION
<br />EM - EMERGENCY LTG. / LOCKING TAB IG - ISOLATED GROUND
<br />LC - LIGHTING CONTACTOR OL - RE: ONE -LINE DIAGRAM
<br />NOTE:
<br />ALL CONDUCTORS SHALL BE COPPER, WITH
<br />THWN/THHN INSULATION.
<br />NOTE:
<br />CONTRACTOR TO VERIFY IF EXISTING PANEL WITHIN SPACE CAN BE REUSED. FIELD VERIFY PANEL SIZE AND
<br />VERIFY EXISTING PANEL MATCHES INFORMATION LISTED HERE. PROVIDE ALL NEW CIRCUIT BREAKERS AS
<br />SCHEDULED. CONTRACTOR IS RESPONSIBLE TO PROVIDE NEW PANEL'B' AS SHOWN ON PLANS.
<br />NOTE:
<br />ALL HOOD, OVEN AND FRYER CIRCUITS ARE TO BE ROUTED FROM PANELBOARD 'A', THROUGH THE HOOD
<br />CONTROL PANEL, THEN TO FINAL TERMINATION POINT. REFER TO PANELBOARD SCHEDULE FOR HOOD CONTROL
<br />PANEL CIRCUIT DESIGNATION.
<br />TS,EM
<br />IG
<br />GF,IG
<br />IG
<br />GF,IG
<br />GF,IG
<br />GF,IG
<br />GF,IG
<br />1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC
<br />CODE (NEC), THE AMERICANS WITH DISABILITIES ACT (ADA), AND ALL STATE AND LOCAL
<br />REQUIREMENTS AND CODES.
<br />2. REFER TO RELATED ARCHITECTURAL AND MECHANICAL DRAWINGS FOR RELATED INFORMATION
<br />AND EQUIPMENT DESCRIPTIONS.
<br />3. ALL LIGHTING FIXTURES AND MECHANICAL EQUIPMENT SHALL BE COMPLETELY CONNECTED BY
<br />ELECTRICAL CONTRACTOR (BOTH POWER AND CONTROL WIRING).
<br />4. ALL NEW LIGHTING FIXTURES SHALL BE FURNISHED WITH LAMPS.
<br />5. ALL NEW TELEPHONE OUTLETS SHALL HAVE 3/4" CONDUIT WITH PULL WIRES ROUTED TO
<br />TELEPHONE TERMINAL BOARD. CONDUIT SHALL BE INSTALLED BY ELECTRICAL CONTRACTOR.
<br />VERIFY TELEPHONE REQUIREMENTS WITH LOCAL TELEPHONE COMPANY.
<br />6. VERIFY ALL OUTLET LOCATIONS ON THE JOB PRIOR TO ROUGH -IN.
<br />7. PANELBOARDS SHALL BE U.L. LISTED FOR A MINIMUM 22,000 AIC FAULT CURRENT. CONTRACTOR
<br />TO COORDINATE WITH SERVING UTILITY COMPANY AND LANDLORD TO PROVIDE PANELBOARDS
<br />PROPERLY BRACED FOR AVAILABLE FAULT CURRENT.
<br />8. PROVIDE TYPEWRITTEN SCHEDULE INDICATING EQUIPMENT DESCRIPTION AND/OR LOCATION FOR
<br />EACH CIRCUIT IN PANEL DOOR.
<br />9. SAFETY SWITCHES SHALL BE GENERAL DUTY WITH CLASS "J" FUSE CLIPS.
<br />10. FUSES SHALL BE BUSSMAN LPJ OR EQUAL BY GOULD SHAWMUT OR LITTLE FUSE.
<br />11. PROVIDE SWITCH DUTY BREAKERS FOR CIRCUITS BEING SWITCHED AT PANEL.
<br />12. PROVIDE HACR TYPE BREAKERS FOR ALL HVAC EQUIPMENT.
<br />13. ALL BREAKERS SHALL BE 1" BREAKERS. ELECTRICAL CONTRACTOR SHALL NOT PLACE (2) CIRCUIT
<br />BREAKERS IN (1) CIRCUIT BREAKER SPACE (I.E. TANDEM BREAKER OR 1/2" BREAKER).
<br />14. USE ONLY INSULATED COPPER CONDUCTORS IN CONDUIT. CONDUCTORS SHALL BE SIZED PER
<br />DRAWINGS AND N.E.C. (MINIMUM # 12 COPPER) MINIMUM CONDUCTOR INSULATION SHALL BE TYPE
<br />"THWN/THHN" FOR ALL CONDUCTORS. NO ROMEX ALLOWED. A GROUND WIRE SIZED PER N.E.C. ART,
<br />250-66 (SERVICE GROUND) OR N.E.C. ART. 250-122 (EQUIPMENT GROUND) SHALL BE PULLED IN ALL
<br />CONDUIT.
<br />15. ALUMINUM CONDUCTORS ARE SPECIFICALLY PROHIBITED.
<br />16. COMPLETE SYSTEM SHALL BE GROUNDED PER N.E.C. ARTICLE 250-66.
<br />17. ISOLATED GROUND OUTLETS: CONNECT PANEL B ISOLATED GROUND BUS TO SYSTEM GROUND AT
<br />PANEL A. RUN ISOLATED GROUND IN SAME CONDUIT WITH CIRCUIT CONDUCTORS.
<br />18. ALL CONDUIT WILL BE INSTALLED CONCEALED IN WALLS OR ABOVE ACCESSIBLE CEILING TILES. DO
<br />NOT EXPOSE CONDUIT.
<br />19. PROVIDE ELECTRICAL DEVICES AND WIRING TO COMPLY WITH N.F.P.A. 96.7-3.1.3 FOR POWER
<br />SHUT-OFF ON ALL ELECTRICAL EQUIPMENT UNDER OVEN HOOD. VERIFY INSTALLATION AND
<br />OPERATION REQUIREMENTS WITH EXTINGUISHING SYSTEM SUPPLIER.
<br />20. BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME RUNS FOR CLARITY ONLY, CONTRACTOR
<br />MAY GROUP SINGLE POLE BRANCH CIRCUITS IN MULTIPLE CIRCUIT HOME RUNS. (2 CIRCUITS MAX @
<br />120/240V. 30 & 10). A GROUND CONDUCTOR SIZED PER N.E.C. ARTICLE 250 IS REQUIRED IN ALL
<br />POWER, RECEPTACLE, AND LIGHTING CONDUITS.
<br />21. FINAL CONNECTIONS TO ALL DIRECT CONNECTED KITCHEN EQUIPMENT SHALL BE WITH U.L.
<br />APPROVED LIQUIDTIGHT CONDUIT. PROVIDED WITH GROUND WIRE SIZED PER N.E.C. ART. 250-122.
<br />22. PROVIDE STAINLESS STEEL COVERPLATES FOR ALL WIRING DEVICES. COVERPLATES SHALL BE
<br />EQUAL TO PASS & SEYMOUR.
<br />23. ALL RECEPTACLES AND SWITCHES TO BE GRAY.
<br />24. ALL CONDUITS TO BE CONCEALED INCLUDING SECURITY SYSTEM CONDUITS. E.C. SHALL INSTALL
<br />SECURITY SYSTEM CONDUITS AND LABEL CONDUIT FOR SECURITY USE.
<br />25. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONNECTIONS FOR FIRE ALARM CONTROL PANEL
<br />AND DUCT SMOKE DETECTORS AND COMPLY WITH N.F.P.A. 90A 4-4.
<br />26. RACEWAYS, CABLE ASSEMBLIES, BOXES, CABINETS, FITTINGS, LOW VOLTAGE WIRING AND LINE
<br />VOLTAGE WIRING SHALL BE SECURELY FASTENED IN PLACE TO THE ABOVE STRUCTURE.
<br />ELECTRICAL DEVICES LAYING DIRECTLY ON THE CEILING GRID IS STRICTLY PROHIBITED. SUPPORT
<br />WIRES THAT DO NOT PROVIDE SECURE SUPPORT SHALL NOT BE PERMITTED AS THE SOLE SUPPORT.
<br />SUPPORT WIRES AND ASSOCIATED FITTINGS THAT PROVIDE SECURE SUPPORT AND THAT ARE
<br />INSTALLED IN ADDITION TO THE CEILING GRID SUPPORT WIRES SHALL BE PERMITTED AS THE SOLE
<br />SUPPORT. WHERE INDEPENDENT SUPPORT WIRES ARE USED, THEY SHALL BE SECURED AT BOTH
<br />ENDS. CABLES AND RACEWAYS SHALL NOT BE SUPPORTED BY CEILING GRIDS.
<br />F.A.C.P. IS FOR MONITORING SMOKE
<br />DUCT DETECTORS ONLY. E.C. SHALL
<br />PROVIDE ALL CONNECTIONS TO
<br />COMPLY WITH N.F.P.A 90A 4-4.
<br />ELECTRICAL SERVICE RISER 1 6 1 ELECTRICAL PANELS 1 5 1 ELECTRIC GENERAL NOTES 14 1
<br />AMP.INC.
<br />#558260-1 (12 PORT) CAT. 5, MINI PATCH
<br />PANEL,
<br />MOUNT VERTICALLY AT 6" BELOW CEILING
<br />BACK WALL AT TELEPHONE BOARD
<br />BACK WALL AT TELEPHONE BOARD
<br />RJ45 TYPICAL
<br />z
<br />O
<br />2 z
<br />NOTES:
<br />P.O.S. ORDER ENTRY STATION (FRONT COUNTER) 1
<br />w
<br />_jui
<br />Ww
<br />z
<br />1.
<br />RJ45 FEMALE WALL PLATES TYPICAL AT ALL
<br />P.O.S. ORDER ENTRY STATION (DISPATCH) 2
<br />� J
<br />TERMINATION POINTS (CAT 5).
<br />Q
<br />__T_3
<br />U
<br />2.
<br />ALL WIRING FROM WALL PLATES TO
<br />P.0 S. ORDER ENTRY STATION (FRONT COUNTER)
<br />EQUIPMENT BY OWNER.
<br />P.O.S. ORDER ENTRY STATION 4
<br />3.
<br />ELECTRICAL CONTRACTOR TO MARK EACH
<br />RJ45 WALL PLATE AND EACH DATA CABLE AT
<br />PATCH PANEL TO INDICATE WHICH STATION
<br />P.O.S. ORDER ENTRY STATION 5
<br />-
<br />OR PIECE OF EQUIPMENT EACH WIRE RUNS.
<br />P.O.S. ORDER ENTRY STATION 6
<br />4.
<br />P.O.S. INSTALLATION CONTRACTOR TO VERIFY
<br />QUANTITY AND LOCATION OF ALL ORDER
<br />-'
<br />ENTRY STATIONS,
<br />P.O.S. ORDER ENTRY STATION (BACK AREA) 7
<br />z
<br />I
<br />a-
<br />5.
<br />ELECTRICAL CONTRACTOR IS RESPONSIBLE
<br />(BUMP PAD/MONITOR AT CUT TABLE 8
<br />�
<br />_
<br />FOR ALL POS WIRING AND ALL TELEPHONE
<br />WIRING WITHIN THE SPACE. COORDINATE
<br />WITH NPC CONSTRUCTION MANAGER.
<br />BUMP PAD/MONITOR #1 AT MAKETABLE 9
<br />O
<br />z I
<br />J
<br />6.
<br />ELECTRICAL CONTRACTOR TO PROVIDE A SET
<br />BUMP PAD/MONITOR #2 AT MAKETABLE 10
<br />z
<br />OF (4) FOUR CONDUCTORS CAT 5 CABLES
<br />01
<br />FROM PIZZA HUT SPACE TO INCOMING
<br />w
<br />PHONE PROVIDER JUNCTION POINT.
<br />P.O.S. WINGSTREET LINE (FINISH STATION SIDE} 71-1
<br />w I -
<br />7.
<br />ELECTRICAL CONTRACTOR TO RUN A
<br />WINGSTREET UPLINK (FRONT COUNTER) 12
<br />~
<br />uj
<br />CONTINUITY CHECK ON EVERY DATA CABLE
<br />a_
<br />AND PROVIDE DOCUMENTATION WITH NPC
<br />OFFICE COMPUTER AT MANAGER'S DESK 13
<br />i
<br />_
<br />CONSTRUCTION MANAGER.
<br />Q
<br />fr
<br />8.
<br />ELECTRICAL CONTRACTOR TO PUNCH DOWN
<br />OFFICE PRINTER AT MANAGER'S DESK I j14
<br />Ella
<br />fr
<br />(B TYPE) EVERYTHING TO DATA PATCH PANEL.
<br />9.
<br />ELECTRICAL CONTRACTOR TO PROVIDE (2)
<br />OFFICE APPLIANCE AT MANAGER'S DESK (NOT PHONE) 15
<br />I
<br />L -
<br />`U
<br />.-
<br />TWO PATCH PANELS AS SPECIFIED.
<br />CUSTOMER CASH OUT MONITOR (MOUNT AT 7'-8" A.F.F.) 16
<br />(4 PAIR, 24 GA. CAT. 5 TYP.) TO
<br />PATCH PANEL
<br />POS WIRING DIAGRAM
<br />3
<br />_
<br />n
<br />v
<br />N
<br />INTERNET IN
<br />DSL/
<br />CABLE
<br />MODEM
<br />ROUTER
<br />PORTABLE BASE
<br />CONTROLLER
<br />APC 750
<br />BATTERY BACKUP
<br />- - - - TELEPHONE LINES (CAT 5)
<br />DATA LINES (CAT 5)
<br />BACKBOARD NETWORK EQUIPMENT LAYOUT 12
<br />NOTE:
<br />PER SECTION NEC, ALL 15 AND 20A, 120V RECEPTACLES IN COMMERCIAL KITCHENS REQUIRED TO
<br />BE GFCI PROTECTED.
<br />LEGEND
<br />SYMBOL DESCRIPTION
<br />DOUBLE DUPLEX GROUNDED OUTLET
<br />@=GFCI
<br />DUPLEX GROUNDED OUTLET (GFCI)
<br />SIG
<br />ISOLATED GRD.DUPLEX GROUNDED RECEPTACLE & MTG. HT.
<br />@=WP
<br />WEATHER PROOF
<br />0=15"
<br />DUPLEX GROUNDED-NEMA 5-20R (UNO) RECEPTACLE & MTG. HT.
<br />&
<br />SINGLE GROUNDED RECEPTACLE-NEMA 5-20R (UNO)
<br />01
<br />SPECIAL OUTLET SEE SCHEDULE
<br />O ©
<br />JUNCTION BOX
<br />©
<br />JUNCTION BOX WITH COAXIAL CABLE FACE PLATE
<br />$ $3 $P
<br />SWITCHES 1P, 3P, PILOT LT. ECT.
<br />0
<br />WALL MOUNTED OCCUPANCY SENSOR
<br />a,b,c
<br />INDICATES SWITCH SCHEME
<br />v
<br />TELEPHONE
<br />I-O
<br />P.O.S. CASH REG. CONDUIT W/ 4 PAIR CAT. 5 CABLE
<br />D
<br />DIMMER SWITCH
<br />®
<br />FAN RHEOSTAT
<br />T
<br />THERMOSTAT
<br />QS
<br />SPEAKER IN CEILING
<br />EXIT LIGHT CEILING/WALL
<br />EM
<br />EMERGENCY LIGHT HEADS UNIT WITH BATTERY BACK-UP
<br />p1
<br />DISCONNECT SWITCH
<br />60/3 = 60 AMP SWITCH, 3 POLE
<br />60/3/40 = 60 AMP SWITCH, 3 POLE, 40 AMP FUSE
<br />NOTE:
<br />NOT ALL SYMBOLS MAY BE USED ON THIS PROJECT,
<br />SYMBOL LEGEND 11
<br />6
<br />z
<br />O
<br />UI
<br />w
<br />O
<br />U.
<br />I-
<br />r w
<br />y
<br />v
<br />a
<br />N
<br />6
<br />O
<br />Z
<br />Y
<br />CLi z
<br />C 00
<br />U
<br />Q
<br />or J
<br />W W
<br />< VJ
<br />0- W
<br />J 0'^6 u VJ 0
<br />U W
<br />V�cf)
<br />W
<br />_I Q
<br />ON
<br />coo
<br />J
<br />m LL
<br />J
<br />J
<br />Q J
<br />Lc)
<br />LCK
<br />`n a
<br />r LLI
<br />cD N
<br />�n
<br />U10
<br />10
<br />W
<br />_j10
<br />aLO
<br />�
<br />ILc:
<br />c
<br />�
<br />N
<br />E
<br />O
<br />N
<br />c`'
<br />o
<br />COU
<br />V
<br />0
<br />a
<br />U-
<br />O
<br />O
<br />Illz
<br />J
<br />N
<br />}
<br />N
<br />N
<br />a
<br />�2
<br />o,
<br />ZN
<br />O3:
<br />a�
<br />CL
<br />V00
<br />q
<br />```,,`,``P�
<br />•�eopO 0000000
<br />.\ C E NSA 000000�
<br />�r 00° No. 65765 000
<br />o * 00 �
<br />0 STATE OF / o W
<br />Oc� 0°o F•C R
<br />SHEET NUMBER
<br />El
<br />
|