ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />150AI200A INDOOR <br />PANEL CENTER <br />#14 to lights & outlets <br />NEMA 1 10 #12 to appliances and GFI <br />150 AMP/ <br />200 AMP 10 #10 to WH <br />10 #8 to Range <br />10 #6 to HVAC <br />MAIN <br />0150-2/0 <br />' <br />200=4/0 in 2" Conduit <br />200 amp <br />150 amp <br />UNDERGROUND <br />SERVICE BY POWER CO. <br />INTERSYSTEM4 <br />V <br />Bare Cu Ground <br />BONDING4 <br />GROUNDING WIRE <br />TERMINATION PER <br />WITH CODE APPROVED <br />NEC 17, 250.94 <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />GENERAL ELECTRICAL NOTES . Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />1. Electrical outlet heights as measured from finished floor to center line of Lite box to be: 16" AFF (general). CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I� <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />© <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />NN 2 <br />0 <br />119 <br />WALL MOUNTED LIGHT FIXTURE <br />RECESSED LIGHT FIXTURE <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CHIMES (OPTIONAL) <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SMOKE DETECTOR <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />1.5" VTR ,Ilt 3" VTR <br />I� <br />I I <br />II, I <br />I I <br />I I <br />I <br />� I \ <br />\ <br />3" VTR <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />DEDICATED <br />RECEPTACLI <br />MICROWAVE <br />HOOD PER S <br />SPEC 3 & 4 KITCHEN <br />SCALE: 4'=1'-0" <br />A/C PAD <br />DISC. WP <br />GFI <br />Ak <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />O <br />r <br />FIM \4—DB & GFI TO <br />10<1 <br />— — — — — — — ' BE ALIGNED <br />VERTICALLY <br />1 <br />COACH LIGHTS ACOACH LIGHTS <br />OR PREWIRE AS OR PREWIRE AS <br />PER SPECS / / PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I <br />I <br />I <br />I <br />f <br />I <br />I <br />1 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I � <br />I I <br />I I <br />{ I <br />I <br />I <br />I <br />I <br />I <br />i <br />I <br />I <br />I <br />I <br />1 <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />L— — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — -j <br />I <br />I <br />I <br />1 <br />l <br />I <br />I <br />I <br />I <br />I <br />I <br />FIRST FLOOR ELECTRICAL PLAN —A SECOND FLOOR ELECTRICAL PLAN —A <br />T W <br />a>, <br />r x <br />L- <br />to 87.. <br />a <br />N <br />N <br />0 <br />N <br />ti <br />CV <br />r-- <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />a <br />8 <br />Si <br />® <br />0 <br />14 N 6 N N <br />r• <br />atom In <br />,p� <br />N M ,t Ll <br />C LL <br />V <br />-J W <br />CU E LL 1 <br />Z <br />J <br />_� 0- <br />r to <br />�9 Q <br />��m w <br />Z <br />MLW <br />to N Z Q J <br />0 <br />a <br />N <br />O U U O <br />Z <br />W <br />El� <br />M � <br />z N <br />o g <br />z N <br />z a � <br />n Cq <br />N <br />M <br />z to <br />Q <br />X <br />� o <br />L <br />W <br />o <br />� <br />0 <br />W <br />N <br />c <br />�V) <br />_ CO <br />f6CO <br />U <br />LLJ J <br />_ E <br />S Lc � <br />zl1 <br />U o °� <br />Q �o <br />AL <br />r` <br />m <br />ffi <br />Ch <br />M <br />w ¢ <br />o <br />Z <br />I <br />�o <br />CL 0Lu <br />U� <br />Z <br />oa <br />►ca <br />0° <br />0 <br />C14 @ <br />W t <br />w o <br /><om° <br />w W <br /><� <br />ro <br />Cif C <br />o > <br />U <br />� <br />° <br />Z <br />Z'aW <br />z <br />cn <br />o <br />o� <br />g° <br />Q <br />a <br />NW <br /><� <br />a2 <br />w� <br />>° <br />o <br />V <br />M <br />a <br />O°3 <br />.N p <br />J <br />>M <br />Cm <br />00 <br />CO <br />C) <br />Q <br />Cr �L <br />r <br />a. <br />U m <br />CN <br />004 <br />� <br />O <br />O <br />Q <br />T <br />ui <br />cu <br />2 <br />N <br />r <br />o <br />Z <br />E ( <br />to <br />a0 <br />-j <br />¢ o <br />—J <br />JOB <br />NO : <br />22-08307 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />