Laserfiche WebLink
HRU HRU <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />RF/V IF/V 0/A, 100 CFM <br />:E:21 <br />0/A, 250 CFM <br />AD4 IN ATTIC <br />200 CFM <br />SEE NOTES <br />AD3-IN ATT <br />50 CFM <br />SEE NOTES <br />Q <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />AD3-IN ATTIC I <br />50 CFM <br />SEE NOTES <br />AD4 IN ATTIC <br />100 CFM <br />SEE NOTES <br />AH4 <br />6X6 <br />AD3 <br />75 CFM <br />AD4, 100 CFM <br />UP ABOVE CEILING <br />OF STORAGE ROOM <br />J6X6 <br />S <br />I <br />1 <br />1 <br />AD3-IN ATTIC 50 CFM <br />SEE NOTES <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />AD3-IN ATTIC <br />AD3-IN ATTIC 50 CFM <br />50 CFM SEE NOTES <br />6X6 SEE NOTES <br />ABOVE CEILING OF <br />STORAGE ROOM <br />AD5 AD5 <br />200 CFM 250 CFM <br />AD3-IN ATTIC 50 CFM <br />SEE NOTES <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />RF/V <br />0/A, 110 CF <br />ABOVE CEILING OF <br />STORAGE ROOM <br />AD3-IN ATTIC AD3-IN ATTIC <br />50 CFM 50 CFM <br />SEE NOTES SEE NOTES <br />AIR HANDLER <br />UNIT #2 ROOM <br />FILE STORAGE AREA <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />AD5 <br />200 CFM <br />AD4 IN ATTIC <br />200 CFM <br />SEE NOTES <br />7X7 <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />-AD3-IN ATTIC <br />50 CFM SEE NOTES <br />AD3 AD4, 150 CFM <br />® 75 CFM UP ABOVE CEILING N <br />OF STORAGE ROOM = <br />SEE NOTES <br />EWH ♦ <br />7X7 <br />AH5 <br />T5 <br />AD6 <br />725 CFM <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />RF/V <br />0/A, 1110 CFM <br />AD4 IN ATTIC <br />200 CFM <br />-SEE NOTES <br />HEATING, VENTILATING AND AIR CONDITIONING SPECIFICATIONS <br />1.8 CONTROLS: <br />J. Fire dampers, ceiling radiation dampers, fire/smoke dampers and smoke dampers, <br />C. All equipment used shall be UL listed. All references to manufacturers shall be <br />A. The thermostats control wires shall be run in EMT conduit where in the walls. <br />shall be installed where shown or as required in the referenced codes. These <br />1.1 BRIEF DESCRIPTION OF WORK <br />interpreted as establishing a standard of quality and shall not be construed as <br />locations include, but are not limited to air distribution system penetrations of a <br />g ys g <br />A. Install a heating,air conditioning and ventilations system including but not <br />as limiting competition. <br />g p <br />B. COVERS: Provide a clear plastic, locking cover for each thermostat. <br />fire -rated; partition, wall, ceiling floor, etc. See building drawings for location of <br />necessarily limited to: an air distribution system composed of ductwork, scheduled <br />D. All power wiring and disconnect switches to be furnished and installed by the <br />C. THERMOSTAT LOCATION: If not shown, locate near return air grille 5 ft.-0 in. <br />CC SSTAT <br />afore mentioned fire -rated structures. Access doors for the purpose of resetting <br />supply registers and rilles, automatic controls, exhaust system vents, scheduled <br />electrical contractor. All motor starters and other control devices shall be <br />THEERRM LOCgTIpN: If not shc �wn, locate near return grill ®5' aff. <br />D: INTERL�CK CONTROLS: Where the Fan Schedule or other notes indicate the exhaust <br />ire dampers shall be installed at each damper location. Where duct access doors must <br />equipment, refrigerant condensation piping and other related necessary <br />furnished by the mechanical contractor and installed by the electrical contractor. <br />fan(s) is to be interlocked with two or more items, these items shall be connected in <br />be installed above the ceiling (due to space limitations) provide architectural access <br />appurtenances. It is the intent that the work shall be complete in every respect <br />This includes, but not limited to, auxiliary contacts for magnetic starters. All motors <br />a parallel electrical circuit so that either of the items will cause the fan to run. <br />doors through the ceiling. All such items (dampers and doors) shall be manufactured <br />and that any material or work not specifically mentioned or shown on the drawings <br />1/2 HP and larger shall be furnished with magnetic starters and with start -stop <br />E. SMOKE DETECTORS: Smoke detectors shall be installed in each supply and return <br />according to UL555, installed according to manufacturers instructions and shall meet <br />but necessary to fully complete the work shall be provided. <br />pushbuttons. All motors 1/3 HP and smaller shall be furnished with manual off -on <br />duct or as required by NFPA 90A & 908 or local Fire Official. Unless specified <br />or exceed the rating of the penetrated structure according to ANSI/UL263. <br />mechanical systems that will fit within the allotted space with <br />B. Totally functioning mec a sys e p <br />switches. All motors shall be protected wtih termal overload devices at the motor, in <br />p <br />otherwise in section 1600 the smoke detector shall be Air Products and Controls <br />L. All duct turns renter than 30 degrees(supply, <br />9 9 return, exhaust, makeup, etc.) <br />for servicing, operating and adjusting the equipment. <br />adequate clearance o se c g, ope g Ju gthes <br />manual wi r in magnetic r <br />tch o the mag etc starter. All switches and starters shall be <br />Model MS-UNI-P and shall be of the solid state photoelectric type and shall operate P YP P <br />shall be made with mitered elbows using sheet metal turning vanes. Turning vanes shall <br />C. All equipment shall be started, tested, adjusted and placed in satisfactory <br />identified with block plastic nameplates having white lettering. All tow voltage (24V ) <br />at air velocities of 300 to 4,000 FPM. The duct detector housings shall be of metal <br />be single thickness with 2 straight leading and leaving edges. <br />operating condition by the contractor. This contractor shall balance air flows <br />control wiring shall be installed by the mechanical contractor. <br />construction and complete mechanical installation may be performed without removal of <br />M. Splitters shall be installed at every rectangular branch take -off from main or <br />according to the drawing and other requirements herein. <br />E. Mechanical equipment shall be installed according to manufacturers specific <br />detector cover. Visual indication of alarm or pilot must be provided on detector <br />secondary ducts. <br />Related work: Documents affecting work of this Section include but are not <br />D a g � <br />recomendations and suggested clearances. <br />99 <br />front. A manual reset shall be located on the front cover. Detector heads shall not <br />N.transitions <br />Duct (size or shape) shall be constructed with a maximum 20 degree <br />necessarily limited to, General Conditions Supplementary Conditions And Sections in <br />F. Condensate pans shall be pitched toward the drain line such that the pan drains <br />require additional filters or screens which must be maintained. Wire terminals shall be <br />angle per side for diverging air flow. For contracting air flow use 30 degree maximum <br />Division 1 of these Specifications. <br />P <br />completely with no standing water. Provide and install a condensate trap according to <br />of the screw type,#6 minimum. Terminals shall be provided for remote pilot and alarm <br />angle r i <br />a g per side. <br />1.2 STANDARDS, CODES, PERMITS, INSPECTIONS AND FEES <br />equipment manufacturers specifications. <br />indication. Detector shall operate on either; 24VAC, 24VDC or 115VAC. Mechanical <br />F. Where flexilbe duct is indicated it shall not exceed 10 feet. Where longer branch <br />A. APPLICABLE STANDARDS: Comply with the latest edition of the following standards: <br />G. Outside air intake ducts shall be insulated galvanized sheet metal, and shall be <br />contractor shall provide correct detector tube length (according to manufacturers <br />runs are needed the additional length required shall be round sheet metal duct <br />01, ASHRAE 05, Fla BuildingCode 09. FLA. ENERGY CODE <br />located so that no ventilation or plumbing vent exhaust or any other contaminant <br />instructions). The smoke detector shall be installed such that when activated (or if <br />originating at the trunk and extending to attach to the last 10' of flexible duct. <br />02. SMACNA 06. OSHA 10. Chapter 6a-2 Fla. <br />could enter the building through it. The requred spacing shall be in accordance <br />the head is removed) the evaporator fan motor and any exhaust or supply fan <br />The round sheet metal duct shall insulated with approved R6 insulation and <br />03. Nat'l Electrical code 07. NFPA 9OaA & 90B Admin. Code. <br />with ASHRAE Standard 62 latest editon. Install according to referenced codes. <br />(larger than 150 cfm and located in the zone served by the evaporator fan motor) <br />properly sealed vapor tight. <br />04. Local/City Ordinances 08. NFPA 101 11. ASHRAE Standard 62 <br />H. A new set of MERV 6 rated filters for all air passing through the cooling coil. Filters <br />shall have its supply power interupted. <br />B. PERMINTS, INSPECTIONS, AND FEES: Secure and pay for all permits, inspections, <br />to be provided and installed by the mechanical contractor hen constructon is complete. <br />F. MOTORIZED OUTSIDE AIR DAMPERS: Motorized outside air dampers shall be installed <br />1.11 A DUCTWORK -SHEET METAL <br />and fees required of the work. <br />I. Air distribution system balancing dampers are required on each supply, return, <br />on the outside air supply to each air handler. The dampers shall be 24V A.C. and <br />A. All duct materials, accessories, fabrication and installtion shall meet the <br />1.3 WARRANTY <br />outside air intake and exhaust branch line. Locate where branch line connects to <br />shall be the continous full stall operation type. The dampers shall be located in an <br />requirements of the latest edition of SMACNA for low pressure metal ducts for 1" <br />A. For one year, warrant the work specified herein against becoming unserviceable or <br />trunk line or, if no trunk line, as close to fan motor as practical. <br />accessible location. Leakage shall not exceed 5% of the outside air flow. During building <br />static pressure, NFPA 90A, the Florida Energy Code, the Standard Mechanical Code, <br />causing an objectionable appearance resulting from either defective or nonconforming <br />J. Condenser/outside unit slabs: The mechanical contractor shall supply a concrete <br />occupied hours when thermostat is in "Cool" position each system's damper <br />local codes and UL 181 - class 1. <br />material and workmanship, <br />slab that is 6 minimum larger on all sides than the equipment placed on it. The <br />shall be open when its' compressor operates. During building occupied hours when <br />B. Duct work shall be supported at not more than six (6) foot centers and at all <br />B. Defects shall include, but not be limited to, the following: 01 Loss of freon <br />thickness and reinforcement of the slab shall be as follows: <br />thermostat is set in the "Heat' position each system's damper shall be be open. <br />turns and transitions. Hangers shall be 3/4 gauge straps or No. 12 wire securely <br />02 Excessive noise or vibration <br />Unit weight Concrete thickness Reinforcement <br />During unoccupied hours all dampers shall be closed. Provide and install the necessary <br />anchored to construction above. All duct work shall be adequately protected at <br />03 Loss of capacity <br />0 - 200 Ibs 2" " none required <br />timers, controls, etc. <br />comers from hanging straps with sheet metal angles (2"x2" minimum). Duct shall <br />04 Condensate dripping <br />200 - 800 Ibs 4 #5 rebar, 12" spacing each way <br />„ <br />shall be supported in accordance with the Florida Energy Code. <br />C. Warrant the compressor for 5 years. <br />800 - 2,000 Ibs 6 5 rebar, 12 spacing each way <br /># p g y <br />C. Exernal duct wrap insulation: Wrap shall be fiberglass laminated to a <br />p p g <br />1.4 SUBMITTALS <br />2,000 - 8,000 Ibs 8" #5 rebar, 8 spacing each way <br />1.9 Deleted <br />reinforced foil/kraft vapor barrier facing such as, Owens/coming type 75. <br />A. PRODUCT DATA: The General Contractor, within 35 days after receiving the Owners <br />K. These specifications are an integral part of the drawings. <br />1.10 PIPE AND FITTINGS <br />Installation shall be per manufacturers instructions and referenced codes. The <br />Notice to Proceed shall submit to the Engineer 5 sets of schedules, charts, <br />L. Use adequate numbers of skilled workmen who are thoroughly trained and <br />A. REFRIGERANT CIRCUIT: Unless otherwise shown on the drawing use ACR copper piping <br />insulation shall meet the requirements of the Florida Energy Code for the specific <br />literature, manufacturers recommended installation procedure and illustrations to <br />experienced in the necessary crafts and who are completely familiar with the <br />with silver brazed sweated joints and wrought copper fittings. Provide refrigerant <br />1° g PP g g <br />application in which it is used. <br />indicate the performance, fabrication procedures, product variations and accessories <br />specified requirements and the methods needed for proper performance of the work <br />line valves for servicing the systems. Provide sight lass on liquid line at exit of <br />g Ys g g q <br />D. All duct and insulation seams, joints, connections, etc., shall be sealed b mastic <br />� y <br />on the submitted items. The submittal shall be approved b the General Contractor <br />PP Y <br />of this Section. <br />condenser. Provide suction line accumulators sized according to equipment <br />and glass fabric, using methods and materials approved by the manufacturer and <br />for exact conformance with the plans and specifications and shall bear his approval <br />M. Without additional cost provide such other labor n materials r required <br />su oand as a e e u ed <br />Pq <br />- <br />manufacturer r ccommend tions. Provide solenoid valves freon filter driers <br />e a <br />- <br />meeting the requirements of UL 181-class 1 <br />9 q ass <br />stamp. If deviations or substitutes are submitted they must be clearly noted on the <br />to complete the work of this Section in accordance with the requirement of <br />P q <br />governmental agencies having jurisdiction, regardless of whether such materials and <br />receivers, traps and other items as required or recommended by the manufacturer <br />1.12 EXHAUST -FANS: Schedule on HVAC drawings. <br />cover sheet. Cost of review for deviations or substitutions shall be billed to theP <br />associated labor are called for elsewhere in these Contract <br />for the equipment s specified, as installed for this application. Whenever refri erant <br />PP <br />g <br />with the manufacturers recommendations and the ASHRAE REFRIGERATION VOLUME. <br />A. Locate exhaust outlets at least 12 feet from any building air intakes, windows, <br />mechanical contractor at the Engineers current consulting rate. The Engineer shall <br />N. Layout work and set sleeves or order rough openings throw h prefabricated <br />Yo ( 99 P <br />B. CONDENSATE DRAIN LINES: PVC schedule 40 unless shown otherwise on the drawing. <br />etc. Install according to referenced codes. <br />review the submittal for general design intent only. Submitted items shall not be <br />wall, floors, etc. so there shall be a minimum of cutting,drilling and patching. <br />g P g <br />Ol Material: PVC schedule 40 unless otherwise shown on drawing. <br />B. Exhaust ducts shall be constructed of galvanized sheet metal. <br />purchased or any work commenced until the engineer has reviewed the submittal. <br />0. Makeup air to bathrooms shall be provided by installing a transfer grill to each <br />02 For roof -top installations condensate shall be supported with <br />of flexible duct shall be installed at the terminal end of each branch run for noise <br />Substituted or optional equipment where permitted or approved, must conform to space <br />bathroom/janitor room entry door. The grill shall be located as near the bottom as possible <br />pipe pipestands <br />Mirro Industries Mod. 3 R with accessory. Maxium spacing of 6 feet <br />reduction. <br />requirements. An substituted equipment that cannot meets ace requirements, even if <br />the_ <br />g <br />xdoo <br />�� pipestrap <br />" <br />1.13 INSPECTIONS: <br />accepted for general design intntshall be replaced at the contractors expense. <br />tion, 20 z2O" size non-rate doors. 1t hour r rated doors use Nailor Industries model <br />for 3 4 din and smaller. Maxium s acin of 8 feet for 1 din and larger. <br />spacing 9 <br />A. Provide personnel and equipment, make required tests, and secure required <br />Any modifications as a result of substitutions shall be made at the contractors <br />series 2600, 1.5 hours rated door grill, 20 x20 size. <br />C. INSULATIO <br />01 Insulate refrigerant lines with insulation: 1/2 » thick for pipes up to 1 » <br />approvals from the Engineer and governmental agencies having jurisdiction. <br />expense. Submittals shall be made on the following items: <br />P. All motor driven equipment shall require vibration isolators and sound control as <br />diameter, 3/4 " thick for pipes 1 1/4 to 2" diameter and 1" thick for pipes 2 1/2" to <br />B. Make written notice to the Engineer at least ten (10) day in advance of each <br />01 Major equipment items, such as heating, ventilating refrigeration and air <br />shown on the drawing or if not shown provide the following: (a) suspended equipment <br />4" diameter. Material shall be of the closed cell foam type. Insulation shall have <br />of the following stages of construction. <br />conditioning equipment. <br />shall use rubber -in -shear type suspensions for loads of 25 Ibs or less at each <br />an "R" value meeting the requirements of the Florida Energy Code. <br />a <br />01. When rough -in (ductwork and other systems are completed to the extent they <br />02 Registers, grilles, thermostats, hoods, fans, vibration isolators, specialty <br />suspension point. Spring type mountings shall be used for larger loads. (b) Floor, pad <br />Insulate condensate lines within the building with 1" closed -cell foam insulation. <br />are ready to be covered with the ceiling, floor, wall, etc.) is complete. <br />items. <br />mounted or roof -top mounted equi ment shall be installed with open spring isolators <br />1.11 DUCTWORK t}1-1/2 THICK RIGID FIBROUS GLASS DUCT) <br />02. When all work in this section is complete. <br />P <br />B. MANUAL: The mechanical contractor upon completion of this portion of the work, <br />P P P <br />Amber Booth type SW or a uivalent� for a ui ment wei hin less than two hundred <br />( / YP q q P 9 9 <br />A. All duct materials, fabrication and installation shall meet the requiremensts of <br />1.14 AIR FILTERS <br />and as a condition of its acceptance, deliver to the Architect two copies of an <br />pounds and enclosed spring type Amber Booth types XLS XL or equivalent) for <br />you s e p g yp ( / yp , q ) " <br />the latest edition of the SMACNA Fibrous glass duct Construction Standard, NFPA 90A, <br />A. Filter Media: The filter media shall have an average ASHRAE dust -spot <br />operation and maintenance manual containing the following: <br />heavier equipment. (c) Roof top curb mounted equipment shall have a continous 3/8 <br />UL 181 - class 1, the Standard Mechanical Code, the Florida Energy Code and local <br />efficiency of 60 % as tested against the method contained in ASHRAE standard <br />- <br />01 Hardback three ring loose-leaf binder. <br />thick cross ribbed neoprene ad Amber Booth type NR or a uivelent installed <br />P P ( / YP q ) <br />codes or requirements. Closures (joints, seams and penetrations) shall be by mastic <br />52.1-1992. The fileter media shall have an average ASHRAE arrestance of 70 % as <br />02 Title sheet with job name, General Contractor and this subcontractor listed <br />between curb and equipment for equipment weighing less than 600 pounds. Heavier <br />and glass fabric, using methods and materials approved by the duct board <br />tested by that standard. <br />including address and telephone number. <br />equipment shall have continous spring rail isolators with a weather seal (Amber/Booth <br />manufacturer to meet the requirements of UL 181 - class 1. Duct board shall be <br />B. Underwriters' Laboratories Listing: The filter shall be listed by Underwriters' <br />03 Index of contents. <br />type RTIR or equivalent). All vibration isolators shall be selected according to the <br />manufactured by Knauf, type M or equiv. <br />Laboratories as Class (1 or 2). <br />04 Typewritten operating instructions for the Owner describing: <br />manufacturers recommendations for weight and type of equipment. The roof deck shall <br />B. Duct be than (6) foot <br />1.15 TESTS: <br />a. How to stop and start each piece of equipment. <br />be cut no larger than to allow clearance for the duct penetration. Acoustical duct <br />work shall supported at not more six centers and at all <br />turns transitions. Hangers be 3/4", 24 No. 12 <br />A. The mechanical contractor shall demonstrate to the satisfaction the <br />b. How to set equipment and systems for normal operation. <br />liner (1-1/2) shall be attached (by adhesive) to the remaining roof deck within the <br />and shall gauge straps or wire securely <br />engineer, at the time f final system <br />9 e o f a acceptance, that the entire Hper system is free from <br />c. Normal restartingprocedures before contacting the service contractor. <br />P g <br />curb perimeter and snugly fit to the duct exterior and the curb. <br />This do backfill for the installation <br />anchored to construction above. All duct work shall be adequately protected at <br />corners from hanging straps with sheet metal angles (2"x2" minimum). <br />defects in materials and workmanship and that the system performs as intended. The <br />d. Complete description of functions and operations of each piece of <br />Q. contractor shall all excavation and required <br />q <br />of his work, except where specific requirements are given, excavation and placement <br />C. All surfaces behind diffusers or grilles visible from room shall be painted flat <br />mechanical contractor shall furnish all necessary equipment and personnel to perform <br />YP <br />equipment including description of how equipment o erates in <br />9 PP <br />black. <br />h <br />these tests. <br />conjunction with automatic control systems. <br />and compaction of backfill in connection with mechanical work will have the same <br />P <br />requirements as specified in other sections of these specifications. <br />D. Insulated flexible duct shall be manufactured by Thermaflex or approved equal and <br />B. Balancing: The mechanical contractor shall balance the air flows according to <br />e. Complete instructions for cleaning, oiling, greasing, filter sizes and all <br />P 9� 9. 9 9� <br />R. Hangers, anchors and other devices used to secured mechanical equipment to <br />shall be approved by UL standard 181-class I and NFPA 90A. Duct shall be constructed <br />the values shown on the drawing. A report shall be submitted to the engineer <br />other maintenance procedures as recommended b the manufacturer. <br />P Y <br />structural steel, shall be placed prior to the fireproofing of the structural steel. <br />of a zinc coated, high carbon spring steel helix permanently bonded to the core, <br />containing the following information, neatly arranged in tabular form. <br />OS Approved shop drawings and submittal data and parts maintenance <br />PP P 9 P <br />booklet for each item of material and equipment furnished under this division. <br />S. Air Ducts shall have have no more than two additional ninty degree turns (from <br />insulated with a nominal 1 Ib/cu.ft. density fiber glass that is completely shielded rom <br />01 Date of test, ambient wet and dry bulb temperatures and wet and dry <br />06 Any as -built wiring diagrams as called for in other sections of this Division <br />the air inlet to the air terminal) than indicated on the drawings without the approval <br />the air stream by a full interior liner. The insulation shall be sheathed in a outside <br />bulb temperatures in each one at time f <br />p z e o test. <br />as needed to show how equipment controls interface with related systems. <br />Ys <br />of the Engineer. If a detail is shown, no additional turns shall be allowed for that <br />vapor barrier jacket of metalized polyester film and meet the requirements of the <br />02 List each instrument used and record manufacturer, model and serial <br />07 Test and Balance report. <br />P <br />section shown in the detail. No additional turns shall be allowed in flexible ducts.of <br />Florida Energy Code for the specific application in which it is used. Maximum allowed <br />number. Indicate the type measurements taken with each instrument. Instruments <br />of certification of inspection. <br />08 Copies p <br />T. Deleted <br />length of each branch shall not exceed six feet. <br />used shall provide 5% (plus or minus) accuracy for the measurement taken. <br />09 Guarantees and warranties. <br />U. Delays caused by equipment not being on the job site when required shall be <br />E. All round take -offs shall be made with spin in fittings with 90 degree scoops. <br />03 Each air handler, condenser, fan, heater and other scheduled equipment shall be <br />avoided by temporary substitution of other equipment. This temporary equipment is <br />Balancingdampers shall be factor installed with spring loaded retractable bearing <br />P Y P 9 9 <br />listed with the following information:.. manufacturers name, model, serial no., and all <br />1.5 Deleted <br />subject to approval of the engineer and shall be removed and replaced with the <br />and a positive locking nut for easy readjustment. <br />other nameplate information (voltage, amps, <br />p ( g p etc.). The corresponding field measurement <br />1.6 GENERAL PROVISIONS FOR MECHANICAL WORK <br />specified equipment when it is arrives. <br />F. All duct dimensions are clear inside dimensions. <br />of voltage, amps, freon r equipment <br />g p pressures, etc. shall be listed when a ui ment is in use. <br />A. The drawings are to be considered diagrammatic and indicate the general <br />V. Provide and install an emergency condensate pan with an emergency shut-off <br />G. It shall be the contractors responsibility to verify dimensions and clearances <br />04 The final measurement (CFM) of each outlet, supply, intake, or exhaust <br />arrangement of the work and systems. Refer to building drawings to verify exact <br />float switch and a separate condensate drain line. This applies to horizontal) <br />P PP Y <br />with the building structure and work of other trades. Drawings are to be considered <br />rill shall be recorded and identified as to its location . The air flows specified on the <br />9 P <br />space locations and space conditions. Drawing scales prohibit the indication of all <br />mounted air handlers. <br />diagrammatic. Drawing scales prohibit the indication of offsets, fittings, and <br />drawing shall be listed next to the measured value. The total supply, return, intake <br />9 PP Y• <br />features including but not limited to: offsets, fittings and accessories required. <br />W. This contractor shall provide and install the required supports, brackets <br />accessories required, however these items will be provided by this subcontractor at <br />or exhaust from each piece of equipment shall be listed. <br />P <br />However, these items will be furnished and installed by this subcontractor AT NO <br />extensions, fasteners and frames to bridge between building structural members <br />or other items to properly support; ducts, equipment, attachments <br />P P Y PPH. <br />no cost to the owner. <br />Smoke detectors shall be installed where shown or as required in the referenced <br />05 The mechanical contractor shall submit the test report with a statement <br />P <br />EXTRA COST. If the contractor believes the space allowance is inadequate he should <br />and all devices which he provides or installs. When questions of strength, durabilti <br />P q 9 Y <br />codes. Installation shall be in accordance with NFPA 90A & 906. <br />attestingthat the report is true and accurate within the tolerances s <br />P specified. The <br />statement shall be signed b the contractor and his license number shall be listed <br />g Y <br />report this to the engineer before submitting his bid. <br />or suitabilityarise he shall consult with the project architect or structural engineer. <br />P J 9 <br />I. Fire stats shall be installed where shown or as required in the referenced codes. <br />below. <br />B. This subcontractor shall coordinate his installation with the work of other trades <br />and the General contractor with a plan to prevent interference of available <br />1.7 Deleted <br />Installation shall be in accordance with NFPA 90A & 90B. <br />06 After the report is submitted the engineer may request further tests, <br />provide <br />time. <br />adjustments or measurements. The mechanical contractor shall provide these services <br />space and <br />at no additional cost to the owner. The final payment may be withheld until the <br />engineer accepts the report. <br />F_� .'.�+; PLAN-STO"AGE/MECH'F h i ''=, 1 I IC <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />AD3--IN ATTIC <br />50 CFM <br />SEE NOTES <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />AD3-IN ATTIC <br />50 CFM <br />SEE NOTES <br />- I L__ - _ _ <br />BUILDING STRUCTURAL MEMBER AS <br />APPROVED BY ARCHITECT. <br />1/2-13 BOLT W/NYLOCK NUT <br />THRU CENTER OF MEMBER. <br />.1/2-13 EYE BOLT <br />(2) 1/2-13 JAM NUTS <br />�1/2-13 COUPLING <br />1/2-13 THREADED ROD <br />ISOLATION SPRINGS <br />AIR HANDLER <br />1 1 /2"x 1 1 /2"x 3/16" angle iron <br />1 /2-13 NYLOCK NUT <br />NOTE: ALL COMPONENTS <br />RIP PAN <br />ARE STEEL <br />EMERGENCY PE <br />R ER F LA. BLDG CODE <br />NO SCALE WITH FLOAT SWITCH WIRED TO SHUT OFF UNIT <br />IF WATER ACCUMULATES. <br />HORIZONTAL AIR HANDLER SUPPORT ARRANGEMENT <br />(THREE REQUIRED EACH AIR HANDLER) <br />ROUTE PIPING DOWN INSIDE WALL <br />AS NOTED ON PLAN ---� <br />FLOOR <br />EXTERIOR <br />WALL <br />'CONDENSATE DRAIN: EXIT WALL AS <br />LOW AS POSIBLE,AND SEAL <br />OPENING WEATHERTIGHT <br />DRIP IN CENTER OF DRYWELL <br />o° o;o, <br />$:0 \-PAVEMENT OR <br />ors FINISHED <br />°• GRADE <br />o .O; <br />0 <br />o:°'ao a ; ; , <br />o O•O, <br />• o <br />00::- <br />. • e <br />O e <br />O <br />WASHED, CRUSHED w:0• SOIL <br />ROCK OR STONE <br />WELL: 12" DEEP & 30" <br />DIA, WRAPPED WITH FILTER <br />CLOTH TO COMPETELY ENCLOSE <br />ROCK/STONE NOT INSIDE OF <br />CONDENSATE DRYWELL DETAIL THE SLEEVE <br />NO SCALE <br />WEATHERPROOF DISCONNECT <br />SWITCH <br />CMUt .:.' <br />WALL - <br />CLEARANCES TO WALLS, ETC <br />PER MANUFACTURERS INSTRUCTIONS <br />1 <br />O <br />CONCRETE PAD, 4" THICK <br />REFRIGERANT CON N A / CONTROL WIRES INSIDE OF STRENGTH. PITCH PAD <br />PSI COMPRESSIVE <br />4"PVC SCHEDULE 40 CHASE AWAYFROM BUILDING. <br />OR UP OUTSIDE WALL WITH <br />AWAY <br />4"x4" GALVANIZED COVER. 3/4" PVC CONDENSATE <br />SEAL OPENING WITH EXPANDING <br />FOAM OR ROOFING TAR, BOTH <br />ENDS OF CHASE. <br />O 14-16 GAGE, GALVANIZED SHEET METAL X 2" WIDE STRAP, 1 /2" OVERLAP OF CONDENSER BOTTOM PAN. <br />LOCATE ONE STRAP IN THE CENTER OF EACH OF (4) SIDES. ATTACH TO CONCRETE WITH 3/16"DIA x 2" <br />TAPCON. ATTACH TO PAN WITH #10 SHEET METAL SCREW. <br />CONDENSING UNIT INSTALLATION (TYP.) <br />N.T.S. <br />1J a <br />Z/r� C,� <br />I <br />V) <br />U Q <br />I Z <br />z N CV U <br />u7 <br />z m W <br />U 00 Q X <br />W LL- J <br />O <br />Q <br />Z = � <br />O r1_ W <br />Uj %' C) <br />< O U N O <br />U <br />/••� 00 W N <br />J 0 u7 <br />Q 0 CV Q <br />Of u7 F_- <br />1`0 Z <br />W LLJ <br />U 0 <br />LLL V) <br />LL_ LEI <br />O <br />N <br />� <br />L.0 W <br />J W <br />o <br />�� <br />Q Z p <br />a <br />N <br />vJw <br />W`0 <br />=paui�o <br />JLa <br />W(n <br />aJ��N <br />-Z <br />V <br />Zm <br />Z Oa <br />NZ <br />"'S2� <br />WW <br />z W <br />n�J <br />OZXLN <br />pUin <br />T <br />i a <br />0. d GW N <br />p <br />L-1i <br />� Ira o.. <br />a <br />0 <br />Z <br />O <br />N <br />w <br />Jo <br />00 <br />m N <br />z� <br />� �i <br />Q I--- <br />o Q <br />00 <br />z <br />O <br />I- U <br />M <br />a In <br />0 N <br />o0 <br />YEo <br />0 U <br />Q <br />� C140 <br />0 N r` 8 <br />v /() <br />m J <br />= Ca O <br />Z <br />� a v <br />O O <br />WN <br />U -J <br />J <br />LL <br />Of <br />z LL <br />W <br />Q <br />O <br />M <br />O <br />LL <br />W <br />J W <br />O <br />a_ W <br />p� <br />C <br />G Z <br />0E-O <br />I..L <br />U <br />LL <br />Q <br />♦^w <br />0 <br />LL _ <br />LL <br />TJ <br />O <br />LL <br />J�}T' <br />Q 0 <br />2 <br />UWCL <br />Q. <br />W <br />0 <br />N <br />W <br />2 <br />