FLORIDA HOSPITAL = ZEPHYRHILLS, FL
<br />CHILLER NO. 2 REPLACEMENT
<br />100%
<br />MECHANICAL SPECIFICATIONS
<br />I ELECTRICAL SPECIFICATIONS
<br />DRAWING LIST
<br />1. ALL SYSTEMS AND MATERIALS SHALL BE CONSTRUCTED IN STRICT ACCORDANCE WITH THE CURRENT EDITION OF ASHRAE FUNDAMENTALS,
<br />1. GENERAL: PROVIDE MATERIALS, EQUIPMENT, ACCESSORIES, INCIDENTALS, ARTICLES, ITEMS OPERATIONS,
<br />NATIONAL ELECTRICAL CODE, NATIONAL FIRE PROTECTION ASSOCIATION, THE FLORIDA BUILDING CODE, MECHANICAL, PLUMBING, AND ENERGY
<br />INCLUDING LABOR, NECESSARY FOR COMPLETION OF WORK CALLED FOR ON THESE DRAWINGS.
<br />CONSERVATION, LATEST ADOPTED EDITIONS, AND ALL CITY, COUNTY, STATE, AND FEDERAL CODES AND STANDARDS AS APPLICABLE FOR AND ALL
<br />ME-1 COVER SHEET
<br />AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT.
<br />2. REGULATORY REQUIREMENTS: ALL WORK SHALL CONFORM TO THE LATEST EDITION, ADOPTED BY THE
<br />AUTHORITY HAVING JURISDICTION, OF THE FLORIDA BUILDING CODE, THE NATIONAL ELECTRICAL CODE AND
<br />2. IF MECHANICAL EQUIPMENT OTHER THAN AS SPECIFIED IS UTILIZED WITH DIFFERENT ELECTRICAL, MECHANICAL, PLUMBING, OR DIMENSIONAL
<br />THE NFPA. WORK SHALL COMPLY WITH THE REQUIREMENTS OF OSHA AND THE LOCAL BUILDING
<br />M-1 MECHANICAL PLAN - CHILLER ROOM - DEMOLITION
<br />CHARACTERISTICS, THAN THE CONTRACTOR SHALL COORDINATE WITH OTHERS AND PROVIDE THE NECESSARY CHANGES WITHOUT ADDITIONAL COST
<br />DEPARTMENT PLANS REVIEWERS AND FIELD INSPECTORS. MATERIALS SHALL BE UNDERWRITERS
<br />TO THE OWNER.
<br />LABORATORIES APPROVED.
<br />M-2 MECHANICAL PLAN - CHILLER ROOM - RENOVATION
<br />3. SUBMIT SHOP DRAWINGS OF ALL EQUIPMENT AND MATERIALS FOR REVIEW BY THE ENGINEER. PROVIDE ADEQUATE COPIES FOR OWNER,
<br />3, COORDINATION: INSTALLATION OF ALL WORK SHALL BE COORDINATED WITH EXISTING CONDITIONS IN THE
<br />ENGINEER, CONTRACTOR, VENDOR RECORDS. PROVIDE WRITTEN INSTALLATION INSTRUCTIONS AND RECOMMENDATIONS FROM EACH
<br />MANUFACTURER FOR ALL EQUIPMENT. SUBMIT DRAWINGS AND CATALOG CUT SHEETS FOR ALL EQUIPMENT AND MATERIALS SPECIFIED.
<br />BUILDING. THE ELECTRICAL CONTRACTOR SHOULD VISIT THE SITE PRIOR TO SUBMITTING A FEE
<br />PROPOSAL FOR THE WORK. THE ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OF
<br />M-3 MECHANICAL - DETAILS - SCHEDULES
<br />4. SYSTEM CONTROLS SHALL BE PROVIDED BY TRANE CONTROLS. COORDINATE WITH AND REFER TO TRANE CONTROL DOCUMENTS FOR SEQUENCE
<br />ELECTRICAL SERVICE TO EQUIPMENT FURNISHED BY OTHER TRADES. ELECTRICAL WORK SHALL BE
<br />OF OPERATION AND METHODS OF CONTROL FOR ALL EQUIPMENT. THE CONTRACTOR SHALL COORDINATE ELECTRICAL REQUIREMENTS TO
<br />PHASED AS REQUIRED BY THE WORK OF OTHER TRADES.
<br />PROVIDE POWER TO LOCATIONS REQUIRED FOR OPERATION OF SYSTEMS AND ASSOCIATED CONTROLS.
<br />E-1 ELECTRICAL - PARTIAL PLAN - RENOVATION
<br />4. GUARANTEES: THE CONTRACTOR SHALL PROVIDE AONE-YEAR WRITTEN GUARANTEE FOR ALL MATERIALS
<br />5. PROVIDE ALL NECESSARY VALVES, FITTINGS, AND ACCESSORIES IN THE CHILLED & CONDENSER WATER PIPING SYSTEMS AS REQUIRED FOR
<br />AND LABOR FROM THE DATE OF SUBSTANTIAL COMPLETION. GUARANTEE SHALL COVER ALL LABOR AND
<br />REMOVAL AND RENOVATION OF SYSTEMS AS INDICATED. COORDINATE WITH THE TRANE CO. TO DETERMINE ANY SPECIAL REQUIREMENTS OR
<br />MATERIALS TO REPLACE DEFECTIVE MATERIALS AND TO ENSURE PROPER OPERATION OF ALL SYSTEMS.
<br />ACCESSORIES REQUIRED FOR THE CONTROLS AND PROVIDE THESE ACCESSORIES IN THE PIPE SYSTEMS.
<br />E-2 ELECTRICAL - PARTIAL PLAN - DEMOLITION
<br />5. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS AND PRODUCT INFORMATION FOR ALL ELECTRICAL EQUIPMENT
<br />6. ALL ABOVE GRADE CHILLED AND CONDENSER WATER PIPING SHALL BE SCHEDULE 40 BLACK STEEL WITH WITH THREADED JOINTS FOR SIZES
<br />AND DEVICES.
<br />UP THROUGH 0/2". CONTRACTOR MAY USE SWEAT COPPER, TYPE L, FOR SMALL SIZES. PIPING LARGER THAN 2Y" SHALL BE WELDED OR
<br />FLANGED JOINTS. PROVIDE DIELECTRIC COUPLING BETWEEN DISSIMILAR METALS. FLANGE GASKETING MATERIALS FOR FLANGED CONNECTIONS
<br />6. CONDUIT: MINIMUM SIZE SHALL BE 3 / 4 INCH. GALVANIZED RIGID STEEL CONDUIT WITH LIQUIDTIGHT
<br />SHALL BE SUITABLE FOR THE CHEMICAL AND THERMAL CONDITIONS OF THE PIPING SYSTEM CONTENTS, ASME B16.21, NONMETALLIC, FLAT,
<br />FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT OUTDOOR LOCATIONS. ELECTRICAL METALLIC TUBING
<br />ASBESTOS FREE, 1/8" MAXIMUM THICKNESS. FLANGES SHALL BE FULL FLAT FACE, CLASS 125 CAST IRON, ASME B16.20. FLANGE BOLTS AND
<br />WITH COMPRESSION FITTINGS SHALL BE PROVIDED AT INDOOR/DRY LOCATIONS.
<br />NUTS SHALL BE ASME B18.2.1, CARBON STEEL. REFER TO PLANS FOR THERMOMETERS, GAGES, AND OTHER ACCESSORIES AND COMPONENTS
<br />TO BE PROVIDED ON PIPING SYSTEMS AT CHILLER. PROVIDE WELDOLETS, AS REQUIRED, FOR CONTROL DEVICES ON EXISTING AND NEW
<br />7. BUILDING WIRE AND CABLE: CONDUCTORS SHALL BE COPPER RATED FOR 600 VOLTS, WITH THHN/THWN
<br />PIPING.
<br />INSULATION. CONDUCTOR SIZES NO. 10 AWG AND SMALLER SHALL BE SOLID. CONDUCTOR SIZES NO.
<br />8 AND LARGER SHALL BE STRANDED. COLOR CODING SHALL MATCH EXISTING.
<br />7. ALL VALVES IN CHILLED AND CONDENSER WATER PIPING SHALL BE BRONZE OR CAST IRON BODY WITH BRONZE FITTED TRIM. DRAIN VALVES,
<br />SPANISH TRAILS BLVD.
<br />WHERE REQUIRED, SHALL BE 1 /4 TURN, TWO-PIECE, BRONZE BALL VALVES WITH TEFLON OR PTFE SEATS AND CHROME PLATED BRASS BALL,
<br />8. ELECTRICAL IDENTIFICATION: PROVIDE ENGRAVED NAMEPLATE LABELS, INDICATING LOAD OR EQUIPMENT
<br />THREADED OR SOLDER CONNECTION. GLOBE VALVES 2Y" AND SMALLER SHALL BE CLASS 125, FNPT CONNECTION, BRONZE BODY, TOP
<br />SERVED, FOR DISCONNECTS AND CONTROL EQUIPMENT. LETTERS/NUMBERS SHALL BE MINIMUM 5/8"
<br />WORK AREA
<br />MALLEABLE IRON HAND WHEEL, RISING BRONZE STEM, UNION STYLE BONNET,BRONZE WEDGE, STD. MSS-SP-80. WAFER BUTTERFLY WAFER
<br />HIGH ETCHED INTO BLACK LAMACOID AND ATTACHED WITH STAINLESS -STEEL SCREWS. PROVIDE NEW
<br />FLORIDA HOSPRAL7050
<br />LUG -STYLE SHUTOFF VALVES TO FIT BETWEEN FLANGES SHALL BE CAST IRON BODY, 200 PSI PRESSURE RATING, EPDM MOLDED -IN SEAL
<br />TYPEWRITTEN DIRECTORY, FOR PANELS AFFECTED BY THIS WORK, WITH EXISTING/REMAINING CIRCUITS
<br />GeV A�
<br />CENTRAL PLANT
<br />ZEPHAHtiLS, FL o CENTRAL
<br />LINER, ALUMINUM BRONZE DISC, STAINLESS STEEL STEM WITH COPPER BUSHINGS, GEOMETRIC DRIVE, EXTENDED NECK, WITH MANUAL GEAR
<br />TRACED AND IDENTIFIED, NEW CIRCUITS IDENTIFIED AND SPARES AND/OR SPACES IDENTIFIED IN PENCIL.
<br />OPERATOR OPERATING MECHANISM; LEAD FREE, MEETING MSS SP-87 AND MSS SP-25 SPECIFICATIONS, NIBCO MODEL WC-2000 OR EQUAL.ry
<br />CONTRACTOR HAS OPTION TO USE BRONZE VALVES IN LIEU OF IRON BODY.
<br />9. GROUNDING: BOND NON -CURRENT -CARRYING METAL PARTS OF EQUIPMENT ENCLOSURES, METAL
<br />o
<br />RACEWAY SYSTEMS, GROUNDING CONDUCTOR IN RACEWAYS AND CABLES AND RECEPTACLE GROUND
<br />8. ALL NEW AND EXISTING PIPING SHALL BE SUPPORTED WITH RE -USED EXISTING OR NEW CLEVIS TYPE HANGERS AND/OR UNISTRUT SYSTEMS
<br />CONNECTORS. PROVIDE INSULATED GROUND CONDUCTOR IN ALL RACEWAYS. INSPECT GROUNDING AND
<br />ATTACHED TO THE EXISTING BUILDING OR STEEL SUPPORT STRUCTURE. SIZE HANGERS TO ACCOMMODATE PIPING INSULATION THICKNESS AND
<br />BONDING SYSTEM CONDUCTORS AND CONNECTIONS FOR TIGHTNESS AND PROPER INSTALLATION.
<br />PROVIDE HANGER SPACING PER CODE. PROVIDE INSULATION SADDLES AT ALL HANGER LOCATIONS. PROVIDE A SHEET METAL PROTECTIVE
<br />COVERING OVER INSULATION AT ALL HANGERS OR SUPPORT POINTS WITH MINIMUM 6" LONG GALV. SHEET METAL PIPING PROTECTION SADDLE
<br />10. INSTALLATION: ALL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE
<br />DAUGHTERY RD.
<br />SHIELDS. LOCATE AT THE BOTTOM OF EACH PIPE TO FIT BETWEEN THE HANGER OR SUPPORT AND THE BOTTOM OF PIPING INSULATION.
<br />RESPECTIVE MANUFACTURER'S WRITTEN INSTRUCTIONS/REQUIREMENTS. PROVIDE ADEQUATE CLEARANCE
<br />FOR ALL EQUIPMENT. ANY RE -USED WIRING SHALL BE DE -ENERGIZED AND INSULATION RESISTANCE
<br />SITE PLAN
<br />SHALL BE TESTED USING A "MEGGER". TEST EACH CONDUCTOR IN A RACEWAY INDIVIDUALLY TO EACH
<br />9. ALL DRAIN PIPING, WHERE REQUIRED, SHALL BE SWEAT COPPER DWV PIPING AND FITTINGS, AS SELECTED BY CONTRACTOR. SLOPE PIPING AT
<br />MIN. Y4" PER FT.
<br />OTHER AND TO GROUND.
<br />NOT TO SCALE
<br />GENERAL DRAWINGS AND COORDINATION NOTES'
<br />10, REMOVE EXISTING CONDENSER WATER PIPING, CHILLED WATER PIPING, ALL FITTINGS, HANGERS, ETC., AND REMOVE ALL CHILLED WATER PIPING
<br />11. CONTROL SYSTEM: CONTROL SYSTEM RACEWAYS, CONDUCTORS AND CONNECTIONS WILL BE PROVIDED BY
<br />OTHERS.
<br />INSULATION ON PIPING AND FITTINGS, AS REQUIRED TO PERFORM RENOVATION WORK. REPAIR AND REPLACE INSULATION ON EXISTING CHILLED
<br />WATER PIPING AND FITTINGS AS REQUIRED AND PROVIDE NEW INSULATION ON ALL NEW CHILLED WATER PIPING, FITTINGS, VALVES, AND OTHER
<br />ACCESSORY COMPONENTS IN THE PIPING SYSTEM.
<br />THE NOTES SHOWN ON THIS SHEET APPLY TO GENERAL CONDITIONS OF ALL WORK FOR HEATING, VENTILATING, AIR CONDITIONING,
<br />ELECTRICAL, AND PLUMBING REQUIRED FOR THIS PROJECT. REFER TO SPECIFICATIONS AND SCHEDULES THAT ARE SHOWN OR
<br />11. NEW AND REPLACED OR REPAIRED CHILLED PIPING INSULATION SHALL BE PITTSBURGH CORNING "FOAMGLASS" RIGID CELLULAR FOAM
<br />NOTED ON THESE DRAWINGS FOR ALL WORK AND MATERIALS REQUIRED FOR THIS PROJECT.
<br />INSULATION, 2" THICK ON ALL CHILLED WATER SUPPLY AND RETURN PIPING TO MATCH EXISTING. INSULATION SHALL BE APPLIED TO PIPING
<br />WITH ALL JOINTS SEALED FULL DEPTH WITH JOINT SEALANT. ALL JOINTS SHALL BE TIGHTLY FILLED WITH NO VOIDS. JOINT SEALER SHALL NOT
<br />THE CONTRACTOR AND SUB -CONTRACTORS ARE RESPONSIBLE FOR COORDINATION WITH ALL WORK OF OTHER TRADES AND
<br />BE USED TO FILL VOIDS OR CRACKS. JOINTS LESS THAN OR EQUAL TO 1/8 IN ARE DESIRABLE. INSULATION SHALL BE SECURED WITH
<br />SPECIALTIES. THE CONTRACTOR SHALL LOCATE AND INSTALL ALL PRODUCTS AND SYSTEMS IN ACCORDANCE WITH AND IN
<br />CONJUNCTION WITH THE PLANS AND SPECIFICATIONS OF WORK SHOWN ON ALL ARCHITECTURAL, STRUCTURAL, ELECTRICAL, AND
<br />REINFORCED TAPE WHEN JACKETING IS APPLIED SEPARATELY, TWO STRIPS OF TAPE PER SECTION OF INSULATION. THE TAPE SHALL OVERLAP
<br />OTHER TRADE DRAWINGS TO INSURE PROPER LOCATIONS, SERVICE ACCESS, AND COORDINATION FOR ALL EQUIPMENT AND DEVICES.
<br />BY 50%. FITTINGS SHALL BE INSULATED IN A MANNER SIMILAR TO THAT FOR PIPING. APPLY MASTIC AND HARD CAST FINAL FINISH TO ALL
<br />INSULATED PIPING AND PAINT TO MATCH EXISTING PIPING. PROVIDE FLOW AND PIPING LABELS OVER FINAL INSULATE PIPE TO MATCH EXISTING.
<br />TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THESE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING
<br />CODES AND THE APPLICABLE FIRE PREVENTION CODE AND STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE
<br />WITH CHAPTER 1 OF THE FLORIDA BUILDING CODE AND FLORIDA STATUTE 633.
<br />12, PROVIDE NEW INSULATED CUSTOM COVERS FABRICATED AROUND THE BODY OF EACH CHILLED WATER PUMP, AND AROUND ALL GLOBE, GATE,
<br />BALL, BUTTERFLY WAFER VALVES, SPECIAL FITTINGS, FLEXIBLE CONNECTORS, FLANGES, ETC. USING INDUSTRY STANDARD COVERS FOR THESE
<br />DEVICES. MAKE COVERS REMOVABLE WHERE REQUIRED FOR SERVICE ACCESS. PROVIDE COVERS MADE FROM PITTSBURGH-CORNING
<br />CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF INSTALLATION AND DEMOLITION WORK WITH OTHER TRADES TO AVOID
<br />"FOAMGLAS ONE" 2" THICK INSULATION PRE -FORMED BLOCKS. SEAL, COVER, AND FINISH TO MATCH PIPING WITH SAME MATERIALS USED ON
<br />CONFLICTS. ALL EQUIPMENT SCHEDULED FOR DEMOLITION SHALL BE REMOVED FROM THE SITE AND PROPERLY DISPOSED OF AT
<br />PIPING INSULATION.
<br />APPROVED FACILITIES. CONTRACTOR SHALL COORDINATE EXACT LOCATIONS OF NEW MECHANICAL EQUIPMENT WITH STRUCTURAL
<br />SUPPORTS AND OTHER EXISTING ROOFTOP EQUIPMENT THAT REMAINS.
<br />13. TEST AND BALANCE ALL SYSTEMS TO PROVIDE SPECIFIED WATER FLOWS TO WITHIN PLUS OR MINUS 10%. SEE PLANS OR SCHEDULES FOR
<br />EXISTING EQUIPMENT LOCATIONS AND DATA ARE BASED ON FIELD MEASUREMENTS AND EXISTING DRAWING DATA. CONTRACTOR SHALL
<br />WATER FLOW VALUES. PROVIDE TEMPERATURE, PRESSURE, AND FLOW READINGS FOR WATER FOR CHILLED AND CONDENSER WATER FLOWS
<br />FIELD VERIFY EXACT LOCATIONS OF ALL ITEMS.
<br />THRU CHILLER. COORD AND REPORT ALL FLOW, TEMPERATURE AND PRESSURE READINGS FOR ALL DEVICES AND COMPONENTS IN A
<br />TABULATED REPORT FORMAT TO THE ENGINEER FOR REVIEW. ALL TEST AND BALANCE WORK AND REPORTING PROCEDURES SHALL BE IN
<br />ANY ROOF OR WALL PENETRATIONS LEFT AS A CONSEQUENCE OF DEMOLITION OR NEW WORK SHALL BE REPAIRED TO MATCH
<br />ACCORDANCE WITH NEBB OR OTHER RECOGNIZED STANDARDS.
<br />EXISTING CONSTRUCTION AND FINISHES.
<br />14. CONTRACTOR SHALL COMPILE ALL WRITTEN MANUFACTURER'S WARRANTIES AND OPERATION/MAINTENANCE INSTRUCTIONS AND SUBMIT TO THE
<br />OWNER.
<br />or ZEPMYRHILLS
<br />CIT`�
<br />PLANS
<br />'/ �
<br />SKALL COMPLY
<br />WICH ALL �� V
<br />ALLWORK CODES, CODE OD
<br />pREVA11 ELECTIRIC ANCES
<br />CODE 1w10NAL ILLS ORI�
<br />CITY OF ZEPHYRtt
<br />Tampa Bay Trane
<br />® �d
<br />•��N •CNN M •�N •�•
<br />• 00NN90IMI*968 00
<br />z
<br />W
<br />0
<br />W
<br />J
<br />Revisions:
<br />No.
<br />Description
<br />Date
<br />1
<br />INITIAL ISSUE
<br />1/11/15
<br />z
<br />O
<br />LZLI
<br />�U
<br />f
<br />�
<br />Z J
<br />JLua.
<br />M
<br />U.
<br />6
<br />Cl)Q N
<br />O 0
<br />-d J
<br />E
<br />J
<br />_ a- z
<br />J
<br />m
<br />z
<br />WW
<br />=
<br />c0�
<br />v
<br />.i
<br />0_=
<br />0.
<br />a
<br />LL U 0
<br />pW
<br />ti N
<br />Cn
<br />W
<br />O
<br />z
<br />Cl)
<br />\
<br />J
<br />z
<br />O W
<br />Q J
<br />z
<br />—vv
<br />o
<br />E
<br />z
<br />z
<br />M
<br />z
<br />Q
<br />..
<br />— LL W
<br />J
<br />VWW
<br />Q
<br />i
<br />W J
<br />a v
<br />o
<br />W
<br />Cn Cn
<br />Project
<br />Engineer:
<br />G. BARBARI
<br />Project
<br />Manager:
<br />S. HELMER
<br />Sales
<br />Engineer:
<br />R. GERUN
<br />Date:
<br />11 /11 /15
<br />Job #: CROH5298715
<br />File Name:
<br />Sheet #: ME-1of 1