GENERAL ELECTRICAL NOTES <br />1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (N.E.C. 2008) AND <br />GOVERNING MUNICIPAL, STATE AND LOCAL CODES. ALL MATERIAL SHALL BE NEW AND SHALL BEAR THE <br />U.L. LABEL WHERE APPLICABLE. <br />2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS <br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY THE <br />OWNER. <br />3. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE <br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM <br />AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING <br />ORDER. <br />4. CONTRACTOR SHALL MAKE ALL NECESSARY CUTTING AND DO ALL THE REPATCHING AS NECESSARY FOR <br />THE PROPER EXECUTION OF THIS WORK. <br />5. AFTER COMPLETION OF THE INSTALLATION, THE SYSTEM SHALL TEST FREE FROM SHORT CIRCUITS AND <br />GROUNDS. <br />6. WHERE ELECTRICAL CONDUCTORS ARE INSTALLED IN CONDUIT, THE CONDUIT SHALL COMPLY WITH THE <br />N.E.C. REQUIREMENTS. <br />7. ALL CONDUCTORS SHALL BE COPPER. NO CONDUCTOR SHALL BE SMALLER THAN #12 AWG AND SHALL <br />BE RATED FOR 600VOLTS THWN OR THHN INSULATION. INSTALL A GROUNDING CONDUCTOR WITH ALL <br />CIRCUITS, UNLESS NOTED OTHERWISE, SIZED PER N.E.C. 250-122. <br />8. VERIFY BREAKER AND CORRESPONDING WIRE SIZES FOR ALL ELECTRICAL EQUIPMENT. DO NOT ORDER <br />MATERIAL BEFORE VERIFYING BREAKER & WIRE SIZE. REPORT ANY DISCREPANCY IMMEDIATELY TO THE <br />ENGINEER OF RECORD. <br />9. SAFETY SWITCHES SHALL BE SQUARE 'D', GENERAL ELECTRIC, OR WESTINGHOUSE, FUSED OR <br />NON -FUSED AND SIZED AS INDICATED. NEMA 3R WHEN EXPOSED TO WEATHER <br />10. PANELS SHALL BE SQUARE 'D', GENERAL ELECTRIC OR EQUAL, TYPE AND NUMBER OF BREAKERS AS <br />INDICATED ON PANEL SCHEDULE, STENCIL PANEL DESIGNATION ON INSIDE OF PANEL. ALL TWO -POLE <br />BREAKERS SHALL BE COMMON TRIP. PROVIDE TYPE WRITTEN SCHEDULE IN EACH LOAD CENTERS. <br />CONNECTION TO MAIN BUS SHALL BE WITH BURNDY ANNULAR COMPRESSION LUGS. PANELS AIC RATING <br />SHALL BE AS INDICATED ON PLANS. <br />11. PROVIDE NAMEPLATES FOR ALL PANEL BOARDS, DISCONNECTS, TRANSFORMER, TERMINAL CABINETS AND <br />ALL ELECTRICAL EQUIPMENT IDENTIFIED BY NAME ON DRAWINGS. <br />12. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN <br />APPROVED THIRD PARTY TESTING AGENCY. <br />13. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT TIME OF DESIGN. VERIFY ALL EQUIPMENT <br />AND PANEL SIZES BEFORE ORDERING AND BEFORE INSTALLATION. <br />14. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE ANCHORED TO COMPLY WITH LOCAL CODE FOR WIND <br />RESISTANCE. <br />15. ALL ELECTRICAL AND COMMUNICATIONS OUTLETS TO BE AT 15" A.F.F TO BOTTOM OF OUTLET UNLESS <br />OTHERWISE NOTED, ALL LIGHT SWITCHES SHALL BE ® 42" AFF. TO BOTTOM OF SWITCH. <br />16. TIME CLOCK FOR LIGHTING CONTROL TO BE AN ASTRONOMICAL TIME CLOCK. <br />17. THE CONTRACTOR SHALL CONTACT THE LOCAL POWER COMPANY AND OBTAIN, IN WRITING, THE AVAILABLE <br />FAULT CURRENT OF THE UTILITY TRANSFORMER. THE CONTRACTOR SHALL ENSURE THAT ALL ELECTRICAL <br />EQUIPMENT HAS AN AMP INTERRUPTING CAPACITY (AIC) GREATER THAN THE AVAILABLE FAULT CURRENT <br />AT ANY POINT IN THE ELECTRICAL DISTRIBUTION SYSTEM. <br />18. WIRING METHOD: <br />ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE <br />NOTED. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL RAIN TIGHT <br />COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE. <br />SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL BE <br />USED UNDERGROUND OR BELOW SLABS ON GRADE. <br />TYPE MC CABLE WITH ALUMINUM ARMOR AND INTERNAL GROUND IS ACCEPTABLE FOR USE AS GENERAL <br />BRANCH CIRCUIT WIRING FOR CIRCUITS 20 AMPERES OR LESS AND CONCEALED IN WALLS OR ABOVE <br />SUSPENDED CEILING AND APPROVED BY AUTHORITY HAVING JURISDICTION, <br />19, SEAL ALL NEW CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS, FLOORS, ETC., TO <br />MAINTAIN EXISTING FIRE RATING CONDITIONS. FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR ALL <br />EQUIPMENTS PENETRATING FIRE RATED ENVELOPES, SPACES, ECT, <br />20. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE WIRING FOR HVAC SYSTEM: A/C EQUIPMENT(S), <br />SMOKE DETECTORS, THERMOSTATS, TEST STATIONS, MOTORIZED VOLUME DAMPERS, ETC. ELECTRICAL <br />CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL <br />WIRING. ELECTRICAL CONTRACTOR TO THOROUGHLY REVIEW MECHANICAL PLANS AND PROVIDE POWER TO <br />ANY MECHANICAL EQUIPMENT OR DEVICE THAT IS NOT SHOWN ON ELECTRICAL PLANS BUT IS SHOWN ON <br />MECHANICAL PLANS, <br />21. INSTALL "GFCI" GROUND FAULT INTERRUPTER RECEPTACLES WITH WEATHERPROOF COVER WITHIN 25 FT <br />OF HVAC EQUIPMENT, MOUNT RECEPTACLE ON UNISTRUT (UNLESS HVAC EQUIPMENT IS SPECIFIED WITH <br />FACTORY INSTALLED CONVENIENT RECEPTACLE) . <br />22. WHEN NEW ELECTRIC SERVICE IS BEING INSTALLED, IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY. <br />TO COORDINATE WITH FPL/FPL ENGINEERS ON THE SIZE OF THE FPL TRANSFORMER THAT IS REQUIRED <br />TO PROVIDE THE NEW ELECTRIC SERVICE SHOWN ON ELECTRIC PLANS, GC HAS TO INFORM THE OWNER <br />ABOUT ANY EXTRA FPL CHARGES THAT MIGHT OCCUR IN ORDER TO PULL NEW SERVICE. THIS HAS TO <br />BE DONE AS EARLY AS POSSIBLE DURING THE BIDDING PROCESS. <br />23. ELECTRICAL SERVICE EQUIPMENT MUST BE 3' ABOVE MSL, AND 8' ABOVE NN.G.D. VERIFY AT SITE. ALL <br />ELECTRICAL EQUIPMENTS SHALL BE INSTALLED ABOVE FLOOD LEVEL. <br />24. CONTRACTOR MUST VISIT THE SITE PRIOR TO BID OR CONSTRUCTION TO VERIFY ALL EXISTING <br />CONDITIONS. BEFORE SUBMITTING BID, BECOME THOROUGHLY FAMILIAR WITH ACTUAL EXISTING CONDITIONS <br />AT THE BUILDING SITE. THE INTENT OF THE WORK IS SHOWN ON THE DRAWINGS AND DESCRIBED <br />HEREINAFTER. BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK, THE CONTRACTOR SHALL BE <br />DEEMED TO HAVE MADE SUCH STUDY AND EXAMINATION AND TO ACCEPT ALL CONDITIONS PRESENT AT <br />THE SITE. NO REQUEST FOR ADDITIONAL PAYMENT SHALL BE CONSIDERED AS VALID, DUE TO THE <br />FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST, CONTRACTOR TO REPLACE ANY EXISTING DEVICE <br />OR COMPONENT THAT IS CALLED AS EXISTING IF IT IS NOT FULLY OPERATIONAL. <br />ELECTRICAL <br />SERVICE POLE <br />120/208V, 3PH, 4W SERVICE <br />TO TENANTS 4#500 MCM CU IN 3" CONDUIT <br />N/O ROSS 400A, 120/208V, 3PH, 4W SERVICE <br />PROVIDE HAND HOLE <br />AND COIL 30' OF WIRE <br />TO BE CONNECTED BY UTILITY <br />HAND <br />HOLE <br />EAST WALL 0 F <br />ADJACENT TENANT <br />S/O ROSS <br />4#500 MCM CU IN 3" CONDUIT <br />400A, 120/208V, 3PH, 4W SERVICE <br />RELOCATED <br />10gA <br />NEMA 3R <br />LMAIN <br />PANEL <br />1 PH. <br />120/208V <br />3#3 CU IN <br />1-1/2" <br />CONDUIT <br />RELOCATED <br />MAIN <br />PANEL NEMA 3R <br />HSE <br />1 PH, <br />120/208V <br />3#3 CU IN <br />1-1/2" CONDUIT <br />4 #1 /0 CU & <br />1 #6 CU GRND. <br />RELOCATED IN 2" CONDUIT <br />LIGHTING <br />CONTROL <br />WIRING <br />3#3 CU IN 3#3 CU IN <br />1-1/2" 1-1/2" <br />CONDUIT CONDUIT <br />5/8" Cu <br />GIRD Rod <br />6' APART <br />#1 /0 Cu Grounding <br />Conductor <br />RELOCATED <br />HSE-2 <br />PANEL <br />125A <br />3PH. <br />277/480 <br />ELOCATEI <br />LIGHTING <br />CONTROL <br />RELOCATED <br />125A 3P <br />125A <br />NEMA 3R <br />4 #1/0 CU IN <br />"�'-- 2" CONDUIT <br />RELOCATED <br />METER <br />#2 Cu Grounding <br />Conductor <br />4 #1 /0 CU IN <br />2" CONDUIT <br />ELECTRICAL RISER DIAGRAM <br />ELECTRICAL <br />SERVICE POLE <br />277/48OV, 3PH, 4W SERVICE <br />HAND <br />HOLE <br />125A, 277/48OV, <br />3PH, 4W SERVICE <br />PROVIDE HAND HOLE <br />AND COIL 30' OF WIRE <br />TO BE CONNECTED BY UTILITY <br />- <br />HAND <br />HOLE <br />600A, 277/48OV, <br />3PH, 4W SERVICE <br />ROSS STORE <br />TWO 3" CONDUITS <br />WITH PULL STRINGS TO <br />ROSS ELECTRICAL ROOM <br />MAIN <br />NEW <br />NEMA 3R <br />2 SETS OF 4#350 MCM CU IN <br />3" CONDUIT (EACH SET) <br />2 SETS OF 4#350 MCM CU IN <br />3" CONDUIT (EACH SET) " <br />(1) #3/0 GROUNDING ELECTRODE <br />CONDUCTOR IN 3/4" <br />SCHEDULE: 40 PVC CONDUIT. <br />EXOTHERMIC CONNECTION. ELECTRICALLY CONTINUOUS <br />25FT LONG STEEL REINFORCING BAR IN BOTTOM OF <br />BUILDING FOUNDATION IN DIRECT CONTACT WITH EARTH. <br />SEE NEC-250 FOR ALTERNATE METHODS I <br />USE TWO <br />1O'LONG 5/8" <br />DIA. CU CLAD <br />GROUND RODS <br />G <br />#3/0 Cu Grounding <br />Conductor <br />G <br />C/W <br />AKE CONNECTION TO METALUC <br />COLD WATER ENTRANCE PIPE <br />BEFORE FIRST VALVE WITH HEAVY <br />DUTY BRONZE GROUND CLAMP. <br />Pro j. Mgr. <br />JU <br />Job, Gapt. <br />SG <br />©raven by <br />JT <br />RON <br />BARR, <br />A.I.A. <br />Raev'd by <br />STATE <br />OF FLORIDA <br />I5 <br />AR <br />0016160 <br />w <br />O <br />W¢ <br />w <br />0E- I- <br />- E <br />Upgi_oN <br />37w <br />§ <br />O O - <br />-K <br />Qo <br />w0om <br />woFN <br />Z <br />U <br />p= <br />E d o <br />a _ j <br />to <br />w <br />m X o <br />z W~ <br />O <br />w o <br />w F <br />O� w <br />z0 <br />O <br />w z j Z <br />It w w <br />i- W <br />U a <br />�- <br />Z¢ <br />j F p <br />a, Zo <br />m° <br />O= <br />w L <br />D Z <br />W, o°� <br />LLal z a� D <br />w°_ <br />¢oo�ooc�i¢oz <br />a= X <br />C <br />0 2 <br />lo- o z o <br />O U) F- <br />a w <br />K <br />r <br />U= <br />o <br />Y W <br />a t- <br />c~i <br />Zw= <br />z <br />_ <br />= <br />w <br />m <br />w <br />M" <br />O <br />w <br />K <br />0 0 2 w <br />o <br />D a V <br />c�7 <br />o z <br />z <br />O� <br />O <br />Z <br />W O m <br />Z F z D <br />a <br />U U w <br />o O w F <br />U o <br />Ow <br />O O <br />w z <br />0 <br />1- <br />y� <br />0 p w U it Q, <br />~ mo <br />2 z w .c <br />t2 z d w <br />2 O <br />LL. O <br />0' <br />w w O W Q O <br />I- ¢ a <br />I-- a <br />o o <br />a <br />R P 2? M a <br />O <br />COPYRIGHT <br />2012 <br />BARR ARCHITECTURAL STUDIO <br />Revisions: <br />1. 9/4/13 COORDINATION <br />CADFILE No. <br />H <br />� <br />kf) <br />M <br />a <br />M <br />O <br />y <br />naIL <br />�Aou <br />���a <br />a <br />o <br />w <br />z <br />� <br />�0 <br />MMA <br />L <br />0 <br />N <br />CO 0 <br />N <br />o N 'c <br />r- c <br />N <br />CD E <br />E <br />o <br />moo�// <br />LA <br />d-� j <br />0 <br />0 <br />0 TLo <br />r 0) <br />CL U <br />i <br />CIO <br />Sheet Title <br />ELECTRICAL NOTES <br />& RISER DIAGRAM <br />sca le: <br />BUCHANAN P.E. CONSULTING I <br />ELECTRICAL * MECHANICAL * PLUMBING <br />ENGINEERIN G <br />6191 W. ATLANTIC BLVD., SUITE #2 <br />MARGATE, FL 33063 <br />Ph: 954-590-3300 Fax: 954-590-2232 <br />Email: mepengineers@aol.com <br />RAJA BUCHANAN FL RE # 48916 <br />CERTIFICATE OF AUTHORIZATION # 8842 <br />SEAL <br />FL P. 9?6 <br />SEP 0 4 2013 <br />DATE: <br />Date: <br />01-31-2013 <br />Project (No. <br />12-027 <br />Sheet No. <br />E2-0 <br />2 OF 2 <br />FILE: 1612-E2-O.DWG <br />