HN.A.C. GENERAL NOTES: <br />ALL WORK SHALL BE DONE IN ACCORDANCE WITH FBC-2010, 2006 NFPA-101, 2006 NFPA-1, 2008 NFPA-70. <br />IIALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER, THE COMPLETE SYSTEM SHALL <br />BE FULLY OPERATIVE AND ACCEPTANCE BY THE OWNER AND/OR ARCHITECT MUST BE CONDITION OF THE CONTRACT, SUBMIT SHOP DRAWINGS <br />ON ALL EQUIPMENT, FOR REVIEW PRIOR TO PURCHASING. <br />2. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES IN ORDER TO AVOID CONFLICTS. NO CHARGES WILL BE ACCEPTED <br />UNLESS A PRIOR WRITTEN APPROVAL HAS BEEN ISSUED BY THE OWNER/ARCHITECT. <br />3. THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE WITH EXISTING CONDITIONS. PRIOR TO INSTALLING EQUIPMENT <br />AND/OR FABRICATING DUCTWORK, A.C. CONTRACTOR SHALL CHECK THAT THERE IS SUFFICIENT CLEARANCES FOR EQUIPMENT, DUCTWORK, ETC. <br />AND ALSO TO AVOID ANY INTERFERENCE WITH THE PROCESS OF CONSTRUCTION. <br />4. DRAWINGS ARE DIAGRAMMATIC ILLUSTRATIONS. DO NOT SCALE DRAWINGS FOR THE EXACT LOCATION OF EQUIPMENT. PIPING, DUCTWORK, <br />ETC. THESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL FURNISH AND <br />INSTALL ALL ITEMS REQUIRED FOR A COMPLETE ACCEPTABLE WORKING SYSTEM, <br />5. CONTRACTOR WILL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTS. <br />6. INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE RECOMMENDATIONS SET FORTH IN THE LATEST ASHRAE GUIDE. ALL MATERIALS <br />SHALL BE NEW AND SHALL BEAR UNDERWRITER'S LABEL WHERE APPLICABLE, <br />7. AIR FILTERS SHALL BE INSTALLED ON .ALL RETURN AIR EQUIPMENT INLETS. PROVIDE AN EXTRA FILTER, INSTALL AT END OF <br />CONSTRUCTION. <br />8. ALL REQUIRED INSURANCE SHALL BE PROVIDED BY THE CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE <br />FOR THE DURATION OD THE WORK. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH THE APPLICABLE NATIONAL, <br />STATE, AND LOCAL CODES, RULES, AND ORDINANCES. <br />9. PROVIDE MAIN CONDENSATE DRAIN AND AUXILI.IARY DRAIN PAN (AUXILIARY DRAIN PAN SHALL BE EQUIPPED WITH A WATER -LEVEL <br />DETECTION DEVICE THAT WILL SHUT OFF THE EQUIPMENT SERVED PRIOR TO OVERFLOW OF THE PAN AS PER FMC 2010 SECTION 307.2.3) <br />FOR ALL AIR CONDITIONING UNITS AND DRAIN TO EXTERIOR PERMEABLE SOIL OR AS SHOWN ON THE PLANS. <br />10. AIR CONDITIONING CONDENSATE PIPING AND FITTINGS SHALL BE PVC OR DWV ( AST-D2662). COPPER IN PLENUM AREAS. ALL INTERIOR <br />CONDENSATE PIPING IN UNCONDITIONED SPACES SHALL BE WRAPPED WITH A MINIMUM 1 /2" SELF SEALING INSULATING FOAM JACKET. THE <br />CONTRACTOR SHALL PROVIDE ALL NECESSARY CONTROLS FOR THE OPERATION OF THE HVAC SYSTEM, <br />11. NA <br />12. THERMOSTAT MUST BE PROGRAMMABLE TO BE ABLE TO SET THE TEMPERATURE BACK (OR OFF) WHEN SPACE IS UNOccur-YE0 OR AT <br />OTHER TIMES AS NEEDED BY USER, <br />13. ALL MATERIAL EXPOSED WITHIN PLENUM MUST BE NON COMBUSTIBLE OR RATED 25/50 FLAME SPREAD. <br />14, NA <br />15, ALL VENTILATION DUCTWORK SHALL BE GALVANIZED SHEET METAL <br />16. NA <br />17. HANGERS SHALL BE PROVIDED IN ACCORDANCE WITH S.M.A.C.N.A. RECOMMENDATIONS. <br />18. AIR DISTRIBUTION ACCESSORIES SHALL BE AIR GUIDE, ANEMOSTAT, TITUS, OR APPROVED EQUAL. ALL SUPPLY A.C. DUCT ELBOWS MUST <br />BE FURNISHED WITH APPROVED TURNING VANES, BRANCH TAKEOFFS MUST BE PROPORTIONAL SPLITS, <br />19, THE OWNER SHALL APPROVE THE FINISH COLOR OF ALL EXPOSED AIR DISTRIBUTION DEVICES. <br />20. PROVIDE FIRE DAMPERS IN ALL DUCTS PASSING THROUGH FIRE DIVISION ASSEMBLIES. FIRE DAMPERS MUST HAVE FIRE RATING EQUAL TO <br />OR GREATER THAN THE PENETRATED ASSEMBLY RATING, FIRE DAMPER INSTALLATIONS SHALL COMPLY WITH ALL LOCAL CODES. PROVIDE <br />ACCESS PANEL TO ALL FIRE DAMPERS. <br />21. ELECTRIC STRIP HEATERS SHALL BE BLAST COIL TYPE WITH NICKEL CHROMIUM WIRE AND INSULATING BUSHINGS FACTORY MOUNTED AND <br />WIRED INCLUDING ALL HEAT LIMITERS, HOGH LIMIT SWITCHES, AND CONTRACTORS IN ACCORDANCE WITH THE "NATIONAL ELECTRIC CODE". <br />22. EXHAUST FANS SHALL HAVE THE CAPACITIES AS STATED ON THE DRAWINGS AND BE PROVIDED WITH BACK DRAFT DAMPER, BIRD SCREEN. <br />23, THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD NOT LESS THAN 1 YEAR <br />FROM THE DATE OF ACCEPTANCE, UNLESS OTHERWISE NOTED, CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL <br />CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIRS OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED OR <br />IS NOT OPERATING PROPERLY. <br />24. ARCHITECTURAL AND/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO REVISIONS FOR SUBSTITUTIONS BY THE CONTRACTOR <br />SHALL BE PAID FOR BY THE CONTRACTOR. <br />25. AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING AND BALANCING. A WRITTEN BALANCE REPORT SHALL BE PROVIDED TO THE OWNER OR <br />THE DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR WAG SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED AREA <br />EXCEEDING 5000 SQUARE FEET. AIR DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND BALANCED BY AN ENGINEER LICENSED IN <br />THIS STATE OR A COMPANY OR INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A RECOGNIZED TESTING AND BALANCING AGENCY <br />ORGANIZATION IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS. <br />EXCEPTIONS: <br />1. BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES OF 15 TONS OR LESS PER SYSTEM MAY BE TESTED AND BALANCED BY A <br />MECHANICAL CONTRACTOR LICENSED TO DESIGN AND INSTALL SUCH SYSTEM(S). <br />2. BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES OF 65,000 BTU/H OR LESS PER SYSTEM ARE EXEMPT FROM THE <br />REQUIREMENTS OF THIS SECTION. <br />AIR SYSTEM BALANCING SHALL COMPLY WITH FBC 2010 ENERGY CONSERVATION SECTION 503.2.9.1 <br />26. AS PER FBC 2010 ENERGY CONSERVATION SECTION 503.2.9.3, AN OPERATING AND MAINTENANCE MANUAL SHALL BE PROVIDED TO <br />THE BUILDING OWNER BY THE MECHANICAL CONTRACTOR, THE MANUAL SHALL INCLUDE, AT LEAST, THE FOLLOWING: <br />1, EQUIPMENT CAPACITY (INPUT AND OUTPUT) AND REQUIRED MAINTENANCE ACTIONS, <br />2. EQUIPMENT OPERATION AND MAINTENANCE MANUALS, <br />3. HVAC SYSTEM CONTROL MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING DIAGRAMS, SCHEMATICS, AND CONTROL. <br />SEQUENCE DESCRIPTIONS. DESIRED OR FIELD -DETERMINED SET POINTS SHALL BE PERMANENTLY RECORDED ON CONTROL DRAWINGS, AT <br />CONTROL DEVICES OR, FOR DIGITAL CONTROL SYSTEMS, IN PROGRAMMING COMMENTS. <br />4. A COMPLETE WRITTEN NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE. <br />27. ALL PIPING SERVING AS PART OF A HEATING OR COOLING SYSTEM SHALL BE THERMALLY INSULATED IN ACCORDANCE WITH FBC <br />2010 ENERGY CONSERVATION TABLE 50328. <br />28. IF THERE ARE ANY CHANGES IN ENGINEER'S DRAWINGS, IN DESIGN OR IN EQUIPMENT, WITHOUT ENGINEER'S CONSENT, THE A.C. <br />CONTRACTOR SHALL ASSUME ALL RESPONSIBILITIES FOR THE PROJECT. <br />29, SMOKE DETECTORS ARE REQUIRED ON ALL PRIMARY AIR CONDITIONING SYSTEMS WHERE TOTAL AIR VOLUME EXCEEDS 2,000 C.F.M. <br />(FBC-MECHANICAL 2010, SEC11ON 606.2.1) A DUCT ACCESS DOOR IS REQUIRED TO ACCESS THE DETECTOR. THE SYSTEM SHALL BE WIRED <br />SO AS WHEN THE DUCT SMOKE DETECTOR DETECTS SMOKE, IT SHALL STOP THE AC SUPPLY FAN AND CAUSE A VISUAL AND AUDIBLE <br />SIGNAL IN A NORMALLY OCCUPIED LOCATION. ALSO, THE DETECTOR SHALL INDICATE A TROUBLE CONDITION EITHER VISUALLY OR AUDIBLY IN <br />THE NORMALLY OCCUPIED LOCATION, AND BE IDENTIFIED AS AIR DUCT DETECTOR TROUBLE, NFPA 90A, 4-4A.3 <br />(THE TESTER SHOULD BE EQUIPPED WITH AN LED LIGHT TO INDICATE TROUBLE). <br />30, AS PER FBC 2010 ENERGY CONSERVATION SECTION 503.2.5.4 (SHUTOFF DAMPER CONTROLS) <br />PROVIDE MOTORIZED DAMPERS FOR O/A INTAKE FOR AHU, CONNECT MOTORIZED DAMPER TO TIME CLOCK TO CLOSE OUTSIDE AIR INTAKE <br />AUTOMATICALLY WHEN THE SPACE SERVED IS NOT IN USE (OFF BUSINESS HOURS). <br />31. GRAVITY HOODS, VENTS, AND VENTILATORS, ALL OUTDOOR AIR SUPPLY AND EXHAUST HOODS, VENTS, AND VENTILATORS SHALL BE <br />EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SPACES SERVED ARE NOT IN USE, <br />EXCEPTION: VENTILATION SYSTEMS SERVING UNCONDITIONED SPACES. <br />32. NA <br />33, AS PER FBC-301.4 ALL APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND LABELED UNLESS OTHERWISE APPROVED IN <br />ACCORDANCE WITH SECTIONS 301.4.1 THROUGH 301.4.4. <br />34. AS PER FMC-304.10 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT REQUIRE <br />SERVICE AND ROOF HATCH OPENINGS ARE LOCATED WITHIN 10 FT. OF ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE <br />OR OPEN SIDE IS LOCATED MORE THAN 30" ABOVE THE FLOOR, ROOF OR GRADE BELOW, <br />35, AS PER 306.5.1 SLOPED ROOFS. WHERE APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE INSTALLED <br />ON A ROOF HAVING A SLOPE OF THREE UNITS VERTICAL IN 12 UNITS HORIZONTAL OR GREATER AND HAVING AN EDGE MORE THAN 30" <br />ABOVE GRADE AT SUCH EDGE A LEVEL PLATFORM SHALL BE PROVIDED ON EACH SIDE OF THE APPLIANCE TO WHICH ACCESS IS REQUIRED <br />FOR SERVICE, REPAIR OR MAINTENANCE. THE PLATFORM SHALL BE NOT LESS THAN 30" IN ANY DIMENSION AND SHALL BE PROVIDED WITH <br />GUARDS. THE GUARDS SHALL EXTEND NOT LESS THAN 42"ABOVE THE PATFORM, SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE <br />OF A 21" DIAMETER SPHERE AND SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR QUARDS SPECIFIED IN THE FBC. <br />36. ANY INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 1OFT. FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, <br />37. ALL COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT INSTALLATION SHALL BE LISTED , LABELED AND INSTALLED IN <br />ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTION. <br />38. ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES (203 MM) <br />ABOVE THE ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT SUPPORTS <br />PROVIDING A MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7. <br />TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS <br />WIDTH OF MECHANICAL UNIT (INCHES) <br />SURFACES (INCHES) <br /><24 /24<36 / 36 < 48 / 48 < 60 / > 60 <br />14" 18" 24" 30" 48" <br />39. ROOF TOP A/C UNIT CURB SHALL BE MINIMUM 14 GAUGE (HURRICANE RATED CURB). <br />40. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND INFORM THE PROJECT ENGINEER AND ARCHITECT OF ANY <br />DISCREPANCY BETWEEN THESE PLANS AND THE EXISTING CONDITIONS. THE CONTRACTOR SHALL INCLUDE IN HIS BID TO CORRECT SUCH <br />CONDITION AS DIRECTED. THE ENGINEER AND ARCHITECT ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING FROM VERIFIABLE <br />EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED. <br />NOTE: <br />PROVIDE FLOAT SWITCH, TO BE INSTALLED <br />IN THE PRIMARY DRAIN PAN OF THE UNIT, <br />4' MAX BETWEEN SUPPORTS -- <br />ABOVE r+r a <br />.B <br />GALV METAL STRAP W/ NEOPRENE GASKET FASTEN <br />TO PIPE STAND <br />PVC CONDENSATE SEE MECH. PLANS <br />FOR CONTINUATION <br />RTU TO CURB ATTACHMENT & DRAIN DETAL <br />NTSC <br />G310, <br />__ -_ANEW 4 x 4 x 1/4" STEEL <br />OPTION 1. <br />ANGLES (6'-0" O.C.MAX) FULLY <br />CONNECT PREFABRICATED RTU CURB <br />WELDED TO EX. BAR JOISTS <br />DIRECTLY TO STEEL ANGLES / BAR <br />JOIST W/ MIN. 3/8" DIAM, S.S. BOLTS <br />W/ WASHERS THRU FLANGE OF CURB <br />AND STEEL ANGLE / BAR JOIST <br />BELOW AT ALL CORNERS AND BALANCE <br />0 12" O.C. MAX ALL 4 SIDES <br />OPTION 2. <br />WELD CURB TO STEEL ANGLES "FRAME" <br />NOTE: <br />CURB MUST BE INSULATED FROM INSIDE, <br />WITH 1/2" BEAD EVERY 6 INCHES. <br />CURB TO ROOF JOIST <br />ATTACHMENT DETAIL <br />NTSC <br />V:1 0610,30 <br />RELIEF VENT SAME SIZE AS CONDENSATE LINE <br />CONC. COVER WITH LIFT HANDLE-- r, <br />GRADE <br />NATURAL EARTH <br />24"0 x 36" LONG <br />GALVANIZED STEEL <br />NOTES: <br />1. STABALIZER STONES MIN. ONE HALF CUBIC YARD <br />DRYWELL DETAIL <br />NTSC <br />PVC CONDENSATE DRAIN <br />LINE SEE PLAN FOR SIZE <br />SEAL WITH SILICONE <br />CAULK (OR EQ.) <br />THE EXCAVATED PIT SHALL <br />BE COMPLETELY FILLED <br />WITH COARSE GRAVEL <br />2"0 CLEAN STONES <br />(STABALIZED) <br />GASKET, TYP, __. s SCHEDULED RTU, SEE MECH, DWGS. <br />NAILING STRIP f PRE -FABRICATED ROOF CURB (14 GA. MIN.) <br />DUCT GAILY. MTL COUNTER FLASHING <br />INSULATION - --- 4" CANT AND MTL FLASHING + <br />COUNTER FLASHING AND ROOF <br />,--PATCH AND REPAIR ALL AROUND <br />INSULATION -------W�,/// - "" ROOF INSULATION AND MTL DECK <br />CURB INSTALATION DETAIL <br />NTSC <br />V:1 :)h <br />PACKAGED GAS / ELECTRIC HIGH EFFICIENCY AIR CONDITIONING UNITS <br />MARK <br />SERVICE <br />MAKE <br />MODEL <br />S.A. <br />MIN. <br />EXT, <br />FAN <br />HP <br />HEATING <br />COOLING CAPACITY <br />REFRIG. <br />SEER f <br />FLA/MCA <br />ELECTRICAL <br />WEIGHT <br />ACCESSORIES <br />CFM <br />O.A, <br />STATIC <br />RPM <br />FUEL <br />INPUT <br />TOTAL / SENS <br />EAT <br />AMBIENT <br />EER <br />MOCP <br />CFM <br />MBH/STAGES <br />MBH <br />DB / WB <br />DB <br />AC / 1 <br />STOCK <br />LENNOX <br />LGHO6OH4E <br />2000 <br />210 <br />1.0 <br />1110 <br />1 <br />GAS <br />65 / 1 <br />57.5 / 47.0 <br />77 / 64 <br />105 <br />R-410A <br />17.0 / <br />14.8 / 18 <br />480 / 3 / 60 <br />1100 LBS <br />1 - 7 <br />12.7 <br />25 <br />AC / 2 <br />OFFICE AREA <br />LENNOX <br />LGH048H4E <br />1600 <br />175 <br />1.0 <br />1195 <br />3/4 <br />GAS <br />65 / 1 <br />45.4 / 37.7 <br />77 / 64 <br />105 <br />R-410A <br />17.0 / <br />11,6 / 14 <br />480 / 3 / 60 <br />1000 LBS <br />1 -- 7 <br />12,8 <br />15 <br />AC / 3 <br />SALES <br />LENNOX <br />LGH156H4B <br />5200 <br />1270 <br />1.0 <br />945 <br />5 <br />GAS <br />169 / 1 <br />148.3 / 114.2 <br />80 / 67 <br />105 <br />R-410A <br />--- / <br />30.4 / 35 <br />480 / 3 / 60 <br />2400 LBS <br />1 - 7 <br />12.0 <br />40 <br />AC / 4 <br />FITTING/ <br />LENNOX <br />LGHO361­14E <br />1200 <br />165 <br />1,0 <br />1110 <br />1/2 <br />GAS <br />65 / 1 <br />33.2 / 27.4 <br />78 / 65 <br />105 <br />R-410A <br />17.0 / <br />8.8 / 10 <br />480 / 3 / 60 <br />1000 LBS <br />1 - 7 <br />TOILETS <br />12.5 <br />15 <br />AC / 5 <br />SALES <br />LENNOX <br />LGH156H4B <br />5200 <br />1270 <br />1.0 <br />945 <br />5 <br />GAS <br />169 / 1 <br />148.3 / 114.2 <br />80 / 67 <br />105 <br />R 410A <br />-- f <br />30.4 / 35 <br />480 / 3 / 60 <br />2400 LBS <br />1 - 7 <br />12.0 <br />40 <br />AC / 6 <br />SALES <br />LENNOX <br />LGH156H4B <br />5200 <br />1270 <br />1.0 <br />945 <br />5 <br />GAS <br />169 / 1 <br />148.3 / 114.2 <br />80 / 67 <br />105 <br />R-410A <br />-- / <br />30.4 / 35 <br />480 / 3 / 60 <br />2400 LBS <br />1 - 7 <br />12.0 <br />40 <br />AC / 7 <br />SALES <br />LENNOX <br />LGH18OH4B <br />1.0 <br />970 <br />5 <br />GAS <br />169 / 1 <br />176.0 / 167.8 <br />77 / 65 <br />105 <br />R-410A <br />-- / <br />36.8 / 42 <br />480 / 3 / 60 <br />2700 LBS <br />1 - 7 <br />�6000 <br />11460 <br />12.0 <br />45 <br />NQIE; ROOFTOP UNITS SHALL BE PURCHASED THROUGH LENNOX NATIONAL ACCOUNT. SUBSTITUTIONS ARE NOT PERMITTED. <br />ACCESSORIES: <br />1. NON -PRORATED WARRANTY OF 5 YEARS FOR THE COMPRESSORS AND 10 YEARS FOR THE HEAT EXCHANGERS, DUAL 115 VOLT GFCI TYPE SERVICE OUTLET (WIRING TO THE OUTLET <br />SHALL BE FIELD PROVIDED BY THE ELECTRICAL CONTRACTOR ON SITE), COMPRESSOR TIME DELAY RELAY, FREEZE STAT, HIGH AND LOW PRESSURE SWITCHES, CRANKCASE HEATER, <br />CONDENSER COIL GUARD, COIL DEFROST THERMOSTAT, 2" PLEATED FILTERS AND SPARE SET. <br />2. CONTROLLED FROM FACTORY INSTALLED AND TESTED PRODIGY M2 WITH BACNET CONTROL MODULE, <br />3. FACTORY INSTALLED PHOTO ELECTRIC SMOKE DETECTOR IN SUPPLY AND RETURN AIR SECTIONS OF UNIT WITH REMOTE MOUNTED STATUS AND TEST STATIONS INTERLOCKED TO STOP FAN ON <br />ACTIVATION. REFER TO DETAIL ON THIS SHEET. <br />4. PROVIDE WITH 14" INSULATED ROOF CURB WITH FACTORY INSTALLED BURGLAR BARS. <br />5. MECHANICAL CONTRACTOR TO PROVIDE 12" HIGH REFLECTIVE UNIT NUMBERS WITH SPECIFIC A/C UNIT NUMBER TO BE POSTED ON EACH UNIT ON THE CONTROL PANEL DOOR AND SIDE WITH <br />DISCONNECT IN A LOCATION VISIBLE FROM THE ROOF HATCH. <br />6. FACTORY INSTALLED GEAR DRIVEN ECONOMIZER WITH GLOBAL ENTHALPY CONTROLS AND OUTDOOR AIR HOOD. TWO CLEANABLE ALUMINUM MESH OUTDOOR AIR FILTERS TO BE FURNISHED <br />BY LENNOX WITH ECONOMIZER. PROVIDE WITH POWER EXHAUST FANS (BAROMETRIC RELIEF DAMPER FOR 5 TON UNITS AND BELOW), <br />7. HACR CIRCUIT BREAKERS TO BE FACTORY INSTALLED AND FACTORY WIRED BY LENNOX ON ALL UNITS ABOVE 12.5 TONS. UNITS 12.5 TONS AND BELOW SHALL BE SUPPLIED WITH <br />NON -FUSED SERVICE DISCONNECT" FACTORY INSTALLED AND FACTORY WIRED. <br />NOTES: <br />1. PER FBC 2010 ENERGY CONSERVATION SECTION 503.2.5.4 (SHUTOFF DAMPER CONTROLS) <br />PROVIDE MOTORIZED DAMPERS FOR O/A INTAKE FOR AHU. CONNECT MOTORIZED DAMPER TO TIME CLOCK TO CLOSE <br />OUTSIDE AIR INTAKE AUTOMATICALLY WHEN THE SPACE SERVED IS NOT IN USE (OFF BUSINESS HOURS), <br />F'roj. M!@r. <br />JU <br />Job. C.apt. <br />SG <br />T>raum by <br />JT <br />RON BARR, A.I.A. <br />Rev'd by <br />STATE OF FLORIDA <br />I <br />AR 0016160 <br />o w <br />w Z ~ <br />O w¢ w w <br />Fw H <br />U o w 0 0 m <br />O <br />U O <br />Q z rUj l=_- 0 0 U z F <br />2 0, 8 g,- <br />z <br />Ir w <br />,L <br />c 8 <br />s o <br />m0 o <br />¢ <br />W� <br />z F- <br />tr W t7 C? w Z ] z <br />O O w O <br />O° W <br />co <br />} F na ] ui <br />m w c7 z z ¢ F-? U <br />o m <br />o <br />. w zw <br />af_o00 W <br />IL 2 <br />U O Z O <br />a cn <br />H U 7I <br />ILLn W <br />d W w z h p H <br />z= w <br />w <br />a O <br />r w o 0 cn <br />z 0 F- z m z E z <br />aQ <br />a o <br />w° a zw <br />o z T <br />z a- w <br />2a Oit zw <br /><z 0 <br />O� <br />0LL W Uz <br />O w w <br />F- < w< <br />! <br />F- < 0❑ o R I- z-z 2 4 <br />O <br />COPYRIGHT 2012 <br />BARR ARCHITECTURAL STUDIO <br />«# <br />y� <br />I, <br />v, <br />ik> <br />Naw <br />S <br />A <br />a <br />� <br />v,� <br />v <br />/ <br />1 N <br />� <br />M9, <br />a <br />1.evistons - <br />C�7.1!1�1��►fa <br />� <br />M <br />ail <br />,IL <br />I� <br />7 <br />1 <br />V <br />I..1 <br />x <br />Q <br />H <br />N <br />� <br />L <br />O <br />cm (0 <br />cy) <br />_m N cy) <br />o N 'c <br />LL N T <br />N U. <br />MC Lo tU <br />~ 0 <br />Q <br />C <br />C <br />O <br />O <br />IY <br />(0 C <br />(a r O <br />U <br />J✓ N <br />U <br />�- cn <br />0 N <br />LO U <br />r~ <br />Sheet Titles <br />MECHANICAL <br />NOTES & DETAILS <br />sca le; <br />BUCHANAN P.E. CONSULTING I <br />ELECTRICAL * MECHANICAL * PLUMBING <br />ENGINEERING <br />6191 W. ATLANTIC BLVD., SUITE #2 <br />MARGATE, FL 33063 <br />Ph: 954-590-3300 Fax: 964-590-2232 <br />Email: mepengineers@aol.com <br />RAJA BUCHANAN FL P.E # 48916 <br />CERTIFICATE OF AUTHORIZATION # 8842 <br />SEAL, <br />RAJ.? UCW <br />FL E # 48E <br />SEP 0 4 2013 <br />DATE: <br />Date- <br />01-31-2013 <br />Pro jest No. <br />12-027 <br />Shreet No. <br />M2-0 <br />2 OF 2 <br />FILE: 1612-M 1-0. D WG <br />