HN.A.C. GENERAL NOTES:
<br />ALL WORK SHALL BE DONE IN ACCORDANCE WITH FBC-2010, 2006 NFPA-101, 2006 NFPA-1, 2008 NFPA-70.
<br />IIALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER, THE COMPLETE SYSTEM SHALL
<br />BE FULLY OPERATIVE AND ACCEPTANCE BY THE OWNER AND/OR ARCHITECT MUST BE CONDITION OF THE CONTRACT, SUBMIT SHOP DRAWINGS
<br />ON ALL EQUIPMENT, FOR REVIEW PRIOR TO PURCHASING.
<br />2. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES IN ORDER TO AVOID CONFLICTS. NO CHARGES WILL BE ACCEPTED
<br />UNLESS A PRIOR WRITTEN APPROVAL HAS BEEN ISSUED BY THE OWNER/ARCHITECT.
<br />3. THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE WITH EXISTING CONDITIONS. PRIOR TO INSTALLING EQUIPMENT
<br />AND/OR FABRICATING DUCTWORK, A.C. CONTRACTOR SHALL CHECK THAT THERE IS SUFFICIENT CLEARANCES FOR EQUIPMENT, DUCTWORK, ETC.
<br />AND ALSO TO AVOID ANY INTERFERENCE WITH THE PROCESS OF CONSTRUCTION.
<br />4. DRAWINGS ARE DIAGRAMMATIC ILLUSTRATIONS. DO NOT SCALE DRAWINGS FOR THE EXACT LOCATION OF EQUIPMENT. PIPING, DUCTWORK,
<br />ETC. THESE DRAWINGS ARE NOT INTENDED TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE CONTRACTOR SHALL FURNISH AND
<br />INSTALL ALL ITEMS REQUIRED FOR A COMPLETE ACCEPTABLE WORKING SYSTEM,
<br />5. CONTRACTOR WILL PAY FOR ALL PERMITS, FEES, INSPECTIONS, AND TESTS.
<br />6. INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE RECOMMENDATIONS SET FORTH IN THE LATEST ASHRAE GUIDE. ALL MATERIALS
<br />SHALL BE NEW AND SHALL BEAR UNDERWRITER'S LABEL WHERE APPLICABLE,
<br />7. AIR FILTERS SHALL BE INSTALLED ON .ALL RETURN AIR EQUIPMENT INLETS. PROVIDE AN EXTRA FILTER, INSTALL AT END OF
<br />CONSTRUCTION.
<br />8. ALL REQUIRED INSURANCE SHALL BE PROVIDED BY THE CONTRACTOR FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE
<br />FOR THE DURATION OD THE WORK. ALL WORKMANSHIP AND MATERIALS SHALL BE IN STRICT ACCORDANCE WITH THE APPLICABLE NATIONAL,
<br />STATE, AND LOCAL CODES, RULES, AND ORDINANCES.
<br />9. PROVIDE MAIN CONDENSATE DRAIN AND AUXILI.IARY DRAIN PAN (AUXILIARY DRAIN PAN SHALL BE EQUIPPED WITH A WATER -LEVEL
<br />DETECTION DEVICE THAT WILL SHUT OFF THE EQUIPMENT SERVED PRIOR TO OVERFLOW OF THE PAN AS PER FMC 2010 SECTION 307.2.3)
<br />FOR ALL AIR CONDITIONING UNITS AND DRAIN TO EXTERIOR PERMEABLE SOIL OR AS SHOWN ON THE PLANS.
<br />10. AIR CONDITIONING CONDENSATE PIPING AND FITTINGS SHALL BE PVC OR DWV ( AST-D2662). COPPER IN PLENUM AREAS. ALL INTERIOR
<br />CONDENSATE PIPING IN UNCONDITIONED SPACES SHALL BE WRAPPED WITH A MINIMUM 1 /2" SELF SEALING INSULATING FOAM JACKET. THE
<br />CONTRACTOR SHALL PROVIDE ALL NECESSARY CONTROLS FOR THE OPERATION OF THE HVAC SYSTEM,
<br />11. NA
<br />12. THERMOSTAT MUST BE PROGRAMMABLE TO BE ABLE TO SET THE TEMPERATURE BACK (OR OFF) WHEN SPACE IS UNOccur-YE0 OR AT
<br />OTHER TIMES AS NEEDED BY USER,
<br />13. ALL MATERIAL EXPOSED WITHIN PLENUM MUST BE NON COMBUSTIBLE OR RATED 25/50 FLAME SPREAD.
<br />14, NA
<br />15, ALL VENTILATION DUCTWORK SHALL BE GALVANIZED SHEET METAL
<br />16. NA
<br />17. HANGERS SHALL BE PROVIDED IN ACCORDANCE WITH S.M.A.C.N.A. RECOMMENDATIONS.
<br />18. AIR DISTRIBUTION ACCESSORIES SHALL BE AIR GUIDE, ANEMOSTAT, TITUS, OR APPROVED EQUAL. ALL SUPPLY A.C. DUCT ELBOWS MUST
<br />BE FURNISHED WITH APPROVED TURNING VANES, BRANCH TAKEOFFS MUST BE PROPORTIONAL SPLITS,
<br />19, THE OWNER SHALL APPROVE THE FINISH COLOR OF ALL EXPOSED AIR DISTRIBUTION DEVICES.
<br />20. PROVIDE FIRE DAMPERS IN ALL DUCTS PASSING THROUGH FIRE DIVISION ASSEMBLIES. FIRE DAMPERS MUST HAVE FIRE RATING EQUAL TO
<br />OR GREATER THAN THE PENETRATED ASSEMBLY RATING, FIRE DAMPER INSTALLATIONS SHALL COMPLY WITH ALL LOCAL CODES. PROVIDE
<br />ACCESS PANEL TO ALL FIRE DAMPERS.
<br />21. ELECTRIC STRIP HEATERS SHALL BE BLAST COIL TYPE WITH NICKEL CHROMIUM WIRE AND INSULATING BUSHINGS FACTORY MOUNTED AND
<br />WIRED INCLUDING ALL HEAT LIMITERS, HOGH LIMIT SWITCHES, AND CONTRACTORS IN ACCORDANCE WITH THE "NATIONAL ELECTRIC CODE".
<br />22. EXHAUST FANS SHALL HAVE THE CAPACITIES AS STATED ON THE DRAWINGS AND BE PROVIDED WITH BACK DRAFT DAMPER, BIRD SCREEN.
<br />23, THE CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD NOT LESS THAN 1 YEAR
<br />FROM THE DATE OF ACCEPTANCE, UNLESS OTHERWISE NOTED, CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL
<br />CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIRS OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED OR
<br />IS NOT OPERATING PROPERLY.
<br />24. ARCHITECTURAL AND/OR ENGINEERING EXPENSES THAT ARE INCURRED DUE TO REVISIONS FOR SUBSTITUTIONS BY THE CONTRACTOR
<br />SHALL BE PAID FOR BY THE CONTRACTOR.
<br />25. AIR DISTRIBUTION SYSTEM TESTING, ADJUSTING AND BALANCING. A WRITTEN BALANCE REPORT SHALL BE PROVIDED TO THE OWNER OR
<br />THE DESIGNATED REPRESENTATIVE OF THE BUILDING OWNER FOR WAG SYSTEMS SERVING ZONES WITH A TOTAL CONDITIONED AREA
<br />EXCEEDING 5000 SQUARE FEET. AIR DISTRIBUTION SYSTEMS SHALL BE TESTED, ADJUSTED, AND BALANCED BY AN ENGINEER LICENSED IN
<br />THIS STATE OR A COMPANY OR INDIVIDUAL HOLDING A CURRENT CERTIFICATION FROM A RECOGNIZED TESTING AND BALANCING AGENCY
<br />ORGANIZATION IN ACCORDANCE WITH GENERALLY ACCEPTED ENGINEERING STANDARDS.
<br />EXCEPTIONS:
<br />1. BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES OF 15 TONS OR LESS PER SYSTEM MAY BE TESTED AND BALANCED BY A
<br />MECHANICAL CONTRACTOR LICENSED TO DESIGN AND INSTALL SUCH SYSTEM(S).
<br />2. BUILDINGS WITH COOLING OR HEATING SYSTEM CAPACITIES OF 65,000 BTU/H OR LESS PER SYSTEM ARE EXEMPT FROM THE
<br />REQUIREMENTS OF THIS SECTION.
<br />AIR SYSTEM BALANCING SHALL COMPLY WITH FBC 2010 ENERGY CONSERVATION SECTION 503.2.9.1
<br />26. AS PER FBC 2010 ENERGY CONSERVATION SECTION 503.2.9.3, AN OPERATING AND MAINTENANCE MANUAL SHALL BE PROVIDED TO
<br />THE BUILDING OWNER BY THE MECHANICAL CONTRACTOR, THE MANUAL SHALL INCLUDE, AT LEAST, THE FOLLOWING:
<br />1, EQUIPMENT CAPACITY (INPUT AND OUTPUT) AND REQUIRED MAINTENANCE ACTIONS,
<br />2. EQUIPMENT OPERATION AND MAINTENANCE MANUALS,
<br />3. HVAC SYSTEM CONTROL MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING DIAGRAMS, SCHEMATICS, AND CONTROL.
<br />SEQUENCE DESCRIPTIONS. DESIRED OR FIELD -DETERMINED SET POINTS SHALL BE PERMANENTLY RECORDED ON CONTROL DRAWINGS, AT
<br />CONTROL DEVICES OR, FOR DIGITAL CONTROL SYSTEMS, IN PROGRAMMING COMMENTS.
<br />4. A COMPLETE WRITTEN NARRATIVE OF HOW EACH SYSTEM IS INTENDED TO OPERATE.
<br />27. ALL PIPING SERVING AS PART OF A HEATING OR COOLING SYSTEM SHALL BE THERMALLY INSULATED IN ACCORDANCE WITH FBC
<br />2010 ENERGY CONSERVATION TABLE 50328.
<br />28. IF THERE ARE ANY CHANGES IN ENGINEER'S DRAWINGS, IN DESIGN OR IN EQUIPMENT, WITHOUT ENGINEER'S CONSENT, THE A.C.
<br />CONTRACTOR SHALL ASSUME ALL RESPONSIBILITIES FOR THE PROJECT.
<br />29, SMOKE DETECTORS ARE REQUIRED ON ALL PRIMARY AIR CONDITIONING SYSTEMS WHERE TOTAL AIR VOLUME EXCEEDS 2,000 C.F.M.
<br />(FBC-MECHANICAL 2010, SEC11ON 606.2.1) A DUCT ACCESS DOOR IS REQUIRED TO ACCESS THE DETECTOR. THE SYSTEM SHALL BE WIRED
<br />SO AS WHEN THE DUCT SMOKE DETECTOR DETECTS SMOKE, IT SHALL STOP THE AC SUPPLY FAN AND CAUSE A VISUAL AND AUDIBLE
<br />SIGNAL IN A NORMALLY OCCUPIED LOCATION. ALSO, THE DETECTOR SHALL INDICATE A TROUBLE CONDITION EITHER VISUALLY OR AUDIBLY IN
<br />THE NORMALLY OCCUPIED LOCATION, AND BE IDENTIFIED AS AIR DUCT DETECTOR TROUBLE, NFPA 90A, 4-4A.3
<br />(THE TESTER SHOULD BE EQUIPPED WITH AN LED LIGHT TO INDICATE TROUBLE).
<br />30, AS PER FBC 2010 ENERGY CONSERVATION SECTION 503.2.5.4 (SHUTOFF DAMPER CONTROLS)
<br />PROVIDE MOTORIZED DAMPERS FOR O/A INTAKE FOR AHU, CONNECT MOTORIZED DAMPER TO TIME CLOCK TO CLOSE OUTSIDE AIR INTAKE
<br />AUTOMATICALLY WHEN THE SPACE SERVED IS NOT IN USE (OFF BUSINESS HOURS).
<br />31. GRAVITY HOODS, VENTS, AND VENTILATORS, ALL OUTDOOR AIR SUPPLY AND EXHAUST HOODS, VENTS, AND VENTILATORS SHALL BE
<br />EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN THE SPACES SERVED ARE NOT IN USE,
<br />EXCEPTION: VENTILATION SYSTEMS SERVING UNCONDITIONED SPACES.
<br />32. NA
<br />33, AS PER FBC-301.4 ALL APPLIANCES REGULATED BY THIS CODE SHALL BE LISTED AND LABELED UNLESS OTHERWISE APPROVED IN
<br />ACCORDANCE WITH SECTIONS 301.4.1 THROUGH 301.4.4.
<br />34. AS PER FMC-304.10 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT REQUIRE
<br />SERVICE AND ROOF HATCH OPENINGS ARE LOCATED WITHIN 10 FT. OF ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE
<br />OR OPEN SIDE IS LOCATED MORE THAN 30" ABOVE THE FLOOR, ROOF OR GRADE BELOW,
<br />35, AS PER 306.5.1 SLOPED ROOFS. WHERE APPLIANCES, EQUIPMENT, FANS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE INSTALLED
<br />ON A ROOF HAVING A SLOPE OF THREE UNITS VERTICAL IN 12 UNITS HORIZONTAL OR GREATER AND HAVING AN EDGE MORE THAN 30"
<br />ABOVE GRADE AT SUCH EDGE A LEVEL PLATFORM SHALL BE PROVIDED ON EACH SIDE OF THE APPLIANCE TO WHICH ACCESS IS REQUIRED
<br />FOR SERVICE, REPAIR OR MAINTENANCE. THE PLATFORM SHALL BE NOT LESS THAN 30" IN ANY DIMENSION AND SHALL BE PROVIDED WITH
<br />GUARDS. THE GUARDS SHALL EXTEND NOT LESS THAN 42"ABOVE THE PATFORM, SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
<br />OF A 21" DIAMETER SPHERE AND SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR QUARDS SPECIFIED IN THE FBC.
<br />36. ANY INTAKE OPENINGS SHALL BE LOCATED A MINIMUM OF 1OFT. FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE,
<br />37. ALL COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT INSTALLATION SHALL BE LISTED , LABELED AND INSTALLED IN
<br />ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTION.
<br />38. ROOF MOUNTED MECHANICAL UNITS SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES (203 MM)
<br />ABOVE THE ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT SUPPORTS
<br />PROVIDING A MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
<br />TABLE 1509.7 CLEARANCE BELOW RAISED ROOF MOUNTED MECHANICAL UNITS
<br />WIDTH OF MECHANICAL UNIT (INCHES)
<br />SURFACES (INCHES)
<br /><24 /24<36 / 36 < 48 / 48 < 60 / > 60
<br />14" 18" 24" 30" 48"
<br />39. ROOF TOP A/C UNIT CURB SHALL BE MINIMUM 14 GAUGE (HURRICANE RATED CURB).
<br />40. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND INFORM THE PROJECT ENGINEER AND ARCHITECT OF ANY
<br />DISCREPANCY BETWEEN THESE PLANS AND THE EXISTING CONDITIONS. THE CONTRACTOR SHALL INCLUDE IN HIS BID TO CORRECT SUCH
<br />CONDITION AS DIRECTED. THE ENGINEER AND ARCHITECT ARE NOT RESPONSIBLE FOR ANY ADDITIONAL COSTS RESULTING FROM VERIFIABLE
<br />EXISTING CONDITIONS DISCOVERED AFTER CONTRACT HAS BEEN AWARDED.
<br />NOTE:
<br />PROVIDE FLOAT SWITCH, TO BE INSTALLED
<br />IN THE PRIMARY DRAIN PAN OF THE UNIT,
<br />4' MAX BETWEEN SUPPORTS --
<br />ABOVE r+r a
<br />.B
<br />GALV METAL STRAP W/ NEOPRENE GASKET FASTEN
<br />TO PIPE STAND
<br />PVC CONDENSATE SEE MECH. PLANS
<br />FOR CONTINUATION
<br />RTU TO CURB ATTACHMENT & DRAIN DETAL
<br />NTSC
<br />G310,
<br />__ -_ANEW 4 x 4 x 1/4" STEEL
<br />OPTION 1.
<br />ANGLES (6'-0" O.C.MAX) FULLY
<br />CONNECT PREFABRICATED RTU CURB
<br />WELDED TO EX. BAR JOISTS
<br />DIRECTLY TO STEEL ANGLES / BAR
<br />JOIST W/ MIN. 3/8" DIAM, S.S. BOLTS
<br />W/ WASHERS THRU FLANGE OF CURB
<br />AND STEEL ANGLE / BAR JOIST
<br />BELOW AT ALL CORNERS AND BALANCE
<br />0 12" O.C. MAX ALL 4 SIDES
<br />OPTION 2.
<br />WELD CURB TO STEEL ANGLES "FRAME"
<br />NOTE:
<br />CURB MUST BE INSULATED FROM INSIDE,
<br />WITH 1/2" BEAD EVERY 6 INCHES.
<br />CURB TO ROOF JOIST
<br />ATTACHMENT DETAIL
<br />NTSC
<br />V:1 0610,30
<br />RELIEF VENT SAME SIZE AS CONDENSATE LINE
<br />CONC. COVER WITH LIFT HANDLE-- r,
<br />GRADE
<br />NATURAL EARTH
<br />24"0 x 36" LONG
<br />GALVANIZED STEEL
<br />NOTES:
<br />1. STABALIZER STONES MIN. ONE HALF CUBIC YARD
<br />DRYWELL DETAIL
<br />NTSC
<br />PVC CONDENSATE DRAIN
<br />LINE SEE PLAN FOR SIZE
<br />SEAL WITH SILICONE
<br />CAULK (OR EQ.)
<br />THE EXCAVATED PIT SHALL
<br />BE COMPLETELY FILLED
<br />WITH COARSE GRAVEL
<br />2"0 CLEAN STONES
<br />(STABALIZED)
<br />GASKET, TYP, __. s SCHEDULED RTU, SEE MECH, DWGS.
<br />NAILING STRIP f PRE -FABRICATED ROOF CURB (14 GA. MIN.)
<br />DUCT GAILY. MTL COUNTER FLASHING
<br />INSULATION - --- 4" CANT AND MTL FLASHING +
<br />COUNTER FLASHING AND ROOF
<br />,--PATCH AND REPAIR ALL AROUND
<br />INSULATION -------W�,/// - "" ROOF INSULATION AND MTL DECK
<br />CURB INSTALATION DETAIL
<br />NTSC
<br />V:1 :)h
<br />PACKAGED GAS / ELECTRIC HIGH EFFICIENCY AIR CONDITIONING UNITS
<br />MARK
<br />SERVICE
<br />MAKE
<br />MODEL
<br />S.A.
<br />MIN.
<br />EXT,
<br />FAN
<br />HP
<br />HEATING
<br />COOLING CAPACITY
<br />REFRIG.
<br />SEER f
<br />FLA/MCA
<br />ELECTRICAL
<br />WEIGHT
<br />ACCESSORIES
<br />CFM
<br />O.A,
<br />STATIC
<br />RPM
<br />FUEL
<br />INPUT
<br />TOTAL / SENS
<br />EAT
<br />AMBIENT
<br />EER
<br />MOCP
<br />CFM
<br />MBH/STAGES
<br />MBH
<br />DB / WB
<br />DB
<br />AC / 1
<br />STOCK
<br />LENNOX
<br />LGHO6OH4E
<br />2000
<br />210
<br />1.0
<br />1110
<br />1
<br />GAS
<br />65 / 1
<br />57.5 / 47.0
<br />77 / 64
<br />105
<br />R-410A
<br />17.0 /
<br />14.8 / 18
<br />480 / 3 / 60
<br />1100 LBS
<br />1 - 7
<br />12.7
<br />25
<br />AC / 2
<br />OFFICE AREA
<br />LENNOX
<br />LGH048H4E
<br />1600
<br />175
<br />1.0
<br />1195
<br />3/4
<br />GAS
<br />65 / 1
<br />45.4 / 37.7
<br />77 / 64
<br />105
<br />R-410A
<br />17.0 /
<br />11,6 / 14
<br />480 / 3 / 60
<br />1000 LBS
<br />1 -- 7
<br />12,8
<br />15
<br />AC / 3
<br />SALES
<br />LENNOX
<br />LGH156H4B
<br />5200
<br />1270
<br />1.0
<br />945
<br />5
<br />GAS
<br />169 / 1
<br />148.3 / 114.2
<br />80 / 67
<br />105
<br />R-410A
<br />--- /
<br />30.4 / 35
<br />480 / 3 / 60
<br />2400 LBS
<br />1 - 7
<br />12.0
<br />40
<br />AC / 4
<br />FITTING/
<br />LENNOX
<br />LGHO36114E
<br />1200
<br />165
<br />1,0
<br />1110
<br />1/2
<br />GAS
<br />65 / 1
<br />33.2 / 27.4
<br />78 / 65
<br />105
<br />R-410A
<br />17.0 /
<br />8.8 / 10
<br />480 / 3 / 60
<br />1000 LBS
<br />1 - 7
<br />TOILETS
<br />12.5
<br />15
<br />AC / 5
<br />SALES
<br />LENNOX
<br />LGH156H4B
<br />5200
<br />1270
<br />1.0
<br />945
<br />5
<br />GAS
<br />169 / 1
<br />148.3 / 114.2
<br />80 / 67
<br />105
<br />R 410A
<br />-- f
<br />30.4 / 35
<br />480 / 3 / 60
<br />2400 LBS
<br />1 - 7
<br />12.0
<br />40
<br />AC / 6
<br />SALES
<br />LENNOX
<br />LGH156H4B
<br />5200
<br />1270
<br />1.0
<br />945
<br />5
<br />GAS
<br />169 / 1
<br />148.3 / 114.2
<br />80 / 67
<br />105
<br />R-410A
<br />-- /
<br />30.4 / 35
<br />480 / 3 / 60
<br />2400 LBS
<br />1 - 7
<br />12.0
<br />40
<br />AC / 7
<br />SALES
<br />LENNOX
<br />LGH18OH4B
<br />1.0
<br />970
<br />5
<br />GAS
<br />169 / 1
<br />176.0 / 167.8
<br />77 / 65
<br />105
<br />R-410A
<br />-- /
<br />36.8 / 42
<br />480 / 3 / 60
<br />2700 LBS
<br />1 - 7
<br />�6000
<br />11460
<br />12.0
<br />45
<br />NQIE; ROOFTOP UNITS SHALL BE PURCHASED THROUGH LENNOX NATIONAL ACCOUNT. SUBSTITUTIONS ARE NOT PERMITTED.
<br />ACCESSORIES:
<br />1. NON -PRORATED WARRANTY OF 5 YEARS FOR THE COMPRESSORS AND 10 YEARS FOR THE HEAT EXCHANGERS, DUAL 115 VOLT GFCI TYPE SERVICE OUTLET (WIRING TO THE OUTLET
<br />SHALL BE FIELD PROVIDED BY THE ELECTRICAL CONTRACTOR ON SITE), COMPRESSOR TIME DELAY RELAY, FREEZE STAT, HIGH AND LOW PRESSURE SWITCHES, CRANKCASE HEATER,
<br />CONDENSER COIL GUARD, COIL DEFROST THERMOSTAT, 2" PLEATED FILTERS AND SPARE SET.
<br />2. CONTROLLED FROM FACTORY INSTALLED AND TESTED PRODIGY M2 WITH BACNET CONTROL MODULE,
<br />3. FACTORY INSTALLED PHOTO ELECTRIC SMOKE DETECTOR IN SUPPLY AND RETURN AIR SECTIONS OF UNIT WITH REMOTE MOUNTED STATUS AND TEST STATIONS INTERLOCKED TO STOP FAN ON
<br />ACTIVATION. REFER TO DETAIL ON THIS SHEET.
<br />4. PROVIDE WITH 14" INSULATED ROOF CURB WITH FACTORY INSTALLED BURGLAR BARS.
<br />5. MECHANICAL CONTRACTOR TO PROVIDE 12" HIGH REFLECTIVE UNIT NUMBERS WITH SPECIFIC A/C UNIT NUMBER TO BE POSTED ON EACH UNIT ON THE CONTROL PANEL DOOR AND SIDE WITH
<br />DISCONNECT IN A LOCATION VISIBLE FROM THE ROOF HATCH.
<br />6. FACTORY INSTALLED GEAR DRIVEN ECONOMIZER WITH GLOBAL ENTHALPY CONTROLS AND OUTDOOR AIR HOOD. TWO CLEANABLE ALUMINUM MESH OUTDOOR AIR FILTERS TO BE FURNISHED
<br />BY LENNOX WITH ECONOMIZER. PROVIDE WITH POWER EXHAUST FANS (BAROMETRIC RELIEF DAMPER FOR 5 TON UNITS AND BELOW),
<br />7. HACR CIRCUIT BREAKERS TO BE FACTORY INSTALLED AND FACTORY WIRED BY LENNOX ON ALL UNITS ABOVE 12.5 TONS. UNITS 12.5 TONS AND BELOW SHALL BE SUPPLIED WITH
<br />NON -FUSED SERVICE DISCONNECT" FACTORY INSTALLED AND FACTORY WIRED.
<br />NOTES:
<br />1. PER FBC 2010 ENERGY CONSERVATION SECTION 503.2.5.4 (SHUTOFF DAMPER CONTROLS)
<br />PROVIDE MOTORIZED DAMPERS FOR O/A INTAKE FOR AHU. CONNECT MOTORIZED DAMPER TO TIME CLOCK TO CLOSE
<br />OUTSIDE AIR INTAKE AUTOMATICALLY WHEN THE SPACE SERVED IS NOT IN USE (OFF BUSINESS HOURS),
<br />F'roj. M!@r.
<br />JU
<br />Job. C.apt.
<br />SG
<br />T>raum by
<br />JT
<br />RON BARR, A.I.A.
<br />Rev'd by
<br />STATE OF FLORIDA
<br />I
<br />AR 0016160
<br />o w
<br />w Z ~
<br />O w¢ w w
<br />Fw H
<br />U o w 0 0 m
<br />O
<br />U O
<br />Q z rUj l=_- 0 0 U z F
<br />2 0, 8 g,-
<br />z
<br />Ir w
<br />,L
<br />c 8
<br />s o
<br />m0 o
<br />¢
<br />W�
<br />z F-
<br />tr W t7 C? w Z ] z
<br />O O w O
<br />O° W
<br />co
<br />} F na ] ui
<br />m w c7 z z ¢ F-? U
<br />o m
<br />o
<br />. w zw
<br />af_o00 W
<br />IL 2
<br />U O Z O
<br />a cn
<br />H U 7I
<br />ILLn W
<br />d W w z h p H
<br />z= w
<br />w
<br />a O
<br />r w o 0 cn
<br />z 0 F- z m z E z
<br />aQ
<br />a o
<br />w° a zw
<br />o z T
<br />z a- w
<br />2a Oit zw
<br /><z 0
<br />O�
<br />0LL W Uz
<br />O w w
<br />F- < w<
<br />!
<br />F- < 0❑ o R I- z-z 2 4
<br />O
<br />COPYRIGHT 2012
<br />BARR ARCHITECTURAL STUDIO
<br />«#
<br />y�
<br />I,
<br />v,
<br />ik>
<br />Naw
<br />S
<br />A
<br />a
<br />�
<br />v,�
<br />v
<br />/
<br />1 N
<br />�
<br />M9,
<br />a
<br />1.evistons -
<br />C�7.1!1�1��►fa
<br />�
<br />M
<br />ail
<br />,IL
<br />I�
<br />7
<br />1
<br />V
<br />I..1
<br />x
<br />Q
<br />H
<br />N
<br />�
<br />L
<br />O
<br />cm (0
<br />cy)
<br />_m N cy)
<br />o N 'c
<br />LL N T
<br />N U.
<br />MC Lo tU
<br />~ 0
<br />Q
<br />C
<br />C
<br />O
<br />O
<br />IY
<br />(0 C
<br />(a r O
<br />U
<br />J✓ N
<br />U
<br />�- cn
<br />0 N
<br />LO U
<br />r~
<br />Sheet Titles
<br />MECHANICAL
<br />NOTES & DETAILS
<br />sca le;
<br />BUCHANAN P.E. CONSULTING I
<br />ELECTRICAL * MECHANICAL * PLUMBING
<br />ENGINEERING
<br />6191 W. ATLANTIC BLVD., SUITE #2
<br />MARGATE, FL 33063
<br />Ph: 954-590-3300 Fax: 964-590-2232
<br />Email: mepengineers@aol.com
<br />RAJA BUCHANAN FL P.E # 48916
<br />CERTIFICATE OF AUTHORIZATION # 8842
<br />SEAL,
<br />RAJ.? UCW
<br />FL E # 48E
<br />SEP 0 4 2013
<br />DATE:
<br />Date-
<br />01-31-2013
<br />Pro jest No.
<br />12-027
<br />Shreet No.
<br />M2-0
<br />2 OF 2
<br />FILE: 1612-M 1-0. D WG