System No. C-AJ-1226
<br />�fF' System No. C-AJ-3180
<br />System No. W-L-1054
<br />System No. W-L-1412
<br />c ®L us F Rating-3 Hr
<br />T Rating - 0 Hr
<br />Classified by g
<br />c oL us F Ratin - 3 Hr
<br />g
<br />Classified by T Rating = 0 Hr
<br />c °L US F Ratings -1 and 2 Hr See Items 1 and 3
<br />g ( )
<br />Classified by T Rating - 0 Hr
<br />c °L US F Rating -1 Hr
<br />g
<br />Classified by T Rating - 0 Hr
<br />>::>=»A<
<br />" ""''
<br />tud io3
<br />Underwriters Laboratories, Inc. L Rating At Ambient - Less Than 1 CFM/Sq Ft
<br />Underwriters Laboratories, Inc.
<br />Underwrites Laboratories, Inc.
<br />Underwriters Laboratories, Inc.
<br />to UL 1479 and CANNLC-S715 L Rating At 400 F - 4 CFWSq Ft
<br />to UL 1479 and CANNLC-S115
<br />to UL 1479 and CANNLC-Si15 L Rating At Ambient - Less Than 1 CFM/Sq Ft
<br />to UL 1479 and CANIULC-S115
<br />LRating at400E-4CFM/SgFt
<br />A
<br />� 3
<br />5
<br />1
<br />California Florida Nevada,
<br />I I
<br />4B
<br />1
<br />4B 1
<br />A
<br />�A 1A
<br />2211 E. 7TH Avenue, Tampa, Florida 33605
<br />2
<br />3
<br />P:239.357.4983 AA26002373
<br />`
<br />3 3 2
<br />Peninsula Engineering, INC.
<br />MEPS�FP
<br />4
<br />3
<br />2016 Alden Road Orlando, FL 32803
<br />3
<br />f�
<br />A 2
<br />3
<br />(SIDE B) (SIDE A)
<br />P: 407.246.1688
<br />A
<br />SECTION A -A
<br />4
<br />2 1 B
<br />F: 407.246.1664
<br />3
<br />A
<br />FRONT VIEW FRONT VIEW CROSS -SECTIONAL
<br />1. Floor or Wall Assembly- Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall
<br />SECTION A -A
<br />(SIDE A) (SIDE B) VIEW
<br />LBA INTERIORS
<br />may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 32 in.
<br />SECTION A -A
<br />2. Metallic Sleeve - (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted
<br />into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both
<br />1. Floor or Wall Assembly Min 4-1/2 in: 114 mm thick reinforced lightweight or normal weight 100-150 pcf or
<br />Y - ( )9 ( P
<br />1. Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the
<br />in the in the individual U300 U400 Series Wall Partition Designs in the UL
<br />1. Wall Assembly - The 1 hr fire -rated gypsum board/steel stud wall assembly shall be constructed of the materials
<br />INTERIOR DESIGNER
<br />DT PA
<br />5650 C PARKWAY, SUITE 100
<br />surfaces of wall.
<br />2A. Sheet Metal Sleeve - (Optional) Max 6 in. diam, min 26 ga galy steel provided with a 26 ga galy steel square
<br />1600 2400 kg/m3) concrete floor or min 4-3/4 in. (121 mm) thick reinforced lightweight or normal weight concrete
<br />wall. Wall may also be constructed of an UL Classified Concrete Blocks*. Max diam of opening is 6 in. 152 mm
<br />Y Y P 9 ( )•
<br />materials and manner specified or and
<br />Fire Resistance Directory and shall include the following construction features:
<br />and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire
<br />Resistance Directory and shall include the following construction features:
<br />ENGLEWOOD CO.80111
<br />,
<br />flange spot welded to the sleeve at approxmtd-height, or flush with bottom of sleeve in floors, and sized to be a min
<br />See Concrete Blocks CAZT category in the Fire Resistance Directory for names of manufacturers.
<br />( ) 9 rY rY
<br />2. Steel Sleeve - (Optional) - Nom 6 in. (152 mm) diam (or smaller) Schedule 40 (or heavier) steel pipe cast or
<br />A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2
<br />i
<br />by 4 n lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC. When steel
<br />A. Studs -Wall framing shall consist of steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102
<br />of 2 in. larger than the sleeve diam. The sleeve is to be cast in lace and may extend a max of 4 in. below the
<br />g p Y
<br />bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
<br />grouted into floor or wall assembly, flush with floor or wall surfaces.
<br />studs are used and the diam of opening exceeds the width of stud cavity, opening
<br />p g ty, the o enin shall be framed on all
<br />mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8 in. (92 mm) wide and spaced max 24 in.
<br />(610 mm) OC.
<br />P:303.773.0436
<br />2B. Sheet Metal Sleeve - (Optional) Max 12 in. diam, min 24 a alv steel provided with a 24 a alv steels square
<br />( p ) - g g p g g q
<br />3. Cables - Aggregate cross -sectional area of cables in opening to be max 45 percent of the aggregate
<br />cross -sectional area of the opening. Cables to be rigidly supported on both sides of floor or wall assembly. Any
<br />sides using lengths of steel stud installed between the vertical studs and screw -attached to the steel studs at
<br />each end. The framed opening in the wall shall be 4 to 6 in. wider and 4 to 6 in. higher than the diam of the
<br />B. Gypsum Board* -Min 5/8 in. (16 mm) thick gypsum board. Max diam of opening shall be 3 in. (76 mm) on
<br />F:303.773.0053
<br />flange spot welded to the sleeve at a rox mid -height, or flush with bottom of sleeve in floors, and sized to be a min
<br />g p pp g
<br />of 2 in, larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the
<br />combination of the following types and sizes of metallic conductor or fiber optic cable may be used:
<br />penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 in. clearance is
<br />through penetration side. Maximum width of opening on membrane penetration is to be max 3 in. (76 mm).
<br />2. Through Penetrant - One nom 2 in. 51 mm pipe to be installed concentrically or eccentrically within opening on
<br />9 ( ) P P Y Y P 9
<br />bottom of the deck and a max of 1 in. above the top surface of the concrete floor.
<br />A. Max 500 kcmil single copper connector power cable with thermoplastic insulation andpolyvinyl chloride PVC
<br />9 PP P P (PVC)
<br />jacket.
<br />present between the penetrating item and the framing on all four sides.
<br />B. Gypsum Board* -- 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness,
<br />one side of the wall. On one side of the wall the pipe is allowed to penetrate the membrane continuously in a plane
<br />3. Through -Penetrant - One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within
<br />g p�p y y
<br />the firestopsystem. The annular space between penetrant and periphery of opening shall be min 0 in. (point
<br />y p p p p ry p g (p
<br />B. Max 300 pair No. 24 AWG copper conductor telecommunication cables with polyvinyl chloride (PVC) insulation
<br />number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400
<br />parallel with the wall and the studs. The annular space between the through penetrant and the periphery of opening
<br />shall be min 0 in. (0 mm, point contact) to max 3/4 in. 19 mm). Through penetrant to be rigidly supported on the
<br />contact) to max 1-7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly supported
<br />on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be used:
<br />and jacket material.
<br />1
<br />C. Max 7/C copper conductor No. 12 AWG multiconductor power and control cables with polyvinyl chloride (PVC)
<br />Series Design n e UL Fire Resistance Directory. Max diam of opening is 32-1/4 in. for steel stud walls. Max
<br />t Di t R th i i D i S
<br />diam of opening is 14-1/2 in. for wood stud walls. The F Rating of the firestop system is equal to the fire rating
<br />through penetration side of the wall assembly. The following types and sizes of through penetrants may be used:
<br />A. Steel Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />A. Steel Pipe - Nom 30 in. diam or smaller Schedule 10 or heavier steel pipe.
<br />P ( ) ( ) p�p
<br />B. Iran Pipe -Nom 30 in. diam (or smaller) cast or ductile iron pipe.
<br />or cross -linked polyethylene (XLPE) insulation and PVC jacket.
<br />D. Multiple fiber optical communication cables jacketed with PVC and having a max outside diam of 1/2 in. 13
<br />P P 1 9 (
<br />of the wall assembly.
<br />2. Through -Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically
<br />B. Iron Pipe.-Nom 2 in. (51 mm) diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit -Nom 2 in. (51 mm) diam (or smaller) rigid steel conduit or electrical metallic tubing (ENT).
<br />C. Copper Pipe -Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
<br />D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
<br />mm ).
<br />E. Max 3/C copper conductor No. 12 AWG with bare aluminum ground, polyvinyl chloride (PVC) insulated steel,
<br />within the firestop system. The annular space shall be min 0 in. to max 2-1/4 in. Pipe may be installed with
<br />continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from
<br />3. Firestop System - Sealant -Min 5/8 in. (16 mm) thickness of fill material applied with annulus flush with both
<br />surfaces of the wall. Additional min 1/4 in. (6 mm) diam bead of fill material applied at the penetrant/gypsum board
<br />E. Conduit - Nom 6 in. diam (or smaller) steel conduit.
<br />Metal -clad cable.
<br />perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types
<br />interface on both sides of wall.
<br />F. Conduit- Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT).
<br />F. Max 3/C with round 2/0 AWG copper conductor SER cable with cross-linkedpolyethylene XLPE Insulation
<br />9 PP ( )
<br />andpolyvinyl chloride PVC jacket.
<br />(PVC)
<br />and sizes of metallic pipes, conduits or tubing may be used:
<br />A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE Sealant
<br />*Bearing
<br />4. Firestop System -The firestop system shall consist of the following:
<br />A. Packing Material - Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a
<br />G. RG/U coaxial cable with polyethylene (PE) insulation and polyvinyl chloride (PVC) jacket having a max outside
<br />B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe.
<br />the UL Classification Mark
<br />permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of
<br />wall or sleeve as required to accommodate the required thickness of fill material.
<br />diameter of in. 13 mm
<br />( )
<br />H. Fire Resistive Cables* - Max 1-1/4 in. (32 mm) diam single conductor or multi conductor Type MI cable. A min
<br />C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit.
<br />D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
<br />B. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. thickness of fill material applied within the annulus, flush
<br />with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact
<br />1/8 in. (3 mm) separation shall be maintained between MI cables and any other types of cable.
<br />4. Packing Material - Min 4-1/4 in. 108 mm thickness of min 4 pcf 64 k /m3 mineral wool batt insulation firm)
<br />g ( ) P ( g ) Y
<br />E. Copper Pipe -- Nom 6 in. diam (or smaller) regular (or heavier) copper pipe.
<br />3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with
<br />Reproduced by HILTI, Inc. Courtesy of
<br />Underwriters Laboratories, Inc.
<br />locations between penetrant and concrete or sleeve, a min 1!4 in. diam bead of fill material shall be applied at
<br />packed into opening as a permanent form. Packing material to be recessed from to surface of floor to
<br />P P 9 P 9 P
<br />accommodate the required thickness of fill material.
<br />both surfaces of wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. diam bead of
<br />fill material shall be applied at the pipe wall interface on both surfaces of wall .
<br />May
<br />y 24, 2007
<br />Hilti Firestop Systems
<br />the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of wall.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-One Sealant
<br />5. Fill, Void or Cavity Material* - Sealant - Min 1/4 in. (6.4 mm) thickness of fill material applied within the annulus,
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS-One Sealant
<br />*Bearing the UL Classification Mark
<br />flush with top surface of floor or with both surfaces of wall.
<br />*Bearing the UL Classification Mark
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-One Sealant.
<br />*Bearing
<br />Reproduced by HILTI, Inc. Courtesy of
<br />the UL Classification Mark
<br />Underwriters Laboratories, Inc.
<br />Reproduced by HILTI, Inc. Courtesy of
<br />Hilti Firestop Systems December 4, 2002
<br />Underwriters Laboratories, Inc.
<br />Reproduced by HILTI, Inc. Courtesy of
<br />Hilt! Firestop Systems StemS June 27, 2007
<br />Underwriters Laboratories, Inc.
<br />October 23, 2006
<br />Hilti Firestop Systems
<br />No. W-L-2075
<br />F,
<br />System No. W-L-2244System
<br />V
<br />REVISIONS:
<br />UL
<br />F Ratings -1 & 2 Hr (See Item 4)
<br />O System No. W-L-3065
<br />UL
<br />F Ratings --1 and 2 Hr (See Item 1)
<br />T Ratings 1 and 2 Hr (See Item 1)
<br />C © US F Ratings -1 and 2 Hr (See Item 1)
<br />Classified b
<br />Underwriters Laboratories, Inc. T Ratings - 0 and 2 Hr (see Item 4)
<br />to UL 1479 L Rating At Ambient - Less Than 1 CFWSq Ft
<br />Underwrite) s Laboratories, Inc. assilled by T Rating - 0 and 3/4 Hr (See item 3)
<br />Underwriters Laboratories, Inc. L Rating at Ambient - Less Than 1 CFM/sq ft
<br />to UL 1479 L Rating at 400 F - 2 CFWsq ft
<br />L Rating At 400 F - 4 CFWSq Ft
<br />to UL 1479 and CAN/ULC-S115
<br />A 2 1A
<br />�A 2 1A
<br />�A 2
<br />3
<br />2 4
<br />9
<br />�q
<br />1B
<br />3
<br />SECTION A -A
<br />A
<br />A 3
<br />1. Floor or Wall Assembly The fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials
<br />and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire
<br />Resistance Directory and shall include the following construction features:
<br />SECTION A -A 1 B
<br />A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2
<br />SECTION A -A
<br />by 4 in. lumber spaced 16 in. OC, Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC.
<br />B. Gypsum Board* -- Nom 5/8 in. thick gypsum wallboard, as specified in the individual Wall and Partition Design.
<br />1. Wall Assembly - The 1 and 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials
<br />Max diam of opening is 4 in.
<br />2. Metallic Sleeve -- (Optional) -- Nom 4 in. diam (or smaller) Schedule 40 (or thinner) steel pipe cast into wall
<br />1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials
<br />and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire
<br />and in the manner described in the individual U300, U400 or V400 Series Wall and Partition Design in the UL Fire
<br />Resistance Directory and shall include the following construction features:
<br />assembly with joint compound and installed flush with wall surfaces.
<br />3. Electrical Nonmetallic Tubing+ -- Nom 2 in. diam (or smaller) corrugated wall electrical nonmetallic tubing (ENT)
<br />Resistance Directory and shall include the following construction features:
<br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2
<br />A. Studs -- Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2
<br />by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide by
<br />constructed of polyvinyl chloride (PVC). Tubing to be rigidly supported on both sides of wall assembly. A nom
<br />by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 2-1/2 in. (64 mm) wide and
<br />1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.
<br />annular space of 3/4 in. is required within the firestop system.
<br />See Electrical Nonmetallic Tubing (FKHU) category in the Electrical Construction Materials Directory for names of
<br />spaced max 24 in. 610 mm OC.
<br />p ( )
<br />B. Gypsum Board* - Nom 5/8 in. (16 mm) thick gypsum board, with square or tapered edges. The gypsum board
<br />B. Gypsum Board_ -- The gypsum board type, thickness, number of layers, fastener type and sheet orientation
<br />shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory.
<br />manufacturers.
<br />4. Fill, Void or Cavity Material* -- Sealant -- Installed symmetrically on both sides of the wall. The hourly F Rating of
<br />type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual
<br />U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 5-1/2 in. (138
<br />Max diam of opening is 3 in. (76 mm).
<br />The hourly F and T Ratings of the firestop system are equal to the hourly fire rating of the wall assembly in which it
<br />the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. Fill material applied
<br />mm) when sleeve (Item 2) is employed. Max diam of opening is 4 in. (102 mm) when sleeve (Item 2) is not
<br />is installed.
<br />within the annulus, flush with each end of the steel sleeve at the thickness shown in the table below:
<br />employed.
<br />2. Through Penetrant -- One nonmetallic pipe, conduit or tubing installed either concentrically or eccentrically within
<br />F Rating Hr T Rating Hr Fill Mtl Depth In.
<br />The F Rating of the firestop system is equal to the fire rating of the wall assembly,
<br />2. Metallic Sleeve - (Optional) - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing (EMT) or
<br />the firestop system. The annular space between pipe and periphery of opening shall be min of 0 in. (point contact)
<br />to a max 5/8 in. .(16 mm). Pipe to be rigidly supported on both sides of wall assembly. The following types and sizes
<br />ARCHITECT OF RECORD:
<br />1 0 5/8
<br />Schedule 5 (or heavier) steel pipe or min 0.016 in. thick (0.41 mm, No. 28 ga) gals steel sleeve installed flush with
<br />wall surfaces. The annular space between steel sleeve and periphery of opening shall be min 0 in. (0 mm, point
<br />of nonmetallic pipes may be used:
<br />A. Polyvinyl Chloride (PVC) Pipe -- Nom 2 in. (51 mm) diam (or smaller) cellular or solid core Schedule 40 (or
<br />JOSE A PEREZ, NCARB AIA
<br />2 2 1-1/4
<br />contact) to max 1 in. (25mm). When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. (457
<br />heavier) pipe for use in closed (process or supply) piping systems.
<br />AR97653
<br />mm) beyond the wall surfaces. As an option when Schedule 5 steel pipe or EMT is used, sleeve may extend
<br />B. Chlorinated Polyvinyl Chloride (CPVC) -- Nom 2 in. (51 mm) diam (or smaller) SDR 13.5 CPVC pipe for use in
<br />continuously beyond one wall surfaces. When cable bundle penetrates wall assembly at an angle of 45 degrees, no
<br />closed (process or supply) piping systems.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS-One Sealant
<br />metallic sleeve is used.
<br />3. Fill, Void or Cavity Material* - Sealant -- Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush
<br />Q F ( 0
<br />+Bearing the UL Listing Mark
<br />*Bearing the UL Classification Marking
<br />3. Cables - Aggregate cross -sectional area of cable in opening to be max 45 percent of the cross -sectional area of
<br />the opening. The annular space between the cable bundle and the periphery of the opening to be min 0 in. (0 mm,
<br />with both surfaces of wall. At point contact location, a min 1/2 in. (13 mm) diam bead of fill material shall be applied
<br />interface
<br />A
<br />to the wall/penetrant on both surfaces of the wall.
<br />point contact)to max 1 in. (25 ni Cables to be rigidly supported on both sides of the wall assembly. Cable bundle,
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS-ONE Sealant
<br />using cables described below, may penetrate the wall at an angle not greater than 45 degrees. Any combination of
<br />*Bearing the UL Classification Mark
<br />ell
<br />Reproduced by HILTI, Inc. Courtesy of
<br />the following types and sizes of copper conductor cables may be used:
<br />q ,�
<br />Underwriters Laboratories, Inc.
<br />January 9, 2003
<br />A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
<br />Reproduced by HILTI, Inc. Courtesy of
<br />AR9%�53
<br />Hilt! Firestop Systems
<br />B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.
<br />B1. Max 4 pr No. 22 AWG Cat 5 or Cat 6 computer cables.
<br />Underwriters Laboratories, Inc.
<br />Al
<br />Q "
<br />C. Type RG/U coaxial cable with (PE) insulation and PVC jacket having a max outside diameter of Yz
<br />April 11, 2005
<br />Hilti Firestop Systems
<br />polyethylene
<br />in.
<br />s l
<br />(13 mm).
<br />R ARQ,
<br />C1. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.
<br />D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. (16 mm).
<br />'
<br />`
<br />E. Through Penetrating Products*- Max three copper conductor No. 8 AWG .Metal -Clad Cable+.
<br />AFC CABLE SYSTEMS INC
<br />F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
<br />C TITLE:
<br />G. Max 3/4 in. (19 mm) diam copper ground cable with or without a PVC jacket.
<br />H. Fire Resistive Cables* - Max 1-1/4 in. (32 mm) diam single conductor or multi conductor Type MI cable. A min
<br />RH I LLS HEALTH &
<br />4RHAEB
<br />1 /8 in. (3 mm) separation shall be maintained between MI cables and any other types of cable.
<br />I. Max 4/C with ground 300 kcmil (or smaller) aluminum SER cable with PVC insulation and jacket.
<br />CENTER
<br />J. Through Penetrating Product* - Any cables, Metal -Clad Cable+ or Armored Cable+ currently Classified under
<br />the Through Penetrating Products category.
<br />K. Maximum 31C No. 8 AWG metal -clad cable.
<br />SKILLED NURSING -10 B E D
<br />L. Maximum 5/8 diam fiber-optic cable with PVC jacket.
<br />For cable bundle penetrating the wall assembly at an angle of 45 degrees, the T rating is % hr for a 2 hr wall
<br />CONVERSION
<br />assembly.
<br />See Through Penetrating Product (XHLY) category in the Fire Resistance Directory for names of manufacturers.
<br />4. Fill, Void or Cavity Material*- Sealant or Putty - Fill material applied within the annulus, flush with each end of
<br />PROJECT ADDRESS:
<br />the steel sleeve or wall surface. Fill material installed symmetrically on both sides of the wall. A min 5/8 in. 16 mm)
<br />thickness of sealant is required for the 1 or 2 hr F Rating . An additional 1/2 in. (13 mm) diam bead of fill material
<br />shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of
<br />NOTE: CONTRACTOR SHALL
<br />7350 DAIRY RD. ZEPHYRHILLS, FL. 33540
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP601S, CP606, FS-One Sealants or CP618 Putty
<br />*Bearing the UL Classification Mark
<br />+Bearing the UL Listing Mark
<br />PROVIDE U.L. LABELS AT ALL
<br />PROJECT NUMBER:
<br />Reproduced by HILTI, Inc. Courtesy of
<br />N AT
<br />FLTSP15008
<br />Underwriters Laboratories, Inc.
<br />P E RATIONS THROUGH
<br />Hilti Firestop Systems March 15,2012
<br />RATED
<br />TED WALLS.
<br />SHEET
<br />TITLE:
<br />UL DETAILS - THRU WALL
<br />PENETRATIONS
<br />LS1 m40
<br />© 2015 Studio+