<br />CONDUIT PENETRATION
<br />SEALED WITH SILICONE
<br />SEALANT
<br />CONDUIT AND WIRING TO
<br />NEXT JUNCTION BOX ON
<br />SAME SYSTEM
<br />CONDUIT AT CEILING PENETRATION
<br />FILLED WITH SEALANT
<br />CONDUIT AND WIRING TO PANEL FURNISHED
<br />BY OWNER, INSTALLED BY G.C.
<br />COOLER/FREEZER BOX CEILING
<br />CEILING MOUNTED WP JUNCTION BOX
<br />WITH THREADED HUBS AND GASKETED
<br />COVERPLATE
<br />PROVIDE CEILING MOUNTED MANUAL
<br />TWO -POLE SWITCH IN WEATHERPROOF
<br />ENCLOSURE.
<br />�— LIQUID TIGHT FLEX CONDUIT TO
<br />KNOCKOUT ON UNIT. FINAL
<br />-- - -- ---- - CONNECTION TO COIL BY GC
<br />NOTE: DO NOT LOCATE WP JUNCTION BOX DIRECTLY IN FRONT OF DISCHARGE FAN, OFFSET TO SIDE.
<br />EVAPORATOR COIL WIRING
<br />N.T.S.
<br />ATM WIRING
<br />4 N.T.S.
<br />NOTE 8
<br />C S-4
<br />CEILING
<br />NOTE 9
<br />S-6
<br />DESK
<br />REFER TO ARCH INTERIOR OFFICE
<br />ELEVATIONS FOR EXACT DIMENSIONS
<br />MGR'S OFFICE WIRING
<br />N.T.S.
<br />INSTALL LIGHTIN,
<br />OVERRIDE SWITC
<br />PROVIDED BY EM;
<br />REF EMS1.
<br />S-10
<br />NOTE 5
<br />TYPICAL WORKSTATION ELEVATION. MAY NEED
<br />MODIFICATION PER ACTUAL CONDITIONS.
<br />WORKSTATION WIRING
<br />L-22
<br />+154"
<br />¢ CC
<br />0 0
<br />LU it
<br />W�w
<br />X ~
<br />LU z TO WIRE
<br />WAY
<br />m
<br />IW
<br />0 ¶
<br />> o IIIIII�
<br />P It
<br />NEW
<br />PANEL
<br />MDP
<br />CT O METER
<br />CABINET
<br />DD
<br />W
<br />GENERATOR
<br />DOCKING STATION I WIRE WAY
<br />ofli
<br />— — — — — — — — — — — j— — -
<br />�Lu cc cc
<br />J cc cc I to rn
<br />Z
<br />Z Z
<br />oco U)
<br />o 0
<br />O P
<br />-� RR
<br />MC CABLE
<br />al
<br />CEILING -
<br />w
<br />PI
<br />I LL >I
<br />m
<br />U
<br />NEW WIRE WAY
<br />PNL
<br />F
<br />I IR I
<br />I IR IR I
<br />LIGHTING oofl�
<br />CONTACTOR L0
<br />WIRE
<br />WAY
<br />------I----I--
<br />a f2 f2 2
<br />a a
<br />in cca
<br />FLOOR
<br />W >
<br />8"
<br />8'
<br />Ca }
<br />�In
<br />�
<br />Q
<br />a=
<br />W
<br />w
<br />O
<br />U Z
<br />0
<br />y
<br />0 U
<br />c
<br />O
<br />PANELBOARD ELEVATION
<br />N.T.S.
<br />IVCIVI/1-JR
<br />A-4
<br />W P/GFCI
<br />2
<br />POWER PLAN
<br />3 � 2
<br />ELECTRICAL NOTES:
<br />1. ALL RECEPTACLES SERVED FROM PANEL "S" SHALL BE OF
<br />THE ISOLATED GROUND TYPE. ALL CIRCUITS SHALL CONTAIN
<br />A HOT, NEUTRAL, GROUND AND ISOLATED GROUND CONDUCTOR.
<br />2. ISOLATED GROUND (IG) 20 AMP CIRCUIT, FLUSH MOUNT QUAD
<br />PLATE WITH ORANGE RECEPTACLES.
<br />2A. ISOLATED GROUND (IG) 20 AMP DUPLEX CIRCUIT FOR ATM.
<br />3. AMPACITY OF ALL CONDUCTOR SIZES SHOWN ON PLANS IS
<br />BASED ON 750C RATED TERMINATIONS AND CONDUCTOR
<br />INSULATION. CONTRACTOR SHALL FIELD VERIFY EQUIPMENT
<br />TEMPERATURE RATINGS OF ALL TERMINATIONS AND ADJUST
<br />CONDUCTOR SIZES PER NEC 110.14(C)
<br />4. ALL WIRING IS COPPER. REFER TO ELECTRICAL SPECIFICATIONS FOR
<br />FURTHER INFORMATION.
<br />5. WORK STATION RECEPTACLE FOR TASK LIGHTING AND TRAINING
<br />COMPUTER.
<br />6. ISOLATED GROUND (IG) 20 AMP CIRCUIT FOR STORE COMPUTER,
<br />FLUSH MOUNT FACE PLATE FOR DUPLEX RECEPTACLE WHICH
<br />RECEIVES PLUG FROM UPS (BATTERY BACKUP) AND FUTURE
<br />PERIPHERALS.
<br />7. ALL WALL MOUNTED RECEPTACLES SHALL BE 18" A.F.F ON CENTER.
<br />UNLESS NOTED OTHERWISE.
<br />8. QUAD RECEPTACLE FOR SECURITY EQUIPMENT. RECEPTACLE
<br />RECEIVES THE FOLLOWING EQUIPMENT PLUGS:
<br />A. VCR
<br />B. MULTIPLEX CONNECTION FOR CAMERAS
<br />C. INTERCOM TO RECORD AUDIO AT SALES COUNTER
<br />D. ALARM RECEIVER.
<br />UTILITY
<br />METER
<br />NEW 600A
<br />GENERATOR
<br />nnnvikin CTATIMI
<br />j
<br />i W GFCI
<br />1.2 1.1 1
<br />9. ISOLATED GROUND (IG) 20 AMP CIRCUIT FOR STORE COMPUTER,
<br />FLUSH MOUNT FACE PLATE FOR QUAD RECEPTACLE.
<br />10. FURNISH AND INSTALL CORD AND CAP FOR ALL EQUIPMENT
<br />CONNECTED TO NEMA L-14R RECEPTACLE.
<br />11. G.C. TO COORDINATE POWER REQUIREMENTS FOR EXTERIOR SIGNAGE.
<br />12. THE UNGROUNDED AND GROUNDED CONDUCTORS OF EACH
<br />MULTIWIRE BRANCH CIRCUIT SHALL BE GROUPED BY WIRE TIES OR
<br />SIMILAR MEANS IN AT LEAST ONE LOCATION WITHIN THE PANELBOARD
<br />OR OTHER POINT OF ORIGINATION. REF 2011 NEC (210.4(D))
<br />13. EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH A
<br />MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED
<br />CONDUCTORS AT THE POINT WHERE THE BRANCH CIRCUITS
<br />ORIGINATE. REF 2011 NEC (210.4)
<br />14. CONDUITS THAT ARE EXPOSED TO WIDELY DIFFERENT
<br />TEMPERATURES, SUCH AS COOLERS, FREEZERS OR SERVICE
<br />ENTRANCE CONDUCTORS, SHALL BE SEALED TO PREVENT
<br />CIRCULATION OF AIR AND/OR MOISTURE. REF 2011 NEC (300.7 (A))
<br />15. CONDUIT AND WIRING IN AREAS WHERE EXPOSED SHALL BE ROUTED
<br />AT 90 DEGREE ANGLES PERPENDICULAR OR PARALLEL TO JOISTS.
<br />COORDINATE PAINTING OF CONDUIT WITH ARCHITECTURAL FINISHES.
<br />16. ALL RECEPTACLES IN FOOD SERVICE AREA SHALL BE 5" A.F.F. TO
<br />BOTTOM, UNLESS NOTED OTHERWISE.
<br />SYMBOL LEGEND
<br />4F TELEPHONE/ (1 SPECIAL RECEPTACLE
<br />DATA OUTLET Y (SEE NEMA CONFIG)
<br />OJ JUNCTION BOX Eh FUSED DISCONNECT
<br />(n1 125 V RECEPTACLE, Eh NON -FUSED DISCONNECT
<br />V DUPLEX
<br />125 V RECEPTACLE, WALL SWITCH
<br />CEILING MOUNT DUPLEX PANEL BOARD
<br />125 V RECEPTACLE,
<br />SIMPLEX WEATHERPROOF SPEAKER
<br />125 V RECEPTACLE, cE53 FUEL E-STOP
<br />DOUBLE DUPLEX
<br />(NOTE: NOT ALL SYMBOLS ARE USED)
<br />KEYNOTES - POWER
<br />1 EXHAUST FAN. SWITCH FAN WITH RESTROOM LIGHTS, TYP.
<br />2 DEVICES SHALL BE NEMA 5-20 UNLESS NOTED OTHERWISE.
<br />TYP OF 120V-20A CIRCUITS.
<br />3 EXTERIOR SIGNAGE J-BOX. COORDINATE FINAL LOCATION
<br />WITH SIGNAGE CONTRACTOR AND CONSTRUCTION MANAGER.
<br />RUN EXTERIOR BUILDING SIGNS THROUGH PHOTOCELL
<br />DRIVEN CONTACTOR. PROVIDE PAD -LOCKABLE BREAKER FOR
<br />MAINTENANCE.
<br />4 ENERGY MANAGEMENT ENCLOSURE PROVIDED BY OTHERS,
<br />PROVIDE 120V DEDICATED CIRCUIT ONLY.
<br />5 RECEPTACLE FOR ATM SIGN. VERIFY LOCATION WITH
<br />CONSTRUCTION MANAGER PRIOR TO COMMENCEMENT OF
<br />WORK.
<br />6 WINDOW RECEPTACLES, MOUNT FLUSH IN CEILING, TYP. PER
<br />NEC
<br />7 TELEPHONE BOARD. 4'X4'X3/4" PLYWOOD WITH (1)#6 CU.
<br />GROUND FOR FUTURE USE MOUNTED ABOVE 4'X4'X3/4"
<br />PLYWOOD WITH (1)#6 CU. GROUND PER TELE. CO.
<br />REQUIREMENTS. MOUNT RECEPTACLE ADJACENT TO OR
<br />ABOVE TELEPHONE BOARD, DO NOT MOUNT BELOW.
<br />8 PROVIDE PAD -LOCKABLE BREAKER FOR MAINTENANCE PER
<br />N.E.C. 422.31(B). COORDINATE EXACT LOCATION OF
<br />ELECTRICAL OUTLET WITH CONSTRUCTION MANAGER PRIOR
<br />TO ROUGH -IN.
<br />9 REFER TO EVAPORATOR COIL WIRING DETAIL, RE: 5/E1.0, TYP.
<br />10 VEEDER ROOT: COORDINATE INSTALLATION WITH FUELING
<br />PLANS. INSTALL IN ACCESSIBLE LOCATION. MOUNT AT 48"
<br />A.F.F. TO BOTTOM.
<br />11 RECEPTACLE FOR MOTION SENSOR FAUCET. REFER TO
<br />ARCHITECTURAL SHEETS FOR EXACT ROUGH -IN LOCATIONS,
<br />TYP.
<br />12 RECEPTACLE FOR WATER FILTRATION BOOSTER PUMP, E.C.
<br />TO INSTALL WATER-RESISTANT, "WHILE -IN -USE" COVER.
<br />13 E.C. TO PROVIDE WIRING FOR COOLER AND/OR FREEZER
<br />DOOR HEATERS AND DOOR FRAMES AND CONNECT TO
<br />MANUFACTURER SUPPLIED JUNCTION BOX(ES).
<br />14 E.C. TO INSTALL WEATHERPROOF J-BOX FOR RAYCHEM HEAT
<br />TRACE WHICH SUPPLIES FREEZE PROTECTION FOR FREEZER
<br />CONDENSATE LINES. FURNISH HEAT TRACE AND PROVIDE
<br />GFI-EPD CIRCUIT BREAKER AND INSTALL PER
<br />MANUFACTURER'S REQUIREMENTS. REF. ELECTRICAL
<br />SPECIFICATIONS.
<br />15 ROUTE CIRCUITRY FOR EQUIPMENT UNDER SLAB, RE: 1/E1.2
<br />16 SERVICE RECEPTACLE, WEATHERPROOF GFCI.
<br />17 REFER TO DETAIL #5 ON GAS PLANS SHEET G10 FOR PANEL 'F'
<br />CONDUIT ROUTING.
<br />18 EMERGENCY GAS SHUT-OFF @ 48" A.F.F.
<br />19 TRANSMITTER RECEPTACLE, G.C. TO PROVIDE. MR. CHIME
<br />ENTRANCE ALERT TRANSMITTER (DA4TAC). CONTACT MR.
<br />CHIME AT 877-672-4463.
<br />20 RECEIVER RECEPTACLE, G.C. TO PROVIDE. MR. CHIME
<br />RECEIVER (DARD).
<br />21 INSTALL WEATHERPROOF SPEAKER, G.C. TO PROVIDE MR.
<br />CHIME SPEAKER (SPK). MOUNT ON WALL IN WALK IN COOLER
<br />AND CONNECT TO NEAREST RECEIVER OUTSIDE OF COOLER.
<br />22 �BRANDSTAND PRODUCTS "CUBIE" ITEM #BPECA-P. MOUNTED
<br />TO TOP OF LEAN BAR PER MANUFACTURER'S SPECIFICATIONS.
<br />PLUG IN TO DUPLEX FLOOR OUTLET BELOW.
<br />Date;
<br />106 N 37TH STREET, SUITE C
<br />ROGERS, ARKANSAS 72756
<br />W W W.BATESARCH ITECTS.COM
<br />TEL: 479.633.8165
<br />Copyright 2016 Bates & Associates, Architects
<br />E Drawings and Specifications as instruments of service are and shall remain
<br />the property of the Architect. They are not to be used on other projects or
<br />extensions to this project except by agreement in writing and with
<br />appropriate compensation to the Architect.
<br />Contractor is responsible for confirming and correlating dimensions at job
<br />site; the Architect will not be responsible for construction means, methods,
<br />techniques, sequences or procedures, or for safety precautions and
<br />programs in connection with the project.
<br />SITE/STORE #:
<br />1037728
<br />CONSTRUCTION MANAGER
<br />CREIGHTON CONST. & MGMT
<br />900 SW PINE ISLAND ROAD, SUITE 202,
<br />CAPE CORAL, FL 33991
<br />DEVELOPER CONTACT
<br />TENANT
<br />7-ELEVEN INC.
<br />1722 ROUTH ST. SUITE 1000 DALLAS, TX 75201
<br />DANIELTUBB
<br />STRUCTURAL CONSULTANT
<br />ARCH CONSULTING ENGINEERS
<br />510 S CONGRESS SUITE B-100 AUSTIN, TX 78704
<br />JUSTIN BILLODEAU
<br />MEP CONSULTANT
<br />WALTER J. FITZGERALD, P.E. 24636
<br />2566 NEBRASKA AVE. APT 443
<br />PALM HARBOR, FL 34684 PH (813) 785-7526
<br />F IJ
<br />Clie— N
<br />c N
<br />UJ
<br />W
<br />T
<br />d' 06 � rn
<br />cc zLO
<br />0 M M
<br />O � M �- Q M
<br />le-eaw � � �
<br />z w O o Q
<br />a. m <
<br />C > � CC z Ov
<br />J T >" O — w
<br />W « a. lie—z
<br />I� >' N :CCL U
<br />W W
<br />O
<br />U �
<br />�'011111111111111
<br />�::• s o.2463� �0
<br />-'1111H111111".
<br />0313r1z';'11
<br />Architect Name - RYAN M FAUST
<br />Architect Number - AR97905
<br />THE SEAL AND SIGNATURE APPLY ONLY TO THE DOCUMENTTO WHICH
<br />THEY ARE AFFIXED AND WE EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR
<br />ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS OR OTHER
<br />DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED
<br />FOR ANY PART OR PARTS OF THE PROJECT.
<br />REVISIONS
<br />NO. DATE I DESCRIPTION
<br />A PROJECT NUMBER: 16-021
<br />RELEASE DATE: 03/31/2016
<br />ELECTRICAL FLOOR PLAN