ELECTRICAL SPECIFICATIONS <br />I. SCOPE OF WORK <br />A. ALL WORK SHALL BE IN COMPLIANCE WITH THE LATEST APPLICABLE CODES, LAWS AND ORDINANCES, <br />AND THE NATIONAL ELECTRICAL CODE. PROVIDE AND FURNISH ALL LABOR, MATERIALS, PERMITS, AND <br />INCIDENTALS REQUIRED TO COMPLETE ALL WORK AS SHOWN ON CONTRACT DOCUMENTS. <br />B. CONTRACTOR SHALL INSPECT ALL NEW MATERIAL AND EQUIPMENT PRIOR TO INSTALLATIONS FOR <br />DAMAGES, AND SHALL VERIFY EQUIPMENT OPERATES SATISFACTORILY. <br />C. CONTRACTOR SHALL WARRANT ALL MATERIAL AND EQUIPMENT FURNISHED TO COMPLETE ALL WORK <br />FOR ONE YEAR AFTER FINAL ACCEPTANCE OF COMPLETION. MATERIALS AND EQUIPMENT DEFECTS OF <br />FAILURES DUE TO ABUSE, OR WORKMANSHIP NEGLECT SHALL BE MADE GOOD BY THE CONTRACTOR <br />WITHOUT COST TO THE OWNER. <br />D. PROVIDE ONLY NEW, STANDARD UNDERWRITER'S LABORATORY INC. LISTED FIRST -GRADE MATERIALS <br />THROUGHOUT, AND SHALL BE MARKED WITH UNDERWRITER'S LABORATORY INC. LISTED AND WITH <br />MANUFACTURER'S BRAND OR TRADEMARK. ALL MATERIALS SHALL BE OF ONE MANUFACTURER. <br />E. CONTRACTOR SHALL BE EXPERIENCED IN THEIR TRADE. CONTRACTOR'S WORK SHALL PRESENT A <br />NEAT APPEARANCE UPON COMPLETION. MATERIALS AND EQUIPMENT INSTALLED SHALL BE PLUMB, <br />STRAIGHT, AND LEVEL <br />F. CONTRACTOR SHALL COORDINATE WITH THE ARCHITECT AND OWNER ON EXACT LOCATION OF WIRING <br />DEVICES AND RACEWAY FOR OWNER -FURNISHED EQUIPMENT PRIOR TO ROUGH -IN. <br />G. UPON COMPLETION OF WORK, THE CONTRACTOR SHALL TEST ALL WIRING AND EQUIPMENT <br />INSTALLATION, AND SHALL BE IN PERFECT WORKING CONDITION IN ACCORDANCE WITH THE INTENT OF <br />THE CONTRACT DOCUMENTS. <br />II. ELECTRICAL IDENTIFICATION <br />A. NAMEPLATES: <br />ENGRAVED PLASTIC LAMINATE NAMEPLATES: PROVIDE ENGRAVING PHENOLIC PLASTIC LAMINATE, IN <br />SIZES AND THICKNESS INDICATED, ENGRAVED WITH 1/16 INCH THICK LINES WITH SQUARE STANDARD <br />PICA LETTERING AND WORDING AS SPECIFIED HEREIN, BLACK FACE AND WHITE LETTER FOR NORMAL <br />SYSTEMS AND RED AND WHITE FOR FIRE ALARM AND WHERE NOTED IN THE SPECIFICATIONS. PUNCH <br />FOR MECHANICAL FASTENING, EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF <br />SUBSTRATE. MATERIAL THICKNESS SHALL BE 1 /16 INCH. PROVIDE BEVELED EDGE IN ORDER TO <br />ELIMINATE SHARP CORNERS. PROVIDE SELF -TAPPING STAINLESS STAINLESS STEEL ROUND HEAD <br />SCREWS. PROVIDE CONTACT TYPE PERMANENT ADHESIVE WHERE SCREWS CANNOT OR SHALL NOT <br />PENETRATE THE SUBSTRATE. ADHESIVE NAMEPLATE SHALL BE PERMANENTLY INSTALLED. TITLES SHALL <br />BE 1/2 INCH HIGH AND ALL OTHER LETTERING SHALL BE 1/4 INCH HIGH. <br />B. JUNCTION BOXES: <br />JUNCTION BOX IDENTIFICATION: PROVIDE NEAT INDELIBLE FELT TIP, STENCILED MARKING ON JUNCTION <br />BOXES AND PULL BOX COVERS. LETTER SIZES SHALL BE 1 INCH HIGH MINIMUM. PROVIDE <br />NON -STENCILED MARKINGS INSIDE THE JUNCTION BOX AND ON THE EXTERIOR EDGE TO MATCH THE <br />COVER MARKINGS. <br />III. BASIC MATERIALS AND METHODS <br />A. PANEL BOARDS: <br />PROVIDE PANEL BOARDS WITH MAIN BREAKER OR MAIN LUGS WHERE SHOWN ON THE DRAWINGS, OF A <br />DEAD FRONT, DISTRIBUTED PHASE SEQUENCE DESIGN. PANEL BOARDS SHALL BE EQUIPPED WITH <br />THERMAL -MAGNETIC MOLDED CASE CIRCUIT BREAKERS WITH FRAME AND TRIP RATINGS AS INDICATED IN <br />THE SCHEDULES. <br />DIRECTORIES: A TYPED PANEL BOARD DIRECTORY SHALL BE PROVIDED FOR EACH PANEL BOARD AND <br />SHALL INDICATE THE ACTUAL CIRCUIT NUMBER USED, ROOM NAME AND TYPE OF LOAD. ROOM NAMES <br />SHALL BE THE ACTUAL NAME OR ROOM NUMBER USED NOT NECESSARILY AS SHOWN ON THE DRAWING. <br />PANEL DIRECTORIES SHALL INCLUDE ALL ROOM NUMBERS AND NAMES. WHERE PANEL SCHEDULES ARE <br />INDICATED ON THE DRAWINGS AS "RECEPTACLES OR "UGHTING ETC, IT SHALL BE THE RESPONSIBILITY <br />OF THE CONTRACTOR TO INCLUDE THE SPECIFIC AREA SERVED. <br />B. CIRCUIT BREAKERS: <br />CIRCUIT BREAKERS SHALL BE BOLT -ON QUICK -MAKE, QUICK -BREAK THERMAL -MAGNETIC TYPE, FOR <br />ALTERNATING CURRENT. BREAKERS SHALL TRIP FREE OF THE HANDLE AND TRIPPING SHALL BE <br />INDICATED BY THE HANDLE ASSUMING A POSITION BETWEEN OFF AND ON. MULTI- POLE BREAKERS <br />SHALL BE INTERNAL, COMMON TRIP WITH SINGLE OPERATING HANDLE; EXTERNAL HANDLE TIES ARE NOT <br />ACCEPTABLE. <br />C. CONDUIT: <br />RIGID SHALL BE MINIMUM 1", GALVANIZED OUTSIDE AND INSIDE BY HOT DIPPING, E.M.T. SHALL <br />BE MINIMUM 1/2" AND SHALL BE ELECTRO-GALVANIZED. CONDUITS SHALL BE AS <br />MANUFACTURED BY REPUBLIC, PITTSBURGH STANDARD, WHEATLAND, TRIANGLE, ALLIED, OR <br />YOUNGSTOWN. <br />TYPE "MC" CABLE IS ACCEPTABLE FOR BRANCH CIRCUIT WIRING. TYPE "MC" CABLE IS ACCEPTABLE <br />TO MAKE FINAL CONNECTIONS FROM SOURCE JUNCTION BOXES TO LIGHT FIXTURES, MAXIMUM <br />LENGTH 6'-0" (DO NOT DAISY CHAIN). <br />PROVIDE END BUSHINGS ON ALL CONDUITS. PROVIDE PULL STRINGS IN ALL EMPTY RACEWAYS. <br />PULL STRINGS SHALL BE NYLON AND SHALL BE IMPERVIOUS TO MOISTURE. PULL STRINGS SHALL <br />HAVE A TENSILE STRENGTH NOT LESS THAN 200 LBS. <br />CONDUIT ABOVE GRADE SHALL BE EMT (INTERIOR ONLY), IMC, OR GALVANIZED. <br />CONDUIT BELOW GRADE SHALL BE RIGID GALVANIZED (HEAVY WALL), IMC, OR PVC (SCHEDULE 40). <br />SEALANT. PROVIDE A CLOSED CELL SILICONE FOAM SEALANT RATED TO PROVIDE A RATING <br />EQUAL TO THE WALL, CEILING, OR FLOOR ASSEMBLY RATING. PROVIDE SEALS FOR THE EXTERIOR <br />OF CONDUIT PENETRATIONS CONSISTING OF A CAST -IN -PLACE SLEEVE WITH A COMPRESSIBLE <br />RUBBER GASKET BETWEEN THE CONDUIT AND THE SLEEVE. PROVIDE SEALS FOR THE INTERIOR <br />OF THE CONDUIT PENETRATIONS CONSISTING OF GLAND TYPE SEALING BUSHING OR CLOSED CELL <br />SILICONE FOAM. PROVIDE DUCT SEAL INSIDE AN APPROPRIATE SEAL -OFF FITTING TO SEAL THE <br />INTERIOR OF THE CONDUIT SYSTEM FROM WATER SEEPAGE OR HAZARDOUS GASES. <br />D. ALL COUPLINGS AND CONNECTORS FOR EMT SHALL BE OF COMPRESSION TYPE. <br />E. OUTLET BOXES: <br />SHALL BE STANDARD TYPE, WITH KNOCKOUTS, MADE OF HOT DIPPED GALVANIZED STEEL AS <br />MANUFACTURED BY STEEL CITY, RACO OR APPLETON. <br />CEILING OUTLET BOXES SHALL BE 4-INCH OCTAGON 1-1/2 INCH DEEP OR LARGER WHEN <br />REQUIRED DUE FOR NUMBER OF CONDUCTORS OR CONDUIT ENTRY. <br />BOXES SHALL BE PROVIDED WITH APPROVED 3/8 INCH FIXTURE STUDS WHERE REQUIRED. <br />PROVIDE JUNCTION OR PULL BOXES WHERE SHOWN ON THE DRAWINGS AS REQUIRED TO <br />FACILITATE INSTALLING CONDUCTORS. SUCH BOXES SHALL BE "CODE" SIZED. ALL JUNCTION <br />BOXES SHALL BE ACCESSIBLE. <br />F. WIRE AND CABLE 600 VOLT: <br />GENERAL: CONDUCTORS SHALL HAVE CURRENT CARRYING CAPACITIES AS PER N.E.C. AND WITH <br />600 VOLT INSULATION, J12 MINIMUM EXCEPT FOR CONTROLS, AND FIXTURE WIRE. CONDUCTORS <br />SHALL BE COPPER. <br />GENERAL USE: #12 AND #10 SHALL BE SOLID, INSULATION TYPE THHN OR THWN. <br />FEEDERS AND GENERAL USE: #8 AND LARGER AND ALL MOTORS CONDUCTORS SHALL BE <br />STRANDED TYPE XHHW OR THWN. <br />COLOR -CODING FOR CONDUCTORS SHALL BE CONSISTENT THROUGHOUT ENTIRE LENGTH. PHASE <br />TAPE COLOR CODING IS NOT ACCEPTABLE. APPLIES TO FEEDERS AND BRANCH CIRCUIT <br />CONDUCTORS OF ALL SIZES. COLOR CODING SHALL BE BLACK, RED, AND BLUE (WHITE NEUTRAL) <br />FOR 120/208 VOLT 3-PHASE WIRING, AND BROWN, ORANGE, AND YELLOW (GREY NEUTRAL) FOR <br />277/480 VOLT 3-PHASE WIRING. GROUND CONDUCTORS SHALL BE GREEN. <br />G. BASIC DEVICES: <br />PROVIDE IVORY COLORED DEVICES WHERE AVAILABLE, UNLESS OTHERWISE NOTED. <br />20-AMP, 120/277 VAC, HEAVY DUTY, QUIET TYPE, SPECIFICATION GRADE: <br />1. SINGLE POLE TOGGLE: PASS AND SEYMOUR NO. CS20AC1W. <br />2. THREE-WAY TOGGLE: PASS AND SEYMOUR NO. CS20AC3W. <br />RECEPTACLES: <br />SPECIFICATION GRADE 20A, 125V, 2P, 3W GROUNDED, MOUNTED 18"AFF TO THE CENTERUNE <br />UNLESS NOTED OTHERWISE. COLOR SHALL MATCH TOGGLE SWITCHES. <br />1. 20A DUPLX, 3W, 125V, NEMA 5-20R LEVITON #5362 <br />PROVIDE CAST ALLOY OR STAMPED METAL PLATES ON EXPOSED SWITCHES AND RECEPTACLES. <br />INSTALL DEVICE PLATES IN FULL CONTACT WITH WALL SURFACE. PLATES SHALL NOT PROJECT <br />OUT FROM THE WALL. <br />INSTALL DEVICE PLATES IN FULL CONTACT WITH SURFACE MOUNTED BOX. PLATES SHALL NOT <br />PROJECT OUT FROM THE EDGE OF THE BOX. <br />ALL DEVICE PLATES FOR RECEPTACLES AND SWITCHES SHALL BE LABELED. SHOW PANEL <br />DESIGNATION AND BRANCH CIRCUIT SERVING EACH RECEPTACLE. USE ENGRAVED PLATES UNLESS <br />OTHERWISE NOTED. <br />ACCEPTABLE MANUFACTURERS: PASS do SEYMOUR, G.E., LEVITON <br />H. SAFETY SWITCHES: <br />GENERAL: ALL DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE, UNLESS SPECIFICALLY NOTED <br />OTHERWISE. SWITCHES SHALL BE FUSIBLE OR NON -FUSIBLE AND SIZED AS NOTED ON THE DRAWINGS. <br />SWITCHES SHALL BE 240 VOLT RATED ON SYSTEMS UP TO AND INCLUDING 120/24OV. ALL <br />SWITCHES SERVING MOTOR LOADS SHALL BE HORSEPOWER RATED. <br />PROVIDE SWITCHES WITH AN EXTERNALLY OPERATED HANDLE; QUICK MAKE QUICK BREAK MECHANISM; <br />THE HANDLE SHALL BE INTERLOCKED WITH THE SWITCH COVER BY MEANS OF A DEFEATABLE <br />INTERLOCK DEVICE. THE SWITCH SHALL BE LOCKABLE IN THE "OFF" POSITION WITH A PADLOCK. <br />I. LIGHTING FIXTURES: <br />LIGHTING FIXTURES SHALL BE FURNISHED AS SHOWN IN FIXTURE SCHEDULE. IT SHALL <br />SPECIFICALLY BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY EXACT TYPE OF CEILING <br />AND RECESSING DEPTH OF ALL RECESSED FIXTURES AND TO FURNISH THE MOUNTING TRIMS AND <br />ACCESSORIES OF THE SPECIFIED AND/OR APPROVED FIXTURES FOR THE CEILING TO BE INSTALLED. <br />FIXTURES SHALL BE SUPPORTED INDEPENDENTLY OF CEILING SYSTEMS. <br />FLUORESCENT LAMPS SHALL BE T8, 28W, 3500 DEGREES K, 85 CRI MINIMUM. <br />LAMP DESIGN SELECTION: OSRAM-SYLVANIA, GE, OR PHILLIPS. <br />J. GROUNDING: <br />GROUNDING SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND <br />LOCAL CODES AND REQUIREMENTS. <br />FEEDERS AND BRANCH CIRCUITS SHALL HAVE INSTALLED IN THE SAME RACEWAY AS THE <br />CIRCUIT CONDUCTORS, AN INSULATED COPPER GROUNDING CONDUCTOR SIZED IN ACCORDANCE <br />WITH NEC. <br />DESCRIPTION OF SYSTEM: IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR <br />FRAMES, PANEL BOARDS, ETC.) SHALL BE BONDED TOGETHER WITH A GREEN INSULATED OR <br />BARE COPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF <br />ARTICLE 250 OF THE N.E.C. EQUIPMENT GROUNDING CONDUCTORS THROUGH THE RACEWAY <br />SYSTEM SHALL BE CONTINUOUS FROM MAIN SWITCH GROUND BUS TO PANEL GROUND BAR OF <br />EACH PANEL BOARD, AND FROM PANEL GROUNDING BAR OF EACH PANEL BOARD TO BRANCH <br />CIRCUIT EQUIPMENT AND DEVICES. <br />ADDITIONAL SENSORS <br />WIRED IN SERIES IF <br />REQUIRED <br />MMAAXIIMUM NUMBER OF SENSORS PER POWER PACK <br />DEPENDS ON THE MODEL OF SENSOR. SEE THE <br />PRODUCT DATA SHEET TO DETERMINE THE SPECIFIC <br />CURRENT CONSUMPTION OF EACH SENSOR. <br />OCCUPANCY SENSOR DETAIL (LOW VOLTAGE <br />N.T.S. <br />LOCAL <br />OFF <br />A ', 1 <br />Line <br />Ground <br />Any Line <br />Neutral <br />Voltage <br />Line <br />Occupancy <br />Load <br />Sensor Using <br />Terminals <br />OCCUPANCY SENSOR DETAIL (LINE VOLTAGE <br />N.T.S. <br />PROVIDE A WALL MOUNTED DUAL TECHNOLOGY OCCUPANSCY SENSOR, MANUAL ON, IN EACH <br />OFFICE TO CONTROL THE LIGHTS AUTOMATIC OFF WITHIN 30 MINUTES OF THE LAST OCCUPANT <br />LEAVING THE SPACE: EQUAL TO WATT STOPPER DSW-200-W. <br />CEILING OCCUPANCY SENSOR WHERE NOTED SHALL BE DUAL TECHNOLOGY TYPE EQUAL TO WATT <br />STOPPER DT-300 SERIES TO CONTROL THE LIGHTS AUTOMATIC OFF WITHIN 30 MINUTES OF THE <br />LAST OCCUPANT LEAVING THE SPACE. <br />PROVIDE A 20 AMP RELAY ABOVE THE OCCUPANCY SENSOR SWITCH OR AT THE CEILING <br />OCCUPANCY SENSOR, CONTROLLED WITH THE LIGHTS VIA THE OCCUPANCY SENSOR TO <br />AUTOMATICCALY TURN OFF 50% OF THE RECEPTACLES WITHIN THE SPACE VIA N.O. CONTACTS. <br />VERIFY WITH OWNER WHICH RECEPTACLES SHALL BE CONTROLLED WITH THE OCCUPANCY <br />SENSOR. RECEPTACLE POWER SHALL BE CONTROLLED OFF WITHIN 30 MINUTES OF ALL <br />OCCUPANTS LEAVING THE SPACE IN ACCORDANCE WITH FBC ENERGY CODE C405.7 AND ASHRAE <br />90.1 SECTION 8.4.2 (b). <br />TEST ALL WALL MOUNTED AND CEILING MOUNTED OCCUPANCY SENSORS IN ACCORDANCE WITH <br />FBC ENERGY CODE C408.3 / C408.3.1 <br />ELECTRICAL SYMBOLS <br />LEGEND <br />LINEAR FLUORESCENT LIGHT FIXTURE - RECESSED <br />,z 3P/60A 3R <br />COMBINATION STARTER/DISCONNECT SWITCH, <br />NORMAL POWER (NL - Night Light) <br />NEMA 0 <br />SHOWN SIZE 3-POLE, 60 AMP, NEMA 0 RATED <br />3R = NEMA 3R ENCLOSURE <br />LINEAR FLUORESCENT LIGHT FIXTURE - RECESSED <br />P A 3R <br />DISCONNECT SWITCH, SHOWN SIZE - 2-POLE, <br />HALF SHADED FOR EMERGENCY LIGHTING CIRCUIT <br />F:50A <br />60 AMP, FUSED AT 50 AMP. NF = NON -FUSED <br />ON GENERATOR <br />3R = NEMA 3R ENCLOSURE <br />p <br />DOWN LIGHT FIXTURE <br />PANEL BOARD - FLUSH MOUNT, 240V AC <br />®f <br />EXIT LIGHT - SINGLE FACE W/ <br />PANEL BOARD - SURFACE MOUNT, ABOVE 240V AC <br />DIRECTIONAL ARROW <br />e <br />EXIT LIGHT - DOUBLE FACE <br />MOTOR CONNECTION. HP DENOTES HORSEPOWER RATING <br />$ <br />SINGLE POLE TOGGLE SWITCH <br />(LOWER CASE LETTER DENOTES FIXTURE CONTROLLED) <br />I-QF <br />FIRE ALARM STROBE ONLY DEVICE <br />WITH MINIMUM 75CD RATING (LION) - 80" AFF TO <br />$3 <br />THREE-WAY TOGGLE SWITCH <br />BOTTOM OF DEVICE <br />$os <br />WALL SWITCH OCCUPANCY SENSOR <br />FIRE ALARM COMBINATION AUDIBLE/STROBE DEVICE <br />WATT STOPPER JDW-100 (DUAL TECH./SINGLE RELAY) <br />WITH MINIMUM 75CD RATING (LION) - 80" AFF TO <br />BOTTOM OF DEVICE <br />$o <br />DIMMER SWITCH <br />® <br />SMOKE DETECTOR - CEILING MOUNTED <br />CEILING MOUNTED OCCUPANCY SENSOR <br />WITH POWER PACK <br />HOMERUN TO PANEL, NUMBER OF ARROWS <br />DUPLEX RECEPTACLE <br />INDICATE NUMBER CIRCUITS IN CONDUIT, <br />DEDICATED NEUTRAL SHALL BE PROVIDED <br />ggfi <br />DUPLEX RECEPTACLE GROUND FAULT CIRCUIT INTERRUPTER <br />IF MORE THAN ONE CIRCUIT. <br />DUPLEX RECEPTACLE MOUNTED 48", UNLESS NOTED <br />WIRE IN CONDUIT CONCEALED, #12AWG SIZEWIRE IN 3/4" CONDUIT MINIMUM, UNLESS <br />OTHERWISE (TYPICAL FOR ALL RECEPTACLES) <br />NOTED OTHERWISE <br />QUADRUPLEX RECEPTACLE <br />CONDUIT EXPOSED <br />GFI-TYPE DUPLEX RECEPTACLE <br />WP DENOTES WEATHERPROOF COVER <br />�' -'' <br />WIRE IN CONDUIT CONCEALED BELOW SLAB <br />SPECIAL PURPOSE RECEPTACLE <br />OR GRADE <br />® <br />CEILING MOUNTED DUPLEX RECEPTACLE <br />EMPTY CONDUIT <br />TELE/DATA (BOX AND RACEWAY ONLY) <br />FLEXIBLE CONDUIT <br />OJ <br />JUNCTION BOX <br />CONDUIT TURNING UP <br />TELE OUTLET (BOX AND RACEWAY ONLY) <br />I-QTV <br />TV OUTLET (RACEWAY ONLY) <br />CONDUIT TURNING DOWN <br />(EX) <br />EXISTING TO REMAIN <br />-1 <br />CONDUIT STUB <br />(LION) <br />UNLESS OTHERWISE NOTED <br />3/4" PLYWOOD TELEPHONE BACKBOARD <br />ALL SYMBOLS SHOWN MAY NOT BE USED. <br />EXISTING PANEL A FLUSH MOUNTED, NEMA 1 <br />120016 VOLT, 3 PHASE, 4 WIRE FIRM VERIFY AXC RATING, MATCH NEW DEVICES <br />225A MLO VIA20DA MAIN CKT SKR PROVIDii WITH EQUIPMENT GROUND BAR <br />CKT <br />OESCRIPTION <br />SREAICER <br />VOLT <br />KVA <br />LOAD <br />CKT <br />DESCRIPTION <br />SPEAKER <br />VOLT <br />KVA <br />LOAD <br />TRIP <br />I POLE1 <br />TRIP <br />POLE <br />1 <br />EXISTING AHU NORTH <br />100 <br />a <br />20a <br />10.5 <br />a <br />2 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />1.1 <br />1 <br />3 <br />2A <br />4 <br />4 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />0.0 <br />1 <br />6 <br />a <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />1.6 <br />1 <br />7 <br />EXISTING EMIRGFJNCY LIGHTS <br />20 <br />1 <br />120 <br />0.8 <br />1 <br />a <br />EXBTMIG LIGHTS <br />20 <br />1 <br />120 <br />0.7 <br />1 <br />a <br />E EST" SMOKE DETIECTORS <br />20 <br />1 <br />In <br />0.a <br />7 <br />10 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />1.1 <br />1 <br />1, <br />EXIST" LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />12 <br />EXISTING LIGHTS <br />2D <br />1 <br />120 <br />1.1 <br />1 <br />18 <br />OWING ROOF WPAGFI R1ECEPTCLE <br />20 <br />1 <br />120 <br />0.2 <br />8 <br />14 <br />EXISTING RECEPTACLES <br />20 <br />1 <br />120 <br />0.7 <br />5 <br />to <br />EXISTING RECEPTACLES <br />20 <br />1 <br />170 <br />1.1 <br />a <br />Is <br />EXISTING FRONT SIGN <br />20 <br />1 <br />120 <br />0.7 <br />1 <br />17 <br />EXISTING CIRCUT <br />20 <br />1 <br />120 <br />1.0 <br />a <br />1s <br />EXCISTING LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />1E <br />OWING CIRCUT <br />20 <br />1 <br />130 <br />1.0 <br />a <br />20 <br />EXISTING CIROLJT <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />21 <br />EXISTING RECEPTACLES <br />20 <br />1 <br />120 <br />1.0 <br />a <br />29 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />as <br />EXSTING LIGHTS <br />20 <br />1 <br />120 <br />0.0 <br />1 <br />24 <br />OWING LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />M <br />EXIST" LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />2S <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />0.9 <br />1 <br />27 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />20 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />0.9 <br />1 <br />20 <br />MUTING L*FITS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />30 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />0.9 <br />1 <br />31 <br />EXISTING LIGHTS <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />82 <br />DEDICATED CO'UNM OUTLET (3) <br />20 <br />1 <br />120 <br />0.8 <br />7 <br />33 <br />FRONT RECEPTACLES (8) <br />20 <br />1 <br />120 <br />ILA <br />5 <br />34 <br />DEDICATED COUNTER OURET (3) <br />20 <br />1 <br />120 <br />0.8 <br />7 <br />sa <br />SAOK RECL9rTA4CLES (3) <br />20 <br />1 <br />120 <br />4A <br />a <br />38 <br />DEDICATED COUNTER OUTLET (3) <br />20 <br />1 <br />120 <br />0.6 <br />7 <br />37 <br />OFFICE RECEPTACLES (3) <br />20 <br />1 <br />120 <br />0.2 <br />a <br />38 <br />ISFRIGERATOR (3) <br />20 <br />1 <br />120 <br />0.0 <br />7 <br />M <br />OFFICE RECEPTACLES (3) <br />20 <br />1 <br />120 <br />a 2 <br />a <br />40 <br />RANGE M <br />s0 <br />2 <br />2M <br />6.0 <br />7 <br />41 <br />OFFICE RECEPTACLES M <br />20 <br />1 <br />120 <br />0.2 <br />a <br />1 42 <br />--- <br />SCOPE OF WORK <br />1. ADD NEW LIGHT FIXTURES PER FLOOR PLAN - LIGHTING. PROVIDE LIGHTING CONTROLS AS <br />INDICATED ON DRAWINGS. REFER TO ELECTRICAL SPECIFICATIONS, LIGHTING FIXTURE SCHEDULE, <br />LIGHTING NOTES, AND DETAILS IF APPLICABLE TO THIS PROJECT. <br />2. ADD NEW POWER AND SYSTEMS DEVICES PER FLOOR PLAN - POWER AND SYSTEMS. REFER TO <br />ELECTRICAL SPECIFICATIONS, POWER AND SYSTEMS NOTES, PANEL SCHEDULES, AND POWER <br />RISER DIAGRAMS IF APPLICABLE M THIS PROJECT. <br />CODES AND STANDARDS <br />FLORIDA BUILDING CODE, 6TH EDITION (2017) <br />THE FLORIDA FIRE PREVENTION CODE 2010 EDITION <br />NFPA 101: FLORIDA EDITION 2010 <br />NFPA 70: NATIONAL ELECTRICAL CODE 2011 <br />WMINSPAWLI FLUSH 1 <br />IZD= VOLT, a PHASE. 4 WIRE FIELD VERIFY Ale RATING, MATCH NEW DEVICES <br />a26A1 MLO VIA 200A MAIN CNT GM PROVIDE WITH EQUIPMENT GROUND BAR <br />CICT <br />DESCRIPTION <br />BREAKER <br />VOLT <br />KvA.cow <br />LOAD <br />CKT <br />DESORPTION <br />BREAKER <br />VOLT <br />KVA <br />LOAD <br />CO <br />TRIP <br />POLE <br />TRIP <br />POLE <br />1 <br />EXSTINO AHU MOUTH <br />100 <br />3 <br />208 <br />10.6 <br />2 <br />2 <br />NG WATER HEATER (FIELD VERIFY30 <br />2 <br />4.5 <br />7 <br />3 <br />2A <br />4 <br />4 <br />--� <br />a <br />a <br />EXISTING LIGHTS <br />ENQ <br />20 <br />1 <br />120 <br />1.0 <br />1 <br />7 <br />EXISTING LIGHTS <br />2D <br />1 <br />120 <br />0.8 <br />1 <br />8EXISTING <br />RECEPTACLES <br />20 <br />1 <br />120 <br />0 7 <br />a <br />a <br />EXISTING ROOF WPIGFI RE�TCLE <br />20 <br />1 <br />IN <br />0.2 <br />5 <br />10 <br />WATER HEATER (FIELD VERIFV <br />20 <br />1 <br />120 <br />1.5 <br />7 <br />11 <br />EXOSTSNG FRONT awl <br />2D <br />1 <br />120 <br />1.2 <br />1 <br />12 <br />EXIS I NO DRINK FOUNTAIN <br />20 <br />1 <br />12D <br />0.7 <br />7 <br />13 <br />EXISTING FRONT SIGN <br />M <br />1 <br />120 <br />1.2 <br />1 <br />14 <br />EXISTING GROUT <br />20 <br />1 <br />120 <br />0.7 <br />a <br />1a <br />EXISTING GROUT <br />24 <br />1 <br />IN <br />0.S <br />a <br />1a <br />EXISTING GROUT <br />2D <br />1 <br />120 <br />0.7 <br />a <br />17 <br />EXISTING CIRCUT <br />20 <br />1 <br />in <br />0.9 <br />a <br />18 <br />rxanNO CRCUT <br />20 <br />1 <br />IN <br />1.0 <br />a <br />12 <br />EXISTING CIRCUT <br />20 <br />1 <br />10 <br />0.0 <br />a <br />0 <br />EXISTING GROUT <br />20 <br />1 <br />IN <br />1.0 <br />a <br />21 <br />EXISTING CIRCUT <br />20 <br />1 <br />120 <br />0.1 <br />a <br />22 <br />EXISTING GROUT <br />20 <br />1 <br />IN <br />1.0 <br />a <br />23 <br />EXISTING CIRCUT <br />20 <br />1 <br />IN <br />0.0 <br />a <br />24 <br />EXISTING GROUT <br />20 <br />1 <br />IN <br />1.0 <br />a <br />as <br />EXISTING CIRCUT <br />20 <br />1 <br />In <br />0.9 <br />a <br />2a <br />l70STING GROUT <br />20 <br />1 <br />IN <br />0.7 <br />a <br />27 <br />EXISTING GROUT <br />20 <br />1 <br />12D <br />0.9 <br />a <br />26 <br />EXISTING GROUT <br />20 <br />1 <br />IN <br />1.1 <br />a <br />a <br />EXISTING OIROUT <br />20 <br />1 <br />1N <br />0.0 <br />a <br />so <br />EXISTING GROUT <br />20 <br />1 <br />120 <br />1.1 <br />a <br />31 <br />EXISTING CIRCUT <br />20 <br />1 <br />120 <br />0.0 <br />5 <br />32 <br />EXISTING GROUT <br />2D <br />I <br />12D <br />IA <br />a <br />M <br />OUTWGALARM <br />20 <br />1 <br />In <br />0.6 <br />7 <br />34 <br />SPACE <br />1 <br />36 <br />DRINC FOUNTAIN (3) <br />N <br />1 <br />120 <br />ILI <br />7 <br />38 <br />SPACE <br />1 <br />37 <br />SPACE <br />1 <br />36 <br />SPACE <br />1 <br />30 <br />SPACE <br />1 <br />40 <br />SPACE <br />1 <br />41 <br />SPACE <br />1 <br />42 <br />SPAN <br />1 <br />LOAD CODES <br />CONNECTS <br />DEMAND <br />DEMAND LOAD <br />LOAD CODES <br />CONNECTED <br />DEMAND <br />DEMAND LCAO <br />LOM (KVA) <br />FACTOR <br />LOAD (KVA) <br />FACTOR <br />1. LIGHTING <br />20 <br />1.20 <br />26.4 <br />1. LIGHTING <br />4 <br />1.26 <br />a.0 <br />2. HEAT <br />11 <br />1.00 <br />10.5 <br />2. HEAT <br />I 1 <br />1.00 <br />10.5 <br />3. AN COMN11ONING <br />0 <br />1.00 <br />0.0 <br />3. AR CONDITIONING <br />0 <br />I.W <br />0.0 <br />4. MOTORS <br />a <br />26% LRGST MTR <br />3.0 <br />4. MOTO" <br />2 <br />26% LRUT MTR <br />s.D <br />a. RECWTACLES <br />8 <br />NEC 21C.44 <br />8.4 <br />a. REcEPTAICM <br />18 <br />NEO= 44 <br />142 <br />S. MISC. CONTINUOUS LOADS <br />0 <br />1.6 <br />0.0 <br />8. MIS . CONTINUOUS LOADS <br />0 <br />1.1E <br />0.0 <br />7. MSC. NONCONTUJOUG ROADS <br />12 <br />1.00 <br />11.8 <br />7. MISC. NON -CONTINUOUS LOADS <br />6 <br />1.00 <br />80 <br />61 a7., <br />3.0 LESS SMALLEST OF HEAT/AC <br />NOTES <br />(1) ALL OMIT WALSLIS AND LOADS ARE OEM Ma UNLSN OTHERWISE NtXM $4.1 TOTAL DEMAND LOAD <br />P) INNIT!N8 CIRWIT aREANNIL L411aTM16 LOAD MACX= DURMIB DEMOLITION (FXLD VIM M. <br />ii) NEW ORWIT IREAItSI AND LOAD. VOLTAGE 208 <br />, <br />PHASE 3 <br />150 AMPS <br />43 <br />N= <br />(1) ALL CKIJIT IRiAI M AND LOADS ARE OWN11 UNLESS OTHERWM NCTI M <br />(2) EXI41M CIRCUI T IREAERI. WTIM LOAD Rl ADM DURR10 DEMOLITION (N®.0 VERIPIX. <br />(3) NEW CIRCUIT SRLM= AND LOAD. <br />40.7 <br />&0 LESS SMALLEST OF MEATAC <br />.f" <br />27.7 TOTAL DEMAND LOAD <br />VOLTAGE US <br />PHASE 3 <br />105 AMPS <br />L. <br />a) <br />N <br />a� <br />ov <br />a� s <br />(n U <br />o�p <br />Lam+ <br />O <br />Go <br />a <br />r-1 <br />°O <br />i <br />V <br />a <br />C <br />sq <br />N <br />�M <br />cp <br />Tom, <br />TEQ <br />Cq <br />IN <br />U <br />ice4 <br />Ld <br />O <br />U <br />cD <br />z <br />0 <br />m <br />� z <br />� o <br />3 0 <br />z <br />CL 3 <br />o a <br />U g <br />Ln Lr) <br />a <br />W O <br />�_: M <br />0 <br />LLT <br />cn <br />o z <br />J o <br />o w <br />Y (n <br />0 0 <br />w pLLJ <br />L <br />0 <br />>~ <br />ad <br />V <br />4� <br />0 <br />Cc) <br />.� <br />0 <br />0 <br />E-4 <br />70 <br />go <br />>G•r <br />� <br />Dy <br />>~( <br />0 <br />r <br />m <br />(L <br />e-I <br />A, <br />ELECTRICAL NOTES <br />Scale: As Noted <br />Revisions: <br />Date: <br />12-29-17 <br />Drawn by. <br />CTK <br />Checked by. <br />CTK <br />E � 2 <br />Sheet No. of <br />