TURNING VANES
<br />(TYPICAL)
<br />B CFM � I .�'1� I - I � C CFM
<br />MAX. 200 TRANSITION 0.25 D (4" MIN. PER SMACNA)
<br />H.
<br />RECTANGULAR DUCT
<br />N -�
<br />BRANCH DUCT
<br />o
<br />o
<br />- BRANCH DUCT
<br />a
<br />a
<br />-VOLUME DAMPER
<br />U-
<br />U-
<br />Y
<br />SPLITTER DAMPER
<br />CONTROL ROD
<br />(TYPICAL)
<br />Z
<br />(TYPICAL)
<br />CONICAL FITTING WITH
<br />LOCKING TYPE VOLUME
<br />A (CFM)
<br />MAIN DUCT
<br />DAMPER.
<br />X
<br />TO SIZE SPLITTER:
<br />FLEX DUCT OR ROUND SHEET METAL
<br />AM
<br />DUCT. FLEX DUCT MAX. 8'-0" LONG,
<br />Y = (B/A) (X)
<br />USE CLAMP TO ATTACH FLEX DUCTS
<br />Z = X-Y
<br />AND SEAL. SUPPORT DUCT EVERY
<br />NOTE: FOR RETURN AIR FLOW,
<br />DEPTH REMAINS
<br />FOUR FEET FROM STRUCTURE
<br />DELETE SPLITTER DAMPER
<br />CONSTANT
<br />-HANGER
<br />SCREWS
<br />Splitter Detail
<br />SCALE: NONE
<br />FASTENER
<br />-HANGER
<br />STRAP
<br />2" -MIN. BAND OF SAME SIZE j
<br />AS HANGER STRAP ,
<br />NOTE:
<br />HANGER STRAP SIZE PER SMACNA.
<br />2 Rectangular/Round Duct Hanger Detail
<br />SCALE: NONE
<br />MOUNT CAP LEVEL -
<br />O.C.
<br />FLASHING BY ROOFER
<br />1 1/2" EXTERNAL -
<br />INSULATION
<br />SEAL WATERTIGHT
<br />BIRD SCREEN
<br />CAULKING BEAD OR GASKET FULL
<br />PERIMETER OF CURB BY HVAC.
<br />TREATED WOOD NAILER
<br />13-1/2' PREFABRICATED
<br />CURB FURNISHED BY HVAC
<br />INSTALLED BY GENERAL
<br />CONTRACTOR
<br />- ROOF
<br />SUPPORT ANGLES AS
<br />REQUIRED BY GENERAL
<br />CONTRACTOR
<br />2"
<br />3 Gravity Roof Vent Detail
<br />SCALE: NONE
<br />4'-0" MAXIML
<br />MAXIMUM SAG 1/2" PER FOOT
<br />OF SUPPORT SPACING.
<br />FLEXIBLE DUCT
<br />NOTES:
<br />1. DUCT SHOULD EXTEND STRAIGHT FOR
<br />SEVERAL INCHES FROM A CONNECTION
<br />BEFORE BENDING.
<br />2. SUPPORT SYSTEM MUST NOT DAMAGE DUCT
<br />OR CAUSE OUT OF ROUND SHAPE.
<br />4 Flex Duct Support Detail
<br />SCALE: NONE
<br />METAL STRAP
<br />1-112" MINIMUM
<br />- SUPPLY DUCT SPIN -IN FITTING INSULATED ROUND
<br />WITH DAMPER FLEXIBLE DUCT
<br />(MAX. V-0" LONG)
<br />j SIZE TO MATCH
<br />DIFFUSER NECK.
<br />ROUND METAL DUCT INSULATION
<br />(EXTERNAL INSULATION)
<br />CEILING - -CEILING DIFFUSER
<br />5 Ceiling Diffuser Runout Detail
<br />SCALE: NONE
<br />6 Branch Duct Detail
<br />SCALE: NONE
<br />A 12"O
<br />1TO
<br />EXISTING 5
<br />TON RTU TO
<br />REMAIN.
<br />12"0
<br />DUCT WORK LOCATIONS SHOWN
<br />ARE DIAGRAMMATIC. EXACT
<br />LOCATIONS OF DUCT WORK
<br />SHALL BE COORDINATED WITH
<br />ALL OTHER TRADES AND SHALL
<br />MINIMIZE THE TOTAL AMOUNT
<br />OF DUCTING USED.
<br />(TYP OF 2)
<br />7 Mechanical Floor Plan
<br />Z SCALE: 1/8" =1'-W
<br />MECHANICAL GENERAL NOTES
<br />1. CONTRACTOR TO VISIT SITE AND VERIFY ALL CLEARANCES BEFORE FABRICATION OF DUCTWORK AND PROVIDE ADDITIONAL OFFSET AND/OR
<br />16. VERIFY VOLTAGE WITH ELECTRICAL CONTRACTOR BEFORE ORDERING EQUIPMENT.
<br />CHANGES IN DUCT SIZES TO MEET FIELD CONDITIONS AND COORDINATE WITH ELECTRICAL, PLUMBING AND FIRE PROTECTION
<br />SUBCONTRACTOR BEFORE ANY CONSTRUCTION WORK.
<br />17. PROVIDE A TRAP IN ALL CONDENSATE PIPING LOCATED AT AIR HANDLING UNITS. SLOPE CONDENSATE LINES 118" PER FOOT. CONDENSATE
<br />LINES SHALL BE PVC SCH. 40. ALL CONDENSATE DRAIN PIPING SHALL BE PROPERLY SUPPORTED. SEE "CONDENSATE DRAIN TRAP" DETAIL.
<br />2. SUPPLY, RETURN AND OUTSIDE AIR DUCTWORK SHALL BE EXTERNALLY INSULATED SHEET METAL CONSTRUCTION IN ACCORDANCE WITH
<br />LATEST SMACNA STANDARDS. INSULATION SHALL HAVE VAPOR BARRIER AND AN INSTALLED MINIMUM THERMAL RESISTANCE (R) VALUE OF 6.0.
<br />18. ALL MECHANICAL WORK SHALL MEET ALL THE REQUIREMENTS OF THE 2007 FLORIDA BUILDING CODE, MECHANICAL AND 2009 SUPPLEMENT.
<br />ALL EXHAUST DUCTWORK SHALL BE UNINSULATED SHEET METAL CONSTRUCTION IN ACCORDANCE WITH LATEST SMACNA STANDARDS. ALL
<br />JOINTS SHALL BE SECURELY TAPED WITH 3" WIDE GLASS FABRIC TAPE WITH FOSTER 30/35 MASTIC OR EQUAL.
<br />19. GUARANTEE; FOR ONE YEAR AFTER DATE OF ACCEPTANCE BY THE OWNER, ALL EQUIPMENT, MATERIALS AND WORKMANSHIP TO BE FREE
<br />FROM DEFECT.
<br />3. DUCT SHALL BE SECURELY SUPPORTED, HUNG OR SUSPENDED IN ACCORDANCE WITH THE LATEST SMACNA EDITION AND SECTION 603 OF THE
<br />2007 FLORIDA BUILDING CODE, MECHANICAL WITH 2O09 SUPPLEMENT.
<br />20. DO NOT CUT STRUCTURAL MEMBERS WITHOUT PRIOR WRITTEN APPROVAL OF THE STRUCTURAL ENGINEER OR ARCHITECT. ARRANGE FOR
<br />REPAIRS REQUIRED TO RESTORE OTHER WORK, BECAUSE OF DAMAGE CAUSED AS A RESULT OF MECHANICAL INSTALLATIONS.
<br />4. ROOFTOP UNIT OUTSIDE AIR INTAKE SHALL MAINTAIN A MINIMUM OF 10'-0" FROM ANY EXHAUST OR SANITARY VENT THROUGH ROOF PIPING.
<br />ALL TRANSFER DUCTWORK LEADING TO REST ROOMS SHALL HAVE A ZERO LEAKAGE BACK DRAFT DAMPER AS SHOWN ON MECHANICAL
<br />21. FLEXIBLE AND RIGID ROUND DUCT TAKE -OFFS FOR DIFFUSERS SHALL BE THE SAME SIZE AS DIFFUSER NECK. MAXIMUM FLEXIBLE DUCT
<br />DRAWINGS.
<br />LENGTH SHALL BE 12'-0". FLEXIBLE DUCT SHALL BE THERMAFLEX TYPE M-KC OR EQUAL.FLEXABLE DUCT SHALL BE INSULATED FIBERGLASS,
<br />R-6, CLASS 1, UL181 LISTED AND COMPLY WITH NFPA 90AAND NFPA90B.
<br />5. PROVIDE ALL MECHANICAL EQUIPMENT WITH MANUFACTURER'S RECOMMENDED SERVICE AREA CLEARANCES.
<br />22. ALL WALL MOUNTED THERMOSTATS SHALL BE INSTALLED AT AN ELEVATION OF 54" ABOVE FINISHED FLOOR TO THE TOP UNLESS
<br />6. ALL ROOF TOP UNITS SHALL BE REINFORCED TO WITHSTAND LOCAL WIND LOAD DESIGN. SEE STRUCTURAL DRAWING(S) FOR DETAIL(S)
<br />OTHERWISE NOTED ON DRAWINGS. LOCATION OF THE WALL MOUNTED THERMOSTAT SHALL BE COORDINATED WITH OTHER TRADES FOR A
<br />/CONSULT WITH BUILDING STRUCTURAL ENGINEER.
<br />NEAT APPEARANCE. FINAL LOCATION OF THERMOSTAT SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER OR HIS REPRESENTATIVE
<br />IN THE FIELD.
<br />7. DUCT SMOKE DETECTORS SHALL BE FURNISHED BY THE FIRE ALARM CONTRACTOR, INSTALLED IN DUCT BY THE MECHANICAL CONTRACTOR
<br />AND WIRED BY THE FIRE ALARM CONTRACTOR. SMOKE DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE
<br />23. ALL UNITS SHALL BE BALANCED TO WITHIN 10 PERCENT OF THE DESIGN AIR QUANTITY. BALANCE DIFFUSERS AND REGISTERS TO WITHIN 10
<br />ALARM CODE; NFPA 90A, STANDARD FOR INSTALLATION OF AIR-CONDITIONING AND VENTILATING SYSTEMS, 2007 FLORIDA BUILDING CODE,
<br />PERCENT OF QUANTITIES SHOWN ON DRAWINGS.
<br />MECHANICAL WITH 2O09 SUPPLEMENT AND THE MANUFACTURER'S INSTALLATION IN STRUCTIONS. COORDINATE LOCATION OF SMOKE
<br />DETECTORS WITH FIRE ALARM CONTRACTOR. PROVIDE A VISIBLE/AUDIBLE NOTIFICATION PANEL. MAKE: SYSTEM SENSOR SSK451 OR EQUAL,
<br />24. PROVIDE FLEXIBLE NEOPRENE DUCT CONNECTORS ON THE DISCHARGE AND ENTERING SIDES OF ALL VIBRATING EQUIPMENT TO WHICH
<br />COMPATIBLE WITH BUILDING FIRE ALARM SYSTEM.
<br />DUCTWORK IS ATTACHED.
<br />8. IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED.
<br />25. CONTRACTOR SHALL PROVIDE 3 COPIES OF A TEST AND BALANCE REPORT. AIR BALANCING SHALL BE PERFORMED BY AN INDEPENDENT
<br />TESTING AND BALANCING CONTRACTOR WHICH SHALL BE QUALIFIED AND CERTIFIED BY EITHER ASSOCIATED AIR BALANCE COUNCIL (AABC)
<br />9. HVAC CONTRACTOR IS RESPONSIBLE FOR ANY ADDED ELECTRICAL COSTS WHICH MAY RESULT FROM SUBSTITUTED EQUIPMENT.
<br />OR NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB). THIS REPORT MUST BE REVIEWED AND APPROVED BY THE ENGINEER PRIOR
<br />TO THE FINAL INSPECTION.
<br />10. DUCTWORK INSULATION SHALL BE FOIL FACED FIBERGLASS DUCT WRAP WITH A MINIMUM THERMAL RESISTANCE (R) OF 6.0. INSULATION
<br />SHALL HAVE VAPOR BARRIER. INSTALL PER MFR. REQUIREMENTS.
<br />26. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL TRADES' INSTALLATION SCHEDULES, COORDINATE WORK SCHEDULE WITH GENERAL
<br />CONTRACTOR.
<br />11. COORDINATE AIR DEVICE LOCATIONS WITH LIGHTING FIXTURES.
<br />27. WHEN THE INTENT OF THE DRAWINGS AND SPECIFICATIONS IS NOT CLEAR, OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH
<br />12. TURNING VANES SHALL BE PROVIDED IN ALL SUPPLY DUCT RECTANGULAR ELBOWS WITH ANGLES BETWEEN 15 DEGREES AND LESS THAN 90
<br />MATTERS WILL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS. THE
<br />DEGREES PER FIG. 2-5 OF THE SMACNA MANUAL.
<br />ARCHITECT/ENGINEER SHALL MAKE CORRECTION OR EXPLANATION IN WRITING.
<br />13. DUCT DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. DUCTWORK, DIFFUSERS, REGISTERS, GRILLES, AND OTHER ITEMS
<br />28. PLANS AND SPECIFICATIONS ARE INTENDED AS A GENERAL DESCRIPTION OF THE WORK TO BE PERFORMED. ALL ITEMS NOT SPECIFICALLY
<br />OF THE AIR HANDLING SYSTEM SHALL NOT BE SUPPORTED BY THE CEILING OR CEILING SUSPENSION SYSTEM.
<br />MENTIONED OR SHOWN, BUT NECESSARY FOR THE COMPLETION OF THE INSTALLATION, SHALL BE FURNISHED AND INSTALLED BY THIS
<br />CONTRACTOR. THIS CONTRACTOR SHALL THOROUGHLY ACQUAINT HIMSELF WITH THE MECHANICAL, ARCHITECTURAL, STRUCTURAL AND
<br />14. UNLESS OTHERWISE NOTED, INSTALL DUCTWORK AS HIGH AS POSSIBLE, TIGHT TO BOTTOM OF STRUCTURE. COORDINATE DUCT ELEVATION
<br />ELECTRICAL PLANS BEFORE SUBMITTING HIS FINAL BID. NO ADDITIONAL COMPENSATION WILL BE ALLOWED DUE TO THE CONTRACTOR'S
<br />WITH STORM LEADERS, WATER PIPING, SANITARY DRAINS AND MAJOR ELECTRICAL CONDUITS.
<br />FAILURE TO FAMILIARIZE HIMSELF/ HERSELF WITH THE PLANS.
<br />15. CONTRACTOR TO PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND MECHANICAL EQUIPMENT & MATERIALS. INSTALLATION
<br />OF EQUIPMENT SHALL COMPLY WITH MANUFACTURER'S SPECIFICATIONS AND CLEARANCE REQUIREMENTS FOR SERVICING OF EQUIPMENT.
<br />FAN SCHEDULE
<br />MARK
<br />QTY.
<br />SERVICE
<br />CFM
<br />EXT. STATIC
<br />PRESSURE (IN.
<br />WATER)
<br />FAN TYPE
<br />DRIVE
<br />SONES
<br />WATTS
<br />RPM
<br />V/0
<br />MANUFACTURER
<br />MODEL
<br />NOTES
<br />EF-1
<br />1
<br />EXHAUST
<br />100
<br />0.375
<br />CEILING
<br />DIRECT
<br />3.2
<br />98
<br />1100
<br />120/1
<br />COOK
<br />GC-144
<br />1,2
<br />NOTES: 1. WITH PLUG-IN DISCONNECT. 2. PROVIDE CONTROL BY MANUAL LIGHT WITH OCCUPANCY SENSOR. COORDINATE WITH ELECTRICAL DRAWINGS FOR LOCATION OF SWITCH.
<br />HVAC SYMBOLS
<br />SYMBOL
<br />DESCRIPTION
<br />RIGID DUCT
<br />FLEXIBLE DUCT
<br />B
<br />SUPPLY AIR DUCT WORK UP THRU PLAN
<br />RETURN AIR OR EXHAUST DUCT WORK UP THRU PLAN
<br />DUCT WORK TRANSITION
<br />MANUAL AIR VOLUME CONTROL DAMPER
<br />/ ®
<br />SUPPLY AIR DEVICE
<br />zRETURN
<br />AIR DEVICE
<br />®
<br />EXHAUST AIR DEVICE
<br />OT
<br />WALL MOUNTED THERMOSTAT
<br />SD
<br />DUCT SMOKE DETECTOR
<br />A®
<br />DIFFUSER DEVICE TYPE - AIR QUANTITY
<br />CONDENSATE PIPING
<br />e
<br />CONNECTION OF NEW TO EXISTING
<br />(N)
<br />NEW
<br />(E)
<br />EXISTING
<br />MECHANICAL KEY PLAN NOTES:
<br />1Q UNDERCUT DOOR 1" TO ALLOW FOR TRANSFER OF AIR TO BATHROOM.
<br />O VERIFY THAT THERE IS AN EXISTING SMOKE DUCT DETECTOR IN THE
<br />SUPPLY DUCT. IF THE SMOKE DETECTOR IS NOT INSTALLED, REFER TO
<br />MECHANICAL GENERAL NOTE # 7. THE GC SHALL BE RESPONSIBLE FOR
<br />COORDINATING THE EXACT SCOPE OF WORK REQUIRED BETWEEN THE
<br />MECHANICAL SUB AND THE ELECTRICAL SUB PRIOR TO BIDDING. NO
<br />CHANGE ORDERS WILL BE APPROVED FOR FAILURE TO VERIFY EXISTING
<br />CONDITIONS OR COORDINATE BETWEEN SUBS.
<br />O3 CEILING MOUNTED BATHROOM EXHAUST FAN. COORDINATE EXACT
<br />LOCATION OF PENETRATION WITH ARCHITECTURAL PLAN. INSTALL
<br />GALVANIZED DUCT WORK DOWN FROM GRAVITY ROOF VENT. SIZE OF DUCT
<br />TO MATCH SIZE OF GRAVITY ROOF VENT OPENING. RUN DUCT IN
<br />CEILING/JOIST SPACE AND CONNECT TO CEILING MOUNTED EXHAUST FAN
<br />PER MANUFACTURERS RECOMMENDATIONS.
<br />® REFER TO SPLITTER DETAIL ON MECHANICAL DETAIL SHEET. INSTALL
<br />SPLITTER BELOW UNIT IN CEILING SPACE. CONTRACTOR TO INSTALL AT AN
<br />ELEVATION ENSURING THE LEAST AMOUNT OF OFFSETS AND DEVIATIONS IN
<br />THE DUCT WORK.
<br />Q5 RELOCATE EXISTING THERMOSTAT SUPPLIED IN SHELL PROJECT TO
<br />LOCATION SHOWN.
<br />© SUPPLY AND RETURN DUCT SIZE UP TO THE RTU SHALL BE THE SAME AS
<br />THE UNIT OPENING.
<br />OUTSIDE AIR CALCULATION
<br />AREA SERVED
<br />AREA (SQFT)
<br />CFM /SQFT (1)
<br />CFM CALCULATED
<br />CFM SUPPLIED
<br />SPACE D2
<br />1,400
<br />0.30
<br />420
<br />420
<br />(1) PER TABLE 403.3 - FLORIDA BUILDING CODE - MECHANICAL 2007
<br />BALANCE EXISTING 5 TON RTU TO 420 CFM OF OUTSIDE AIR.
<br />GRAVITY ROOF VENT SCHEDULE
<br />TYPE
<br />QTY.
<br />CFM
<br />SERVICE
<br />THROAT
<br />SIZE
<br />MANUFACTURER
<br />MODEL
<br />NOTES
<br />GRV-1
<br />1
<br />100
<br />EXHAUST
<br />0.394
<br />COOK
<br />PR 8
<br />1,2
<br />NOTES: 1. PROVIDE MANUFACTURER'S ROOF CURB. COORDINATE WITH ROOF TYPE. 2. PROVIDE INSECT SCREEN.
<br />AIR DEVICE SCHEDULE
<br />TAG
<br />MFG./CAT. #
<br />TYPE
<br />NECK
<br />FRAME
<br />FINISH
<br />NOTES
<br />0-125CFM = 6"RND
<br />12x12
<br />130-150CFM = 6' RND
<br />A
<br />TITUS - TMS-AA
<br />CD
<br />160 - 275 CFM = 8" RND
<br />BAK. WHT. ENAMEL
<br />1,2,3,4,5
<br />280 - 390 CFM =10" RND
<br />24 x 24
<br />400 - 600 CFM =12" RND
<br />B
<br />TITUS - 50F
<br />RAR
<br />22 x 22 (MAX 1280 CFM)
<br />24 x 24
<br />BAK. WHT. ENAMEL
<br />1,2,4,E
<br />C
<br />TITUS - 350FL
<br />EAR/RAR
<br />SEE PLANS
<br />SEE PLANS
<br />BAK. WHT. ENAMEL
<br />1,2,4,6
<br />D
<br />TITUS - 300FL
<br />SAG
<br />SEE PLANS
<br />SEE PLANS
<br />BAK. WHT. ENAMEL
<br />1,2,4,E
<br />DEVICE TYPE LEGEND:
<br />NOTES: 1. PROVIDE CEILING DEVICES WITH PROPER FRAME STYLE TO MATCH CEILING
<br />TYPE AS CALLED FOR BY THE ARCHITECT.
<br />CD = CEILING DIFFUSER
<br />2.
<br />DEVICES SHALL BE PROVIDED WITH FACTORY FINISH.
<br />RAR = RETURN AIR REGISTER
<br />3.
<br />CEILING DIFFUSERS SHALL BE 4-WAY THROW UNLESS NOTED OTHERWISE OR
<br />EAR = EXHAUST AIR REGISTER
<br />SHOWN ON PLANS WITH DIRECTIONAL ARROW(S).
<br />SAG = SUPPLY AIR GRILLE
<br />4.
<br />IF NECESSARY, PROVIDE TOP HAT FOR GRILLES REGISTERS AND DIFFUSERS.
<br />5.
<br />PROVIDE EQUALIZING GRID (TITUS MODEL EG). FOR DIFFUSERS TAPPED DIRECTLY
<br />FROM BOTTOM OF DUCT, PROVIDE OPPOSED BLADE DAMPER (TITUS MODEL D-57).
<br />6. PROVIDE OPPOSED BLADE DAMPER FOR REGISTERS.
<br />TYPICAL SEQUENCE OF OPERATION
<br />THE A/C UNIT SHALL BE STARTED AND STOPPED FROM A ROOM
<br />THERMOSTAT. ON A CALL FOR COOLING, THE THERMOSTAT SHALL
<br />ENERGIZE THE COMPRESSOR(S) TO MAINTAIN SET POINT. ON A CALL FOR
<br />HEATING, THE THERMOSTAT SHALL ENERGIZE THE ELECTRIC HEAT IN
<br />STAGE(S) TO MAINTAIN SET POINT. SUPPLY FAN SHALL RUN
<br />CONTINUOUSLY DURING OCCUPIED HOURS.
<br />DRAWING INDEX
<br />SHEET #
<br />TITLE
<br />M101
<br />Mechanical Floor Plan & General
<br />Information
<br />U
<br />u
<br />V
<br />N
<br />0
<br />CL
<br />Ow
<br />cugV_
<br />0 M
<br />Q
<br />ch
<br />._j
<br />w
<br />�aQ
<br />z
<br />a
<br />•nL N
<br />J
<br />U
<br />Cn
<br />0
<br />E
<br />E
<br />0
<br />U
<br />L
<br />W
<br />N_o
<br />ea J
<br />Q
<br />_m �
<br />Z
<br />�CM
<br />O
<br />0Cn
<br />Lu m �
<br />JCli
<br />� a m j
<br />W
<br />Cn J =
<br />Q'=
<br />W
<br />a
<br />Z CoUJ
<br />O
<br />ix
<br />co LLJ
<br />F N
<br />a
<br />Cu
<br />L
<br />W
<br />BCD
<br />0
<br />06
<br />L
<br />_0
<br />U-
<br />Cu
<br />.Cu
<br />W 1
<br />J V
<br />H ^
<br />H W
<br />w
<br />w
<br />Cn
<br />u.i
<br />a
<br />uT
<br />�w
<br />z�
<br />Y co
<br />C4 u, �t
<br />CaU-
<br />w
<br />0
<br />w
<br />co
<br />f-
<br />0
<br />N
<br />J
<br />N
<br />z
<br />pl
<br />o
<br />W
<br />_
<br />W
<br />Y
<br />p
<br />Y
<br />N
<br />W
<br />N
<br />C7LLI
<br />U
<br />2
<br />Q
<br />_
<br />a
<br />o
<br />o
<br />U
<br />m 1 0 1
<br />
|