ELECTRICAL
<br />ABBREVIATIONS
<br />AFCI
<br />ARC FAULT CIRCUIT INTERRUPT
<br />A.F.F.
<br />ABOVE FINISHED FLOOR
<br />EM.
<br />EMERGENCY
<br />EWH
<br />ELECTRIC WATER HEATER
<br />EWC
<br />ELECTRIC WATER COOLER
<br />FAP
<br />FIRE ALARM PANEL
<br />GD
<br />GARBAGE DISPOSAL
<br />GFI
<br />GROUND FAULT CIRCUIT INTERRUPT
<br />HP
<br />HORSE POWER
<br />IWH
<br />INSTANT WATER HEATER
<br />MTD
<br />MOUNTED
<br />MW
<br />MICROWAVE
<br />RECEPT.
<br />RECEPTACLE
<br />REF
<br />REFRIGERATOR
<br />SA
<br />SMALL APPLIANCE BRANCH CIRCUIT
<br />UG
<br />UNDERGROUND
<br />V
<br />VO LT
<br />WP
<br />WEATHER PROOF
<br />XFMR,XFMER
<br />TRANSFORMER
<br />0
<br />PHASE
<br />ELECTRICAL SYMBOLS
<br />(RECEPTACLES)
<br />20A, 125V, 2P, 3W, GNDING TYPE DUPLEX RECEPTACLE MNT.
<br />18" AFF UNLESS NOTED OTHERWISE.
<br />20A, 125V, 2P, 3W, GNDING TYPE DUPLEX RECEPTACLE
<br />MOUNTED 6" ABOVE COUNTER.
<br />20A, 125V, 2P, 3W, GNDING TYPE QUAD RECEPT. MNT.
<br />18" AFF
<br />ELECTRICAL SYMBOLS
<br />(SWITCHES)
<br />20A, 120/277V SINGLE POLE SWITCH MTD. 48" AFF
<br />$3
<br />20A, 120/277V THREE WAY SWITCH MTD. 48" AFF
<br />$D
<br />20A, 120/277V DIMMER SWITCH MTD. 48" AFF
<br />$M
<br />MOTOR RATED SWITCH WITH OVERLOAD PROTECTION EQUIP.
<br />MTD.
<br />20A, 120/277V SINGLE POLE SWITCH MTD. 48" AFF W/INTEGRAL
<br />$
<br />OCCUPANCY SENSOR (PROVIDE DUAL TECHNOLOGY PIR AND US)
<br />"LIGHTOLIER INTELLISIGHT ITS2UW"
<br />NOTE: LIGHT SWITCHES LOCATED ADJACENT TO EACH_ OTHER SHALL BE GANGED
<br />TOGETHER IN ONE COMMON BACKBOX UNDER A COMMON CONTINUOUS
<br />FACEPLATE. PROVIDE VOLTAGE BARRIERS AS REQUIRED.
<br />ELECTRICAL SYMBOLS
<br />(VISUAL/AUDIO)
<br />TELEVISION CABLE OUTLET BOX 4" SQ X 2 1 /2" DEEP SINGLE
<br />191 GANG BOX RECESSED MTD +75"AFF UNLESS NOTED OTHERWISE
<br />AV J-BOX SINGLE GANG WITH MUD RING FOR AUDIO VISUAL
<br />EQUIPMENT
<br />ELECTRICAL SYMBOLS
<br />(POWER DISTRIBUTION)
<br />*
<br />3P30
<br />DISCONNECT SWITCH.
<br />3P = # OF POLES, 30 = FRAME SIZE, * = FUSE PER
<br />MANUFACTURERS RECOMMENDATIONS.
<br />0
<br />120/208V, 30, 4W PANELBOARD
<br />0, a
<br />CEILING & WALL MOUNTED JUNCTION BOX, SIZE AS REQ. TO MEET
<br />NEC-370 (MINIMUM 4"x4"x2-1/2")
<br />MOTOR, HP SIZE AS INDICATED
<br />ELECTRICAL SYMBOLS
<br />(SECURITY)
<br />PCR
<br />SECURITY PROXIMITY CARD READER DEVICE. WALL MTD. 48"
<br />AFF. REFER TO E201 FOR LOCATIONS
<br />SECURITY CARD ACCESS SYSTEM PUSHBUTTON EMERGENCY RELEASE
<br />MTD. 48" AFF. REFER TO SHEET E601.
<br />REX
<br />AUTOMATIC RELEASE EGRESS PROXIMITY MOUNTED ABOVE DOOR.
<br />REFER TO SHEET E601 FOR DETAILS.
<br />DC
<br />DOOR MOUNTED SECURITY SYSTEM DOOR CONTACT.
<br />KP
<br />WALL MOUNTED ARMING STATION KEYPAD
<br />MD
<br />CEILING MOUNTED SECURITY SYSTEM MOTION DETECTOR
<br />GB
<br />CEILING MOUNTED GLASS BREAK DETECTOR
<br />ELECTRICAL SYMBOLS
<br />(TELECOMMUNICATIONS)
<br />TELEPHONE TERMINAL BACKBOARD, 3/4" PLYWOOD 8'X4'
<br />PAINTED ON ALL SIDES IN A FIRE RETARDANT MEDIUM GRAY
<br />COLOR AS PER TIA 5698
<br />TELEPHONE/DATA OUTLET JACK MOUNTED 18" A.F.F. UNLESS
<br />V
<br />OTHERWISE NOTED. EXTEND 3/4" CONDUIT TO DATA SERVER
<br />ROOM IN DATA SERVER RACK
<br />ELECTRICAL SYMBOLS
<br />(LIGHTING)
<br />2'X4' RECESSED FLUORESCENT LIGHT FIXTURE. MOUNTING
<br />®
<br />AS PER FIXTURE SCHEDULE.
<br />2'X4' RECESSED FLUORESCENT LIGHT FIXTURE WITH BATTERY
<br />BACK-UP MOUNTING AS PER FIXTURE SCHEDULE.
<br />O
<br />RECESSED DOWNLIGHT FIXTURE
<br />-E-
<br />PENDANT DECORATIVE FIXTURE
<br />CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE CONTACTORS/
<br />OS
<br />POWER PACKS FOR MULTIPLE CIRCUIT AND OCCUPANCY SENSOR TO
<br />CONTROL ENTIRE ROOM (PROVIDE DUAL TECHNOLOGY PIR AND US)
<br />SET AT 30 MINUTE DELAY.
<br />9
<br />CEILING & WALL MOUNTED EXIT SIGNS WITH BATTERY BACK-UP
<br />A
<br />LIGHTING FIXTURE SCHEDULE TYPE "A"
<br />a
<br />LOWER CASE LETTER DESIGNATES SWITCHING
<br />ELECTRICAL SYMBOLS
<br />(CONDUCTORS/CONDUITS)
<br />-----�
<br />CONCEALED CONDUIT
<br />CONCEALED CONDUIT BELOW GRADE
<br />VVVVV
<br />FLEXIBLE METAL CONDUIT (GREENFIELD)
<br />HOMERUN TO PANELBOARD. SHORT TICKS INDICATE PHASE
<br />CONDUCTORS & LONG TICK INDICATES NEUTRAL. LONG I TICK
<br />INDICATES GROUND CONDUCTOR.
<br />GROUND
<br />ELECTRICAL SYMBOLS
<br />(FIRE ALARM)
<br />❑F
<br />FIRE ALARM PULL STATION MT. 48" AFF
<br />FIRE ALARM SPEAKER/ VISUAL LIGHT COMBINATION
<br />S
<br />(75cd UNLESS NOTED OTHERWISE) MNT. 80" AFF
<br />SL
<br />STROBE LIGHT (75cd UNLESS NOTED OTHERWISE), MTD. 80"
<br />AFF
<br />CEILING MOUNTED FIRE ALARM SPEAKER/ VISUAL LIGHT
<br />COMBINATION
<br />(75cd UNLESS NOTED OTHERWISE) LOCATE WHERE SHOWN ON
<br />PLANS.
<br />OD
<br />SMOKE DETECTOR, CEILING MTD.
<br />DUCTSMOKE DETECTOR WITH AIR SAMPLING TUBES MOUNTED
<br />@
<br />ON THE AIR SUPPLY DUCT W/REMOTE TEST SWITCH, COORD.
<br />W/ MECH. DWGS FOR QTY
<br />GENERAL ELECTRICAL NOTES:
<br />CONTRACTOR MUST VISIT THE PROJECT SITE PRIOR TO BIDDING AND BECOME FAMILIARIZED
<br />WITH ALL EXISTING CONDITIONS THAT MIGHT AFFECT HIS WORK. ANY EXISTING CONDITIONS
<br />CHANGE IN EXTRA MATERIALS AND/OR LABOR WILL NOT BE ACCEPTED FOR ADDITIONAL
<br />PAYMENT. CONTRACTOR MUST PROVIDE A PERCENTAGE COST FOR UNIDENTIFIED ITEMS IN
<br />HIS BID.
<br />1. ALL MATERIALS AND/OR EQUIPMENT SHALL BEAR THE LABEL OF THE UNDERWRITER'S
<br />LABORATORIES (UL) AND SHALL BE MATERIAL APPROVED FOR USE BY LOCAL CODE
<br />ENFORCING AUTHORITIES.
<br />2. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL
<br />ELECTRICAL CODE(NEC), NATIONAL FIRE PROTECTION ASSOCIATION(NFPA), INSTITUTE OF
<br />ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE), ILLUMINATING ENGINEERING SOCIETY OF
<br />NORTH AMERICA (IESNA), THE FLORIDA BUILDING CODE (FBC) AND ALL LOCAL CODES
<br />HAVING JURISDICTION.
<br />3. ANY AND ALL ITEMS NOT SPECIFICALLY MENTIONED IN THE DRAWINGS OR THE CONTRACT
<br />SPECIFICATIONS BUT WHICH ARE OBVIOUSLY NECESSARY FOR A COMPLETE WORKING
<br />INSTALLATION SHALL BE INCLUDED.
<br />4. PRIOR TO SUBMITTING A PROPOSAL, THE CONTRACTOR IS REQUIRED TO VISIT THE SITE
<br />OF THE PROPOSED WORK AND FAMILIARIZE HIMSELF WITH THE NATURE AND EXTENT OF THE
<br />PROPOSED WORK AND ANY LOCAL CONDITIONS WHICH MAY IN ANY WAY AFFECT THE WORK
<br />TO BE DONE.
<br />5. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE ENGINEER OF ANY
<br />DISCREPANCIES ENCOUNTERED DURING THE COURSE OF THIS SITE VISIT:
<br />6. ALL CONDUCTORS SHALL BE COPPER, THWN/THHN, #12 AWG MINIMUM UNLESS
<br />OTHERWISE NOTED ON PLANS. ALL CONDUCTORS SHALL BE RUN IN CONDUIT, 1/2" MINIMUM
<br />TRADE SIZE UNLESS OTHERWISE NOTED ON PLANS.
<br />7. PROVIDE A TYPEWRITTEN PANEL DIRECTORY FOR EACH PANEL. CONTRACTOR IS ALSO
<br />RESPONSIBLE FOR BALANCING THE LOADS ON THE PHASES UNDER NORMAL CONDITIONS.
<br />8. THE CONTRACTOR SHALL SATISFACTORILY REPAIR OR REPLACE EQUIPMENT OR AREAS
<br />DAMAGED AS A RESULT OF HIS WORK.
<br />9. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE EQUAL TO "LITTLEFUSE"
<br />UNLESS NOTED OTHERWISE.
<br />10. APPLIANCE ELECTRICAL LOCATION AND CONNECTIONS TO BE MADE IN ACCORDANCE WITH
<br />MANUFACTURER'S SPECIFICATIONS.
<br />11. FINAL LOCATION OF ALL ELECTRICAL RECEPTACLES AND TELEPHONE AND CABLE
<br />TELEVISION JACKS TO BE COORDINATED WITH ARCHITECT PRIOR TO ROUGH -IN FOR EXACT
<br />LOCATION.
<br />12. ALL ELECTRICAL DEVICES TO COMPLY WITH ADA AND FLORIDA ACCESSIBILITY CODE.
<br />13. WHEN APPLICABLE, ALTERNATE EMERGENCY LIGHTING CIRCUITS SO THAT FAILURE OF A
<br />CIRCUIT BREAKER DOES NOT LEAVE THE AREA IN TOTAL DARKNESS.
<br />14. GROUND BUS BAR IN TELCOM ROOM WILL BE LOCATED BY THE
<br />PROTECTORS.
<br />15. PROVIDE 3/4" CONDUIT FOR A/C CONTROL WIRES.
<br />16. CONDUITS SHALL NOT BE EXPOSED.
<br />17. ALL ELECTRICAL WORK SHALL BE COORDINATED WITH ALL DISCIPLINES THROUGHOUT
<br />THE ENTIRE PROJECT.
<br />19. PROVIDE A GROUND WIRE AT EVERY CIRCUIT, SIZED PER PHASE WIRES AND NEC
<br />250.
<br />20. CONTRACTOR SHALL PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS AND
<br />ANY OTHER ITEM AS REQUIRED FOR THE WORK AS SHOWN ON THESE PLANS AND MUST
<br />MAINTIAIN PROPER INSURANCE FOR THE DURATION OF THE WORK.
<br />21. CONTRACTOR MUST VERIFY ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR
<br />TO ANY INSTALLATION OR FABRICATION. COORDINATE ALL WORK BEFORE ROUGH -IN OF
<br />ALL RECEPTACLES, DATA JACKS, LIGHT SWITCHES, ETC. WITH FURNITURE PLANS,
<br />21. CONTRACTOR MUST VERIFY ALL ROOM DIMENSIONS PRIOR TO EQUIPMENT
<br />INSTALLATIONS TO MEET ALL CODE CLEARANCES. ANY DISCREPANCIES THAT WILL NOT
<br />ALLOW PROPER CLEARANCES SHALL BE SUBMITTED TO THE A/E PRIOR TO INSTALLING
<br />EQUIPMENT.
<br />22. A 20 A SINGLE PHASE, 125V RATED RECEPTACLE OUTLET SHALL BE INSTALLED
<br />WITHIN 25 FT OF THE AIR CONDITIONING EQUIPMENT AS PER ARTICLE 210.63 NEC.
<br />23. FLOOR BOXES WHERE REQUIRED, MUST BE RESOURCE RFB SERIES RECESSED
<br />FLOOR BOX BY WIREMOLD (SLAB ON GRADE), WITH BRUSH ALUMINUM TRIM.
<br />LOCATION OF
<br />ENTRANCE MI
<br />120/208V, 3i
<br />400A MAIN D
<br />SERVING PRO
<br />OVERALL PLAN
<br />NOT TO SCALE
<br />LOCATION OF EXISTING UTILITY
<br />COMPANY "PROGRESS ENERGY"
<br />SERVICE TRANSFORMER
<br />FIRE
<br />FACILITY
<br />(STING STUBBED
<br />UITS
<br />I,L.„ nORK
<br />VERIZON DATA AND CABLE
<br />PICKUP POINTS RUN ALONG
<br />BACK OF BUILDING.
<br />CONTRACTOR MUST COORDINATE
<br />WITH LOCAL VERIZON
<br />REPRESENTATIVE FOR ANY
<br />CONNECTIONS REQUIRED.
<br />Project
<br />HUMANA- ZEPHYRHILLS,
<br />FLORIDA - GUIDANCE
<br />CENTER
<br />7920 GALL BLVD.
<br />ZEPHYRHILLS, FLORIDA 33541
<br />Prepared for
<br />HUMANA INC.
<br />Contract No: 12,01622.00
<br />HOK
<br />One Tampa City Center, Suite 1800
<br />Tampa, FL 33602 USA
<br />t +1 813 229 0300 f +1 813 223 7116
<br />FL Reg: AAC001139
<br />All reproduction & intellectual property rights reserved © 2012
<br />In Association with
<br />SDM Consulting Engineers
<br />MEP Engineer
<br />135 Almeria Ave.
<br />Coral Gables, FL 33134
<br />305.446.2788
<br />www.sdmcorp.com
<br />Key Plan
<br />C'
<br />Professional Seals
<br />ERNESTO ALOMA JOSE I. MARTINEZ
<br />P.E. 53823 - P.E. 53779
<br />No. Issue Description YYYY-MM-DD
<br />01 50% CONSTRUCTION DOCUMENTS 06.15.2012
<br />02 BID SET 06.29.2012
<br />03 ISSUE FOR PERMIT 07.27.2012
<br />No. Revision Description YYYY-MM-DD
<br />1 ADDENDUM 1 2012-07-09
<br />2 ADDENDUM 2 2012-07-19
<br />Drawn by SDM Reviewed by SDM
<br />Project No 12.01622.00
<br />Sheet Title:
<br />LEGEND, NOTES AND
<br />OVERALL PLAN
<br />Original drawing is 36 x 24 Do not scale contents of this drawing
<br />Sheet Number