Laserfiche WebLink
System No. W-L-1054 <br />F Ratings - 1 and 2 Hr (See Items 1 and 3) <br />T Rating - 0 Hr <br />L Rating At Ambient - Less Than 1 CFM/Sq Ft <br />L Rating At 400 F - 4 CFM/Sq Ft <br />SECTION A -A <br />1. Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed <br />of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition <br />Designs in the UL Fire Resistance Directory and shall include the following construction features: <br />A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood studs to <br />consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min 2-1/2 in. wide and <br />spaced max 24 in. OC. When steel studs are used and the diam of opening exceeds the width of <br />stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between <br />the vertical studs and screw -attached to the steel studs at each end. The framed opening in the <br />wall shall be 4 to 6 in. wider and 4 to 6 in. higher than the diameter of the penetrating item such <br />that, when the penetrating item is installed in the opening, a 2 to 3 in. clearance is present <br />between the penetrating item and the framing on all four sides. <br />B. Gypsum Board* -- 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, <br />thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual <br />U300 or U400 Series Design in the UL Fire Resistance Directory. Max diameter of opening is 32-1/4 <br />in. for steel stud walls. Max diameter of opening is 14-1/2 in. for wood stud walls. The F Rating of <br />the fire -stop system is equal to the fire rating of the wall assembly. <br />2. Through -Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or <br />eccentrically within the fire -stop system. The annular space shall be min 0 in. to max 2-1/4 in. Pipe <br />may be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not <br />greater than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides <br />of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe. <br />C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit. <br />D. Copper Tubing -- Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. <br />E. Copper Pipe -- Nom 6 in. diam (or smaller) regular (or heavier) copper pipe. <br />3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in. thickness of fill material applied within the <br />annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and <br />wall, a min 1/2 in. diameter bead of fill material shall be applied at the pipe wall interface on both <br />surfaces of wall. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF <br />HILTI INC -- FS-One Sealant <br />*Bearing the UL Classification Mark <br />,\p, S I Fj�o <br />�OEHFO® Reproduced by HILTI, Inc. Courtesy of <br />FIRESTOP SYSTEMS Underwriters Laboratories, Inc. <br />December 4, 2002 C ® L us <br />FIRE STOP SYSTEM DETAIL IONCRETE OR BLOCK <br />C <br />O <br />System No. C-AJ-1 154 <br />F Rating -- 3 Hr <br />T Rating -- 1/4 Hr <br />L Rating At Ambient -- Less Than 1 CFM/sq f t <br />L Rating At 400 F -- 4 CFM/sq f t <br />SECTION A -A <br />1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) <br />concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is <br />14 in. <br />See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers. <br />2. Through -Penetrants -- One metallic pipe, conduit or tubing to installed either concentrically or <br />eccentrically within the firestop system. The annular space shall be min 0 in. to max 3-1/4 in. Pipe, <br />conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes <br />of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe -- Nom 10 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. <br />C. Copper Tubing -- Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing. <br />D. Copper Pipe -- Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe. <br />3. Firestop System -- The firestop system shall consist of the following: <br />A. Packing Material -- Mineral wool batt insulation firmly packed into opening as a permanent form. <br />Packing material to be recessed from top surface of floor or from both surfaces of wall as required <br />to accommodate the required thickness of fill material. As an option to the above, backer rod <br />and/or foamed plastic backer material may be used. <br />B. Fill, Void or Cavity Material* -- Sealant -- Min 1/2 in. thickness of fill material applied within <br />the annulus, flush with top surface of floor or with both surfaces of wall. At the point contact <br />location between pipe and concrete, a min 1/2 in. diam bead of fill material shall be applied at the <br />concrete/pipe interface on the top surface of floor and on both surfaces of wall. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS-ONE Sealant <br />*Bearing the UL Classification Mark <br />� <br />SS / F/ � ® Reproduced by HILTI, Inc. Courtesy of Underwriters <br />Laboratories, Inc. C.� <br />FIRESTOP SYSTEMS November 24, C 0 US <br />FIRE STOP SYSTEM DETAIL (CONCRETE OR BLOCK <br />GENERAL NOTES <br />1. ALL WORK SHALL COMPLY WITH THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING CODE, N.F.P.A #13, 14, 24, 25, 70, 72, 101, UL <br />LISTING, AND APPLICABLE FACTORY MUTUAL REQUIREMENTS. IN ANY CONFLICT THE MOST RIGID REQUIREMENT SHALL APPLY. <br />2. ALL MATERIALS AND EQUIPMENT PROVIDED SHALL BE UL LISTED AND FM APPROVED FOR THE SPECIFIED SERVICE APPLICATION. <br />3. CONTRACTOR SHALL PAINT ALL ABOVE GROUND FIRE SERVICE PIPING, FITTING AND VALVES WITH A MINIMUM OF 10 MILS RUST PROOF FIRE <br />PROTECTION RED PAINT (OR PAINT TO MATCH BACKGROUND IF REQUESTED BY OWNER AND APPROVED BY A.H.J.). ALL PIPING SHALL <br />COMPLY WITH N.F.P.A.13(07)-8.16.4.2. <br />4. ALL FIRE SERVICE PIPING ABOVE GROUND SHALL BE SCHEDULE 40 STEEL PIPE (A.S.T.M. A-53). <br />5. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, CEILINGS, FLOORS, ROOFS, ETC. <br />6. ALL PIPING OPEN TO EXTERIOR TO BE FACTORY HOT DIPPED GALVANIZED (PIPE, HANGERS AND FITTINGS). <br />7. HANGING, BRACING AND RESTRAINT OF SYSTEM PIPING SHALL COMPLY WITH N.F.P.A.13(07)-9. <br />8. SPRINKLERS SHALL BE PROVIDED IN ALL AREAS EXCEPT WHERE OTHERWISE NOTED. <br />9. UNLESS OTHERWISE NOTED. ALL WET SYSTEM SPRINKLER HEADS SHALL BE OF THE QUICK RESPONSE TYPE, AND SHALL BE UL/FM <br />APPROVED FOR THE HAZARD AND PRESSURE SPECIFIED. <br />10. ALL SPRINKLER HEADS SHALL BE INSTALLED ON CENTER OF CEILING TILE. CONTRACTOR TO PROVIDE A RETURN BEND TO ALLOW TWO <br />DEGREES OF MOVEMENT AT EACH SPRINKLER HEAD LOCATION, REFER TO DETAILS FOR ADDITIONAL INFORMATION. PENDENT SPRINKLER IN <br />I.T. ROOM SHALL BE PROVIDED WITH GUARD (CAGE). <br />11. THE DISTANCE BETWEEN A HANGER AND THE CENTER OF AN UPRIGHT SPRINKLER SHALL NOT BE LESS THAN 3 INCHES. <br />12. PROVIDE STOCK OF SPRINKLER HEADS IN ACCORDANCE WITH N.F.P.A.13(07)-6.2.9. <br />13. WHENEVER SPRINKLERS ARE INSTALLED IN ELECTRICAL ROOMS, HOODS OR SHIELDS MUST BE PROVIDED OVER ALL ELECTRICAL EQUIPMENT IN <br />ACCORDANCE WITH N.F.P.A.13(07)-8.15.10. COORDINATE WITH ELECTRICAL CONTRACTOR. <br />14. PROVIDE AUXILIARY DRAINS WHERE A CHANGE IN PIPING DIRECTION PREVENTS DRAINAGE OF SYSTEM PIPING THROUGH THE MAIN DRAIN <br />VALVE. AUXILIARY DRAINS SHALL COMPLY WITH N.F.P.A.13(07)-8.16.2.5. <br />15. NO STORAGE SHALL BE ALLOWED IN THIS FACILITY. PRESENT FIRE PROTECTION DOES NOT ALLOW FOR STORAGE OF ANY TYPE. ADDITIONAL <br />ENGINEERED FIRE PROTECTION PROVISIONS MUST BE MADE BASED ON STORAGE HEIGHT AND COMMODITY CLASS AS PER <br />NFPA13(07)-CHAPTER 12 PRIOR TO THE REMOVAL OF THIS STORAGE RESTRICTION. <br />16. ALL EXISTING SPRINKLER HEADS SHALL BE REPLACED BY NEW SPRINKLER HEADS OF THE SAME COVERAGE, RESPONSE TYPE AND K-FACTOR <br />AS EXISTING HEADS. CONTRACTOR TO COORDINATE WITH ARCHITECT PRIOR TO PURCHASE AND INSTALLATION. <br />17. THIS PROJECT OCCURS IN AN EXISTING FACILITY. ALL CONTRACTORS AND SUBCONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING <br />CONDITIONS THAT MAY AFFECT THE LOCATION AND ROUTING OF THEIR EQUIPMENT, CONTRACTOR SHALL MAKE ALLOWANCES ON THEIR BIDS <br />FOR PERFORMING A THOROROUGH SURVEY OF EXISTING INSTALLATIONS TO REFLECT ACTUAL SYSTEM REQUIREMENTS IN THEIR SUBMITTALS. <br />THE BIDS SHALL ALSO ALLOW FOR ADDITIONAL FITTINGS AND LENGTHS OF PIPE REQUIRED TO ACCOMMODATE OFFSETS, CHANGES IN <br />DIRECTION AND/OR ELEVATION REQUIRED TO ERECT THEIR SYSTEM IN CONGESTED LOCATIONS. ONLY RADICAL DEVIATIONS FROM BID <br />DOCUMENTS WILL BE RECOGNIZED AS LEGITIMATE FIELD CONDITIONS. <br />18. CONTRACTOR MUST VISIT THE SITE TO VERIFY EXISTING CONDITIONS AND STUDY "AS BUILT" CONDITIONS PRIOR TO BID. CONTRACTOR SHALL <br />INCLUDE IN THEIR BID PRICE THE COST (INCLUDING MATERIAL, LABOR, OVERHEAD, AND PROFIT) OF ALL REQUIRED ITEMS TO SUCCESSFULLY INSTALL <br />ALL ITEMS DESCRIBED OR IMPLIED/REQUIRED TO BE INSTALLED FOR PROVISION OF A COMPLETE FULL COMPLIANT OPERATIONAL SYSTEM. <br />19. AREAS REQUIRING PARTIAL DEMOLITION OF EXISTING CONDITIONS TO PERFORM WORK SHALL BE REFINISHED, PAINTED AND PATCHED TO MATCH <br />SURROUNDING AREAS. COORDINATE WITH OTHER DISCIPLINES AS REQUIRED. <br />20. ALL WORK CONTAINED IN THIS DOCUMENTS SHALL BE INCLUDED AND INSTALLED BY THE CONTRACTOR UNLESS OTHERWISE NOTED. <br />21. CONTRACTOR SHALL MAKE PROVISION FOR REQUEST OF A FIRE WATER FLOW TEST, AND BASE HYDRAULIC CALCULATIONS ON SUCH TEST. <br />22. WORK TO BE CONCEALED SHALL REMAIN UNCOVERED UNTIL REQUIRED TESTS HAVE BEEN COMPLETED IN PRESENCE OF A/E AND OTHER <br />REQUIRED REPRESENTATIVES. <br />23. THE SYSTEM SHALL BE HYDROSTATICALLY TESTED AT 200 PSI FOR 2 HOURS CONFORMING TO N.F.P.A.13(07)-10.10.2.2.1 BEFORE FINAL <br />APPROVAL. <br />24. ALL FIRE SPRINKLER PIPING SHALL BE INSTALLED BY A CERTIFIED LICENSED CONTRACTOR AS PER FLORIDA ADMINISTRATIVE CODE RULE <br />4A-46 AND STATE STATUTE 489.105(N). <br />25. CONTRACTOR SHALL OBTAIN FIRE DEPARTMENT PERMIT BASED ON A/E APPROVED SHOP DRAWINGS - WORKING PLANS AS PER <br />N.F.P.A.13(07)-22.1 - PRIOR TO INSTALLATION OF SYSTEM(S). <br />26. DRAWINGS ARE DIAGRAMMATIC, AND SHOW DESIGN INTENT. CONTRACTOR IS TO COORDINATE SYSTEM LAYOUT WITH EXISTING CONDITIONS AND <br />OTHER DISCIPLINES (MECHANICAL, ELECTRICAL, PLUMBING, ARCHITECTURAL, STRUCTURAL, ETC), TO AVOID CONFLICTS DURING CONSTRUCTION <br />AND FACILITATE ACCESSIBILITY FOR MAINTENANCE. WHERE INTERFERENCE OCCUR, CONTRACTOR SHALL RE-ROUTE PIPING AS REQUIRED. <br />CONTRACTOR SHALL MAKE ALL NECESSARY ALTERATIONS TO SYSTEM LAYOUT DURING THE SHOP DRAWING SUBMITTAL PHASE. ALTERATIONS <br />DUE TO COORDINATION SHALL BE CLEARLY CLOUDED AND LABELED FOR QUICK REFERENCE AND SUBJECT FOR APPROVAL FOR THE A/E <br />TEAM. <br />27. DRAWINGS INDICATE APPROXIMATE LOCATION OF CEILING MOUNTED DEVICES. COORDINATE WITH ARCHITECTURAL CEILING PLANS. <br />28. DESIGN INTENT CONSTITUTES THE PROVISION OF COMPLETE SYSTEM, AS INDICATED WITH ALL NECESSARY COMPONENTS AND ACCESSORIES <br />WETHER EXPLICITLY SPECIFIED OR IMPLIED, TO ACHIEVE FULLY OPERATIONAL STATUS. <br />29. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION AND EXECUTION OF ALL NECESSARY CHANGES ATTRIBUTABLE TO INSTALLATION OF <br />SUBSTITUTE EQUIPMENT AT NO ADDITIONAL COST TO OWNER. <br />30. DRAWINGS FROM VARIOUS DISCIPLINES ARE INTERRELATED. WHAT IS REQUIRED IN ONE SHALL BE AS BINDING AS IF REQUIRED BY ALL. <br />COMPLEMENTARY COMPONENTS BETWEEN DISCIPLINES, REASONABLY INFERRED AS BEING NECESSARY TO PRODUCE INTENDED RESULT SHALL <br />BE DEEMED PART OF THE CONTRACTORS EXPECTED PERFORMANCE. <br />31. FIRE PROTECTION CONTRACTOR SHALL PREPARE SHOP DRAWINGS IN CAD FORMAT COMPATIBLE WITH nAUTOCAD" RELEASE 2007. HARD <br />COPIES SHALL BE SUBMITTED, SIGNED & SEALED BY A PROFESSIONAL ENGINEER IN THE STATE OF FLORIDA, TO A/E TEAM FOR REVIEW. <br />CONTRACTOR SHALL MAINTAIN DETAILED AS -BUILT DRAWINGS (UPDATED DAILY) OF WORK PERFORMED ON SITE. PRIOR TO SUBSTANTIAL <br />COMPLETION WALK-THROUGH, CONTRACTOR SHALL PROVIDE CAD AS -BUILT (INCLUDING ISOMETRICS, SECTIONS, ENLARGED PLANS, ETC) TO <br />A/E TEAM ON CD REFLECTING ACTUAL INSTALLATION. <br />32. WHERE SPRINKLERS ARE LOCATED CLOSER THAN 6' APART, CROSS -BAFFLES SHALL BE PROVIDED MIDWAY BETWEEN SPRINKLERS. <br />................................................................................................... ............ <br />HUMAN.,: <br />A <br />. . ..................... --------------------- ------ ­­_ ----------- ............. <br />Project <br />HUMANA- ZEPHYRHILLS, <br />FLORIDA - GUIDANCE <br />CENTER <br />7920 GALL BLVD. <br />ZEPHYRHILLS, FLORIDA 33541 <br />Prepared for <br />HUMANA INC. <br />Contract No: 12.01622.00 <br />HOK <br />One Tampa City Center, Suite 1800 <br />Tampa, FL 33602 USA <br />t +1 813 229 0300 f +1 813 223 7116 <br />FL Reg: AAC001139 <br />All reproduction & intellectual property rights reserved © 2012 <br />In Association with <br />SDM Consulting Engineers <br />MEP Engineer <br />135 Almeria Ave. <br />Coral Gables, FL 33134 <br />305.446.2788 <br />www.sdmcorp.com <br />Key Plan <br />C-1*1 <br />Professional Seals <br />v �v� <br />ERNESTO ALOMA JOSE I. MARTINEZ <br />P.E. 53823 P.E. 53779 <br />No. Issue Description YYYY-MM-DD <br />01 50% CONSTRUCTION DOCUMENTS 06.15.2012 <br />02 BID SET 06.29.2012 <br />03 ISSUE FOR PERMIT 07.27.2012 <br />No. Revision Description YYYY-MM-DD <br />1 ADDENDUM 1 2012-07-09 <br />2 ADDENDUM 2 2012-07-19 <br />Drawn by SDM Reviewed by SDM <br />Project No 12.01622.00 <br />Sheet Title: <br />FIRE PROTECTION <br />NOTES AND DETAILS <br />Original drawing is 36 x 24 Do not scale contents of this drawing <br />Sheet Number <br />FP1 01 <br />