ABBREVIATIONS
<br />GENERAL NOTES
<br />LEGEND
<br />ABV
<br />ABOVE
<br />HWR
<br />HOT WATER RETURN
<br />1.
<br />INSTALL EQUIPMENT AND MATERIALS IN COMPLIANCE WITH MANUFACTURER'S MINIMUM CLEARANCE REQUIREMENTS AND
<br />SUPPLY DIFFUSER (4-WAY)
<br />0
<br />REFERENCE NOTES
<br />ADJ
<br />ADJUSTABLE
<br />HWS
<br />HOT WATER SUPPLY
<br />RECOMMENDATIONS.
<br />AF
<br />AIRFOIL
<br />HVAC
<br />HEATING VENTILATION AND AIR CONDITIONING
<br />2.
<br />COMPLY WITH THE LATEST EDITIONS OF NFPA AND THE LATEST ADOPTED EDITION FLORIDA BUILDING CODE (MECHANICAL,
<br />RETURN OR OUTDOOR AIR GRILLE
<br />0
<br />REFERENCE NOTE - MULTI -DISCIPLINE SHEETS
<br />AFF
<br />ABOVE FINISHED FLOOR
<br />HV
<br />HEATING AND VENTILATING
<br />PLUMBING, GAS AND ENERGY CONSERVATION).
<br />AC
<br />AIR CONDITIONER
<br />IN.WG
<br />INCHES WATER GAUGE
<br />3.
<br />ALL MATERIALS SHALL FIT THE SPACE AVAILABLE. VERIFY DIMENSIONS AND CLEARANCES ON BUILDING PLANS PRIOR TO
<br />�
<br />EXHAUST GRILLE
<br />FLOW DIRECTION
<br />ACU
<br />AIR CONDITIONING UNIT
<br />KW
<br />KILOWATTS
<br />COMMENCING WORK.
<br />IUI
<br />INDICATES POINT OF CONNECTION BETWEEN NEW
<br />AHU
<br />AIR HANDLING UNIT
<br />L.AT
<br />LEAVING DIFFUSER
<br />4.
<br />AN INDEPENDENT TEST AND BALANCE CONTRACTOR (TABC) SHALL BE HIRED BY THE GENERAL. CONTRACTOR.
<br />AND EXISTING
<br />AP
<br />ACCESS PANEL
<br />LD
<br />LINEAR DIFFUSER
<br />SUPPLY DUCT UP SECTION (RECTANGULAR)
<br />C
<br />POINT OF DISCONNECT
<br />5.
<br />TABC IS RESPONSIBLE FOR TESTING AND BALANCING OF AIR SYSTEMS IN ACCORDANCE WITH AABC GUIDELINES. A TEST AND
<br />BAS
<br />BUILDING AUTOMATION SYSTEM
<br />LWT
<br />LEAVING WATER TEMPERATURE
<br />BALANCE REPORT SHALL BE SUBMITTED TO THE ARCHITECT FOR APPROVAL.
<br />BI
<br />BACKWARD INCLINE
<br />MAX
<br />MAXIMUM
<br />6.
<br />PROVIDE 45 DEGREE BRANCH TAKE -OFF PER SMACNA FIG. 2-8 ON ALL RECTANGULAR DUCT TAKE -OFFS.
<br />RETURN DUCT UP SECTION (RECTANGULAR)
<br />CWS
<br />CONDENSER WATER SUPPLY PIPING
<br />BLDG
<br />BUILDING
<br />MBH
<br />1000 X BTUH
<br />BHP
<br />BRAKE HORSEPOWER
<br />MIN
<br />MINIMUM
<br />7.
<br />ALL DUCTWORK TAKE -OFFS AND/OR BRANCH DUCTWORK SHALL BE PROVIDED WITH BALANCING DAMPERS (REMOTE IF IN
<br />CWR
<br />CONDENSER WATER RETURN PIPING
<br />HARD CEILING AREAS).
<br />BTUH
<br />BRITISH THERMAL UNIT PER HOUR
<br />MD
<br />MANUAL VOLUME DAMPER
<br />EXHAUST DUCT UP SECTION (RECTANGULAR)
<br />BDD
<br />BACKDRAFT DAMPER
<br />M
<br />MOTORIZED DAMPER
<br />8.
<br />PROVIDE AND INSTALL DUCT MOUNTED HINGED ACCESS DOORS FOR ALL SMOKE AND/OR FIRE DAMPERS, NOT OTHERWISE
<br />BCWS
<br />BUILDING CONDENSER WATER SUPPLY PIPING
<br />ACCESSIBLE.
<br />CD
<br />CONDENSATE DRAIN
<br />MZ
<br />MULTI -ZONE
<br />i �x`
<br />SUPPLY DUCT DOWN SECTION (RECTANGULAR)
<br />CFM
<br />CUBIC FEET PER MINUTE
<br />N.T.S.
<br />NOT TO SCALE
<br />9.
<br />CONTRACTOR SHAH COORDINATE VOLTAGE AND PHASE OF EACH PIECE OF EQUIPMENT WITH THE ELECTRICAL CONTRACTOR
<br />BCWR
<br />BUILDING CONDENSER WATER RETURN PIPING
<br />PRIOR TO ORDERING AND SHALL COORDINATE WITH ALL OTHER TRADES PRIOR TO OR INSTALLING EQUIPMENT AND MATERIALS.
<br />CLG
<br />CEILING
<br />OA
<br />OUTSIDE AIR
<br />CHIN
<br />CHILLED WATER
<br />OBMVD
<br />OPPOSED BLADE MANUAL VOLUME DAMPER
<br />10.
<br />COORDINATE ALL HVAC SYSTEM DRAWINGS WITH EXISTING/NEW TRUSS TO AVOID INTERFERENCE BETWEEN MECHANICAL
<br />i \� �
<br />RETURN DUCT DOWN SECTION (RECTANGULAR)
<br />CHINS
<br />CHILLED WATER SUPPLY PIPING
<br />SYSTEMS AND ROOF STRUCTURE. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH TRUSS
<br />CHWR
<br />CHILLED WATER RETURN
<br />OPD
<br />OPEN DRIP PROOF
<br />INTERFERENCE THAT OCCURS IN THE FIELD DURING CONSTRUCTION. COORDINATE IN ADVANCE. DUCT SIZES MAY BE
<br />CHWS
<br />CHILLED WATER SUPPLY
<br />PROP
<br />PROPELLER
<br />REVISED TO FIT TRUSS SYSTEM SO LONG AS THE EQUIVALENT INSIDE CROSS SECTIONAL AREA IS NOT DECREASED.
<br />i
<br />EXHAUST DUCT DOWN SECTION (RECTANGULAR)
<br />CHWR
<br />CHILLED WATER RETURN PIPING
<br />CWR
<br />CONDENSER WATER RETURN
<br />PCR
<br />PRE -CONDITIONED AIR SYSTEM RETURN WATER
<br />11.
<br />GAUGES AND CONSTRUCTION FOR DUCTWORK SHALL CONFORM TO THE LATEST EDITION OF SMACNA'S HVAC DUCT
<br />CWS
<br />CONDENSER WATER SUPPLY
<br />PCs
<br />PERCENT
<br />CONSTRUCTION STANDARDS.
<br />HWS
<br />HEATING WATER SUPPLY PIPING
<br />CONC
<br />CONCRETE
<br />PD
<br />PRESSURE DROP
<br />12.
<br />TRANSITION RECTANGULAR DUCTWORK ON BOTTOM AND SIDES. MAINTAIN TOP OF DUCTWORK LEVEL AND HIGH AS POSSIBLE.
<br />SUPPLY DUCT UP SECTION (ROUND)
<br />CONE
<br />CONDENSATE
<br />PERF. PL.
<br />PERFORATED PLATE
<br />FLEXIBLE DUCT RUN -OUTS TO CEILING DIFFUSERS SHALL BE AS STRAIGHT AS POSSIBLE AND FREE OF SAGS AND KINKS.
<br />HWR
<br />HEATING WATER RETURN PIPING
<br />FLEX DUCT SHALL BE THE SAME SIZE AS THE DIFFUSER NECK IT SERVES.
<br />CONT
<br />CONTINUOUS
<br />PL.BG
<br />PLUMBING
<br />i
<br />SUPPLY DUCT DOWN SECTION (ROUND)
<br />CO
<br />CARBON MONOXIDE
<br />PSIA
<br />POUNDS PER SQUARE INCH ABSOLUTE
<br />13.
<br />ALL DUCT TRANSITIONS FROM SQUARE TO ROUND SHALL BE SMOOTH SQUARE TO ROUND TRANSITIONS. SPIN -IN FITTINGS AT
<br />_CD
<br />CONDENSATE DRAIN PIPING
<br />THE END OF CAPPED DUCTS ARE NOT ACCEPTABLE. DUCT DIMENSIONS SHOWN ARE INSIDE CLEAR DIMENSIONS.
<br />COP
<br />COEFFICIENT OF PERFORMANCE
<br />PSIG
<br />POUNDS PER SQUARE INCH GAUGE
<br />14.
<br />THE CONTRACTOR SHALL FULFILL ALL REQUIREMENTS OF THE CONTRACT DOCUMENTS AND SHALL COMPLETE THE WORK
<br />LINEAR SLOT DIFFUSER
<br />R
<br />REFRIGERANT PIPING
<br />CU
<br />CONDENSING UNIT
<br />RA
<br />RETURN AIR
<br />SHOWN ON THESE DRAWINGS. ALL SYSTEMS SHALL BE FINISHED, TESTED AND BALANCED, ADJUSTED, AND PROVEN TO BE
<br />DB
<br />DRYBULB
<br />RD
<br />RADIATION DAMPER
<br />FULLY OPERATIONAL AND USEABLE.
<br />�FLOW
<br />EXISTING LINEAR SLOT DIFFUSER (LIGHT LINETYPE)
<br />y
<br />SENSOR
<br />DWDI
<br />DOUBLE WIDTH, DOUBLE INLET
<br />REG
<br />REGISTER
<br />15.
<br />ADJUST ALL DIFFUSERS IN CORRIDORS OR WITHIN THREE (3) FEET OF A WALL TO PROVIDE 2-WAY OR 3-WAY BLOW AWAY
<br />-�
<br />DWGS
<br />DRAWINGS
<br />REQ'D
<br />REQUIRED
<br />FROM OR PARALLEL TO WALLS. ALL DIFFUSERS SHALL HAVE 4-WAY BLOW UNLESS NOTED OTHERWISE.
<br />RECTANGULAR DUCTWORK WITH TAKE -OFF, BALANCING
<br />DX
<br />DIRECT EXPANSION
<br />RG
<br />RETURN AIR GRILLE
<br />16.
<br />PORTIONS OF DUCTWORK VISIBLE THROUGH GRILLES AND REGISTERS IN FINISHED AREAS SHALL BE PAINTED FLAT BLACK.
<br />A B
<br />DAMPER AND INSULATED FLEXIBLE ROUND DUCT. SAME
<br />SIZE AS DIFFUSER INLET UNLESS NOTED OTHERWISE.
<br />SP
<br />STATIC PRESSURE TRANSMITTER ASSEMBLY
<br />EF
<br />EXHAUST FAN
<br />RH
<br />RELATIVE HUMIDITY
<br />17.
<br />ALL DAMPERS IN AND ABOVE CEILING SHALL BE ACCESSIBLE. CONTRACTOR SHALL COORDINATE ALL ACCESS PANELS IN
<br />FIRST DIMENSION IS THAT OF SIDE SHOWN
<br />EXH
<br />EXHAUST
<br />RPM
<br />REVOLUTIONS PER MINUTE
<br />CEILINGS OR WALLS WITH ARCHITECTURAL REFLECTED CEILING PLANS AND INTERIOR DRAWINGS FOR PROPER LOCATION.
<br />A 0
<br />ROUND DUCTWORK
<br />EA
<br />EAT
<br />EACH
<br />ENTERING AIR TEMPERATURE
<br />RR
<br />RTU
<br />RETURN AIR REGISTER
<br />ROOFTOP UNIT
<br />18.
<br />MOUNT THERMOSTATS WHERE INDICATED ON PLANS 48' ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. IN HANDICAPPED
<br />ACCESSIBLE AREAS, MOUNT CONTROLS AT 48" (MAXIMUM) ABOVE FINISHED FLOOR.
<br />CONICAL FITTING WITH DAMPER ON BRANCH
<br />CONNECTION TO RECTANGULAR MAIN
<br />L
<br />L-t/4w,Vw
<br />RECTANGULAR BRANCH DUCT CONNECTION.
<br />(PROVIDE BALANCING DAMPER AT ALL
<br />(PROVIDE DAMPER. IN LOW PRESSURE DUCTWORK ONLY)
<br />MN• 4'
<br />BRANCH CONNECTIONS)
<br />EER
<br />ENERGY EFFICIENCY RATIO
<br />SA
<br />SUPPLY AIR
<br />19.
<br />COORDINATE DUCTWORK AND PIPING WITH PLUMBING, FIRE PROTECTION AND ELECTRICAL. MAKE OFFSETS AND TRANSITIONS
<br />ELECT
<br />ELECTRICAL
<br />SF
<br />SUPPLY FAN
<br />TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE CONTRACT.
<br />EXISTING DUCTWORK TO REMAIN (LIGHT LINETYPE)
<br />ENT
<br />ENTERING
<br />SD
<br />SMOKE DETECTOR
<br />20.
<br />SEAL ALL TRANSVERSE JOINTS AND FITTINGS WITH DUCT SEALER.
<br />-
<br />TEE (PLAN, UP, DOWN)
<br />EQ
<br />EQUAL
<br />SDMP
<br />SMOKE DAMPER
<br />ER
<br />EXHAUST REGISTER
<br />SDMP
<br />SQUARE FOOT
<br />21.
<br />TRAP AND ROUTE CONDENSATE DRAINS LINES, FULL SIZE OF UNIT CONNECTION, AS INDICATED. SLOPE 1/8" PER FOOT.
<br />-i► R
<br />DUCT OFFSETS UP (RISE) IN DIRECTION INDICATED
<br />-0
<br />ELBOW (PLAN, UP, DOWN)
<br />EWT
<br />ENTERING WATER TEMPERATURE
<br />SR
<br />SUPPLY REGISTER
<br />22.
<br />ALTERNATE MANUFACTURERS AND MODELS WILL BE REVIEWED. THERE MAY BE ARCHITECTURAL, STRUCTURAL AND ELECTRICAL
<br />FC
<br />FORWARD CURVED
<br />STR
<br />STARTER
<br />CHANGES RESULTING FROM THE ALTERNATES. THE COST OF IMPLEMENTING AND ENGINEERING THESE CHANGES SHALL BE
<br />-+-D
<br />DUCT OFFSETS DOWN (DROP) IN DIRECTION INDICATED
<br />BORNE BY THE MECHANICAL SUBCONTRACTOR.
<br />VALVE
<br />FCU
<br />FAN COIL UNIT
<br />SWSI
<br />SINGLE WIDTH, SINGLE INLET
<br />23.
<br />PIPE AND DUCT ROUTING SHOWN IS SCHEMATIC. PROVIDE ANY ADDITIONAL OFFSETS AND FITTINGS, INCLUDING DIVIDED
<br />FD
<br />FIRE DAMPER
<br />SZ
<br />SINGLE ZONE
<br />DUCTS, REQUIRED FOR PROPER INSTALLATION AND TO MAINTAIN CLEARANCES AS ENCOUNTERED IN THE FIELD.
<br />OPPOSED BLADE VOLUME DAMPER (OBD)
<br />FL
<br />FLOOR
<br />TEFC
<br />TOTALLY ENCLOSED FAN COOLED
<br />TWO WAY MOTORIZED CONTROL VALVE
<br />24.
<br />COORDINATE CEILING MOUNTED AIR DEVICE LOCATION WITH REFLECTED CEILING PLAN AND OTHER
<br />FLEX
<br />FLEXIBLE CONNECTOR OR DUCT
<br />TEMP
<br />TEMPERATURE
<br />.TRADES.
<br />FPM
<br />FEEL PER MINUTE
<br />TG
<br />TRANSFER GRILLE
<br />25.
<br />ALL CONTROL WIRING AND .CONDUIT SHALL COMPLY WITH NEC DIVISION 16 SPECIFICATIONS.
<br />MANUAL DAMPER
<br />THREE WAY MOTORIZED CONTROL VALVE
<br />F/S
<br />COMBINATION FIRE AND SMOKE DAMPER
<br />T/O
<br />TRANSFER OPENING ABOVE CEILING
<br />26.
<br />PROVIDE MATERIALS WHICH HAVE A FLAME SPREAD RATING OF 25 OR LESS AND A SMOKE DEVELOPED RATING OF 50 OR
<br />FT. H2O
<br />FEET WATER GAUGE
<br />LESS WHEN TESTED IN ACCORD WITH ASTM E84.
<br />IIIII
<br />FLEXIBLE DUCT CONNECTION
<br />- --
<br />PRESSURE REDUCING VALVE
<br />T'STAT
<br />THERMOSTAT
<br />F
<br />DEGREES FAHRENHEIT
<br />TYP
<br />TYPICAL
<br />27.
<br />SLEEVE AND FIRE STOP PENETRATIONS THROUGH FIRE RATED SYSTEMS TO MAINTAIN RATING OF SYSTEM. USE MINIMUM
<br />STEEL GAUGE DUCT AS REQUIRED TO MAINTAIN RATING OF SYSTEM.
<br />FLOW CONTROL
<br />GALVANIZED
<br />VALVE
<br />GA
<br />GAUGE
<br />VFDC
<br />VARIABLE FREQUENCY DRIVE
<br />FIRE/RADIATION DAMPER WITH ACCESS PANEL
<br />GAL
<br />GALLON
<br />YAV
<br />VARIABLE AIR VOLUME
<br />28.
<br />WHERE THE EXHAUST DUCT IS CONCEALED WITHIN THE BUILDING CONSTRUCTION, THE EQUIVALENT LENGTH OF THE DUCT
<br />TAG SHALL LOCATED WITHIN 6 FEET OF THE
<br />BALL VALVE FOR PIPING 2-INCHES AND SMALLER,
<br />BUTTERFLY VALVE FOR PIPING 2-1/2 INCHES AND
<br />SHALL BE IDENTIFIED ON A PERMANENT LABEL OR TAG. THE LABEL OR BE
<br />--I��-
<br />GALV
<br />GALVANIZED
<br />Vs
<br />VARIABLE SPEED
<br />EXHAUST DUCT CONNECTION.
<br />COMBINATION FIRE/SMOKE DAMPER WITH ACCESS PANEL
<br />LARGER
<br />GPM
<br />GALLONS PER MINUTE
<br />W
<br />WATTS
<br />29.
<br />CONTRACTOR TO ORDER ALL FIRE/SMOKE DAMPERS WITH INTEGRAL SMOKE DETECTORS AND END STOP INDICATOR OPTIONS.
<br />BUTTERFLY VALVE
<br />HP
<br />HTWR
<br />HORSEPOWER
<br />HIGH TEMPERATURE HOT WATER RETURN
<br />W/
<br />WITH
<br />VERIFY VOLTAGE WITH ELECTRICAL DRAWINGS. IF BUILDING IS EQUIPPED WITH FIRE ALARM SYSTEM ALL FIRE/SMOKE
<br />DAMPERS WILL BE CONNECTED TO BUILDING FIRE ALARM SYSTEM.
<br />EXISTING DUCTWORK TO BE REMOVED (DASHED LINETYPE)
<br />-��I--
<br />W/0
<br />WITHOUT
<br />- - -
<br />CHECK VALVE
<br />HTWS
<br />HIGH TEMPERATURE HOT WATER SUPPLY
<br />30.
<br />ALL MECHANICAL EQUIPMENT SHALL BE THOROUGHLY CLEANED OF ALL DIRT, OIL, CONCRETE, ETC. ANY DENTS, SCRATCHES
<br />DUCT MOUNTED SMOKE DETECTOR PROVIDED AND WIRED BY
<br />HW
<br />HOT WATER
<br />WB
<br />WETBULB
<br />OR OTHER VISIBLE BLEMISHES SHALL BE CORRECTED AND THE APPEARANCE OF THE EQUIPMENT MADE "LIKE NEW" AND TO
<br />ELECTRICAL CONTRACTOR AND INSTALLED IN DUCT BY
<br />ZD
<br />ZONE DAMPER
<br />THE SATISFACTION OF THE ARCHITECT/ENGINEER. UPON COMPLETION, AND BEFORE FINAL ACCEPTANCE OF THE WORK, ALL
<br />MECHANICAL CONTRACTOR. REFER TO SPECIFICATIONS FOR
<br />STRAINER
<br />DEBRIS, RUBBISH, LEFTOVER MATERIALS, TOOLS AND EQUIPMENT SHALL BE REMOVED FROM THE SITE. PROTECTION OF WORK
<br />CONTROL REQUIREMENTS.
<br />UNTIL FINAL ACCEPTANCE: PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE, ENTRANCE OF DIRT AND CONSTRUCTION
<br />BALANCE VALVE WITH INTEGRAL TAPS FOR CONNECTION
<br />DEBRIS FROM THE TIME OF INSTALLATION UNTIL FINAL ACCEPTANCE. ANY MATERIALS AND EQUIPMENT WHICH ARE DAMAGED
<br />A-1
<br />AIR DEVICE TAG
<br />OF DIFFERENTIAL PRESSURE METER. VALVE SHALL
<br />SHALL BE REPAIRED TO "AS NEW" CONDITION OR REPLACED AT THE DIRECTION OF THE ARCHITECT/ENGINEER. WHERE
<br />MARK-C
<br />HAVE NAMEPLATE INDICATING WATER FLOW RATE VERSUS
<br />FACTORY FINISHES OCCUR AND DAMAGE IS MINOR, FINISHES MAY BE TOUCHED UP. IF, IN THE OPINION OF THE
<br />VALVE PRESSURE DROP
<br />ARCHITECT/ENGINEER THE DAMAGE IS EXCESSIVE, FACTORY FINISH SHALL BE REPLACED TO "NEW" CONDITION.
<br />SIDEWALL TRANSFER GRILLE
<br />A
<br />AUTOMATIC FLOW CONTROL VALVE WITH INTEGRAL
<br />31.
<br />DRAWINGS ARE DIAGRAMMATIC AND INDICATE THE GENERAL ARRANGEMENT AND EXTENT OF WORK. EXACT LOCATIONS AND
<br />TEMPERATURE AND PRESSURE TEST PORTS
<br />ARRANGEMENT OF MATERIALS AND EQUIPMENT SHALL BE DETERMINED, WITH THE ACCEPTANCE OF THE ARCHTTECT/ENGINEER,
<br />AS WORK PROGRESSES TO CONFORM IN THE BEST POSSIBLE MANNER WITH THE SURROUNDINGS AND WITH THE ADJOINING
<br />WORK OF OTHER TRADES. WHERE LOCATIONS OF EQUIPMENT, DEVICES OR FIXTURES ARE CONTROLLED BY ARCHITECTURAL
<br />SIDEWALL SUPPLY REGISTER
<br />UNION
<br />FEATURES, ESTABLISH SUCH LOCATIONS BY REFERRING TO DIMENSIONS ON ARCHITECTURAL DRAWINGS AND NOT BY SCALING
<br />DRAWINGS.
<br />32.
<br />IN CASE OF DIFFERENCES BETWEEN DRAWINGS AND SPECIFICATIONS, OR WHERE DRAWINGS AND SPECIFICATIONS ARE NOT
<br />SIDEWALL RETURN GRILLE OR OUTSIDE AIR LOWER
<br />VENTURI FLOW METER
<br />CLEAR OR DEFINITE, THE SUBJECT SHALL BE REFERRED TO ARCHITECT/ENGINEER FOR CLARIFICATION AND INSTRUCTIONS.
<br />PRESSURE AND/OR TEMPERATURE PORT
<br />33.
<br />ANY INTERRUPTION OF EXISTING MECHANICAL AND ELECTRICAL SERVICES SHALL BE COORDINATED IN ADVANCE WITH THE
<br />OWNER'S REPRESENTATIVE. THIS INCLUDES, BUT IS NOT LIMITED TO, SERVICES PROVIDING CHILLED WATER, Ell ECTRICITY, OR
<br />SIDEWALL EXHAUST GRILLE
<br />OTHER CRITICAL SYSTEMS AS MAY BE PERTINENT TO THIS PARTICULAR PROJECT. SERVICE INTERRUPTION TIMES AND
<br />THERMOMETER
<br />DURATION OF INTERRUPTION OF SERVICES SHALL BE DECIDED BY THE OWNER. PROVIDE APPROPRIATE PROVISIONS (SUCH AS
<br />WALL MOUNTED DDC TEMPERATURE SENSOR
<br />ISOLATION SHUT-OFF VALVES, DAMPERS, END CAPS, AND SIMILAR ITEMS) AS NECESSARY TO ACCOMMODATE THE REQUIRED
<br />MOUNT 4'-0" ABOVE FINISHED FLOOR
<br />SERVICE INTERRUPTIONS. IF SHUTDOWNS CANNOT BE ACCOMMODATED, PROVIDE MEANS FOR "WET" TAPPING OR "HOT"
<br />PRESSURE GAUGE WITH GAUGE COCK
<br />TAPPING OF PIPING SYSTEMS.
<br />O
<br />WALL MOUNTED THERMOSTAT
<br />34.
<br />ALL MAIN DUCTWORK SHOWN PER PLAN IS TO BE SHEET METAL OR DUCT BOARD. ALL DUCT BOARD INSTALLATIONS ARE TO
<br />MOUNT 4'-0" ABOVE FINISHED FLOOR
<br />FLEXIBLE CONNECTION
<br />BE APPROVED BY BUILDING OWNER PRIOR TO MATERIAL PURCHASE.
<br />©
<br />WALL MOUNTED CO SENSOR
<br />35.
<br />FIRE & FIRE/SMOKE DAMPERS ARE REQUIRED TO BE UL LISTED AND APPROVED FOR THE ASSEMBLIES LISTED ON THE
<br />MOUNT 4'-0" ABOVE FINISHED FLOOR
<br />PRESSURE RELIEF VALVE
<br />ARCHITECTURAL DRAWINGS. THESE DAMPERS MUST ALSO BE REVIEWED AND APPROVED BY THE ARCHITECT PRIOR TO
<br />ORDERING.
<br />H
<br />O
<br />WALL MOUNTED DDC HUMIDITY SENSOR
<br />MOUNT 4'-0" ABOVE FINISHED FLOOR
<br />OPENING IN WAIL ABOVE CEILING
<br />Os
<br />WAIL MOUNTED HUMIDISTAT SENSOR
<br />VALUES
<br />MOUNT 4'-0" ABOVE FINISHED FLOOR
<br />ENERGY CALCULATION
<br />A
<br />PHOTO DETAIL OR SECTION IDENTIFICATION TARGET
<br />� EQUIPMENT
<br />3 TYPE
<br />MARK
<br />EQUIPMENT TAG
<br />ROOF: R-30
<br />A = DETAIL NUMBER
<br />WALLS: R-19
<br />NOTE:
<br />B
<br />B = SHEET NUMBER ON WHICH DETAIL IS LOCATED
<br />1" DOOR UNDER CUT. ARROW
<br />WINDOWS:
<br />THIS PROJECT HAS MET THE MINIMUM ENERGY CODE REQUIREMENTS AND HAS
<br />UC
<br />INDICATES DIRECTION OF FLOW
<br />SHGC: 25
<br />U VALUE: U-.4
<br />BEEN DESIGNED TO THE MINIMUM VALUES NOTED. ALL MATERIALS USED IN THE
<br />CONSTRUCTION OF THIS PROJECT MUST MEET OR EXCEED THE MINIMUM VALUES
<br />RD
<br />RADIATION DAMPER INSTALLED IN AIR DEVICE
<br />FLEX DUCT
<br />VLT: .58
<br />NOTED PER THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING CODE AND
<br />DOORS: R-2.5
<br />FLORIDA ENERGY CODE.
<br />RD
<br />RADIATION DAMPER INSTALLED IN DUCT
<br />Q (�
<br />Joseph, LCIWPQnCe CJC 1�0
<br />FLOORS:
<br />R-11
<br />NOTE.
<br />SYMBOLS
<br />SHOWN ON THIS MECHANICAL LEGEND ARE FOR Consulting Engineers
<br />NOTE:
<br />ELBOW WITH TURNING VANES REFERENCE PURPOSES ONLY. ALL
<br />OF THESE SYMBOLS
<br />GENERAL NOTES ON THIS MECHANICAL SHEET ARE FOR
<br />MAY NOT
<br />BE USED FOR THIS PROJECT. 1180 HARWOOD AVE., SUITE 3000
<br />ALTAMONTE SPRINGS, FLORIDA 32714
<br />GENERAL REFERENCE PURPOSES ONLY. ALL OF THESE
<br />TEL: 321.972.4466
<br />NOTES MAY NOT BE USED FOR THIS PROJECT.
<br />WWW.JLCENG.COM
<br />CA NO. 28730
<br />M
<br />FORUME
<br />ARCHITECTURE &
<br />INTERIOR DESIGN, INC.
<br />237 S. Westmonte Drive, Suite 220
<br />Altamonte Springs, FL 32714
<br />407.830.1400
<br />AA0002731
<br />www.forumarchitecture.com
<br />Zephyr
<br />Commons
<br />Apartments
<br />City of Zephyrhills, FL
<br />JLC21.0058.00
<br />Adam Joseph Barney
<br />P.E. #: 69124
<br />SET DISTRIBUTIONS:
<br />Z�, SHEET REVISIONS:
<br />EDITED BY: SMB/AJB
<br />N
<br />PROJECT NO.
<br />4097
<br />Apartments
<br />Symbols, Abbreviations,
<br />and General Notes -
<br />Mechanical
<br />M15.00
<br />
|