a
<br />ELECTRICAL SYMBOL LEGEND
<br />WIRING AND POWER NOS:
<br />SYMBOLS SHOWN ARE FOR
<br />REFERENCE PURPOSES ONLY.
<br />-e WALL OUTLET BOX AND SINGLE RECEPTACLE ALL OF THESE SYMBOLS MAY
<br />NOT BE USED FOR THIS
<br />=0 WALL OUTLET BOX AND DUPLEX RECEPTACLE I PROJECT.
<br />TWO GANG WALL OUTLET BOX AND (2) DUPLEX RECEPTACLES
<br />WALL OUTLET BOX AND DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
<br />WALL OUTLET BOX AND DUPLEX RECEPTACLE WITH TOP HALF SWITCHED
<br />WALL OUTLET BOX AND DUPLEX RECEPTACLE CONNECTED TO EMERGENCY SYSTEM
<br />m CEILING OUTLET BOX AND SINGLE RECEPTACLE
<br />® CEILING OUTLET BOX AND DUPLEX RECEPTACLE
<br />=9 WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE
<br />-@ WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
<br />=@S WALL OUTLET BOX AND DUPLEX SAFETY RECEPTACLE
<br />=@T WALL OUTLET BOX AND DUPLEX TWIST -LOCK RECEPTACLE
<br />=@WP WALL OUTLET BOX AND GFCI DUPLEX RECEPTACLE WITH WEATHERPROOF COVER
<br />® WALL OUTLET BOX AND SPECIAL PURPOSE OUTLET AS NOTED ON PLANS
<br />® FLUSH FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE
<br />® FLUSH FLOOR OUTLET BOX WITH (2) DUPLEX RECEPTACLES
<br />® FLUSH FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE AND TELECOMMUNICATIONS OUTLET
<br />10 FLUSH WALL JUNCTION BOX AND BLANK PLATE
<br />m JUNCTION BOX AND BLANK PLATE ABOVE CEILING
<br />m SURFACE MOUNTED JUNCTION BOX AND BLANK PLATE
<br />91WP SURFACE MOUNTED WEATHERPROOF JUNCTION BOX AND COVER
<br />mPB FLUSH GRADE FIBER COMPOSITE PULL BOX AS NOTED
<br />,0' MOTOR CONNECTION AS NOTED
<br />0 FLUSH SHUNT -TRIP BUTTON, MOUNTED 80" TO TOP
<br />® CONTROL AND/OR POWER EQUIPMENT CONNECTION
<br />TIME CLOCK
<br />® PHOTO CELL
<br />0-' DISCONNECT SWITCH, SIZE AS NOTED
<br />-_ 120/208V BRANCH CIRCUIT PANELBOARD, SURFACE MOUNTED
<br />120/208V BRANCH CIRCUIT PANELBOARD, FLUSH MOUNTED
<br />-� 277/480V BRANCH CIRCUIT PANELBOARD
<br />QT TRANSFORMER
<br />8 AUTOMATIC TRANSFER SWITCH
<br />BRANCH CIRCUIT HOMERUN WITH PANEL NAME AND CIRCUIT NUMBER,
<br />q_3� QUANTITY OF ARROWHEADS DENOTES QUANTITY OF BRANCH CIRCUITS
<br />BRANCH CIRCUIT WIRING, PROVIDE QUANTITY OF CONDUCTORS REQUIRED
<br />FOR CIRCUITING AND SWITCHING INDICATED ON PLANS
<br />POWER LEG ONLY (NO SWITCH LEG BETWEEN ROOMS)
<br />--3 CONDUIT CAPPED OFF
<br />-� CONDUIT CONTINUED
<br />0 CONDUIT RUN UP
<br />--0 CONDUIT RUN DOWN
<br />-* GROUND OR GROUND ROD AS NOTED
<br />LIGHTING AND SWITCHING
<br />CEILING MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />0 CEILING MOUNTED RECESSED DOWNLIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />0 CEILING MOUNTED RECESSED WALLWASH FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />0 CEILING MOUNTED "CLOSE TO CEILING" FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />+ PENDANT MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />TRACK LIGHT FIXTURE WITH HEADS AS REQUIRED, REFER TO LIGHT FIXTURE SCHEDULE
<br />FO WALL MOUNTED LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />® CEILING MOUNTED LIGHT FIXTURE WITH EMERGENCY BACKUP
<br />O CEILING MOUNTED RECESSED DOWNLIGHT FIXTURE WITH EMERGENCY BACKUP
<br />Q WALL MOUNTED LIGHT FIXTURE WITH EMERGENCY BACKUP
<br />4s;P WALL MOUNTED EMERGENCY BATTERY LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />NEF.a CEILING MOUNTED EMERGENCY BATTERY LIGHT FIXTURE, REFER TO LIGHT FIXTURE SCHEDULE
<br />®1 CEILING MOUNTED EXIT SIGN WITH EMERGENCY BACKUP, REFER TO LIGHT FIXTURE SCHEDULE
<br />1,0+ WALL MOUNTED EXIT SIGN WITH EMERGENCY BACKUP, REFER TO LIGHT FIXTURE SCHEDULE
<br />Al COMBINATION EXIT SIGN AND EMERGENCY LIGHT FIXTURE WITH BATTERY BACKUP
<br />So WALL OUTLET BOX AND SINGLE POLE SWITCH ('a' INDICATES SWITCH LEG)
<br />S3 WALL OUTLET BOX AND THREE-WAY SWITCH
<br />SF WALL OUTLET BOX AND FAN CONTROL SWITCH
<br />SD WALL OUTLET BOX AND DIMMER SWITCH AS REQUIRED FOR LOAD SERVED
<br />SD3 WALL OUTLET BOX AND THREE-WAY DIMMER SWITCH
<br />SM WALL OUTLET BOX WITH SINGLE POLE MANUAL MOTOR STARTER SWITCH
<br />SO WALL OUTLET BOX AND DUAL TECHNOLOGY OCCUPANCY SENSOR
<br />ST WALL OUTLET BOX AND DIGITAL TTMECLOCK SWITCH FOR AUTOMATIC CONTROL
<br />CEILING OUTLET BOX AND DUAL TECHNOLOGY OCCUPANCY SENSOR
<br />® CEILING OUTLET BOX AND DAYLIGHT HARVESTING SENSOR
<br />FIRE ALARM SYSTEM LEGEND
<br />[F MANUAL PULL STATION
<br />n4cd WALL MOUNTED HORN WITH STROBE (cd=CANDELA RATING)
<br />MOP WALL MOUNTED HORN WITH STROBE IN WEATHERPROOF ENCLOSURE
<br />CEILING MOUNTED HORN WITH STROBE
<br />HIM WALL MOUNTED MINI HORN
<br />EMM WALL MOUNTED MINI HORN WITH STROBE
<br />91 WALL MOUNTED VOICE EVACUATION SPEAKER WITH STROBE
<br />(94 CEILING MOUNTED VOICE EVACUATION SPEAKER WITH STROBE
<br />RD WALL MOUNTED STROBE
<br />(D SMOKE DETECTOR
<br />OO CO SMOKE AND CARBON MONOXIDE COMBINATION DETECTOR
<br />DUCT MOUNTED SMOKE DETECTOR
<br />(D HEAT DETECTOR
<br />IM REMOTE DUCT DETECTOR INDICATOR LIGHT AND TEST SWITCH (NUMBER' INDICATES QUANTITY)
<br />® FAN SHUT -DOWN RELAY
<br />❑D ELECTROMAGNETIC DOOR RELEASE DEVICE
<br />41- SMOKE DAMPER (PROVIDE BY MECHANICAL, CONNECTED BY ELECTRICAL)
<br />0 FIREMAN'S PHONE JACK
<br />SPRINKLER SYSTEM SUPERVISORY SWITCH CONNECTION
<br />© SPRINKLER SYSTEM FLOW SWITCH CONNECTION
<br />CEI CONTROL MODULE
<br />FMUI MONITOR MODULE
<br />® LOCK BOX
<br />&M FIRE ALARM CONTROL PANEL
<br />F� FIRE ALARM TERMINAL CABINET
<br />% FIRE ALARM ANNUNCIATOR PANEL
<br />&M DIGITAL ALARM COMMUNICATOR TRANSMITTER
<br />TELECOMMUNICATION SYSTEM LEGEND
<br />COMBINATION TELECOMMUNICATIONS/DATA WALL OUTLET BOX AND BLANK PLATE
<br />WITH MIN. 3/4"C. TO ACCESSIBLE CEILING SPACE. COORDINATE OUTLET
<br />REQUIREMENTS WITH OWNER.
<br />W TELECOMMUNICATIONS WALL OUTLET BOX AND BLANK PLATE FOR WALL MOUNTED
<br />TELEPHONE WITH MIN. 3/4"C. TO ACCESSIBLE CEILING SPACE. COORDINATE
<br />OUTLET REQUIREMENTS WITH OWNER.
<br />DATA WALL OUTLET BOX AND BLANK PLATE WITH MIN. 3/4°C. TO ACCESSIBLE
<br />CEILING SPACE. COORDINATE OUTLET REQUIREMENTS WITH OWNER.
<br />FLUSH FLOOR OUTLET BOX WITH POWER DEVICE AND TELECOMMUNICATIONS OUTLET
<br />® WITH MIN. 3/4"C. TO ACCESSIBLE CEILING SPACE.
<br />A CEILING OUTLET BOX AND BLANK PLATE WITH MIN. 3/4"C. TO TTB FOR WIRELESS
<br />ACCESS POINT. COORDINATE OUTLET REQUIREMENTS WITH OWNER.
<br />TV COMBINATION TELECOMMUNICATIONS/TELEVISION WALL OUTLET BOX AND BLANK
<br />v PLATE. COORDINATE OUTLET AND CABLING REQUIREMENTS WITH OWNER.
<br />® 3/4" PLYWOOD TELEPHONE TERMINAL BOARD, SIZE AS SHOWN ON PLANS.
<br />C&C TELEPHONE TERMINAL CABINET, SIZE AS NOTED ON PLAN.
<br />GENERAL NOTES
<br />1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OF THE NATIONAL
<br />ELECTRICAL CODE (NFPA 70), AND THE LATEST ADOPTED EDITION OF THE FLORIDA BUILDING CODE.
<br />2. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND COORDINATE WITH ALL EQUIPMENT
<br />MANUFACTURER/INSTALLERS PRIOR TO BIDDING.
<br />3. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES, AND EQUIPMENT SHALL BE LABEL LISTED BY AN
<br />APPROVED THIRD -PARTY TESTING AGENCY.
<br />BUILDING_
<br />4. INSTALLATION HEIGHT OF EQUIPMENT (TO CENTERLINE) ABOVE FINISHED FLOOR UNLESS NOTED
<br />OTHERWISE SHALL BE:
<br />RECEPTACLE = 18"
<br />CLOCK = 7'-6"
<br />SWITCH = 44"
<br />MODULAR JACK FOR WALL MOUNTED TELEPHONE = 48"
<br />MODULAR TELEPHONE JACK = 18"
<br />TELEVISION OUTLET = 84"
<br />COMPUTER OUTLET = 18"
<br />CALL SWITCH = 44"
<br />REMOTE TEST STATION FOR DUCT DETECTOR = 52"
<br />C = ABOVE COUNTER BACKSPLASH, COORDINATE WITH ARCHITECTURAL ELEVATIONS AND MILLWORK.
<br />5. ALL CONDUIT AND WIRING SHALL BE CONCEALED IN WALLS OR ABOVE CEILINGS UNLESS NOTED
<br />OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. ALL DEVICE OUTLET BOXES SHALL BE
<br />RECESSED UNLESS NOTED OTHERWISE OR APPROVED BY THE ARCHITECT/ENGINEER. WHERE
<br />APPROVED OR NOTED SURFACE METAL RACEWAY AND DEVICE BOXES SHALL BE USED IN LIEU OF
<br />CONDUIT AND CONCEALED BOXES AT NO EXTRA COST TO THE OWNER.
<br />6. ALL CONDUIT ROUTING SHOWN IS APPROXIMATE ONLY. CONTRACTOR SHALL FIELD VERIFY FINAL
<br />ROUTE WITH ALL OTHER TRADES AND CONDITIONS IN FIELD PRIOR TO ROUGH -IN.
<br />7. CONDUIT RUNS SHOWN ARE SCHEMATIC AND DO NOT INDICATE THE NECESSARY FITTINGS AND
<br />JUNCTION BOXES THAT ARE INCLUDED IN THE SCOPE OF THE WORK.
<br />8. CONTRACTOR SHALL PERMANENTLY IDENTIFY ALL WIRING WITH THE SOURCE AND CIRCUIT AT ALL
<br />ELECTRICAL EQUIPMENT, PULL AND JUNCTION BOXES AND ELECTRICAL TERMINATIONS PROVIDED OR
<br />ASSOCIATED WITH THIS CONSTRUCTION.
<br />9. COORDINATE EXACT LOCATION OF LIGHTING FIXTURES IN MECH. ROOMS/SPACES WITH DUCTWORK
<br />INSTALLER PRIOR TO ROUGH -IN. LOCATE BELOW DUCTWORK(8'-0" AFF MINIMUM) CENTERED IN
<br />ROOM AS MUCH AS POSSIBLE.
<br />10. COORDINATE EXACT INSTALLATION REQUIREMENTS OF OUTLETS IN MILLWORK WITH ARCHITECTURAL
<br />DRAWINGS, APPROVED SHOP DRAWINGS AND MILLWORK INSTALLER PRIOR TO ROUGH -IN.
<br />11. VERIFY EXACT LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL INSTALLER PRIOR TO
<br />ROUGH -IN.
<br />12. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF ALL LIGHT FIXTURES
<br />13. PROVIDE NYLON PULLSTRINGS IN ALL EMPTY CONDUITS.
<br />14. COORDINATE THE EXACT LOCATION OF ALL ELECTRICAL EQUIPMENT LOCATED IN ELEVATOR MACHINE
<br />ROOMS, SHAFTS AND PITS. LOCATE EQUIPMENT AS REQUIRED TO MEET APPLICABLE CODES.PROVIDE
<br />AUTOMATIC DISCONNECTION OF THE ELEVATOR MAIN POWER SUPPLY (PER ANSI A17.1, RULE 102.2
<br />1987 ED.) PRIOR TO ACTIVATION OF AUTOMATIC SPRINKLER LOCATED WITHIN THE ELEVATOR MACHINE
<br />ROOM, PIT OR SHAFT. COORDINATE WITH FIRE PROTECTION AND FIRE ALARM INSTALLER.
<br />15. COORDINATE THE REQUIRED SIZE OF ALL CIRCUIT BREAKERS FEEDING EQUIPMENT, (I.E. MOTORS,
<br />HVAC, KITCHEN EQUIPMENT, SPECIAL PURPOSE OUTLETS, ELEVATORS, OWNER FURNISHED EQUIPMENT
<br />ETC. ) WITH APPROVED EQUIPMENT SHOP DRAWINGS AND OWNER REPRESENTATIVES PRIOR TO
<br />ORDERING PANELBOARDS. BREAKERS SHALL BE SIZED PER THE NEC, THE EQUIPMENT NAME PLATE
<br />AND MANUFACTURERS RECOMMENDATIONS.
<br />16. ALL DIMMED CIRCUITS SHALL BE PROVIDED WITH DEDICATED NEUTRALS FOR EACH DIMMER AND PHASE
<br />CONDUCTOR THROUGHOUT THE ENTIRE CIRCUIT.
<br />17. THE POWER COMPANY SHALL BE CONTACTED WITHIN 10 DAYS OF THE AWARD OF THE CONTRACT BY
<br />THE CONTRACTOR TO VERIFY THE ACTUAL AVAILABLE SHORT CIRCUIT FAULT CURRENT (AIC) AT THE
<br />TRANSFORMER SECONDARY BUSHINGS. THE CONTRACTOR SHALL PROVIDE ELECTRICAL DISTRIBUTION
<br />AND UTILIZATION EQUIPMENT AND PANELBOARDS WHICH HAVE AIC/WITHSTAND RATINGS GREATER THAN
<br />THE AVAILABLE AIC AT EACH POINT IN THE ELECTRICAL SYSTEM.
<br />18. CONTRACTOR SHALL INCLUDE IN HIS BID THE TRANSPORT AND DISPOSAL OR RECYCLING OF ALL
<br />WASTE MATERIALS GENERATED BY THIS PROJECT IN ACCORDANCE WITH ALL RULES, REGULATIONS AND
<br />GUIDELINES APPLICABLE.
<br />19. PANEL SCHEDULES INDICATE CIRCUIT DESIGNATIONS ONLY. CONTRACTOR TO PROVIDE MATERIALS AS
<br />REQUIRED WHEN NEUTRALS ARE SHARED TO COMPLY WITH NEC REQUIREMENTS. ALL SINGLE PHASE
<br />MULTIWIRE BRANCH CIRCUITS SHALL BE FED VIA A TWO POLE BREAKER OR TWO SINGLE POLE
<br />BREAKERS WITH AN IDENTIFIED HANDLE TIE. ALL THREE PHASE MULTIWIRE BRANCH CIRCUITS SHALL
<br />BE FED VIA A THREE POLE BREAKER OR THREE SINGLE POLE BREAKERS WITH AN IDENTIFIED HANDLE
<br />11E (PER NEC 210.413).
<br />20. PER NEC 110.22; PROVIDE PERMANENT LABELING FOR ALL SERIES RATED PANEL ENCLOSURES TO
<br />READ AS FOLLOWS: CAUTION - SERIES COMBINATION SYSTEM RATED AMPERES. IDENTIFIED
<br />REPLACEMENT COMPONENTS REQUIRED.
<br />21. ELECTRICAL CONTRACTOR SHALL PROVIDE FULL LIGHTNING PROTECTION SYSTEM FOR THIS PROJECT
<br />PER NFPA 780.
<br />GROUNDING:
<br />22. ALL METAL RACEWAYS, INCLUDING CONDUIT, WIRE TROUGHS, WIREMOLD, ETC., SHALL BE GROUNDED.
<br />ALL CONNECTIONS IN METAL RACEWAYS SHALL BE COMPLETED IN SUCH A MANNER AS TO MAINTAIN A
<br />CONTINUOUS PATH TO GROUND THROUGHOUT THE ENTIRE LENGTH OF THE RACEWAY.
<br />WIRING:
<br />23. UNLESS NOTED OTHERWISE ON THE DRAWINGS OR ON THE EQUIPMENT WIRING SCHEDULE, EACH
<br />BRANCH CIRCUIT HOME RUN SHALL BE THREE (3) #12 AWG THHN/THWN (1 HOT, 1 NEUTRAL & 1
<br />EQUIPMENT GROUND) IN 3/4" EMT CONDUIT. PROTECT EACH CIRCUIT WITH A 20 AMPERE, 1-POLE
<br />OVERCURRENT DEVICE UNLESS NOTED OTHERWISE. COMBINED NEUTRALS ARE NOT PERMITTED.
<br />24. THE USE OF 'NM' CABLE FOR BRANCH CIRCUIT WIRING IS ACCEPTABLE WHERE ALLOWED BY THE NEC
<br />AND AUTHORITY HAVING JURISDICTION.
<br />BDA SYSTEM:
<br />25. ALL BUILDINGS WITHIN THIS PROJECT SHALL HAVE AN APPROVED THIRD -PARTY PROVIDE A SPECTRUM
<br />ANALYSIS GRID TEST OF THE BUILDINGS AND PROVIDE A COPY OF THE ANALYSIS OF THE RADIO
<br />SIGNAL STRENGTH AND RECOMMENDATIONS FOR THE REQUIREMENT OF A DAS/BDA SYSTEM (WHETHER
<br />NECESSARY TO INSTALL) TO THE G.C. AND AHJ. IF REQUIRED TO BE ADDED, BASED ON TESTING,
<br />DESIGN WILL BE PROVIDED BY OTHERS (DAS/BDA CONTRACTOR) UNDER A SEPARATE PERMIT AND IN
<br />CONFORMANCE TO THE FFPC, FAC AND NFPA. FINAL TESTING WILL BE REQUIRED AT COMPLETION OF
<br />THE BUILDING CONSTRUCTION PRIOR TO OBTAINING THE CERTIFICATE OF OCCUPANCY. THE SIGNAL
<br />STRENGTH SHALL MEET THE REQUIREMENTS OF THE FLORIDA FIRE PREVENTION CODE 6TH EDITION;
<br />NFPA 1 11.10; NFPA 72-2016 EDITION 24.5.2.2, 24.5.2.3; AND MUST BE TESTED IN ACCORDANCE
<br />WITH THE PROVISIONS SET FORTH IN NFPA 72-2016 EDITION 14.4.10 (1-6) AND A14.4.10 (1-3).
<br />Josep%, Laweence CSC Co
<br />Consulting Ingineeps
<br />1180 HARWOOD AVE., SUITE 3000
<br />ALTAMONTE SPRINGS, FLORIDA 32714
<br />TEL: 321.972.4466
<br />WWW.JLCENG.COM
<br />CA NO. 28730
<br />FORUME
<br />ARCHITECTURE &
<br />INTERIOR DESIGN, INC.
<br />237 S. Westmonte Drive, Suite 220
<br />Altamonte Springs, FL 32714
<br />407.830.1400
<br />AA0002731
<br />www.forumarGhitecture.com
<br />Zephyr
<br />Commons
<br />Apartments
<br />City of Zephyrhills, FL
<br />JLC21.0058.00
<br />Blake Lawrence Suddeth
<br />P.E. #: 69060
<br />SET DISTRIBUTIONS:
<br />0 SHEET REVISIONS:
<br />EDITED BY: MAR/BLS
<br />PROJECT N0, 4097
<br />Apartments
<br />Symbols, Abbreviations,
<br />and General Notes -
<br />Electrical
<br />E16-00