GENERAL NOTES: <br />FORUME <br />0 <br />rJ <br />,a <br />ci_�HT-9 <br />Maintenance & Trash - Floor Plan - Power & Systems <br />1 /4" = 1'-0" <br />PANEL'HT' <br />LOCATION: MAINT/TRASH <br />VOLTAGE: 120/208V 30 4W <br />MIN. AIC RATING: 1OK AIC <br />NOTES: <br />PROVIDE TYPED WRITTEN DIRECTORY <br />PROVIDE GROUND &NEUTRAL BUS <br />TYPE: SQUARE 'D' - TYPE NQ <br />MAINS. 100A ❑ MLO ® MCB <br />MOUNTING: SURFACE <br />FED FROM: UTILITY XFMR <br />LUGS: ❑ SUB -FEED <br />❑ FEED-THRU <br />ENCLOSURE: NEMA 3R <br />CIRCUIT DESCRIPTION <br />N <br />o <br />Z <br />BRANCH CIRCUIT <br />BKR <br />LOAD <br />KVA <br />PHASE <br />0 <br />LOAD <br />KVA <br />BKR <br />BRANCH CIRCUIT <br />z <br />CIRCUIT DESCRIPTION <br />Y <br />v <br />NEU <br />GND <br />COND <br />0 <br />NEUT <br />GND <br />COND <br />1 <br />TRASH COMPACTOR <br />4 <br />4 <br />10 <br />1' <br />60/3 <br />3.86 <br />A <br />1.00 <br />30/2 <br />10 <br />10 <br />10 <br />/4' <br />MCU-1 <br />2 <br />3 <br />- <br />4 <br />- <br />- <br />- <br />- <br />3.86 <br />B <br />1.00 <br />- <br />10 <br />- <br />- <br />- <br />- <br />4 <br />5 <br />- <br />4 <br />- <br />- <br />- <br />- <br />3.86 <br />C <br />0.50 <br />20/1 <br />12 <br />12 <br />12 <br />1/2" <br />GARAGE DOOR OPENER <br />6 <br />7 <br />LIGHTS - MAINTENANCE <br />12 <br />12 <br />12 1/2' <br />20/1 <br />0.10 <br />A <br />0.36 <br />20/1 <br />12 <br />12 <br />1 12 <br />1/2 0 <br />RECEPTACLES - EXTERIOR <br />8 <br />9 <br />LIGHTS - EXTERIOR <br />1 <br />12 <br />12 <br />12 1/2' <br />20/1 <br />0.10 <br />B <br />0.36 <br />20/1 <br />12 <br />12 <br />1 12 <br />1/2" <br />IRECEPTACLES - MAINTENANCE <br />10 <br />11 <br />SPARE <br />- <br />- <br />- <br />- <br />20/1 <br />- <br />C <br />0.72 <br />20/1 <br />12 <br />12 <br />12 <br />1/2- <br />RECEPTACLES - MAINTENANCE <br />12 <br />13 <br />SPARE <br />- <br />- <br />- <br />- <br />20/1 <br />- <br />A <br />0.72 <br />20/1 <br />12 <br />1 12 <br />12 <br />1/2' <br />RECEPTACLES - MAINTENANCE <br />14 <br />15 <br />SPARE <br />- <br />- <br />- <br />- <br />20/1 <br />- <br />B <br />1.00 <br />20/1 <br />12 <br />12 <br />12 <br />1/2" <br />CART CHARGER <br />16 <br />17 <br />SPARE <br />- <br />- <br />- <br />- <br />20/1 <br />- <br />C <br />- <br />20/1 <br />12 <br />12 <br />12 <br />1/2" <br />SPARE <br />18 <br />19 <br />SPACE ONLY <br />- <br />- <br />- <br />- <br />20/1 <br />- <br />A <br />- <br />- <br />- <br />- <br />- <br />- <br />SPACE ONLY <br />20 <br />21 <br />SPACE ONLY <br />- <br />- <br />- <br />- <br />- <br />- <br />B <br />- <br />- <br />- <br />I - <br />I - <br />- <br />SPACE ONLY <br />22 <br />23 <br />SPACE ONLY <br />- <br />- <br />- <br />- <br />- <br />- <br />C <br />- <br />- <br />- <br />- <br />- <br />- <br />SPACE ONLY <br />24 <br />25 <br />SPACE ONLY <br />- <br />- <br />- <br />- <br />- <br />- <br />A <br />- <br />30/3 <br />10 <br />10 <br />10 <br />3/4' <br />SURGE PROTECTIVE DEVICE (SPD) <br />26 <br />27 <br />SPACE ONLY <br />- <br />- <br />- <br />- <br />- <br />- <br />B <br />- <br />- <br />10 <br />- <br />- <br />- <br />- <br />28 <br />29 <br />SPACE ONLY <br />- <br />- <br />- <br />- <br />- <br />- <br />C <br />- <br />- <br />10 <br />- <br />- <br />- <br />- <br />30 <br />EQUIPMENT <br />SERVED <br />CONN. <br />LOAD <br />L.F. <br />D.F. <br />DEMAND LOAD <br />LIGHTING <br />0.20 KVA <br />125% <br />0.25 KVA <br />RECEPTACLES - GENERAL <br />2.16 KVA <br />100% <br />2.16 KVA <br />EQUIPMENT <br />15.08 KVA <br />100% <br />15.08 KVA <br />NOTES: <br />1) CONNECT CIRCUIT VIA PHOTOCELL <br />2) NON -COINCIDENTAL LOAD NOT INCLUDED IN CALC <br />TOTAL DEMAND LOAD: 17.49 KVA <br />TOTAL DEMAND AMPS: 48.58 AMPS <br />LIGHTING FIXTURE <br />SCHEDULE <br />- MAINTENANCE/T11 RASH <br />MARK <br />DESCRIPTION <br />MANUFACTURER <br />MODEL <br />VOLTS <br />LAMP <br />LAMP <br />LAMP <br />FIXTURE <br />QTY <br />WATTS <br />MODEL <br />WATTS <br />TA <br />1'X4' LED SURFACE MOUNTED ENCLOSED AND GASKETED <br />COLUMBIA <br />LXEM4-35ML-DFA-EU <br />120 <br />1 <br />47 <br />LED <br />47 <br />FIBERGLASS FIXTURE. UL WET LABEL RATED. <br />TB <br />EXTERIOR BUILDING LED WALL SCONCE IN DIE-CAST ALUMINUM <br />TBD <br />TBD <br />120 <br />1 <br />36 <br />LED <br />36 <br />HOUSING, IP RATED, UL WET LABEL RATED <br />NOTES: <br />1. DIVISION 16 CONTRACTOR SHALL VERIFY ALL FIXTURE TYPES AND FINISHES WITH OWNER PRIOR TO ORDERING. <br />Maintenance & Trash - Floor Plan - Lighting <br />TO UTILITY PAD MOUNT <br />TRANSFORMER <br />COORDINATE REQUIREMENTS WITH <br />UTILITY COMPANY PRIOR TO ROUGH -IN <br />(4)#1/0 AWG. AL. IN 2"C. <br />NOTE: <br />PER (2020 FBCEC C405.5.3, 7th EDITION): <br />ALL CONDUCTORS FOR FEEDERS AND <br />BRANCH CIRCUITS ARE DESIGNED FOR A <br />MAXIMUM OF 5% VOLTAGE DROP TOTAL. <br />U11 LITY <br />MET <br />ER <br />(4)#1/0 AWG. AL. IN 2"C. <br />AIC=7,961A <br />HOUSE <br />PNL 'HPP' <br />100A MCB <br />120/208V <br />10, 3W <br />BOND <br />Power Riser Diagram <br />1 /4" = 1'-0" <br />PROVIDE HARD WIRED SURGE PROTECTIVE <br />DEVICE OF SAME MANUFACTURER AS <br />PANEL <br />FINISHED GRADE <br />#8 CU <br />6ft MIN <br />CONCRETE ENCASED <br />\___�i-5/8-X20' CU CLAD GROUND ROD <br />Not To Scale <br />A. DO NOT SCALE ELECTRICAL DRAWINGS FOR ANY DIMENSIONS. <br />B. ALL WORK SHALL COMPLY WITH THE 2017 NATIONAL ELECTRICAL CODE, NATIONAL, STATE <br />AND LOCAL CODES. PROVIDE GROUNDING AND BONDING PER NEC 250. <br />C. SEE SINGLE LINE DIAGRAM FOR FEEDER WIRE AND CONDUIT SIZE. ALL CIRCUITS NOT <br />SIZED ON DRAWING SHALL BE INSTALLED TO MEET MINIMUM SIZE REQUIRED BY NEC. ALL <br />CONDUCTORS SHALL HAVE AN EQUIPMENT GROUND WIRE SIZED PER NEC. <br />D. FIELD VERIFY EXACT LOCATION OF ALL DEVICES AND EQUIPMENT PRIOR TO ROUGH IN. <br />E. SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT FIXTURE LOCATIONS AND <br />ORIENTATIONS. <br />F. REFER TO ARCHITECTURAL ELEVATIONS AND SECTIONS FOR ADDITIONAL LIGHTING FIXTURE <br />MOUNTING DETAILS AND INFORMATION. <br />G. ALL EMERGENCY LIGHTING FIXTURES AND EXIT SIGNS SHALL BE CONNECTED "HOT" TO <br />THE INDICATED LOCAL LIGHTING CIRCUIT. <br />H. VERIFY ALL MOUNTING HEIGHTS AND PENDANT LENGTHS WITH ARCHITECT AND ENGINEER <br />PRIOR TO ORDERING FIXTURES. <br />I. EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A PERIOD OF 90 MINUTES IN THE <br />EVENT OF FAILURE OF NORMAL LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE <br />ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS AT LEAST AN AVERAGE OF 1 <br />FOOTCANDLE (10 LUX) AND A MINIMUM AT ANY POINT OF 0.1 FOOTCANDLE (1 LUX) <br />MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL. ILLUMINATION LEVELS SHALL <br />BE PERMITTED TO DECLINE TO 0.6 FOOTCANDLE (6 LUX) AVERAGE AND A MINIMUM AT <br />ANY POINT OF 0.06 FOOTCANDLE (0.6 LUX) AT THE END OF THE EMERGENCY LIGHTING <br />TIME DURATION. A MAXIMUM -TO -MINIMUM ILLUMINATION UNIFORMITY RATIO OF 40:1 <br />SHALL NOT BE EXCEEDED. <br />REFERENCE NOTES: O <br />O1 CONNECT CIRCUIT VIA PHOTOCELL FOR AUTOMATIC CONTROL OF LIGHT FIXTURES. <br />0 PROVIDE DISCONNECT SWITCH FOR CONNECTION OF TRASH COMPACTOR. COORDINATE <br />DISCONNECT SIZE, LOCATION AND FUSING REQUIREMENTS WITH TRASH COMPACTOR <br />MANUFACTURER PRIOR TO ROUGH -IN. PROVIDE CONDUIT AND CONTROL WIRING FOR <br />CONTROL PANEL PER MANUFACTURER INSTRUCTIONS. <br />O COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS OF TRASH COMPACTOR <br />POWER PACK UNIT WITH EQUIPMENT INSTALLER PRIOR TO ROUGH -IN. <br />COORDINATE PANEL AND METER LOCATION WITH OWNER, CIVIL CONTRACTOR AND UTILITY <br />COMPANY PRIOR TO ROUGH -IN. <br />O5 PROVIDE WALL MOUNTED, DUAL TECHNOLOGY, LOW VOLTAGE VACANCY SENSOR, <br />WATTSTOPPER #DW-100-24 (OR APPROVED SUBSTITUTION) FOR AUTOMATIC CONTROL OF <br />LIGHTING. CONNECT LIGHTING IN SPACE AS SHOWN ON PLANS VIA WATTSTOPPER LIGHTING <br />POWER PACK #BZ-200 (OR APPROVED SUBSTITUTION). PROVIDE ALL ADDITIONAL POWER <br />PACKS, RELAYS, SENSORS AS REQUIRED FOR COMPLETE COVERAGE OF SPACE AND <br />SWITCHING AS SHOWN ON PLANS. INSTALLATION SHALL COMPLY WITH FLORIDA ENERGY <br />CONSERVATION CODE 2020 7TH EDITION SECTION C405.2.1. <br />© PROVIDE PUSHBUTTON CONTROL AND LOW VOLTAGE WIRING FOR GARAGE DOOR OPENER <br />AS REQUIRED BY OWNER/MANUFACTURER. <br />O7 PROVIDE 120V CEILING MOUNTED OUTLET FOR GARAGE DOOR OPENER. COORDINATE <br />LOCATION WITH DOOR INSTALLER PRIOR TO ROUGH -IN. PROVIDE LOW VOLTAGE WIRING <br />AND PUSH BUTTON LOCATED NEAR DOOR AS REQUIRED. <br />® PROVIDE EXTERIOR GARAGE DOOR KEYPAD. COORDINATE LOCATION AND REQUIREMENTS <br />WITH GARAGE DOOR INSTALLER. PROVIDE LOW VOLTAGE WIRING AS REQUIRED. <br />O9 PROVIDE 120V ELECTRICAL CONNECTION FOR CHARGING STATION. COORDINATE EXACT <br />LOCATION AND REQUIREMENTS WITH ARCHITECT/MANUFACTURER PRIOR TO ROUGH -IN. <br />10 CONNECT INTERIOR MECHANICAL MINI -SPLIT UNIT MAU-1 THROUGH EXTERIOR UNIT MCU-1. <br />CONNECT PER MANUFACTURER'S RECOMMENDATIONS, AND PROVIDE ALL CONTROL WIRING, <br />CONDUIT, ETC. AS REQUIRED. <br />Joseph, Lawrence & Co <br />Consulting Engineeips <br />1180 HARWOOD AVE., SUITE 3000 <br />ALTAMONTE SPRINGS, FLORIDA 32714 <br />TEL: 321.972.4466 <br />WWW.JLCENG.COM <br />CA NO. 28730 <br />ARCHITECTURE & <br />INTERIOR DESIGN, INC. <br />237 S. Westmonte Drive, Suite 220 <br />Altamonte Springs, FL 32714 <br />407.830.1400 <br />AA0002731 <br />www.forumarchitecture.com <br />Zephyr <br />Commons <br />Apartments <br />City of Zephyrhills, FL <br />J LC21.0058.00 <br />r <br />a) <br />°c Blake Lawrence Suddeth <br />u P.E. #: 69060 <br />a SET DISTRIBUTIONS: <br />U <br />U <br />C <br />a <br />N <br />0 <br />L <br />0 <br />C <br />0 <br />0 <br />0 <br />m <br />m <br />c <br />m <br />U <br />C <br />C <br />m <br />�N <br />N <br />0 <br />0 <br />0 SHEET REVISIONS: <br />r <br />E <br />2 <br />0 <br />LL <br />0 <br />a <br />0 <br />a <br />EDITED BY: MJR/BLS <br />r PROJECT NO. 4097 <br />U <br />Z <br />Maintenance & Trash <br />Floor Plan <br />Electrical <br />E20.43 <br />