GENERAL NOTES: <br />THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2017 FLORIDA BUILDING CODE <br />6TH EDITION <br />ARKAY ENGINEERING, INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL <br />ENGINEERING COMPANY; HAS APPLIED "RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN <br />OF THIS STRUCTURE. <br />THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE <br />FOLLOWING SUPERIMPOSED LOADS: <br />FLOOR: <br />LIVE LOAD - 50 P.S.F. <br />DEAD LOAD - 10 P.S.F. <br />ROOF: <br />LIVE LOAD - 20 P.S.F. <br />DEAD LOAD - 10 P.S.F. <br />WIND: <br />BUILDING IS DESIGNED TO CONFORM TO ASCE 7-10, CHAPTERS 26 THRU 31; PER 2017 FLORIDA <br />BUILDING CODE 6TH ADDITION SECTION 1609 <br />WIND DESIGN ASSUMPTIONS: <br />BUILDING EXPOSURE - B <br />BUILDING RISK CATEGORY - II <br />MEAN ROOF HEIGHT 30' OR LESS <br />HEIGHT & EXPOSURE ADJUSTMENT <br />COEFFICIENT = 1.0 <br />ENCLOSED BUILDING <br />INTERNAL PRESSURE COEFFICIENT = +!- 0.18 <br />WIND SPEED SHOWN AT THE BOTTOM RIGHT <br />CORNER OF THIS SHEET <br />SOIL BEARING & COMPACTION <br />COMPONENT & CLADDING WIND LOADS <br />ALL OTHER <br />BUILDING <br />ROOF OVERHANG <br />COMPONENT <br />ZONE <br />LOADS <br />LOADS <br />1 <br />N/A <br />+32.3i-35.3 <br />2 <br />-65.7 <br />+32.3/-56.2 <br />3 <br />-110.6 <br />+32.3/-89.0 <br />4 <br />N/A <br />+35.3/-38.2 <br />5 <br />N/A <br />+35.3/-47.2 <br />THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. <br />(MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL <br />ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. <br />FOUNDATION LOADING. <br />ARKAY ENGINEERING, INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL <br />ENGiNEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SiTE <br />NOR PERFORMING ANY SOIL TESTING. <br />ARKAY ENGINEERING, INC. SHALL NOT BE RESPONISiBLE FOR THE SITE SOILS ABILITY TO SUPPORT <br />THE BUILDING LOADS. <br />SOIL TERMITE TREATMENT: <br />TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED T. ERMITICIDES, INCLUDING PESTICIDES <br />APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR <br />USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. <br />A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED <br />PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE <br />SHALL STATE <br />"THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA <br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES." <br />BUILDING DATA - <br />IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION, <br />ABOVE DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE <br />OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE <br />BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR. THE SYSTEM <br />MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL. <br />INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION, <br />BACKFILLING & COMPACTION ARE COMPLETE <br />ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED <br />(INCLUDING ANY BOXED OR FORMED AREAS) - <br />BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE <br />WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN <br />ADEQUATE SIZE & DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE <br />INITIAL TREATMENT. <br />A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL <br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT <br />SHALL BE REQUIRED <br />ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER <br />MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT <br />EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS <br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS <br />COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE <br />VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED. <br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE <br />BUILDING SIDEWALLS <br />AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW <br />AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES <br />FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS. <br />THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE <br />CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION <br />WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION <br />FOR FUTURE TERMITE INFESTATIONS <br />SAFETY GLAZING: <br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF <br />GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308: <br />(1) GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR <br />ASSEMBLIES. <br />(2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM <br />ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL <br />ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS <br />THAN 60 INCHES ABOVE THE DRAIN INLET <br />(3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE <br />THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A <br />CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE <br />FINISHED FLOOR OR WALKING SURFACE. <br />(4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS <br />DESCRIBED IN ITEMS (2) AND (3) ABOVE. THAT MEETS ALL OF THE FOLLOWING <br />CONDITIONS: <br />A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SO. FT. <br />B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR. <br />C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR. <br />D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE <br />PLANE OF THE GLAZING. <br />USE AND OCCUPANCY. - <br />LOW HAZARD FACTORY INDI.'STPI.A.L GROUP F2 <br />REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS <br />THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING. <br />TOTAL AREA 5400 SO. - . 1A,AREHOUSE PER TABLE 1004. 1.2 500 GROSS e 11 PEOPLE <br />TYPE CONSTRUCTION: 1 I B <br />FIRE PROTECTION: NON SPRINKLED <br />PLUMBING PER 2017 FLORIDA BUILDING CODE <br />PLUMBING 6TH EDITION CHAPTER 4, TABLE 403.1. <br />(352) 521-5848 <br />T, L. HANSON <br />4 4ee0CIATEe/ INC;, <br />CONSULTING ENGINEERS <br />ENGINEERING IBUSINESS NO, EE35830 <br />Post Office Box 1128 <br />Dade City, Florida 3352�o <br />THOMAS L. HANSON, PE 38654 <br />K & K GLASS INC <br />ZEPHYRHILLS. FLORIDA <br />SITE LOCATION MAP <br />6TH EDITION FLORIDA FIRE PREVENTION <br />6TH EDITION 2017 FLORIDA BUILDING CODE <br />6TH EDITION 2017 FLORIDA ACCESSIBILITY CODE <br />6TH EDITION 2017 FLORIDA ENERGY CONSERVATION CODE <br />6TH EDITION 2017 FLORIDA MECHANICAL CODE <br />6TH EDITION 2017 FLORIDA PLUMBING CODE <br />2017 NFPA 10 (STANDARD FOR PORTABLE FIRE EXTINGUISHERS) <br />2014 NATIONAL ELECTRICAL CODE (NFPA 70) <br />CONTRACTOR TO PROVIDE TACTICAL SIGNS AS PER NFPA 1:14.14.1.3 <br />CONTRACTOR TO PROVIDE SIGNS DESIGNATING TYPE OF <br />ROOF CONSTRUCTION PER. FAC 6QA-3/012 (6) <br />BUILDING HAS STEEL ROOF SYSTEM <br />LIGHT FRAME CONSTRUCTION SIGN NOT REQUIRED <br />CONTRACTOR TO PROVIDE UL 1037 APPROVED ACCESS BOX PER NFPA 1:18.2.2.1 <br />RESTROOM FLOORS TO BE A NON ABSORBENT MATERIAL <br />RESTROOM WALLS TO BE A NON ABSORBENT MATERIAL <br />MINIMUM 60" ABOVE FINISH FLOOR <br />INTERIOR FINISHES <br />TABLE 803.11 <br />INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY'` <br />�. SPRINKLERED' <br />CROUP _ <br />Interior exit stairways and ramps <br />and exit passageways'' <br />,a- s <br />- - - <br />a-4, A-5 B <br />Corridors and <br />i enclosure for exit <br />! access stairways <br />and ramps <br />NONSPRINKLERED <br />Corridors and !i <br />Rooms and <br />enctosure for exit <br />enclosed <br />! access stairways <br />I and ramps spaces` <br />I Rooms and <br />j enclosed <br />I I <br />spaces` I <br />I Interior exit stairways antd <br />ramps and cell <br />passageways'' c <br />:� <br />B <br />C <br />A' B° <br />- <br />B <br />C <br />A <br />-- <br />A° C <br />h. F', M. R-1 <br />R-4 <br />B <br />C <br />C _ <br />C <br />A <br />A <br />1 B <br />B <br />C <br />B <br />B <br />C <br />1' <br />C <br />C <br />C s <br />C c <br />C I A <br />r l <br />— 1-3 <br />1-1 <br />I <br />B <br />B <br />A <br />B <br />c <br />F-- B <br />Ai —! <br />- -B <br />I B B <br />-- A---, B <br />A B <br />I Fib., I A <br />C A <br />I' B.-_A — <br />A B <br />-R-z — <br />-C— <br />I C <br />C <br />C <br />C- <br />i C B —� <br />8 C <br />R-3 <br />C C <br />I C B <br />C C <br />S <br />C I' <br />B C <br />�- <br />-- -- - -- - --- - -- <br />No resmcnons No restrictions i <br />For SI; I inch = 25.4 ntm, I square foot = 0.002c rn <br />a. Class C interior finish materials shall be pennitt•_d fur �camscwdng u- pan.lier of not more than 1.000 square feet of applied surface area in the grade lobby <br />where applied directly to a noncombustible base or over furring strips applied to a noncombustible bale and fireblocked as required by Section 803.13.1. <br />b. in, ?. - Ciroup 1-3 occupancies in buildings less that. three stories above grade plane. Class B interior finish for nonsprinklered buildings and Clans C <br />int, r. for sprirtklered buildings shall be pear iced it interior exit stairways and ramps. <br />c. Rc•,,.:, r rooms and enclosed space,, shall he bated apon ,paces encioned by parbtiuus. Where a fire-resi�iance rating is required for .structural <br />i sing partitions shall extend from the floor to tae ceiling.. Partitions that do not comply with thi; shall lie considered enclosing spaces and the <br />sides shall be cousidered one. In determining the applicable requirement, for rooms and crclosed spaces, the specific occupancy <br />m n t'actor regardless of the group classification of the building or structure. <br />d. L: 1, ,d A-3 occupancies shall not be less than Class B materials. <br />e. (' . !: n r. :i -rill be permitted in pl: ces of assembly with an occupant load of' N) persons or less. <br />f. F - <!ous is, wood used for ornamental purposes, trusses, paneling o- chancel furnishing shall be permitted. <br />req1111C,1 . i,ere the building exceeds two stories. <br />u rash materials shall be pennitted in administrative spaces. <br />>, < "17 !lnish materials shall be permi-.ted in Torun% with a capacity of four persons or less. <br />j. Class B materials shall be permitted as wainscotting extending not more than -18 inches above the finished floor in corridors and exit access stairways and <br />ramps. <br />k. Finish materials as provided for in other sections of this erode. <br />L Applies when protected by an automatic sprinxler system installed in accordance with Section 903.3.1.1 or 903.3.13. <br />Ftzv;x k.A n: I d <br />3 <br />BUILDING DESIGNS <br />13821 U.S. HWY 98 BY PASS DADE CITY, FLORIDA 33523 <br />OFFICE 352-523-2077 <br />PLAN INDEX: <br />SHEET B 1 : BUILDING FLOOR PLAN <br />SHEET B 2: EXTERIOR ELEVATIONS <br />SHEET B 3: EXTERIOR ELEVATIONS <br />SHEET S 1 : FOUNDATION PLAN <br />FOOTING DETAILS <br />SHEET S 2 -. BUILDING CUT SECTION DETAIL <br />LOADING DOCK CUT SECTION DETAIL <br />LOADING DOCK STAIR DETAIL <br />LOADING DOCK WALL SECTION DETAIL <br />SHEET P 1 : SANITARY PLAN <br />WATER LINE PLAN <br />FIXTURE DETAILS <br />PLUMBING SCHEDULE <br />SHEET E1 : POWER & LIGHTING PLAN <br />SHEET E2 : ELECTRICAL NOTES <br />RISER DIAGRAM <br />ELECTRICAL SYMBOLS <br />PANEL SCHEDULE <br />LOAD CALCULATIONS <br />SHEET E3 : LIFE SAFETY PLAN <br />SHEET E4 : PHOTOMETRIC PLAN <br />9bbby2.t/ <br />Eft � <br />,4RfGAy ENGINEERING INC:. <br />structural engineers <br />IS58 E, Edgewood Drive, Lakeland F 133803 <br />Phone 863-688-6500 Fax 86340884055-7 <br />f State of Florida Certificate of Authorization M E56341 <br />Richard L Kiddey P,E, - Florida License # 312S& <br />1�o I r <br />ARKAY JOB ;r 19064 <br />