ELECTRICAL SPECIFICATIONS <br />1.1 SCOPE <br />A. WORK INCLUDED: Include the following Work in addition to items normally part of this Section: <br />01 Wiring for lighting and power. <br />02 Installation of lighting fixtures with lamps. <br />03 Lighting panelboards and distribution panelboards. <br />04 Connection of equipment shown. <br />05 Control wiring. <br />06 Disconnection and removal of existing fixtures and wiring not to be reused. <br />1.2 MINIMUM COMPLIANCE STANDARDS <br />A. All work shall be done in accordance with the requirements of the following: <br />01 Florida Building Code Sixth Edition (2017). <br />02 Florida Building Code - Electrical Conservation Sixth Edition (2017), Section C405. <br />03 2014 issue of the National Electrical Code (NFPA 70). <br />04 All Receptacle Control to conform to ASHRAE Standard 90.1, 8.4.2, 2010. <br />05 Wiring in Patient Care Areas shall comply with NEC 517. <br />06 Other applicable NFPA Codes. <br />07 Regulation of local authorities having jurisdiction. <br />B. Furnish and install all labor, material and equipment and services necessary for complete and <br />safe installation of the electrical system indicated on the drawings and noted in the <br />specifications hereinafter. Electrical systems and equipment shall in general include the following: <br />01 General provisions for electrical work. <br />02 Wiring, distribution equipment and devices. <br />03 Lighting fixtures and lamps. <br />04 Grounding system. <br />1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK <br />A. DRAWINGS: Electrical drawings considered diagrammatic and indicate general arrangement of work <br />and systems. Refer to other drawings to verify location of equipment, etc. Check drawings of <br />other trades to verify exact space condition or underground lines. Drawing Scales prohibit the <br />indication of all offsets, fittings and accessories required, however these items will be <br />provided by this subcontractor at no extra cost to the owner. <br />B. QUALITY OF MATERIALS: New, best of their respective kind, free from defects, and listed by <br />Underwriter's Laboratories, Inc. or bearing their label. <br />C. SHOP DRAWINGS: Submit four (4) copies of shop drawings for lighting fixtures and panelboards. <br />Obtain approval before equipment is ordered, built or installed. <br />D. EXCAVATION AND BACKFILLING: Excavate, backfill and restore surfaces for all electrical work. <br />E. Visit site and inspect existing facilities before bid in order to ensure proper evaluation of <br />working conditions and location of existing equipment. <br />1.4 WIRING, DISTRIBUTION EQUIPMENT AND DEVICES <br />A. CONDUCTORS: Copper, in accordance with ASTM Standards, size references AWG. Conductors No. 10 and <br />smaller size solid, No. 8 and larger stranded. Insulation of conductor thermoplastic, type THHN <br />(min. size: No. 12) any wire installed outside, underground, in slabs, or exposed to moisture <br />shall have THWN insulation. <br />B. RACEWAYS: RIGID STEEL CONDUIT, full weight pipe galvanized, threaded, and minimum 1 /2 inch except <br />as noted or required for wiring. ELECTRICAL METALLIC TUBING (EMT), thin wall pipe, galvanized, threadless, <br />comression fittings, and minimum 1 /2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT, <br />continuous singlestrip, galvanized, and minimum 1/2" size except as noted or required for wiring. PVC <br />CONDUIT, heavy duty type, size as indicated. Separate raceways shall be used for each voltage system. <br />Type AC or MC Cable where permitted. <br />C. DISCONNECT SWITCHES: General Duty, horsepower rated for motor loads 600 or 250 volt rating, fused <br />or non -fused as noted; number of poles as indicated, cover interlocked with switch. Enclosure <br />NEMA 1 for indoor use and NEMA 3R for weatherproof applications. Switch to be Square "D" or equal. <br />D. CIRCUIT BREAKERS: Molded case, thermal -magnetic quick -make, quick -break, bolt -on type with <br />manually operated insulated trip -free handle. Multi -pole types with internal common trip bar. <br />Terminals suitable for copper or aluminum conductors. Interrupting capacity minimum 10,000 RMS <br />symmetrical amperes circuit breakers to be Square "D" or equal, type as required. <br />E. PANELBOARDS: Voltage, phasing and ampere ratings as indicated, circuit breaker type as indicated, <br />busbars of hard drawn copper, minimum 98% conductivity, galvanized steel back box, door and trim. <br />All corners lapped and welded, hardware chrome plated with flush lock and catch. Hinges semi - <br />concealed, 5 knuckle steel with nonferrous pins, 180 degree openings. Minimum gutter space 5- <br />3/4" sides, top and bottom. Increase size where required by code. Directory holder complete <br />with clear plastic transparent cover indicating typewritten list of feeder cables, conduit sizes, <br />circuit numbers, outlets of equipment supplied, and their location. Circuit breaker type <br />panelboards to be Square "D" type NQOD or I -Line, or equal. A plastic label shall be located on exterior of <br />panelboard identifying the system voltage, phase, and current rating. <br />F. WIRING DEVICES: All devices the product of the same manufacturer. Wall switches single pole, 20 <br />ampere, 120 volt. Wall switches three-way, 20ampere, 120 volt. Receptacles duplex, 2 wire; 3 <br />pole grounded, 20 ampere, 120 volt. <br />G. DEVICE PLATES: Provide for all outlets where devices are installed. Provide engraved marking for <br />special outlets. Provide blank plates for empty or future outlet boxes. DEVICE AND DEVICE PLATES <br />COLORS TO BE VERIFIED WITH INTERIOR DESIGNER AND OWNER. <br />1.5 LIGHTING FIXTURES AND LAMPS <br />A. Furnish and install complete system of lighting fixtures, lamps, accessories and supports as <br />specified and indicated. Submittals of equal quality are allowed. <br />1.6 GROUNDING SYSTEM <br />A. EQUIPMENT: Ground non -current carrying metal parts of ponelboard, raceways and all lighting <br />fixtures. All conduits shall have equipment grounding conductors. <br />1.7 INSTALLATION <br />A. Secure all supports to building structure. Support horizontal runs <br />of metallic conduit not more than 10 feet apart. Run exposed raceways parallel with or at right <br />angles to walls. <br />B. Pass raceways over water, steam or other piping when pull boxes are not required. No raceway <br />within 3 inches of steam or hot water pipes, or appliances, except crossings where raceway shall <br />be at least 2 inches from pipe cover. <br />C. Cut conduit ends square, ream smooth. Paint male threads of field threaded conduit with graphite <br />base pipe compound. Draw up tight with conduit couplings. <br />D. Leave wire sufficiently long to permit making final connections. In raceways over 50 feet in <br />which wiring is not installed, furnish pull wire. <br />E. Verify locations of outlets and switches. <br />F. Support panel, junction and pull boxes independently to building structure with no weight bearing <br />on conduits. <br />G. Connect conduit to motor conduit terminal boxes with flexible conduit; minimum 18 inches in <br />length and 50% slack. Do not terminate in or fasten raceways to motor foundation. <br />H. Contractor to remove and salvage all abandoned electrical equiment. <br />1. This contractor shall warrant all labor and materials for one year from date of final written <br />acceptance. <br />J. Owner assumes responsibility to do periodic maintenance on all Aluminum Wire Connections and will <br />provide a signed letter to attest to this agreement. <br />K. Contractor will provide to the Building Owner, within 30 days after the date of the system acceptance, record <br />drawings of the actual installation Documents and Manuals per C405.6.4 <br />L. Contractor shall provide construction documents that certify lighting controls meet performance criteria of <br />Section C405 of the Florida Building Code Sixth Edition (2017) Energy Conservation, and provided to the <br />Building Owners within 90 days of receipt of the Certificate of Occupancy per C408.3.2 of the same code. <br />M. Contractor shall provide Fault Current Field Markings on all Service Equipment in field. Field markings <br />shall include the date the fault -current calculation was performed and be of sufficient durability to withstand <br />the environment involed per NEC 110.24. <br />N. All Electrical Equipment is to be UL rated. <br />1.8 LOW VOLTAGE <br />A. Low Voltage wiring drawings to be provided by others. <br />P-I FrTRIrAI cYKAPOI c <br />Sap- 3-WAY SINGLE POLE DIMMER SWITCH (0-10V OR LINE VOLT. AS REQUIRED) <br />Sp - SINGLE POLE DIMMER SWITCH (0-10V OR LINE VOLTAGE AS REQUIRED) <br />Sap - 3-WAY SINGLE POLE TOGGLE SWITCH W/PILOT LIGHT <br />S - SINGLE POLE TOGGLE SWITCH <br />S3 - 3-WAY SINGLE POLE TOGGLE SWITCH <br />Sa - "a/b" INDICATES LIGHTS TO BE SWITCHED <br />- TIME CLOCK OVERIDE SWITCH (MAX. 2 HR) <br />10 - LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR <br />- LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR <br />OO - LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR (LARGE RESTROOMS) <br />® - LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR (SMALL RESTROOMS) <br />0 - LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR W/2 LIGHT CONTROL <br />(SEE SWITCH DETAIL) <br />© - WALL MOUNTED OCCUPANCY SENSOR (CLOSETS) <br />0 - WALL MOUNTED DIMMABLE OCCUPANCY SENSOR <br />VERIFY LINE VOLTAGE OR 0-10V <br />® - MANUAL "ON" OCCUPANCY SENSOR <br />O - MANUAL "ON" DIMMABLE OCCUPANCY SENSOR <br />VERIFY LINE VOLTAGE OR 0-10V <br />0 - LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR FOR RECEPTACLES <br />> > - LINE VOLTAGE OCCUPANCY SENSOR FOR MOUNTING ABOVE 12' <br />DS - DAYLIGHT SENSOR <br />.C.,,��,, - SPLIT DUPLEX RECEPTACLE HALF ON TIME CLOCK OR OCCUPANCY SENSOR. <br />RECEPTACLES MUST BE MARKED TO INDICATE THAT THEY ARE CONTROLLED. <br />- QUADRAPLEX RECEPTACLE HALF ON TIME CLOCK OR OCCUPANCY SENSOR. <br />RECEPTACLES MUST BE MARKED TO INDICATE THAT THEY ARE CONTROLLED. <br />- DUPLEX RECEPTACLE ON TIME CLOCK OR OCCUPANCY SENSOR. CONTROLLED <br />RECEPTACLES MUST BE MARKED TO INDICATE THAT THEY ARE CONTROLLED. <br />_e - SIMPLEX RECEPTACLE <br />- DUPLEX RECEPTACLE <br />- QUADRAPLEX RECEPTACLE <br />- FLOOR BOX W/DUPLEX RECEPTACLE. LOCATIONS TO BE VERIFIED W/OWNERS <br />- FLOOR BOX W/QUADRAPLEX RECEPTACLE. VERIFY LOCATIONS W/OWNERS <br />GFI - GROUND FAULT INTERRUPTER <br />WP - WATER PROOF 3R - NEMA 3R <br />NF - NON -FUSED NL - NIGHT LIGHT <br />- DISCONNECT SWITCH <br />- - ELECTRICAL PANELBOARD <br />�- EMERGENCY LIGHTING/EXIT SIGN W/BATTERY BACKUP <br />� EMERGENCY LIGHTING-W/BATTERY BACKUP <br />T -- TIME CLOCK <br />® - PHOTO ELECTRIC SENSOR <br />��- CONDUIT IN FLOOR OR BURIED <br />RC - RECEPTACLE CONTACTOR <br />- 208V CHARGER RECEPTACLE - VERIFY <br />® - RESTROOM EXHAUST FAN <br />- POWER POLE W/DUPLEX RECEPTACLE/ 1 -COMP-TELCO CAPABILITIES <br />NOTE: <br />Occupancy Sensors are to be "Occupancy/Vacancy Sensors unless indicated <br />otherwise. ie: "Manual On" is a Vacancy sensor w/auto off. <br />Cut existing conduit from ATS to existing pane <br />L1. Add J-Box and tap for feed to proposed <br />Panel L4 Main CB. <br />------------ <br />Existing Generator <br />in weather proof housing <br />HANEL L4" SCHEDULE 10,000 AIC <br />SERVES <br />LOAD <br />CB/P <br />CKT <br />B/p <br />LOAD <br />SERVES <br />OA OB ADC <br />OA OB OC <br />Warehouse Lighting <br />1386 <br />20/1 <br />1 <br />2 <br />20/1 <br />Spare <br />Restroom Lights <br />140 <br />20/1 <br />3 <br />4 <br />20/1 <br />1260 <br />Warehouse Receptacles 11 <br />Ext. Building Lts. <br />177 <br />20/1 <br />5 <br />6 <br />20/1 <br />1176 <br />Loading Sump Pump <br />Space <br />7 <br />8 <br />20/3 <br />500 <br />Charging Station <br />9 <br />10 <br />500 <br />11 <br />12 <br />500 <br />13 <br />14 <br />Space <br />15 <br />16 <br />17 <br />18 <br />19 <br />20 <br />21 <br />22 <br />23 <br />24 <br />25 <br />26 <br />27 <br />28 <br />29 <br />30 <br />Sub -Total 1376 140 177 500 1760 1676 <br />Total 1750 1900 1853 5503 = 16 Amps Connected (Highest Phase) <br />Notes: 100A MLO 120/208V 30 4W SN <br />To <br />Utility _ <br />Transformer <br />I <br />I <br />1 <br />1 <br />1 <br />I <br />I <br />Existing Wireway <br />L- - - - - - - - - - - - - - - - J <br />_ r- <br />Exist. F= <br />I Gen. _ _ _ Txisting� I 1 l <br />Control - - - 1200A <br />Existing <br />I I I I Fused <br />ATS II <br />- I pisconnectp I Existing 1 <br />I I I I Meter <br />_J L-_--1 L-_r-_J <br />1� I <br />I <br />1 J-Box <br />I � <br />I 1 <br />(3)3,3N,8G,1.25"C <br />I� I <br />jl I <br />2% SERVICE/FEEDER VOLTAGE DROP CHART <br />This chart is based on a 160A (80% 200A) Amp Demand, 208V 30 <br />Service from Power Most Utility Connection to ATS. Then to Panel L4 <br />80A (80% of 100A). <br />WIRE TYPE AND SIZE FEET VD %VD <br />UTILITY CONNECTION TO ATS <br />4/0 75-C THW/THWN Wire = 30 .51 .24 <br />ATS PANEL L4 <br />3 75'C THW/THWN Wire = 75 2.55 1.22 <br />VD 0.51 = 0.24% @ 208V <br />VD 2.55 = 1.22% ® 208V <br />TOTAL VD 3.06 = 1.46% @ 208V <br />Chart indicates distance with load as shown. Should total distance exceed <br />what is indicated it is to be brought to the attention of this Engineer. <br />NOTE: All wire Copper unless indicated otherwise. <br />100A <br />CB <br />3% EQUIPMENT VOLTAGE DROP CHART <br />This chart is based on a 20 amp single pole <br />breaker load at maximum (16 amps) <br />120/208V 30 Service. <br />WIRE TYPE AND SIZE FEET <br />#12 75-C THW/THWN Wire = 57 <br />#10 75-C THW/THWN Wire = 90 <br />NOTE: <br />This chart is "Worst Case". Actual length of wire <br />when calculated from load to load and how the <br />conduits are run can vary from this chart. <br />ELECTRICAL LOAD CALCULATIONS: <br />Existing 200A, 120/208V 30 4 Wire SN Service <br />Max Demand for 12 Months <br />NEC 220-87 X 1.25 <br />LOAD CHANGES: <br />LIGHTING <br />5400 Sq. Ft. Warehouse ® 0.66 watts per = 3.56 <br />Table C405.4.2(1) FBC Energy conservation <br />Ext. Bldg. Lts. .60 <br />Continuous Load = 4.16 X 1.25 = <br />RECEPTACLES <br />EQUIPMENT <br />(1) Sump Pump @ 1 176 = <br />(1) Chargiong Station © 1500 = <br />Sub Total <br />31.68 KW (Per TECO Records) <br />39.60 <br />KW <br />5.20 <br />1.26 <br />1.18 <br />1.50 <br />Sub Total 2.68 <br />Total 48.74 <br />-8.74 KW ® 277/480V 30 4 Wire SN = 135 Amps. <br />xisting Service = 200A 120/208V 30 4 Wire SN <br />SHORT CIRCUIT CALCULATIONS: <br />20821 (Worst Case)) <br />I SC = 1 + 1.732(250)(20821) <br />(15082)(208) <br />1 SC = 5374.0 AIC Wireway, Meter, Main Fused Disconnect <br />I SC = 5000.0 AIC Let Thru Current @ 200A Fused Disc. <br />w/200A Class RK5 FRN-R Fuses <br />I SC = <10000 AIC 100A CB, Panel L4 <br />� <br />� <br />PE <br />___ <br />Existing <br />Panel L3 I <br />Add Time Clock and PE if <br />1100A ML01 <br />1 <br />existing exterior lighting <br />1 <br />1120/208V I <br />1 <br />controls not feasible to <br />I <br />30 4 Wire <br />I <br />access for control to <br />I SN I <br />1 <br />proposed building exterior <br />I I <br />I <br />lighting. <br />L---J <br />I <br />2nd Floor <br />I (3)3,3N,8G,1.25"C <br />12,12N,12G,3/4"C <br />- - - - - - - - - <br />- - - - - - - <br />- <br />[IF <br />F_Existin -I <br />1 9 <br />FEXlstin 9 -1 <br />I <br />Panel L4 TC <br />1 I Panel L1 I <br />1 1225A MB 1 <br />I Panel L2 I <br />I100A MLO 1 <br />I <br />100A <br />100A MLO <br />120/208V <br />30A <br />I <br />1120/208V1 <br />1 <br />1120/208V1 <br />NF <br />I Dlsconnec <br />30 4 <br />Wire <br />NF <br />Dlsconnec <br />130 4 Wire I <br />130 4 Wire I <br />SN <br />1 SN I <br />1 SN <br />Nipple <br />thru wall <br />12,12N,12G,3/4"C <br />i I I <br />L-- J <br />I <br />I <br />Add WP J-Box if Cable <br />I 1 <br />I <br />from Pump not long <br />1 <br />I � <br />( <br />I <br />enough to reach disc. <br />I I <br />1 <br />I <br />I <br />I <br />1 <br />Proposed <br />Building <br />Cable supplied <br />PP w /Pum P <br />Existing Building I <br />/ <br />/ / <br />�- - - - - - - - - - - - - - I - - - - - - - - - - - - - - - - --- <br />Verify existing grounding <br />Extend to metal water line <br />or building steel in accordance ` - T - _J <br />with NEC 250. <br />(3)3,3N,8G,1.25"C <br />I I <br />Minimum (2)5/8"0 Copper Clad <br />Ground Rods spaced 10' apart. <br />- - - - - - - - - - - - - = Existing <br />RISER DIAGRAM <br />NTS <br />Bond to Concrete enclosed <br />Steel Rebar (min. #4) in <br />Bldg. Foundation per <br />NEC 250.50 <br />(If accessible) <br />Rom? <br />Dock <br />ooa�r9 <br />L <br />1 /2 HP Sump Pump <br />w/ internal "ON/OFF" <br />Float Switch <br />��e •••��G E NS�c•• �® <br />_o pp <br />�STATE OF •; <br />'r 0.c,% <ORIDP••' N ♦� <br />z <br />0 <br />rL <br />UJ <br />w <br />0 <br />O <br />L.L_ <br />Q <br />Z Z F-- � <br />LIJ p w0 <br />J <br />:D(L L- <br />m QV) <br />J <br />U = <br />LLl _J <br />Cf) <br />OCS601) <br />LIJ Y u7 <br />z <br />O <br />F_ <br />Lv <br />�Q N <br />I <br />m <br />v <br />J <br />o <br />w <br />o <br />F <br />w <br />a. <br />a <br />U <br />w <br />O <br />Z <br />w <br />of <br />IL <br />J <br />U <br />w <br />a <br />0 <br />w <br />Z <br />= <br />J <br />CL <br />O <br />w <br />_JQ <br />m <br />O <br />0= <br />Y <br />m <br />/W!�^ <br />V <br />w <br />J <br />F <br />(n <br />Ll..l <br />Q <br />U <br />J <br />m <br />= <br />O <br />> <br />� <br />� <br />J <br />: <br />U <br />o <br />J <br />F- <br />Z <br />= <br />Q <br />• <br />�p U <br />J <br />O <br />V)U <br />J <br />LL_= <br />w J <br />Q <br />Q <br />LL <br />w <br />O <br />- <br />U <br />UU <br />�� <br />BIZ <br />_J C) <br />a� <br />z 0 <br />V) <br />o <br />Q J <br />Z <br />11 <br />0 <br />z <br />o <br />J <br />� <br />Ir <br />w <br />m <br />O <br />Z <br />Z <br />0O) <br />z <br />w <br />I <br />O <br />lf <br />o <br />n <br />°nI <br />Z <br />z <br />It-iL_JI <br />� <br />w <br />O <br />Z <br />= <br />V) <br />C)w <br />al <br />U1 <br />V) <br />�rtnNN � <br />Cr'p�hh <br />U <br />LtJ'n ^ M Z <br />W W N <br />Z <br />o a <br />v z <br />cavi <br />Z v, <br />LLJ <br />= <br />Q <br />U <br />0�av 2 <br />2:-0 <br />O <br />o <br />W <br />O� <br />U W <br />00 <br />h <br />I <br />N <br />Ln <br />04 <br />