Laserfiche WebLink
".. d f <br />ar <br />u <br />}mw <br />co 0 <br />Z Y 0 <br />3uz <br />�LLI <br />_ cr <br />o u n. <br />SECTION 260500 <br />COMMON WORK RESULTS FOR ELECTRICAL <br />PART 1- GENERAL <br />1.01SECTION INCLUDES <br />A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT INCLUDING GENERAL AND SUPPLEMENTARY <br />CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS APPLY TO ALL DIVISION 26 SECTIONS. <br />B. FURNISH AND INSTALL ELECTRICAL SYSTEMS, MATERIALS, EQUIPMENT, AND ACCESSORIES IN <br />ACCORDANCE WITH THIS SPECIFICATIONS AND DRAWINGS. <br />1.02RELATED REQUIREMENTS <br />A. SECTION 03 3000 - CAST -IN -PLACE CONCRETE. <br />B. SECTION 23 0000 - HEATING, VENTILATING, AND AIR-CONDITIONING. <br />C. SECTION 07 8400 - FIRE AND SMOKE PROTECTION. <br />1.030THER RELATED REQUIREMENTS OWNER FURNISHED EQUIPMENT AND SYSTEMS <br />1.04SUBMITTALS <br />A. COMPLY WITH PROVISIONS OF DIVISION 01. <br />B. THE ENGINEER'S APPROVAL SHALL BE OBTAINED FOR ALL EQUIPMENT AND MATERIALS BEFORE <br />DELIVERY TO THE JOB SITE. DELIVERY, STORAGE OR INSTALLATION OF EQUIPMENT AND MATERIALS <br />WHICH HAS NOT HAD PRIOR APPROVAL WILL NOT BE PERMITTED. <br />C. ALL SUBMITTALS SHALL INCLUDE 2 COPIES OF ADEQUATE DESCRIPTIVE LITERATURE, CATALOG, SHOP <br />DRAWINGS, TEST REPORTS, CERTIFICATIONS, SAMPLES, AND OTHER DATA NECESSARY TO ASCERTAIN <br />THAT THE PROPOSED EQUIPMENT AND MATERIALS COMPLY WITH DRAWINGS AND SPECIFICATIONS <br />REQUIREMENTS <br />D. SUBMITTALS FOR INDIVIDUALS SYSTEMS AND EQUIPMENT ASSEMBLIES WHICH CONSIST OF MORE THAN <br />ONE ITEM OR COMPONENT SHALL BE MADE FOR THE SYSTEM OR ASSEMBLY AS A WHOLE. PARTIAL <br />SUBMITTALS WILL NOT BE CONSIDERED FOR APPROVAL. <br />1. MARK THE SUBMITTALS, "SUBMITTED UNDER SECTION" " <br />2. SUBMIT EACH SECTION SEPARATELY. <br />E. SUBMIT ELEMENTARY AND INTERCONNECTION OR POINT-TO-POINT WIRING DIAGRAMS FOR FIRE ALARM, <br />COMMUNICATION AND SIGNAL, AND CONTROL SYSTEMS. ALLTERMINAL POINT SHALL BE IDENTIFIED ON <br />WIRING DIAGRAMS. <br />F. SUBMIT DIMENSIONED EQUIPMENT ROOM LAYOUTS. <br />1. SHOW LOCATION OF ALL ELECTRICAL EQUIPMENT IN ROOMS INCLUDING BUT NOT LIMITED TO: <br />A. ELECTRICAL ROOMS AND CLOSETS <br />G. ELECTRICAL EQUIPMENT SUBMITTALS WILL BE REJECTED WITHOUT DIMENSIONED EQUIPMENT ROOM OR <br />EQUIPMENT LOCATION LAYOUTS.. <br />1.05REFERENCE STANDARDS <br />A. PERFORM WORK SPECIFIED IN DIVISION 26 IN ACCORDANCE WITH STANDARDS LISTED BELOW OF THE <br />LATEST APPLICABLE EDITION ADOPTED BY THE AUTHORITY HAVING JURISDICTION. THE DRAWINGS AND <br />SPECIFICATIONS SHALL TAKE PRECEDENT IN THOSE INSTANCES WHERE REQUIREMENTS ARE GREATER <br />THAN THOSE STATED IN THE BELOW CODES AND STANDARDS. IN CASE OF CONFLICT, OBTAIN A DECISION <br />FROM THE ENGINEER. <br />B. ADA STANDARDS FOR ACCESSIBLE DESIGN(2010) <br />C. AIA GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES (2014) <br />D. FLORIDA BUILDING CODE (2017) <br />E. U.L. FIRE RESISTANCE INDEX. <br />F. NFPA 1: FIRE CODE (2015) <br />G. NFPA 37: STANDARD FOR THE INSTALLATION AND USE OF STATIONARY COMBUSTION ENGINES AND GAS <br />TURBINES; 2015, <br />H. NFPA 70: NATIONAL ELECTRICAL CODE (2014) <br />I. NFPA 90A: STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS (2015) <br />J. NFPA 99: STANDARD FOR HEALTH CARE FACILITIES 2015 <br />K. NFPA 101: LIFE SAFETY CODE (2015) <br />L. NFPA 110: STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS (2013) <br />M. NFPA 241: STANDARD FOR SAFEGUARDING BUILDING CONSTRUCTION, ALTERATION AND DEMOLITION <br />OPERATIONS (2013) <br />N. OTHER STANDARDS: <br />1. ANSI <br />2. ASME <br />3. ASHRAE <br />4. ASTM <br />5. IEEE <br />6. IESNA <br />7. ISO <br />8. NECA <br />9. NEMA <br />10. OSHA <br />11. UL <br />1.06QUALITY ASSURANCE <br />A. COMPLY WITH APPLICABLE LOCAL, STATE, AND FEDERAL CODES. <br />B. WARRANT ELECTRICAL WORK AGAINST FAULTY MATERIAL OR WORKMANSHIP IN ACCORDANCE WITH <br />DIVISION 01. IF THE PROJECT IS OCCUPIED OR THE SYSTEMS PLACED IN OPERATION IN SEVERAL PHASES <br />AT THE REQUEST OF THE OWNER'S REPRESENTATIVE, THEN THE WARRANTY OF EACH SYSTEM OR PIECE <br />OF EQUIPMENT USED, SHALL BEGIN ON THE DATE EACH SYSTEM OR PIECE OF EQUIPMENT WAS PLACED <br />IN SATISFACTORY OPERATION AND ACCEPTED AS SUCH, IN WRITING, BY THE OWNER'S REPRESENTATIVE. <br />THE USE OF BUILDING EQUIPMENT FOR TEMPORARY SERVICE AND TESTING DOES NOT CONSTITUTE THE <br />BEGINNING OF THE WARRANTY. <br />EQUIPMENT MATERIAL PRO C. EQ I UNDER THIS DIVISION SHALL BE PERIODICALLY INSPECTED AND <br />PROVIDED <br />SERVICED BY COMPETENT MECHANICS. THIS FUNCTION BECOMES THE RESPONSIBILITY OF THE <br />OWNER'S REPRESENTATIVE WHEN THE SYSTEM IS ACCEP <br />TED BY THE OWNER'S REPRESENTATIVE. THE <br />ONE YEAR MATERIAL AND WORKMANSHIP WARRANTY IS NOT INTENDED TO SUPPLANT NORMAL <br />INSPECTION OR SERVICE AND SHALL NOT BE CONSTRUED TO MEAN THE CONTRACTOR SHALL PROVIDE <br />FREE SERVICE FOR NORMAL MAINTENANCE ITEMS SUCH AS PERIODIC LUBRICATION AND ADJUSTMENT <br />DUE TO NORMAL USE, NOR TO CORRECT WITHOUT CHARGE, BREAKAGE, MALADJUSTMENT, AND OTHER <br />TROUBLE CAUSED BY IMPROPER MAINTENANCE. <br />D. TURN OVER ELECTRICAL EQUIPMENT PROVIDED UNDER THIS DIVISION TO THE OWNER'S <br />REPRESENTATIVE IN LUBRICATED CONDITION. INCLUDE INSTRUCTIONS ON FURTHER LUBRICATION IN THE <br />OPERATING MANUAL. <br />E. UPON COMPLETION OF CONTRACT AND PROGRESSIVELY AS WORK PROCEEDS, CLEAN-UP AND REMOVE <br />DIRT DEBRIS AND SCRAP MATERIALS. MAINTAIN PREMI <br />SES NEAT AND CLEAN. PROTECT AND PRESERVE <br />ACCESS TOENERGIZED E UIPMENT AT ALL TIMES.CLEAN ITEMS WITH FACTORY FINISHES. TOUCH-UP <br />Q <br />MINOR DAMAGE TO SURFACES; REFINISH ENTIRE PIECE OF EQUIPMENT WHEN SUSTAINED MAJOR <br />DAMAGE. USE ONLY FACTORY SUPPLIED PAINTS OF MATCHING COLOR AND FORMULA. <br />1.07QUALIFICATIONS (PRODUCT AND SERVICES) <br />A. MANUFACTURE'S QUALIFICATIONS: THE MANUFACTURER SHALL REGULARLY AND CURRENTLY PRODUCE, <br />AS ONE OF THE MANUFACTURER'S PRINCIPAL PRODUCTS, THE EQUIPMENT AND MATERIALS SPECIFIED <br />FOR THIS PROJECT, AND SHALL HAVE MANUFACTURED THE EQUIPMENT AND MATERIALS FOR AT LEAST <br />THREE YEARS. <br />B. PRODUCT QUALIFICATION: <br />1. MANUFACTURED EQUIPMENT AND MATERIALS SHALL HAVE BEEN IN SATISFACTORY OPERATION, ON <br />THREE INSTALLATION OF SIMILAR SIZE AND TYPE AS THIS PROJECT AT LEAST FOR THREE YEARS. <br />2. THE ENGINEER RESERVES THE RIGHT TO REQUIRE THE CONTRACTOR TO SUBMIT A LIST OF <br />INSTALLATIONS WHERE THE EQUIPMENT AND MATERIALS HAVE BEEN IN OPERATION BEFORE <br />APPROVAL. <br />C. SERVICE QUALIFICATIONS: THERE SHALL BE A PERMANENT SERVICE ORGANIZATION MAINTAINED OR <br />TRAINED BY THE MANUFACTURER WHICH WILL RENDER SATISFACTORY SERVICE TO THIS INSTALLATION <br />WITHIN FOUR HOURS OF RECEIPT OF NOTIFICATION THAT SERVICE IS NEEDED. SUBMIT NAME AND <br />ADDRESS OF SERVICE ORGANIZATIONS. <br />1.08DELIVERY, STORAGE, AND HANDLING <br />A. DELIVER EQUIPMENT AND MATERIALS IN MANUFACTURER'S ORIGINAL UNOPENED PACKAGING. <br />EQUIPMENT AND MATERIALS SHALL BE PROTECTED DURING SHIPMENT AND STORAGE AGAINST PHYSICAL <br />DAMAGE, VERMIN, DIRT, CORROSIVE SUBSTANCES, FUME, MOISTURE, COLD, AND RAIN. EVIDENCE OF <br />DAMAGE FROM WATER OR OTHER CONTAMINANTS WILL BE CAUSE OF REJECTION. <br />1. STORE EQUIPMENT AND MATERIALS INDOORS IN CLEAN DRY SPACE WITH UNIFORM TEMPERATURE TO <br />PREVENT CONDENSATION. <br />2. DURING INSTALLATION, EQUIPMENT SHALL BE PROTECTED AGAINST ENTRY OF INSTANCES MATTER, <br />AND BE VACUUM -CLEANED BOTH INSIDE AND OUTSIDE BEFORE TESTING AND OPERATING. <br />COMPRESSED AIR SHALL NOT BE USED TO CLEAN EQUIPMENT. REMOVE LOOSE PACKING AND <br />FLAMMABLE MATERIALS FROM INSIDE EQUIPMENT. <br />3. DAMAGED EQUIPMENT SHALL BE REPAIRED OR REPLACED, AS DETERMINED BY THE ENGINEER. <br />4. PAINTED SURFACES SHALL BE PROTECTED WITH FACTORY INSTALLED REMOVABLE HEAVY CRAFT <br />PAPER, SHEET VINYL OR EQUAL. <br />5. DAMAGED PAINT ON EQUIPMENT SHALL BE REFINISHED WITH THE SAME QUALITY OF PAINT AS USED <br />BY MANUFACTURER SO REPAIRED AREAS ARE NT OBVIOUS. <br />1.09OPERATING AND MAINTENANCE MANUALS <br />A. PROVIDE MANUALS IN ACCORDANCE WITH DIVISION 01. <br />B. SUBMIT AS REQUIRED FOR SYSTEMS AND EQUIPMENT SPECIFIED IN THE TECHNICAL SECTIONS. FURNISH <br />IN HARDCOVER OR AN APPROVED EQUIVALENT. <br />1. INSCRIBE THE FOLLOWING IDENTIFICATION "MAINTENANCE AND OPERATION MANUAL", THE NAME AND <br />LOCATION OF THE SYSTEM, EQUIPMENT, BUILDING, NAME OF CONTRACTOR, AND CONTRACT NAME <br />AND NUMBER. <br />2. PROVIDE A TABLE OF CONTENTS AND ASSEMBLE THE MANUAL TO CONFORM TO THE TABLE OF <br />CONTENTS, WITH TAB SHEETS PLACED BEFORE INSTRUCTIONS COVERING THE SUBJECT. THE <br />INSTRUCTION SHALL BE LEGIBLE AND EASILY TO READ, WITH LARGE SHEETS OF DRAWINGS FOLDED <br />IN. <br />3. THE MANUALS SHALL INCLUDE: <br />A. INTERNAL AND INTERCONNECTING WIRING AND CONTROL DIAGRAMS WITH DATA TO EXPLAIN DETAILED <br />OPERATION AND CONTROL OF THE EQUIPMENT. <br />B. A CONTROL SEQUENCE DESCRIBING START-UP, OPERATION, AND SHUTDOWN. <br />C. INSTALLATION INSTRUCTIONS <br />D. SAFETY PRECAUTIONS FOR OPERATION AND MAINTENANCE. <br />E. PERIODIC MAINTENANCE AND TESTING PROCEDURES. <br />F. PERFORMANCE DATA. <br />G. PICTORIAL "EXPLODED" PARTS LIST WITH PART NUMBERS. THE LIST SHALL INDICATE SOURCE OF SUPPLY, <br />RECOMMENDED SPARE AND REPLACEMENT PARTS, AND NAME OF SERVICING ORGANIZATION. <br />C. IN ADDITION TO REQUIRED SUBMITTALS, INCLUDE COPIES OF ALL TEST REPORTS REQUIRED IN PART 3, <br />EXECUTION OF SECTION 26 OS 00. <br />D. PROVIDE COMPLETED WARRANTY CERTIFICATES FOR SYSTEMS AND EQUIPMENT. <br />1.10RECORD DRAWINGS <br />A. COMPLY WITH PROVISIONS OF DIVISION 01. <br />PART 2 - PRODUCTS <br />2.01 MATERIALS AND EQUIPMENT <br />A. ALL EQUIPMENT AND MATERIALS SHALL BE LISTED, LABELED, OR CERTIFIED BY A NATIONALLY <br />RECOGNIZED TESTING LABORATORY (NRTL) TO MEET UNDERWRITES LABORATORIES, UL. (UL), <br />STANDARDS WHERE STANDARDS HAVE BEEN ESTABLISHED. EQUIPMENT AND MATERIALS WHICH ARE <br />NOT COVERED BY UL STANDARDS WILL BE ACCEPTED, PROVIDING THAT EQUIPMENT AND MATERIALS <br />STD LABELED CERTIFIED OR OTHERWISE DETERMINED TO MEET THE SAFETY ARE LISTED, REQUIREMENTS OF <br />A NRTL. EQUIPMENT AND MATERIALS NOT LISTED, LABELED OR DETERMINED TO BE SAFE WILL BE <br />CONSIDERED IF SUBMITTED ACCORDING TO DRAWINGS, SPECIFICATIONS, AND INDUSTRY STANDARDS <br />AND SHALL BE APPROVED BY THE AUTHORITIES HAVING JURISDICTION. <br />B. SPECIFICATIONS AND DRAWINGS INDICATE NAME, TYPE AND/OR CATALOG NUMBER OF MATERIALS AND <br />EQUIPMENT TO ESTABLISH STANDARDS OF QUALITY. SUBMITTALS SHALL BE BASED ON THE STANDARDS <br />Q <br />SPECIFIED. THE STANDARDS SHOULD NOT BE CONSTRUED AS LIMITING COMPETITION. <br />C. IF EQUIPMENT AND MATERIALS OTHER THAN SPECIFIED HEREIN ARE INTENDED TO BE SUBMITTED, A <br />LETTER PROVIDING A LIST OF ALL THE SUGGESTED ALTERNATES BY SECTION NUMBER, BRAND AND <br />SERIES OR MODEL SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW AND APPROVAL. SUBMIT IN <br />ACCORDANCE WITH DIVISION 01 AND A MINIMUM OF 14 DAYS PRIOR TO SUBMISSION FOR BIDS. <br />D. EQUIPMENT AND MATERIALS FURNISHED SHALL BE OF CURRENT PRODUCTION BY MANUFACTURERS <br />REGULARLY ENGAGED IN THE MANUFACTURE OF SUCH PRODUCTS, AND FOR WHICH REPLACEMENT <br />PARTS SHALL BE AVAILABLE <br />2.02 WALL AND CEILING ACCESS PANELS <br />A. STYLE AND TYPE AS REQUIRED FOR MATERIAL IN WHICH INSTALLED. <br />B. SIZE: 16" X 16" MINIMUM, AS INDICATED, OR AS REQUIRED TO ALLOW INSPECTION, SERVICE AND REMOVAL <br />OF ITEMS SERVED <br />C. 14 GAUGE MINIMUM SHEET METAL FOR DOORS, 16 GAUGE FRAMES OF CADMIUM -PLATED OR GALVANIZED <br />CONSTRUCTION. DOORS SHALL HAVE EXPANDED PLASTER RINGS WHERE LOCATED IN PLASTER WALLS <br />OR FLANGED FINISH WHERE LOCATED IN DRYWALL OR BLOCK CONSTRUCTION <br />D. PANELS SHALL HAVE SPRING HINGES WITH SCREWDRIVER LOCKS IN NON-PUBLIC AREAS. KEY LOCK, <br />KEYED ALIKE, FOR PANELS IN PUBLIC AREAS <br />E. PRIME PAINTED OR RUST INHIBITIVE PAINT FINISH <br />F. UL LABELED WHEN IN FIRE -RATED CONSTRUCTION, 1 1/2 HOUR RATING <br />G. PROVIDE IN WALLS FLOORS AND CEILINGS TO PERMIT ACCESS TO ALL EQUIPMENT AND JUNCTION <br />BOXES. <br />H. FURNISH AND LOCATE ACCESS PANELS UNDER THIS DIVISION. COORDINATE WITH TRADES WHO ARE <br />RESPONSIBLE FOR BUILDING SYSTEM IN WHICH PANELS ARE TO BE INSTALLED. <br />I. ACCEPTABLE MANUFACTURES: MILCOR, NYSTROM, KARP, I.L. INDUSTRIES, OR WILLIAMS BROTHERS. USE <br />PANELS EQUAL TO MILCOR STYLE M FOR MASONRY AND DRYWALL CONSTRUCTION; EQUAL TO MILCOR <br />STYLE K FOR PLASTERED MASONRY WALLS AND CEILINGS. STAINLESS STEEL PANELS SHALL BE USED IN <br />CERAMIC TILE OR GLAZED STRUCTURAL TILE <br />PART 3 - EXECUTION <br />3.01 COORDINATION <br />A. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. WHERE CONFLICTS <br />OCCUR BETWEEN CONTRACT DOCUMENTS AND THESE RECOMMENDATIONS, REQUEST A RULING BEFORE <br />PROCEEDING WITH SUCH WORK. <br />VISIT SITE AND OBSERVE CONDITIONS UNDER WHICH WORK MUST BE PERFORMED. NO SUBSEQ <br />UENT <br />UENT Q <br />ALLOWANCE WILL BE MADE BECAUSE OF ERROR OR FAILURE TO OBTAIN NECESSARY INFORMATION TO <br />COMPLETELY ESTIMATE AND PERFORM WORK REQUIRED BY THESE DOCUMENTS. <br />C. EXAMINE SPECIFICATIONS AND DRAWINGS TO BE FAMILIAR WITH ITEMS WHICH REQUIRE ELECTRICAL <br />CONNECTIONS AND COORDINATION. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE <br />SCALED FOR EXACT SIZES. <br />D. PRIOR TO COMMENCEMENT OF INSTALLATION, PREPARE COORDINATION DRAWINGS FOR WORK UNDER <br />THIS DIVISION, AS SPECIFIED IN DIVISION 01 AND AS CALLED FOR HEREIN. COORDINATE WORK UNDER <br />OTHER DIVISIONS, INCLUDING BUT NOT LIMITED TO MECHANICAL, PLUMBING, FIRE PROTECTION, <br />TELECOMMUNICATION AND MISCELLANEOUS STEEL TO DEVELOP THESE COORDINATION DRAWINGS THAT <br />WILL SERVE AS THE AGREED UPON PLAN FOR A COORDINATED INSTALLATION OF WORK FOR ALLTRADES. <br />INCLUDE ELECTRICAL EQUIPMENT, SWITCHGEAR, PANELBOARDS, STARTERS, DISCONNECT SWITCHES, <br />CABLE TRAY, CONDUIT RACKS AND CONDUITS 3" AND LARGER ON DRAWINGS CONFIRMING <br />COORDINATION WITH OTHER TRADES. INCORPORATE THE INFORMATION ONTO THE COORDINATION <br />DRAWINGS REQUIRED UNDER DIVISION 01 AND 23 TO DEVELOP MASTER COORDINATION DRAWINGS. <br />ACCOUNT FOR LIGHTING FIXTURE DEPTHS IN THE COORDINATION. INFORM DESIGN PROFESSIONAL OF <br />CONFLICTS THAT CANNOT BE RESOLVED. <br />3.02 FEES AND PERMITS <br />A. OBTAIN AND PAY FOR ALL NECESSARY PERMITS AND INSPECTION FEES REQUIRED FOR ELECTRICAL <br />INSTALLATION. <br />3.03 CUTTING AND PATCHING <br />A. COMPLY WITH PROVISIONS OF DIVISION 01 <br />B. REPAIR OR REPLACE ROUTINE DAMAGE CAUSED BY CUTTING IN PERFORMANCE OF WORK UNDER THIS <br />DIVISION. <br />C. CORRECT UNNECESSARY DAMAGE CAUSED DUE TO INSTALLATION OF ELECTRICAL WORK, BROUGHT <br />ABOUT THROUGH CARELESSNESS OR LACK OF COORDINATION. <br />D. HOLES CUT THROUGH FLOOR SLABS SHALL BE CORE DRILLED WITH DRILL DESIGNED FOR THIS PURPOSE. <br />ALL OPENINGS, SLEEVES, AND HOLES IN SLABS BETWEEN FLOORS SHALL BE PROPERLY SEALED, FIRE <br />PROOFED AND WATER PROOFED. <br />E. HOLES CUT THROUGH WALLS SHALL BE DRILLED OR CUT WITH TOOLS DESIGNED FOR THE PURPOSE. ALL <br />OPENINGS, SLEEVES AND HOLES IN WALLS THAT EXTEND TO UNDERSIDE OF FLOOR ABOVE SHALL BE <br />PROPER <br />LY SEALED AND FIRE PROOFED. <br />F. REPAIRS SHALL BE PERFORMED WITH MATERIALS WHICH MATCH ATCH EXISTING MATERIALS AND BE <br />INSTALLED IN ACCORDANCE WITH APPROPRIATE SECTIONS OF THESE SPECIFICATIONS. <br />G. CONTRACTOR SHALL NOT BE PERMITTED TO CUT OR MODIFY ANY STRUCTURAL MEMBERS WITHOUT THE <br />WRITTEN PERMISSION OF THE ARCHITECT. <br />3.04 TRENCHING, EXCAVATION, BACKFILLING, AND REPAIRS <br />A. COMPLY WITH PROVISIONS OF DIVISION 31. <br />B. PROVIDE TRENCHING, EXCAVATION, AND BACKFILLING NECESSARY FOR PERFORMANCE OF WORK UNDER <br />THIS DIVISION. <br />E C. PROVIDE SHEATHING, SHORING DEWATERING AND CLEANING NECESSARY TO KEEP TRENCHES AND <br />THEIR GRADES IN PROPER CONDITION FOR WORK TO BE PERFORMED. <br />D. TRENCHING AND EXCAVATION SHALL BE UNCLASSIFIED. NO EXTRA WILL BE PAID IN EVENT THAT ROCK IS <br />ENCOUNTERED. <br />3.05 FOUNDATIONS AND PADS <br />A. PROVIDE CONCRETE FOUNDATIONS AND PADS FOR EQUIPMENT PER THE REQUIREMENTS DIVISION 03. <br />LOCATE AND SIZE FOUNDATIONS, PADS, AND ANCHOR BOLTS AS REQUIRED FOR EQUIPMENT IN THIS <br />DIVISION. <br />B. PROVIDE CONCRETE FOUNDATIONS AND PADS AS REQUIRED FOR ELECTRICAL UTILITY COMPANY'S <br />EQUIPMENT SUCH AS TRANSFORMERS, CT CABINETS, METERING CABINETS, SWITCHES, FUSED <br />S COMPLIANCE IT THE UTILITY DISCONNECTS, AND CIRCUIT BREAKERS ALL WORK HALL BE IN NCE WITH E IL TY <br />COMPANY'S SPECIFICATIONS. <br />3.06 TESTING ELECTRICAL SYSTEMS <br />A. ON COMPLETION OF WORK, INSTALLATION SHALL BE COMPLETELY OPERATIONAL AND ENTIRELY FREE <br />FROM GROUNDS SHORT CIRCUITS AND OPEN CIRCUITS. PERFORM OPERATIONAL TESTS AS REQUIRED <br />TO DEMONSTRATE SUBSTANTIAL COMPLETION OF THE WORK. BALANCE CIRCUITS SO THAT FEEDERS TO <br />PANELS ARE NOT MORE THAN 10% OUT OF BALANCE BETWEEN PHASES WITH ALL AVAILABLE LOAD <br />ENERGIZED AND OPERATING. FURNISH ALL LABOR, MATERIALS AND INSTRUMENTS FOR ABOVE TESTS. <br />ALL AMPERE READINGS SHALL BE MADE WITH A TRUE RMS READING METER. <br />B. PERFORM MEGGER TESTS OF ALL SERVICE ENTRANCE CIRCUITS, FEEDER AND BRANCH CIRCUITS SIZE #4 <br />AWG AND LARGER. PROVIDE A REPORT OF ALL SUCH MEGGER TEST RESULTS. <br />C. FURNISH THE ENGINEER A COPY OF TEST REPORTS AND REQUIRED CERTIFICATION INCLUDING BUT NOT <br />LIMITED TO THE FOLLOWING: <br />1. SERVICE GROUND RESISTANCE TEST <br />2. SWITCHBOARD AND PANELBOARD LOAD TEST- INCLUDE AMPERE READINGS OF ALL PANELS AND <br />MAJOR CIRCUIT BREAKERS <br />D. PRIOR TO FINAL OBSERVATION AND ACCEPTANCE TEST, INSTALL ALL ELECTRICAL SYSTEMS AND <br />EQUIPMENT COMPLETE AND IN SATISFACTORY OPERATING CONDITION. <br />END OF SECTION <br />SECTION 260519 <br />LOW -VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES <br />PART1 GENERAL <br />1.01SECTION INCLUDES <br />A. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY <br />CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS APPLY TO TO THIS SECTION. <br />B. COMPLY WITH PROVISION OF SECTION 26 0500 COMMON WORK RESULTS FOR ELECTRICAL. <br />C. THIS SECTION SPECIFIES THE FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF THE <br />ELECTRICAL CONDUCTORS AND CABLES FOR USE IN ELECTRICAL SYSTEMS RATED 600 V AND BELOW, <br />INDICATED AS CABLE(S), CONDUCTOR(S), WIRE, OR WIRING IN THIS SECTION. <br />D. FURNISH AND INSTALL ELECTRICAL SYSTEMS, MATERIALS, EQUIPMENT, AND ACCESSORIES IN <br />ACCORDANCE WITH THIS SPECIFICATIONS AND DRAWINGS <br />E. SINGLE CONDUCTOR BUILDING WIRE. <br />1.02RELATED REQUIREMENTS <br />A. SECTION 26 0500 - COMMON WORK RESULTS FOR ELECTRICAL. <br />B. SECTION 260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS: ADDITIONAL REQUIREMENTS <br />FOR GROUNDING CONDUCTORS AND GROUNDING CONNECTORS. <br />C. SECTION 26 0534 - RACEWAYS AND CONDUIT SYSTEMS. <br />D. SECTION 260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS: IDENTIFICATION PRODUCTS AND <br />REQUIREMENTS. <br />1.03REFERENCE STANDARDS <br />A. ASTM B3 - STANDARD SPECIFICATION FOR SOFT OR ANNEALED COPPER WIRE; 2013. <br />B. ASTM B8 - STANDARD SPECIFICATION FOR CONCENTRIC -LAY -STRANDED COPPER CONDUCTORS, HARD, <br />MEDIUM -HARD, OR SOFT; 2011. <br />C. ASTM B33 - STANDARD SPECIFICATION FOR TIN -COATED SOFT OR ANNEALED COPPER WIRE FOR <br />ELECTRICAL PURPOSES; 2010 (REAPPROVED 2014). <br />D. ASTM B787/B787M - STANDARD SPECIFICATION FOR 19 WIRE COMBINATION UNILAY-STRANDED COPPER <br />CONDUCTORS FOR SUBSEQUENT INSULATION; 2004 (REAPPROVED 2014). <br />E. NECA 1- STANDARD FOR GOOD WORKMANSHIP IN ELECTRICAL 2010. <br />F. NECA 104 - RECOMMENDED PRACTICE FOR INSTALLING ALUMINUM BUILDING WIRE AND CABLE; 2012. <br />G. NEMA WC 70 - NONSHIELDED POWER CABLE 2000 V OR LESS FOR THE DISTRIBUTION OF ELECTRICAL <br />ENERGY; 2009. <br />H. NETA ATS - ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWER EQUIPMENT AND SYSTEMS; <br />2013. <br />I. NFPA 70 - NATIONAL ELECTRICAL CODE; MOST RECENT EDITION ADOPTED BY AUTHORITY HAVING <br />JURISDICTION INCLUDING ALL APPLICABLE AMENDMENTS AND SUPPLEMENTS. <br />J. UL 44 - THERMOSET -INSULATED WIRES AND CABLES; CURRENT EDITION INCLUDING ALL REVISIONS. <br />K. UL 83 - THERMOPLASTIC -INSULATED WIRES AND CABLES; CURRENT EDITION, INCLUDING ALL REVISIONS. <br />L. UL 493 - THERMOPLASTIC -INSULATED UNDERGROUND FEEDER AND BRANCH -CIRCUIT CABLES; CURRENT <br />EDITION, INCLUDING ALL REVISIONS. <br />1.04ADMINISTRATIVE REQUIREMENTS <br />A. COORDINATION: <br />1. COORDINATE SIZES OF RACEWAYS, BOXES, AND EQUIPMENT ENCLOSURES INSTALLED UNDER OTHER <br />SECTIONS WITH THE ACTUAL CONDUCTORS TO BE INSTALLED, INCLUDING ADJUSTMENTS FOR <br />CONDUCTOR SIZES INCREASED FOR VOLTAGE DROP. <br />2. COORDINATE THE INSTALLATION OF DIRECT BURIAL CABLE WITH OTHER TRADES TO AVOID <br />CONFLICTS WITH PIPING OR OTHER POTENTIAL CONFLICTS. <br />3. COORDINATE WITH ELECTRICAL EQUIPMENT INSTALLED UNDER OTHER SECTIONS TO PROVIDE <br />TERMINATIONS SUITABLE FOR USE WITH THE CONDUCTORS TO BE INSTALLED. <br />4. NOTIFY ENGINEER OF ANY CONFLICTS WITH OR DEVIATIONS FROM THE CONTRACT DOCUMENTS. <br />OBTAIN DIRECTION BEFORE PROCEEDING WITH WORK. <br />1.05SUBMITTALS <br />A. PRODUCT DATA: PROVIDE MANUFACTURER'S STANDARD CATALOG PAGES AND DATA SHEETS FOR <br />CONDUCTORS AND CABLES, INCLUDING DETAILED INFORMATION ON MATERIALS, CONSTRUCTION, <br />RATINGS, LISTINGS, AND AVAILABLE SIZES, CONFIGURATIONS, AND STRANDING. <br />B. DESIGN DATA: INDICATE VOLTAGE DROP AND AMPACITY CALCULATIONS FOR ALUMINUM CONDUCTORS <br />SUBSTITUTED FOR COPPER CONDUCTORS. INCLUDE PROPOSED MODIFICATIONS TO RACEWAYS, BOXES, <br />WIRING GUTTERS, ENCLOSURES, ETC. TO ACCOMMODATE SUBSTITUTED CONDUCTORS. <br />C. PROJECT RECORD DOCUMENTS: RECORD ACTUAL INSTALLED CIRCUITING ARRANGEMENTS. RECORD <br />ACTUAL ROUTING FOR UNDERGROUND CIRCUITS. <br />1.06QUALITY ASSURANCE <br />A. CONFORM TO REQUIREMENTS OF NFPA 70 . <br />B. MAINTAIN AT THE PROJECT SITE A COPY OF EACH REFERENCED DOCUMENT THAT PRESCRIBES <br />EXECUTION REQUIREMENTS. <br />C. MANUFACTURERQUALIFICATIONS: COMPANY SPECIALIZING IN MANUFACTURING THE PRODUCTS <br />SPECIFIED IN THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE. <br />1.07DELIVERY, STORAGE, AND HANDLING <br />A. FURNISH WIRES AND CABLES ON REELS OR COILS FACTORY -WRAPPED WITH WATERPROOF FLEXIBLE <br />COVERING TO PROTECT AGAINST PHYSICAL DAMGE. EACH CABLE AND THE OUTSIDE OF EACH REEL OR <br />COIL, SHALL BE PLAINLY MARKED OR TAGGED TO INDICATE THE CABLE LANGHT, VOLTAGE RATING, <br />CONDUCTOR SIZE, AND MANUFACTURER'S LOT NUMBER AND REEL NUMBER. EACH COIL OR REEL SHALL <br />CONTAIN ONLY ONE CONTINUOS CABLE WITHOT SPLICES. DAMAGED CABLE, WIRE OR CONNECTORS <br />SHALL BE REMOVED FROM PROJECT SITE. <br />B. RECEIVE, INSPECT, HANDLE, AND STORE CONDUCTORS AND CABLES IN ACCORDANCE WITH <br />MANUFACTURER'S INSTRUCTIONS. <br />1.08FIELD CONDITIONS <br />A. DO NOT INSTALL OR OTHERWISE HANDLE THERMOPLASTIC -INSULATED CONDUCTORS AT TEMPERATURES <br />LOWER THAN 14 DEGREES F, UNLESS OTHERWISE PERMITTED BY MANUFACTURER'S INSTRUCTIONS. <br />WHEN INSTALLATION BELOW THIS TEMPERATURE IS UNAVOIDABLE, NOTIFY ENGINEER AND OBTAIN <br />DIRECTION BEFORE PROCEEDING WITH WORK. <br />PART 2 PRODUCTS <br />2.01 CONDUCTOR AND CABLE APPLICATIONS <br />A. DO NOT USE CONDUCTORS AND CABLES FOR APPLICATIONS OTHER THAN AS PERMITTED BY NFPA 70 <br />AND PRODUCT LISTING. <br />B. PROVIDE SINGLE CONDUCTOR BUILDING WIRE INSTALLED IN SUITABLE RACEWAY UNLESS OTHERWISE <br />INDICATED, PERMITTED, OR REQUIRED. <br />2.02 CONDUCTOR AND CABLE MANUFACTURERS <br />A. CERRO WIRE LLC: WWW.CERROWIRE.COM. <br />B. ENCORE WIRE CORPORATION: WWW.ENCOREWIRE.COM. <br />C. SOUTHWIRE COMPANY: WWW.SOUTHWIRE.COM. <br />D. AMERICAN INSULATED WIRE <br />E. SUPERIOR ESSEX <br />F. GENERAL CABLE <br />G. THE OKONITE CO. <br />H. REPUBLIC WIRE <br />I. UNITED COPPER <br />J. ALCAN PRODUCT CORPORATION <br />K. PRYSMIAN POWER CABLES AND SYSTEMS <br />L. SUBSTITUTIONS: SEE SECTION 016000 - PRODUCT REQUIREMENTS. <br />2.03 CONDUCTOR AND CABLE GENERAL REQUIREMENTS <br />A. PROVIDE PRODUCTS THAT COMPLY WITH REQUIREMENTS OF NFPA 70 <br />B. PROVIDE PRODUCTS LISTED CLASSIFIED AND LABELED AS SUITABLE FOR THE PURPOSE INTENDED. <br />R SE INTEND D <br />C. UNLESS SPECIFICALLY INDICATED TO BE EXCLUDED, PROVIDE ALL REQUIRED CONDUIT, BOXES, WIRING, <br />CONNECTORS, ETC. AS REQUIRED FOR A COMPLETE OPERATING SYSTEM. <br />D. COMPLY WITH NEMA WC 70 . <br />E. THERMOPLASTIC -INSULATED CONDUCTORS AND CABLES: LISTED AND LABELED AS COMPLYING WITH UL <br />83. <br />F. THERMOSET -INSULATED CONDUCTORS AND CABLES: LISTED AND LABELED AS COMPLYING WITH UL 44 <br />G. CONDUCTORS FOR GROUNDING AND BONDING: ALSO COMPLY WITH SECTION 260526. <br />H. CONDUCTORS AND CABLES INSTALLED IN CABLE TRAY: LISTED AND LABELED AS SUITABLE FOR CABLE <br />TRAY USE. <br />1. CONDUCTORS AND CABLES INSTALLED WHERE EXPOSED TO DIRECT Y F E RAYS O SUN: LISTED AND LABELED <br />AS SUNLIGHT RESISTANT. <br />J. CONDUCTORS AND CABLES INSTALLEDEXPOSED <br />XPO ED IN SPACES USED FOR ENVIRONMENTAL AIR (ONLY <br />WHERE SPECIFICALLY PERMITTED): PLENUM RATED, LISTED AND LABELED AS SUITABLE FOR USE IN <br />RETURN AIR PLENUMS. <br />K. CONDUCTOR MATERIAL: <br />1. PROVIDE COPPER CONDUCTORS ONLY. ALUMINUM CONDUCTORS ARE NOT ACCEPTABLE FOR THIS <br />PROJECT. CONDUCTOR SIZES INDICATED ARE BASED ON COPPER. <br />2. COPPER CONDUCTORS: SOFT DRAWN ANNEALED, 98 PERCENT CONDUCTIVITY, UNCOATED COPPER <br />CONDUCTORS COMPLYING WITH ASTM B3, ASTM B8, OR ASTM B787/B 787M UNLESS OTHERWISE <br />INDICATED. <br />3. TINNED COPPER CONDUCTORS: COMPLY WITH ASTM B33 . <br />L. MINIMUM CONDUCTOR SIZE: 12 AWG. <br />1. BRANCH CIRCUITS: 12 AWG. <br />A. EXCEPTIONS: <br />1 20 A 120 V CIRCUITS LONGER THAN 75 FEET <br />: 10 AWG, FOR VOLTAGE DROP. <br />2) 20 A, 120 V CIRCUITS LONGER THAN 150 FEET: 8 AWG, FOR VOLTAGE DROP. <br />3) 20 A, 277 V CIRCUITS LONGER THAN 150 FEET: 10 AWG, FOR VOLTAGE DROP. <br />M. WHERE CONDUCTOR SIZE 15 NOT INDICATED, SIZE TO COMPLY WITH NFPA 70 BUT NOT LESS THAN <br />APPLICABLE MINIMUM SIZE REQUIREMENTS SPECIFIED. <br />N. CONDUCTOR COLOR CODING: <br />1. COLOR CODE CONDUCTORS AS INDICATED UNLESS OTHERWISE REQUIRED BY THE AUTHORITY <br />HAVING JURISDICTION. MAINTAIN CONSISTENT COLOR CODING THROUGHOUT PROJECT, <br />2. INSTALL IN EACH BRANCH CIRCUIT PANELBOARD A LEGEND EXPLAINING THE COLOR CODE FOR <br />UNGROUNDED CONDUCTORS <br />3. COLOR CODING METHOD: INTEGRALLY COLORED INSULATION. <br />A. CONDUCTORS SIZE 4 AWG AND LARGER MAY HAVE BLACK INSULATION COLOR CODED USING VINYL <br />COLOR CODING ELECTRICAL TAPE. <br />4. COLOR CODE: <br />A. 480Y/277 V, 3 PHASE, 4 WIRE SYSTEM: <br />1) PHASE A: BROWN. <br />2) PHASE B: ORANGE. <br />3) PHASE C: YELLOW. <br />4) NEUTRAL: GRAY. <br />5) GROUND : GREEN. <br />B. 208Y/120 V, 3 PHASE, 4 WIRE SYSTEM: <br />1) PHASE A: BLACK. <br />2) PHASE B: RED. <br />3) PHASE C: BLUE. <br />4) NEUTRAL : WHITE. <br />5) GROUND : GREEN. <br />C. EQUIPMENT GROUND, ALL SYSTEMS: GREEN. <br />D. FOR CONTROL CIRCUITS, COMPLY WITH MANUFACTURER'S RECOMMENDED COLOR CODE. <br />2.04 SINGLE CONDUCTOR BUILDING WIRE <br />A. DESCRIPTION: SINGLE CONDUCTOR INSULATED WIRE. <br />B. CONDUCTOR STRANDING: <br />1. FEEDERS AND BRANCH CIRCUITS: <br />A. SIZE 10 AWG AND SMALLER: STRANDED. <br />B. SIZE 8 AWG AND LARGER: STRANDED. <br />2. CONTROL CIRCUITS: STRANDED. <br />C. INSULATION VOLTAGE RATING: 600 V. <br />D. INSULATION: <br />1. COPPER BUILDING WIRE: TYPE THHN/THWN OR THHN/THWN-2, EXCEPT AS INDICATED BELOW. <br />A. SIZE 4 AWG AND LARGER: TYPE THHN/THWN. <br />B. INSTALLED UNDERGROUND: TYPE XHHW-2. <br />C. FIXTURE WIRING WITHIN LUMINAIRES: TYPE TFFN/TFN FOR LUMINAIRES WITH LABELED MAXIMUM <br />TEMPERATURE OF 90 DEGREES C; APPROVED SUITABLE TYPE FOR LUMINAIRES WITH LABELED MAXIMUM <br />TEMPERATURE GREATER THAN 90 DEGREES C. <br />2.05 WIRING CONNECTORS <br />A. DESCRIPTION: WIRING CONNECTORS APPROPRIATE FOR THE APPLICATION, SUITABLE FOR USE WITH THE <br />CONDUCTORS TO BE CONNECTED, AND LISTED AS COMPLYING WITH UL 486A-486B OR UL 486C AS <br />APPLICABLE. <br />B. CONNECTORS FOR GROUNDING AND BONDING: COMPLY WITH SECTION 260526. <br />C. WIRING CONNECTORS FOR SPLICES AND TAPS: <br />1. COPPER CONDUCTORS SIZE 8 AWG AND SMALLER: USE TWIST -ON INSULATED SPRING CONNECTORS. <br />2. COPPER CONDUCTORS SIZE 6 AWG AND LARGER: USE MECHANICAL CONNECTORS. <br />D. WIRING CONNECTORS FOR TERMINATIONS: <br />1. PROVIDE TERMINAL LUGS FOR CONNECTING CONDUCTORS TO EQUIPMENT FURNISHED WITH <br />TERMINATIONS DESIGNED FOR TERMINAL LUGS. <br />2. PROVIDE COMPRESSION ADAPTERS FOR CONNECTING CONDUCTORS TO EQUIPMENT FURNISHED <br />WITH MECHANICAL LUGS WHEN ONLY COMPRESSION CONNECTORS ARE SPECIFIED. <br />3. WHERE OVER -SIZED CONDUCTORS ARE LARGER THAN THE EQUIPMENT TERMINATIONS CAN <br />ACCOMMODATE, PROVIDE CONNECTORS SUITABLE FOR REDUCING TO APPROPRIATE SIZE, BUT NOT <br />LESS THAN REQUIRED FOR THE RATING OF THE OVERCURRENT PROTECTIVE DEVICE. <br />4. PROVIDE MOTOR PIGTAIL CONNECTORS FOR CONNECTING MOTOR LEADS IN ORDER TO FACILITATE <br />DISCONNECTION. <br />5. COPPER CONDUCTORS SIZE 8 AWG AND LARGER: USE MECHANICAL CONNECTORS WHERE <br />CONNECTORS ARE REQUIRED. <br />6. STRANDED CONDUCTORS SIZE 10 AWG AND SMALLER: USE CRIMPED TERMINALS FOR CONNECTIONS <br />TO TERMINAL SCREWS. <br />7. CONDUCTORS FOR CONTROL CIRCUITS: USE CRIMPED TERMINALS FOR ALL CONNECTIONS. <br />E. DO NOT USE INSULATION -PIERCING OR INSULATION -DISPLACEMENT CONNECTORS DESIGNED FOR USE <br />WITH CONDUCTORS WITHOUT STRIPPING INSULATION. <br />F. DO NOT USE PUSH -IN WIRE CONNECTORS AS A SUBSTITUTE FOR TWIST -ON INSULATED SPRING <br />CONNECTORS. <br />PART 3 EXECUTION <br />3.01 EXAMINATION <br />A. VERIFY THAT INTERIOR OF BUILDING HAS BEEN PROTECTED FROM WEATHER. <br />B. VERIFY THAT WORK LIKELY TO DAMAGE WIRE AND CABLE HAS BEEN COMPLETED. <br />C. VERIFY THAT RACEWAYS, BOXES, AND EQUIPMENT ENCLOSURES ARE INSTALLED AND ARE PROPERLY <br />SIZED TO ACCOMMODATE CONDUCTORS AND CABLES IN ACCORDANCE WITH NFPA 70 . <br />D. VERIFY THAT FIELD MEASUREMENTS ARE AS SHOWN ON THE DRAWINGS. <br />E. VERIFY THAT CONDITIONS ARE SATISFACTORY FOR INSTALLATION PRIOR TO STARTING WORK. <br />3.02 PREPARATION <br />A. CLEAN RACEWAYS THOROUGHLY TO REMOVE FOREIGN MATERIALS BEFORE INSTALLING CONDUCTORS <br />AND CABLES. <br />B. COMPLETE CONDUIT SYSTEM, INCLUDING BUSHINGS, BEFORE PULLING WIRES OR CABLES. <br />3.03 INSTALLATION <br />A. CIRCUITING REQUIREMENTS: <br />1. ARRANGE CIRCUITING TO MINIMIZE SPLICES. <br />2. INCLUDE CIRCUIT LENGTHS REQUIRED TO INSTALL CONNECTED DEVICES WITHIN 10 FT OF LOCATION <br />SHOWN. <br />3. MAINTAIN SEPARATION OF CLASS 1, CLASS 2, AND CLASS 3 REMOTE -CONTROL, SIGNALING, AND <br />POWER -LIMITED CIRCUITS IN ACCORDANCE WITH NFPA 70 . <br />4. MAINTAIN SEPARATION OF WIRING FOR EMERGENCY SYSTEMS IN ACCORDANCE WITH NFPA 70 . <br />5. CIRCUITING ADJUSTMENTS: UNLESS OTHERWISE INDICATED, WHEN BRANCH CIRCUITS ARE SHOWN <br />AS SEPARATE, COMBINING THEM TOGETHER IN A SINGLE RACEWAY IS NOT PERMITTED. <br />A. PROVIDE NO MORE THAN SIX CURRENT -CARRYING CONDUCTORS IN A SINGLE RACEWAY. DEDICATED <br />NEUTRAL CONDUCTORS ARE CONSIDERED CURRENT -CARRYING CONDUCTORS. <br />6. COMMON NEUTRALS: UNLESS OTHERWISE INDICATED, SHARING OF NEUTRAL/GROUNDED <br />CONDUCTORS AMONG UP TO THREE SINGLE PHASE BRANCH CIRCUITS OF DIFFERENT PHASES <br />INSTALLED IN THE SAME RACEWAY IS NOT PERMITTED. PROVIDE DEDICATED NEUTRAL/GROUNDED <br />CONDUCTOR FOR EACH INDIVIDUAL BRANCH CIRCUIT. <br />B. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. <br />C. INSTALL CONDUCTORS AND CABLE IN A NEAT AND WORKMANLIKE MANNER IN ACCORDANCE WITH NECA <br />1. <br />D. INSTALLATION IN RACEWAY: <br />1. TAPE ENDS OF CONDUCTORS AND CABLES TO PREVENT INFILTRATION OF MOISTURE AND OTHER <br />CONTAMINANTS. <br />2. PULL ALL CONDUCTORS AND CABLES TOGETHER INTO RACEWAY AT SAME TIME. <br />3. DO NOT DAMAGE CONDUCTORS AND CABLES OR EXCEED MANUFACTURER'S RECOMMENDED <br />MAXIMUM PULLING TENSION AND SIDEWALL PRESSURE. <br />4. USE SUITABLE WIRE PULLING LUBRICANT WHERE NECESSARY, EXCEPT WHEN LUBRICANT IS NOT <br />RECOMMENDED BY THE MANUFACTURER. <br />E. EXPOSED CABLE INSTALLATION (ONLY WHERE SPECIFICALLY PERMITTED): <br />1. ROUTE CABLES PARALLEL OR PERPENDICULAR TO BUILDING STRUCTURAL MEMBERS AND SURFACES. <br />2. PROTECT CABLES FROM PHYSICAL DAMAGE. <br />F. SECURE AND SUPPORT CONDUCTORS AND CABLES IN ACCORDANCE WITH NFPA 70 USING SUITABLE <br />SUPPORTS AND METHODS APPROVED BY THE AUTHORITY HAVING JURISDICTION. PROVIDE INDEPENDENT <br />SUPPORT FROM BUILDING STRUCTURE. DO NOT PROVIDE SUPPORT FROM RACEWAYS, PIPING, <br />DUCTWORK, OR OTHER SYSTEMS. <br />1. INSTALLATION ABOVE SUSPENDED CEILINGS: DO NOT PROVIDE SUPPORT FROM CEILING SUPPORT <br />SYSTEM. DO NOT PROVIDE SUPPORT FROM CEILING GRID OR ALLOW CONDUCTORS AND CABLES TO <br />LAY ON CEILING TILES. <br />G. INSTALL CONDUCTORS WITH A MINIMUM OF 12 INCHES OF SLACK AT EACH OUTLET. <br />H. WHERE CONDUCTORS ARE INSTALLED IN ENCLOSURES FOR FUTURE TERMINATION BY OTHERS, PROVIDE <br />A MINIMUM OF 5 FEET OF SLACK. <br />I. NEATLY TRAIN AND BUNDLE CONDUCTORS INSIDE BOXES, WIREWAYS, PANELBOARDS AND OTHER <br />EQUIPMENT ENCLOSURES. <br />J. GROUP OR OTHERWISE IDENTIFY NEUTRAL/GROUNDED CONDUCTORS WITH ASSOCIATED UNGROUNDED <br />CONDUCTORS INSIDE ENCLOSURES IN ACCORDANCE WITH NFPA 70 . <br />K. MAKE WIRING CONNECTIONS USING SPECIFIED WIRING CONNECTORS. <br />1. MAKE SPLICES AND TAPS ONLY IN ACCESSIBLE BOXES. DO NO U T PULL SPLICES INTO RACEWAYS OR <br />MAKE SPLICES IN CONDUIT BODIES OR WIRING GUTTERS. <br />2. REMOVE APPROPRIATE AMOUNT OF CONDUCTOR INSULATION FOR MAKING CONNECTIONS WITHOUT <br />CUTTING, NICKING OR DAMAGING CONDUCTORS. <br />3. DO NOT REMOVE CONDUCTOR STRANDS TO FACILITATE INSERTION INTO CONNECTOR. <br />4. CLEAN CONTACT SURFACES ON CONDUCTORS AND CONNECTORS TO SUITABLE REMOVE CORROSION, <br />OXIDES, AND OTHER CONTAMINATES. DO NOT USE WIRE BRUSH ON PLATED CONNECTOR SURFACES. <br />L. INSULATE SPLICES AND TAPS THAT ARE MADE WITH UNINSULATED CONNECTORS USING METHODS <br />SUITABLE FOR THE APPLICATION, WITH INSULATION AND MECHANICAL STRENGTH AT LEAST EQUIVALENT <br />TO UNSPLICED CONDUCTORS. <br />1. DRY LOCATIONS: USE INSULATING COVERS SPECIFICALLY DESIGNED FOR THE CONNECTORS, <br />ELECTRICALTAPE OR HEAT SHRINK TUBING. <br />A. FOR TAPED CONNECTIONS, FIRST APPLY ADEQUATE AMOUNT OF RUBBER SPLICING ELECTRICAL TAPE OR <br />ELECTRICAL FILLER TAPE, FOLLOWED BY OUTER COVERING OF VINYL INSULATING ELECTRICAL TAPE. <br />B. FOR TAPED CONNECTIONS LIKELY TO REQUIRE RE-ENTERING, INCLUDING MOTOR LEADS, FIRST APPLY <br />VARNISHED CAMBRIC ELECTRICAL TAPE, FOLLOWED BY ADEQUATE <br />AMOUNT OF RUBBER SPLICING <br />ELECTRICALTAPE, FOLLOWED BY OUTER COVERING OF VINYL INSULATING ELECTRICAL TAPE. <br />M. IDENTIFY CONDUCTORS AND CABLES IN ACCORDANCE WITH SECTION 260553. <br />N. INSTALL FIRESTOPPING TO PRESERVE FIRE RESISTANCE RATING OF PARTITIONS AND OTHER ELEMENTS, <br />USING MATERIALS AND METHODS SPECIFIED IN SECTION 078400. <br />0. UNLESS SPECIFICALLY INDICATED TO BE EXCLUDED, PROVIDE FINAL CONNECTIONS TO ALL EQUIPMENT <br />AND DEVICES, INCLUDING THOSE FURNISHED BY OTHERS, AS REQUIRED FOR A COMPLETE OPERATING <br />SYSTEM. <br />3.04 FIELD QUALITY CONTROL <br />A. INSPECT AND TEST IN ACCORDANCE WITH NETA ATS, EXCEPT SECTION 4. <br />B. ELECTRICAL TESTS: <br />1. AFTER INSTALLATION BUT BEFORE CONNECTION TO UTILIZATION DEVICES, SUCH AS FIXTURES, <br />MOTORS, OR APPLIANCES, TEST CONDUCTORS PHASE -TO -PHASE AND PHASE -TO -GROUND <br />RESISTANCE WITH AN INSULATION RESISTANCE TESTER. EXISTING CONDUCTORS TO BE REUSED <br />SHALL ALSO BE TESTED. <br />2. APPLIED VOLTAGE SHALL BE 500 V DC FOR 300 V RATED CABLE, AND 1000 V DC FOR 600 V RATED <br />CABLE. APPLY TEST FOR ONE MINUTE OR UNTIL READING IS CONSTANT FOR 15 SECONDS, <br />WHICHEVER IS LONGER. MINIMUM INSULATION RESISTANCE VALUES SHALL NOT BE LESS THAN 25 <br />MEGOHMS FOR 300 V RATED CABLE AND 100 MEGOHMS FOR 600 V RATED CABLE. <br />A. FEEDER (600A & SMALLER) CIRCUITS AND BRANCH CIRCUITS <br />1) USE EITHER A MOTOR DRIVEN (BIDDLE 359) OR A HAND CRANK (BIDDLE MJ159) MEGGER. <br />2) PERFORM A DIELECTRIC ABSORPTION RATIO TEST USING A 60-SECOND TEST PERIOD. RECORD <br />THE MEGOHM READINGS AT 30 SECONDS AND 60 SECONDS. CALCULATE THE DIELECTRIC <br />ABSORPTION RATIO (60 SEC / 30 SEC READINGS) AND RECORD <br />B. PERFORM INSPECTIONS AND TESTS LISTED IN NETA ATS, SECTION 7.3.2. THE INSULATION RESISTANCE <br />TEST IS REQUIRED FOR ALL CONDUCTORS. THE RESISTANCE TEST FOR PARALLEL CONDUCTORS LISTED <br />AS OPTIONAL IS NOT REQUIRED. <br />1. DISCONNECT SURGE PROTECTIVE DEVICES (SPDS) PRIOR TO PERFORMING ANY HIGH POTENTIAL <br />TESTING. REPLACE SPDS DAMAGED BY PERFORMING HIGH POTENTIAL TESTING WITH NEW SPDS. <br />D. CORRECT DEFICIENCIES AND REPLACE DAMAGED OR DEFECTIVE CONDUCTORS AND CABLES. <br />E. PROVIDE 8 COPIES OF THE MEGGER TEST REPORT TO THE ENGINEER. THE REPORT SHALL BE IN A <br />TABULATED FORMAT AND SHALL INCLUDE THE FOLLOWING AS A MINIMUM. <br />1. CIRCUIT IDENTIFICATION <br />2. TYPE OF RACEWAY <br />3. APPROXIMATE LENGTH OF CIRCUIT <br />4. MEGOHM READINGS <br />5. AMBIENT TEMPERATURE <br />6. APPROXIMATE HUMIDITY (DRY, AVERAGE, OR HUMID) <br />END OF SECTION <br />SECTION 260526 <br />GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS <br />PART 1 GENERAL <br />1.01SECTION INCLUDES <br />A. BASIC MATERIALS AND METHODS ALONG WITH DIVISION 01 GENERA REQUIREMENTS, L THAT ARE <br />APPLICABLE TO ALL DIVISION 26 SECTIONS <br />B. DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDING GENERAL AND SUPPLEMENTARY <br />CONDITIONS AND DIVISION 01 SPECIFICATION SECTIONS APPLY TO ALL DIVISION 26 SECTIONS. <br />C. COMPLY WITH PROVISION OF SECTION 26 0500 COMMON WORK RESULTS FOR ELECTRICAL. <br />D. THIS SECTION SPECIFIES THE FURNISHING, INSTALLATION, CONNECTION, AND TESTING OF GROUNDING <br />AND BONDING EQUIPMENT, INDICATED AS GROUNDING EQUIPMENT IN THIS SECTION. <br />E. "GROUNDING ELECTRODE SYSTEM" REFERS TO GROUNDING ELECTRODE CONDUCTORS AND ALL <br />ELECTRODES REQUIRED OR ALLOWED BY NEC, AS WELL AS MADE, SUPPLEMENTARY, AND LIGHTNING <br />PROTECTION SYSTEM GROUNDING ELECTRODES. <br />F. GROUNDING AND BONDING REQUIREMENTS. <br />G. CONDUCTORS FOR GROUNDING AND BONDING. <br />H. CONNECTORS FOR GROUNDING AND BONDING. <br />I. GROUND BARS. <br />J. GROUND ROD ELECTRODES. <br />K. GROUND ACCESS WELLS. <br />1.02RELATED REQUIREMENTS <br />A. SECTION 26 0500 - COMMON WORK RESULTS FOR ELECTRICAL. <br />B. SECTION 260519 - LOW -VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES: ADDITIONAL <br />REQUIREMENTS FOR CONDUCTORS FOR GROUNDING AND BONDING, INCLUDING CONDUCTOR COLOR <br />CODING. <br />C. SECTION 26-0533 - RACEWAYS AND CONDUIT SYSTEMS. <br />D. SECTION 26 2413 - SWITCHBOARDS. <br />E. SECTION 26 2416 - PANELBOARDS. <br />F. SECTION 26 3213 - ENGINE GENERATORS. <br />G. SECTION 26 3623 - AUTOMATIC TRANSFER SWITCHES. <br />H. SECTION 260553 -IDENTIFICATION FOR ELECTRICAL SYSTEMS: IDENTIFICATION PRODUCTS AND <br />REQUIREMENTS. <br />I. SECTION 264113 - LIGHTNING PROTECTION FOR STRUCTURES. <br />J. SECTION 265600 - EXTERIOR LIGHTING: ADDITIONAL GROUNDING AND BONDING REQUIREMENTS FOR <br />POLE -MOUNTED LUMINAIRES. <br />1.03REFERENCE STANDARDS <br />A. IEEE 81 - IEEE GUIDE FOR MEASURING EARTH RESISTIVITY, GROUND IMPEDANCE, AND EARTH SURFACE <br />POTENTIALS OF A GROUNDING SYSTEM; 2012. <br />B. NECA 1- STANDARD FOR GOOD WORKMANSHIP IN ELECTRICAL CONSTRUCTION; 2010. <br />C. NEMA GR 1- GROUNDING ROD ELECTRODES AND GROUNDING <br />D NG ROD ELECTRODE COUPLINGS; 2007. <br />D. NETA ATS - ACCEPTANCE TESTING SPECIFICATIONS FOR ELECTRICAL POWER EQUIPMENT AND SYSTEMS; <br />2013. <br />E. NFPA 70 - NATIONAL ELECTRICAL CODE; MOST RECENT EDITION ADOPTED BY AUTHORITY HAVING <br />JURISDICTION, INCLUDING ALL APPLICABLE AMENDMENTS AND SUPPLEMENTS. <br />F. NFPA 99 - HEALTH CARE FACILITIES CODE; 2015. <br />G. NFPA 780 - STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION SYSTEMS; 2014. <br />H. UL 467 - GROUNDING AND BONDING EQUIPMENT; CURRENT EDITION, INCLUDING ALL REVISIONS. <br />1.04ADMINISTRATIVE REQUIREMENTS <br />A. COORDINATION: <br />1. VERIFY EXACT LOCATIONS OF UNDERGROUND METAL WAT <br />ER ER SERVICE PIPE ENTRANCES TO BUILDING. <br />2. COORDINATE THE WORK WITH OTHER TRADES TO PROVIDE STEEL REINFORCEMENT COMPLYING WITH <br />SPECIFIED REQUIREMENTS FOR CONCRETE -ENCASED ELECTRODE. <br />3. NOTIFY ENGINEER OF ANY CONFLICTS WITH OR DEVIATIONS FROM THE CONTRACT DOCUMENTS. <br />OBTAIN DIRECTION BEFORE PROCEEDING WITH WORK. <br />B. SEQUENCING: <br />1. DO NOT INSTALL GROUND ROD ELECTRODES UNTIL FINAL BACKFILL AND COMPACTION IS COMPLETE. <br />1.05SUBMITTALS <br />A. SEE SECTION 013000 - ADMINISTRATIVE REQUIREMENTS FOR SUBMITTALS PROCEDURES. <br />B. PRODUCT DATA: PROVIDE MANUFACTURER'S STANDARD CATALOG PAGES AND DATA SHEETS FOR <br />GROUNDING AND BONDING SYSTEM COMPONENTS. <br />C. MANUFACTURER'S INSTRUCTIONS: INDICATE APPLICATION CONDITIONS AND LIMITATIONS OF USE <br />STIPULATED BY PRODUCT TESTING AGENCY. INCLUDE INSTRUCTIONS FOR STORAGE, HANDLING, <br />PROTECTION, EXAMINATION, PREPARATION, AND INSTALLATION OF PRODUCT. <br />D. FIELD QUALITY CONTROL TEST REPORTS. <br />E. PROJECT RECORD DOCUMENTS: RECORD ACTUAL LOCATIONS OF GROUNDING ELECTRODE SYSTEM <br />COMPONENTS AND CONNECTIONS. <br />1.06QUALITY ASSURANCE <br />A. CONFORM TO REQUIREMENTS OF NFPA 70 . <br />B. MANUFACTURER QUALIFICATIONS: COMPANY SPECIALIZING IN MANUFACTURING THE PRODUCTS <br />SPECIFIED IN THIS SECTION WITH MINIMUM THREE YEARS DOCUMENTED EXPERIENCE. <br />C. INSTALLER QUALIFICATIONS FOR SIGNAL REFERENCE GRIDS: COMPANY WITH MINIMUM FIVE YEARS <br />DOCUMENTED EXPERIENCE WITH HIGH FREQUENCY GROUNDING SYSTEMS. <br />1.07DELIVERY STORAG <br />E, AND HANDLING <br />A. RECEIVE, INSPECT, HANDLE, AND STORE PRODUCTS IN ACCORDANCE WITH MANUFACTURER'S <br />INSTRUCTIONS. <br />PART 2 PRODUCTS <br />2.01 GROUNDING AND BONDING REQUIREMENTS <br />A. EXISTING WORK: WHERE EXISTING GROUNDING AND BONDING SYSTEM COMPONENTS ARE INDICATED TO <br />BE REUSED, THEY MAY BE REUSED ONLY WHERE THEY ARE FREE FROM CORROSION, INTEGRITY AND <br />CONTINUITY ARE VE <br />RIFIED, AND WHERE ACCEPTABLE TO THE AUTH <br />ORITY HAVING JURISDICTION. <br />B. DO NOT USE PRODUCTS FOR APPLICATIONS OTHER THAN AS PERMITTED BY NFPA 70 AND PRODUCT <br />LISTING. <br />C. UNLESS SPECIFICALLY INDICATED TO BE EXCLUDED, PROVIDE ALL REQUIRED COMPONENTS, <br />CONDUCTORS, CONNECTORS, CONDUIT, BOXES, FITTINGS, SUPPORTS, ACCESSORIES, ETC. AS <br />NECESSARY FOR A COMPLETE GROUNDING AND BONDING SYSTEM. <br />D. WHERE CONDUCTOR SIZE IS NOT INDICATED, SIZE TO COMPLY WITH NFPA 70 BUT NOT LESS THAN <br />APPLICABLE MINIMUM SI <br />ZE REQUIREMENTS SPECIFIED. <br />E. EQUIPMENT GROUNDING CONDU <br />CTORS UCTORS SHALL BE INSULATED STRANDED COPPE <br />R, EXCEPT THAT SIZES <br />NO. 10 AWG AND SMALLER SO SHALL E l B LID COPPER. INSULATION COLOR SHALL BE CONTINUOUS GREEN <br />FOR ALL EQUIPMENT GROUNDING CONDUCTORS, EXCEPTTHAT WIRE SIZES NO.4 AWG AND LARGER <br />SHALL BE IDENTIFIED PER NEC. <br />F. BONDING CONDUCTORS SHALL BE BARE STRANDED COPPER, EXCEPT THAT SIZES NO. 10 AWG AND <br />SMALLER SHALL BE BARE SOLID COPPER. BONDING CONDUCTORS SHALL BE STRANDED FOR FINAL <br />CONNECTION TO MOTORS, TRANSFORMERS, AND VIBRATING EQUIPMENT. <br />G. CONDUCTOR SIZES SHALL NOT BE LESS THAN SHOWN ON THE DRAWINGS, OR NOT LESS THAN REQUIRED <br />BY THE NEC, WHICHEVER IS GREATER. <br />H. INSULATION: THHN-THWN AND XHHW-2. XHHW-2 SHALL BE USED FOR ISOLATED POWER SYSTEMS. <br />1. GROUNDING SYSTEM RESISTANCE: <br />1. ACHIEVE SPECIFIED GROUNDING <br />ROUND NG SYSTEM RESISTANCE <br />E ISTANCE UNDER NORMALLY DRY CONDITIONS <br />DIT ONS UNLESS <br />OTHERWISE APPROVED BY ENGINEER. PRECIPITATION WITHIN THE PREVIOUS 48 HOURS DOES NOT <br />CONSTITUTE NORMALLY DRY CONDITIONS. <br />2. GROUNDING ELECTRODE SYSTEM: NOT GREATER THAN 5 OHMS TO GROUND, WHEN TESTED <br />ACCORDING- TO IEEE 81 USING FALL OF POTENTIAL METHOD. <br />3. BETWEEN GROUNDING ELECTRODE SYSTEM AND MAJOR ELECTRICAL EQUIPMENT FRAMES, SYSTEM <br />NEUTRAL, AND DERIVED NEUTRAL POINTS: NOT GREATER THAN 0.5 OHMS, WHEN TESTED USING <br />POINT-TO-POINT" METHODS. <br />J. GROUNDING ELECTRODE SYSTEM: <br />1. PROVIDE CONNECTION TO REQUIRED AND SUPPLEMENTAL GROUNDING ELECTRODES INDICATED TO <br />FORM GROUNDING ELECTRODE SYSTEM. <br />A. PROVIDE CONTINUOUS GROUNDING ELECTRODE CONDUCTORS WITHOUT SPLICE OR JOINT. <br />B. INSTALL GROUNDING ELECTRODE CONDUCTORS IN RACEWAY WHERE EXPOSED TO PHYSICAL DAMAGE. <br />BOND GROUNDING ELECTRODE CONDUCTOR TO METALLIC RACEWAYS AT EACH END WITH BONDING <br />JUMPER. <br />2. METAL UNDERGROUND WATER PIPE(5): <br />A. PROVIDE CONNECTION TO UNDERGROUND METAL DOMESTIC AND FIRE PROTECTION (WHERE PRESENT) <br />WATER SERVICE PIPE(S) THAT ARE IN DIRECT CONTACT WITH EARTH FOR AT LEAST 10 FEET AT AN <br />ACCESSIBLE LOCATION NOT MORE THAN 5 FEET FROM THE POINT OF ENTRANCE TO THE BUILDING. <br />B. PROVIDE BONDING JUMPER(S) AROUND INSULATING JOINTS/PIPES AS REQUIRED TO MAKE PIPE <br />ELECTRICALLY CONTINUOUS. <br />C. PROVIDE BONDING JUMPER AROUND WATER METER OF SUFFICIENT LENGTH TO PERMIT REMOVAL OF <br />METER WITHOUT DISCONNECTING JUMPER. <br />3. METAL BUILDING OR STRUCTURE FRAME: <br />A. PROVIDE CONNECTION TO METAL BUILDING OR STRUCTURE FRAME EFFECTIVELY GROUNDED IN <br />ACCORDANCE WITH NFPA 70 AT NEAREST ACCESSIBLE LOCATION. <br />4. CONCRETE -ENCASED ELECTRODE: <br />A. PROVIDE CONNECTION TO CONCRETE -ENCASED ELECTRODE CONSISTING OF NOT LESS THAN 20 FEET OF <br />EITHER STEEL REINFORCING BARS OR BARE COPPER CONDUCTOR NOT SMALLER THAN 4 AWG <br />EMBEDDED WITHIN CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH IN <br />ACCORDANCE WITH NFPA 70. <br />5. GROUND ROD ELECTRODE(S): <br />A. PROVIDE THREE ELECTRODES IN AN EQUILATERAL TRIANGLE CONFIGURATION UNLESS OTHERWISE <br />INDICATED OR REQUIRED. <br />B. SPACE ELECTRODES NOT LESS THAN 10 FEET FROM EACH OTHER AND ANY OTHER GROUND ELECTRODE. <br />C. WHERE LOCATION IS NOT INDICATED, LOCATE ELECTRODE(S) AT LEAST 5 FEET OUTSIDE BUILDING <br />PERIMETER FOUNDATION AS NEAR AS POSSIBLE TO ELECTRICAL SERVICE ENTRANCE; WHERE POSSIBLE, <br />LOCATE IN SOFTSCAPE (UNCOVERED) AREA. <br />D. PROVIDE GROUND ENHANCEMENT MATERIAL AROUND ELECTRODE WHERE INDICATED. <br />E. PROVIDE GROUND ACCESS WELL FOR EACH ELECTRODE. <br />TO THE BEST OF THE ENGINEERS KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE FIRE -SAFETY STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH CHAPTER 553.79 AND CHAPTER 633, FLORIDA STATUTES. <br />(45 <br />Q <br />'sueO <br />Oal <br />�u <br />OOOLn <br />6 <br />6 <br />< <br />z <br />I <br />u <br />m <br />m <br />IiiIiiIiiiIiiiiIiiiiIO <br />Z <br />Ln <br />Ln <br />w <br />n <br />r, <br />2 <br />N <br />cV <br />tj <br />I\ <br />n <br />w <br />u <br />w <br />,u <br />ll <br />J_ <br />�_ <br />0- <br />z <br />- <br />z <br />IiiiiiiiiiIIiiiIiiIiii <br />Op <br />(5 <br />O <br />zIx <br />a <br />w <br />W <br />I% <br />LL <br />W <br />Z <br />m <br />2 <br />O <br />0. <br />cV <br />a <br />N <br />00 <br />- <br />CA <br />J <br />t <br />N <br />u <br />� <br />o <br />Z <br />cM <br />U <br />41 <br />M <br />Lu <br />O <br />C <br />"L_ <br />W <br />CIA <br />C <br />� <br />O <br />- <br />v <br />Q <br />LL <br />J <br />V4) <br />= <br />i <br />C <br />++ <br />N <br />_ <br />Z <br />to <br />.ct <br />M <br />i <br />C <br />r' <br />3 <br />Ln <br />(D <br />00 <br />Luu <br />la-00 <br />T <br />- <br />Q <br />4 <br />U <br />mi <br />= <br />w <br />= <br />a <br />W <br />N <br />W <br />ILA <br />w m <br />LL <br />O <br />O <br />` <br />1 = <br />Q <br />w Z O <br />W Ln <br />.O <br />e+A <br />Z V =M <br />W � c .° <br />v a <br />( I'1 cc O O <br />�j� N. <br />W <br />L � <br />a <br />:E <br />L <br />O A <br />Lu 2 (" m <br />z Q M N <br />\\ ,_\_EWIS JO ��i�� <br />N, <br />4� �CENgF ...6! -� <br />. 'p . <br />.\ I <br />No 38680 <br />_ .: �L <br />,� * �\ _ <br />- t '� � _ <br />ti <br />�.z <br />STATE OF <br />, ;% 11 <br />i tORID ••\ <br />/111111110\ <br />George Johnson, P.E. <br />PE38680 <br />ISSUE DATE: 10/19/2018 <br />PROJECT NUMBER: 2847 <br />REVISIONS: <br />NO. DATE I DESCRIPTION <br />ELECTRICAL SPECIFICATIONS <br />E501 <br />© 2018 APG ENGINEERING <br />