Laserfiche WebLink
WALL CONSTRUCTION <br />FLORIDA BUILDING CODE RFSIDENiIAL, 6th FDtTION (2017) SIFCTION R609 <br />EXTERIOR WINDOWS AND DOORS <br />R609 -1 General. <br />This section prescribes performance and construction requirements for exterior windows and doors installed in walls. Windows and doors shall he <br />installed and flashed in accordance with the fenestration manufacturer s written instructions. Window and door openings shall be flashed in <br />accordance with Section R703.4 Written installation instructions shall be provided by the fenestration manufacturer for each window or door. 8"X 8°X <br />R609.2 Performance. <br />Exterior windows and doors shall be designed to resist the design wind loads specified in Table R301.2(2) adjusted for height and exposure in <br />d th T <br />SHINGLES PER SPECIFICATIONS (w/ & FASTENERS <br />PER SHINGLE) FELT UNDERLAlM 'ENT MUST BE 300 <br />OR EQUIVALENT (ASTM D 220 TYPE 11, ASTM D48�o9 <br />OR PEEL AND STICK ROOF UNDERLATMENT ON 1/2" <br />PT LWOOD OR 055 W/H-CLIPS ON PRE-ENGINEERED <br />WOOD TRUSSES � 24'O.C. (FOR NAILING SCHEDULE <br />SEE SHEET S2G) - SEE ADDITIONAL INFO BELOW <br />actor once wi able R301. 2(3) or determined to accordance with ASCE 7 using the allowable stress design load combinations of ASCE 7. Design wind BRICK MOULD HURRICANE ANCHORS <br />loads for exterior glazing not part of a labeled assembly shall be permitted to be determined in accordance with Chapter 74 cif the Florida Building (SEE ROOF PLAN ) <br />Code, Building. <br />R609. 2. lCustom doors. DOOR FRAME MIN. Ix2 NAILING 5TRIP5 ATTACH SOFFIT TO STRIPS PER <br />Custom (oneof- <br />exterior door assemblies shall be tested by an approved testing laboratory or be designed and engineered in accordance with MANUFACTURERS PRODUCT APPROVAL SPECIFICATIONS R704.2.1 <br />accepted engineering practices by a Florida registered design professional. Signed and sealed copies of the rational analysis and calculations <br />shall be provided to the building official upon permit application. ALUM. DRIP EDGE-, <br />R609.3 Testing and labeling. 3/1G"X 2-1/2" TAPGON <br />Exterior windows and sliding doors shall be tested by an approved independent laboratory, and bear a label identifying manufacturer, performance FASTENERS INTO BL OGK <br />characteristics and approved inspection agency to indicate compliance with AAMA/WDMA/CSA 101/I.S.2/A440 or TAS 202 (HVHZ shall comply with TAS 202 <br />and ASTM E1300). Exterior side --hinged doors sholI be tested and labeled as conforming to AAMA/WDMA/CSA 101/I.S.2/A440 or ANSI/WMA 100, or comply <br />with Section R609.5. Exterior windows and doors shall be labeled with a permanent label, marking, or etching providing traceability to the <br />manufacturer and product. The following shall also be required either on a permanent label. or on a temporary supplemental label applied by the <br />manufacturer: information identifying the manufacturer, the product model/series number, positive and negative design pressure rating, product <br />maximum size tested, impact -resistance rating if applicable, Florida product approval number or Miami -Dade product approval number, applicable test <br />standard(s), and approved product certification aaenr:y, testing laboratory, evaluation entity or Miami -Dade product approvI.il. 3/4" FURRING NAIL F D <br />The Labels are limited to one design pressure rating per reference standard. The temporary supplemental label shall remain nn the window or door <br />TO BLOCK -o allO.G. (2) <br />until final approval by the building official. REQUIRED EACH LIFT <br />Exceptions: • M006' u O O <br />I.Door assemblies installed in nonhabitable areas where the door assembly and area are designed to accept water infiltration need riot be tested for /�/ <br />water infiltration. <br />2.Door assemblies installed where the overhang (01I) calla is equal to or more than 1 need not be tested for water infiltration. The overhang rat8"x O"x 1&" G.M.U. <br />io <br />shall be calculated by the following equation: <br />OH ratio = OH Length/OH Height 3/10" X 1-3/4" TAPCON FASTENERS <br />INTO CONCRETE BLOCK <br />2X(c SUB FASCIA <br />FASCIA COVER INSTALLED IN <br />ACCORDANCE WITH FASCIA <br />MANUFACTURER'S PRODUCT <br />APPROVAL SPECIFICATION AND <br />LIMITATIONS OF USE <br />Where: <br />OH length = The horizontal measure of how far an overhang over a door projects out from door surface. QD ESIVE JEALENT BOTH SURFACES <br />OH height = The vertical measure of the distance from the door sill to the bottom of the overhang over a door. <br />3. Decorative glazed openings. PRIOR TO ATTACHING: BUCK TO GONG, BLK. <br />4.Pass-through windows for serving from a single-family kitchen, where protected by a roof overhang of 5 feet (1.5 m) or more shall be. exempted <br />from the requirements of the water infi It.r ation test. 1/2'' DRYWALL <br />R609. 3. lComparative analysis. <br />Structural wind load design pressures for window and door units different than the size tested in accordance with Section R609.3 shall be permitted <br />to be different than the design value of the Lested unit where determined in accordance with one of the following comparative analysis methods: <br />1.Structural r wind load design pressures for window and door units other than the size tested in accordance with Section R609.3 shall be, permitted <br />Lo be different than the design value of the tested unit provided such different pressures are determined by accepted engineering analysis. All <br />components of the alternate size assembly shall be the same as the tested or labeled assembly: however, lineal components shop be per rill tt.ed to <br />vary in length compared to the tested or labeled assembly <br />Exceptions: Ir7 <br />l.Operable windows and doors rated in this manner shall comply with the following: <br />8"x i" SELF THREADING PHILLIP5 FLAT HEAD <br />a.For windows and doors (other than .sliding or bi-fold), the frame area of the alternate size unit shall not exceed the frame area of the tested CADMINUM PLATE SCREW5 24" O.C. MAX. <br />approved unit. <br />b F 1'd' b' f I _1th WITHIN 4 OF CORNER <br />. or s i ing <br />c.Shot I vary <br />or <br />from <br />- o oars, e panel or ea of <br />the tested approved unit only in <br />the alternate size unit shall not exceed the panel area of the <br />width, height or load requirements. <br />tested approved unit. <br />d.ShaII <br />not <br />exceed <br />100 <br />percent <br />of the <br />proportional <br />deflection for fiber stress of the intermediate members of the <br />approved unit. <br />e.Sri aII <br />not <br />exceed <br />100 <br />percent <br />of the <br />concentrated <br />load at the juncture of the intermediate members and the frame <br />of the approved unit. <br />f.Sha11 <br />not <br />exceed <br />the <br />air and <br />water <br />infiltration <br />resistance of the tested approved unit. <br />g.Shall <br />a licable <br />not <br />exceed <br />the <br />maximum <br />cyciir. <br />pressure of <br />the tested approved unit when tested per TAS 201 and TAS 203 or <br />ASTM E1886 and ASTM E1996 where <br />pp 3/I6"x 1-3/4" TAPCON FASTENERS <br />2. Nonoperable windows and doors rated in this manner shall comply with the following: INTO CONCRETE BLOCKS <br />a. The frame area of the alternate size unit shall net exceed the frame area of the tested approved unit. <br />b.ShalI vary from the tested approved unit anly in width, height or load requirements. <br />CAULKING <br />c.The maximum uniform load distribution (ULD) of any side shall be equal to the uniform load carried by the side divided by the length of the side. <br />d.The OLD of any member shall not exceed the ULD of the corresponding member of the tested approved unit. <br />MARBLE STOOL <br />e.The ULD of each member shall be calculated in accordance with standard engineering analysis. <br />f.SholI not exceed the air and water infiltration resistance of the tested approved unit. <br />g.Shot I not exceed the maximum cyclic pressure of the tested approved unit when tested per TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where <br />applicable. <br />1/2'' DfRYWALL ON Ix 3 P.T. <br />3. In accordance with WDMA 1. S. 11. <br />FURRING -�D Iro" O.C. <br />R609.4 Garage doors. <br />Garage doors shall be tested for determination of structural performance under uniform static air pressure difference in accordance wit(? ANSI/DASMA <br />1.08, ASTM E330 Procedure A, or TAS 202. For garage doors tested in accordance with ASTM E330, acceptance criteria shall be in accordance with <br />ANSI/DASMA 108. (HVHZ shall comply with TAS 202.) Design pressures shall be determined from Table 301.2(4) or ASCE 7. The design pressures, as <br />determined from ASCE 7, are permitted to be multiplied by 0.6. <br />PRECAST SILL <br />R609.4.1 Garage door labeling. <br />Garage doors shall be labeled with a permanent label provided by the garage door manufacturer. The label shall identify the garage door <br />n n n <br />8 X 8 X 1� G.M.U. <br />manufacturer, the garage door model series number, the <br />g g / positive and negative design pressure rating, indicate impact rated if applicable, the <br />Installation instruction drawing reference number, the Florida product approval or Miami -Dade, product approval number if applicable; and the <br />applicable test standards. The required garage door components for an approved garage door assembly may be indicated using a checklist, form on the <br />label. If a checklist format is used on the Lobel, the door installer or the garage door manufacturer shall mark the selected components or the <br />checklist that are required to assemble an approved garage door system. The installation instructions shall be provided and available on the job <br />St te.. <br />R609.5 Other exterior window and door assemblies. <br />Exterior windows and door assemblies not included within the scope of Section R609.3 or R609.4 shall be tested in accordance with ASTM E3.10, Glass <br />���� S <br />W <br />in assemblies covered by this exception shall comply with Section R308.5. <br />ot Wind-borne debris protection. Protection 4 WINDOW W AT - A H N <br />Prtion of exterior glazed openings in buildings located in wind-borne debris regions shall be in accordance with Section R301.2.1.2_. II I 1 <br />R609.6.1 Fenestration testing and labeling. <br />Fenestration shall be tested by an approved independent laboratory, listed by an approved entity, and bear a label identifying manufacturer, <br />performance characteristics, and approved inspection agency to indicate compliance with the requirements of the following sc,ec:ification(s): <br />1.ASTM E1886 and ASTM E1996; or <br />FILLED CELL (3) 1/2"x 8" "J" BOLTS OR <br />2. AAMA 506. w/ (1) * 5 VERT. HILTI DN50 (OR EQUAL) <br />R609.7 Anchorage methods. <br />The methods cited in this section apply only to anrhornq.e of window and glass door assemblies to the main force -resisting system. CONT. WOOD TRIM <br />RF09.7.1 Anchoring requirements. <br />Window and glass door ossemblies shall be anchored in accordance with the published manufacturer s recommendations to achieve `he design pressure <br />specified. Substitute anchoring systems used for substrates not specified by the fenestration manufacturer shall provide equal or greater anchoring <br />performance as demonstrated by accepted engineering practice,. <br />R609.7.2 Anchorage details. <br />Products shall be anchored in accordance with the minimum requirements illus'Lrated in Figures R609.7.2(1), R609. 7. 2(2), R60"1/ 2(3), P609. 7. 2(4), <br />R609. 7. 2(5) , R609. 7. 2( 6) , R609. /. 2( 7) and R609. 7. 2(s) . 2x 6 P.T. WOOD JAMB <br />R609 7 2 1 M th t <br />r <br />ATTACH SOFFIT <br />TO FASCIA OR <br />TO NAILING <br />5TRIP (NOT <br />SHOWN) MAT VART <br />(IF OVER 12'' - <br />INTERMID IATE <br />rt=url it�=n ctl -r-n n\/=r_&T-IIPEt REQ. <br />v r-_ <br />EXTERIOR SIDING-T OVER <br />i X 2 P.T. FURRING � l�" O.C. <br />*5 DWL <br />w/ 10'' <br />5TD, NOOK <br />J <br />Z � <br />M <br />(1) 20'-0'' *5 REBAR TIED TO <br />FTC. STEEL AND GRND. ROD <br />(BT OTHERS) AT ELECTRICAL <br />BOX LOCATION <br />(2,", REBAR CONT. <br />(3" MIN. COVER) <br />GROUND ROD (BT OTHERS) <br />SEE ELEVATIONS <br />FOR ROOF SLOPE <br />PANEL EDGE 5UPPORT FOR NARROW WIDTH ROOF SHEATHING" PER TECHNICAL NOTE *R275A <br />16-24 "-DOUBLE PLT GLIP THE SIDE ADJACENT TO THE FULL WIDTH PANEL - NONE REQUIRED <br />AT RIDGE OR NIP, 12'' TO Ira" - LUMBER ONLY' BLOCKING (2x4) FLAT WI5E OR ENDWISE ON THE <br />SIDE ADJACENT TO THE FULL WIDTH PANEL NONE REQUIRED AT RIDGE OR HIP. FOR PLTWOOD <br />SHEATHING 12'' OR LESS - LUMBER ONL'r' BLOCKING, (2x4) FLAT WISE OR EDGEWISE ON BOTH <br />PANEL EDGES - <br />.sa TOP COURSE <br />5"X8"Xi011 GONG, <br />K.O. BLOCK W/ <br />• •"y POURED GONG. 4 <br />t ', 1-*5 REBAR GONT, <br />PRECAST GONG. LINTEL <br />or POWER5 STEEL LINTEL <br />W/ *5 POURED SOLID <br />rr <br />,li i. WINDOW <br />��► �+'n <br />� 1 <br />RBLE SILL <br />EC,45T GONG. 51LL <br />(1) 20'-0'' 5 REBAR TIED TO <br />FTG, STEEL AND GRND. ROD <br />(BT OTHERS) AT ELECTRICAL <br />3000 PSI GONG. <br />G "x &"x 10/10 E.W.W. ME5iL REINFORCING REQUIRED <br />THROUGHOUT THE CONCRETE SLAB OR FIBER MESH <br />PER SECTION IINI.2, 2010 FLORIDA BUILDING CODE. <br />(o MIL. VAP. BARRIER <br />G X&-*10 WWF OR <br />FIBER MESH 1.5*/GU. YD. <br />HEADER BLOCK W/*54 <br />NOTE: IF WALL HEIGTH EXCEEDS 2'-0'' <br />BRACE WALL UNTIL FLOOR IS POURED <br />*50 W/CELL POURED SOLID <br />8'-0" O.C. MAX. <br />*5� DOWEL <br />SPACING PER FOUNDATION PLAN <br />DE <br />GROUND ROD (BT OTHERS) j� 2- ,� <br />I L\ f <br />SmTom rm �#1 W44LL) <br />CONCRETE -ENCASED ELECTRODE, AN ELECTRODE ENCASED BT AT LEAST 2" OF CONCRETE, <br />LOCATED WITHIN AND NEAR THE BOTTOM OF THE CONCRETE FOUNDATION OR FOOTING THAT IS IN <br />DIRECT CONTACT WITH THE EARTH, CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZINC <br />GALVANIZED OR OTHER ELECTRICiTT CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS <br />OF NOT LESS THAN 1/2 INCH DIAMETER, OR CONSISTING OF AT LEAST 20 FEET OF BARE COPPER <br />CONDUCTOR NOT SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED TO BE BONDED <br />TOGETHER BT THE USUAL STEEL TIE WIRES OR OTHER EFFECTIVE MEANS." <br />. .. <br />Where the <br />asonry, ..oncre-e ar o er <br />structural subst.rate. <br />DOOR AND CONNECTION PER <br />wood shim or- buck thickness <br />is less than tl/2 inches (38 mm), window and glass door assemblies shall be anchored through the jamb, or by <br />jamb clip <br />and anchors shall be embedded directly into the masonry, concrete or other substantial substrate material. Anchors shall adequately <br />GARAGE DOOR MANUFACTURER <br />transfer <br />load from the window or door <br />frame into the rough opening substrate [see Figures R609.7.2(1) and R6097.2(2)]. <br />Where the <br />wood shim or buck thickness <br />is 11/2 inches (38 mm) or more, the buck is securely fastened to the masonry, concrete or other substantial 0L-to <br />substrate, <br />and the buck extends beyond <br />the interior lace of the window or door frame, window and glass door assemblies shall be anchored through <br />4INthe <br />0f <br />'"R J rnb <br />or by jamb clip or through <br />1 <br />the flange trt the secured wood buck Anchors shall be embedded into the --n-ri v, 1 F)ir to nnerli t,=lv i <br />'^IG <br />transfer load from the window or door frame assembly [see Figures R609.7.2(3), P.6097.2(4) and R609.7.2(5)] <br />R609.7.2.2 Wood or other approved framing material. <br />Where the framing material is wood or other approved framing material, window and glass door assemblies shall be anchored through the frame, or by <br />frame clip, or through the flange. Anchors shall be embedded into the frame construction to adequately transfer load [see figures R609 7.2(6), <br />R609. 7. 2( 7) and R609. 7. 2( 8) ]. <br />R609.8 Mullions. <br />Mullions shall be tested by an approved Les tinq laboratory in accordance with AAMA 450, or be engineered in accordance with accepted engineering <br />practice. Mullions tested as stand -atone units or qualified by engineering shall use performance criteria cited in Sections R609.8.1, R609.8.2 and <br />R609 8.3. Mullions qualified by an actual test of an entire assembly shall comply with Sections R609.8.1 and R609.8.3. <br />R609.8.1 Load transfer. <br />Mullions shall be designed to transfer the design pressure loads applied by the window and door assemblies to the rough opening substrate. <br />R609.8.2 Deflection. <br />Mullions shot! be capable of resisting the design pressure loads applied by the window and door assemblies to be supported without deflecting niore <br />than L/175, for spans up to and including 13 foot 6 inches, and L/240 + 1/4 inch for spans over 13 foot 6 inches, where L is the span of the <br />mullion ;n inches. <br />r<609.8.3 Structural safety factor. <br />Mullions shall be capable of resisting a load of 1.5 Limes the design pressure loads applied by the window and door assemblies to be supported <br />without exceeding the appropriate material stress levels. If tested by an approved laboratory, the 1.5 times the design pressure load shalt be <br />sustained for 10 seconds, and the permanent deformation shall not exceed 0.4 percent of the mullion span after the 1.5 times design pressure load <br />is removed. <br />R609.9 Masonry rough openings. <br />Masonry rough opening dimensions shall be within the tolerances specified in Section R606.3.1.1 and, in addition, shall provide for a window <br />perimeter sealant joint a maximum of 1/4 inch (6.4 mrn) in width. <br />R609.10 Door components. <br />Substitution of door components shall comply with either: <br />I.ANSi/WMA 100; or <br />2.P,e evaluated by on approved product evaluation entity, certification agency, testing laboratory, or engineer and may be interchangeable in <br />exterior door assemblies if the components provide equol or greater structural performance as demonstrated by accepted engineering practices. <br />R609 11 Impact -resistant coverings <br />R609.11.1 <br />Impact -resistant coverings shall be tested at 1.5 times the design pressure (positive or negative) expressed in pounds per square feet as <br />determined by the Florida Building Code, Building Section 1609 for which the specimen is to be tested. The design pressures, as determined from <br />Section 1609 of the Florida Building Code. Building or ASCE 7, are permitted to be multiplied by 0.6. <br />R609. 11. 1. 1 <br />Impact -resistant coverings shall be labeled in accordance with the provisions of Section R609.11. <br />R609. 1 1. 2Labe 1 s. <br />i\ permanent label shall be provided by the product approval holder on all impact -resistant coverings. <br />R609. 11. 2. 1 <br />The followina information shall be included on the ithels on impact. -resistant coverings: <br />i.Product approval holder name and address. <br />2.AII applicable methods of approval. Methods of approval include, but, are not limited to Miami Dade NOA; Florida Building Commission, TDI Product <br />Evaluation; ICC-ES. <br />3.The test standard or standards specified in. Section R?01 2.1.2, including standards referenced within the test standards specified in Section <br />R301.2.1.2 used to demonstrate code compliance. <br />4. For products with a Florida product approval number or a Miami -Dade County Building and Neighborhood Compliance Department Notice of Acceptance <br />Number (NOA), such numbers shall be included on the label. <br />R609. 11. 3Loc a t I or) of label. <br />The location of the label on the impact -resistant covering shall be as follows: <br />1.Accordiona: Bottom of the locking baror center rnat.e facing the exterior or outside. <br />2.Rollup: On the bottom of the hood facing the exterior or outside or on the bottom slat facing the exterior or outside. <br />3.Bohoma Awn ng or Colonial Hinged: On the bottom, placed on Lee back of the shutter. <br />4.Ponel-s: For metal and plastic panels the label may be embossed or printed spaced not more than every 3 lineal feet (914 mm) on each panel. The <br />label shall be applied by the holder of the product approval and shall face the exterior or outside. <br />5.Framed products: The label shall be. on the side or bottom facing the exterior or outside. <br />6.1-abets on all other products shall face the exterior cr outside. <br />R609 1!. •4 installation. <br />All impact -resistant coverings shall be installed in accordance with the manufacturer s installation instructions and in accordance with the <br />product. approval. Installation instructions shall be provided and shall be available to inspection personnel on the job site. Opening protection <br />components, fasteners, and other parts evaluated by on approved product evaluation entity, certification agency, testing laboratory, architect, or <br />engineer and approved by the holder of the product approval may be interchangeable in opening protection assemblies provided that the opening <br />protection component s) oruvide equal or greater structural performance and durability as demonstrated by testing in accordance with approved test <br />standards. <br />Thomas L <br />Digitally signed by <br />Thomas L <br />Hanson:A01410 <br />Hdnson:A01410D000001 <br />D00000177EF31 <br />77EF31 B4E000015ADA <br />Date: 2022.04.12 <br />B4E000015ADA <br />14:36:30-04'00' <br />Signodand .`aled1cI.L.liar "pi <br />using a i hgitil Signature and I'll,, <br />Printed Copies ies of the dcx um nt r>,•" ` <br />.rreuotcon,idm(cdsigned .Irul ; <br />s`aled wn t the `i!?nature nntct I", <br />w , . <br />I,cI lied on In, d"Ctonic CO 1H <br />�b <br />O <br />FY <br />(Z <br />0 <br />U <br />