<br />AVIATION STORAGE TANK
<br />SYSTEMS
<br />n
<br />REGULATORY REQUIREMENTS: L J ''
<br />1. NFPA 101 Life Safe Code `s
<br />�' r �� !� REVIEW DATE d
<br />2. NFPA 10 Standard for Potable Fire extinguishers CITY OF ZEPHYR LLS
<br />g L ti FIRE AND LIFE SAFETY EXAMINE
<br />3. NFPA 30 Flammable and Combustible Liquid Code
<br />4. NFPA 70 National Electrical Code (NEC)
<br />5. NFPA 77 Recommended Practice for Static Electricity
<br />6. NFPA 407 Standard for Aircraft Fuel Servicing
<br />ALL WORK SHALL COMPLY WITH
<br />7. UL 142 Standard for Safety, Steel AST's for Flammable and Combustible Liquids NFFA CODES AND STANDARDS
<br />8. UL 842 Standard for Valves for Flammable Fluids
<br />9. ANSI/UL 87, Power Operated Dispensing Devises for Petroleum Products
<br />10. ANSI/UL 913, Standard for Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II,
<br />and III Division 1 Hazardous (Classification) Locations
<br />11. American Petroleum Institute (API) Standards. Regulations and Publications, including Appendices for
<br />design, cleaning, construction, installation of tanks, piping, and dispensing system
<br />12. API Bulletin 1500, 15425 15 81, 2000
<br />13 . API Bulletin 1529 Aviation Hose
<br />14. API Bulletin 1540 Design, Construction, Operation, and Maintenance of aviation Fueling Facilities
<br />15 . PEI Standards RP-200, RP-100-90, RP-3 00, RP-400, and RP 13 00
<br />16.ATA-103 Standard for Jet Fuel Quality Control at Airports
<br />17.Applicable Local, State, and Federal Codes and Regulations
<br />18.FAA Advisory Circular 150/5230-4B Aircraft Fuel Storage, Handling, and Dispensing on Airports
<br />19.Local and State Dept. of Environmental Management
<br />20.Approvals by Authority Having Jurisdiction
<br />2 LNIST Handbook 44 (latest Edition)
<br />22.OSHA
<br />PIPING:
<br />1. System Pipe 1.0" and Larger: 304/304L, ASTM A312, SCH10 Stainless steel, flanges 304/304L,
<br />150#, RF, ASTM A182 Elbow 90-45, reducers 304/304L, ASTM A403 SCH10
<br />2. System Pipe 1.0" and smaller: 304/304L, ASTM A312, SCH40, Stainless steel fittings 304/304L,
<br />ASTM Al82
<br />3. System Instrument Tubing: ASTM A269, grade TP316 stainless .035 wall seamless
<br />4. Compression Fittings: DK-LOK 316 stainless steel
<br />5. Systems piping shall be cleaned internally before final assembly
<br />OPERATION MANUALS:
<br />Provide (2) copies of Operation and Maintenance manuals
<br />for all equipment including parts list, instruction sheets, and
<br />other literature that is provided with systems components
<br />SYSTEM PERFORMACE REQUIREMENTS:
<br />Minimum Working Pressure Ratings*
<br />1. Aboveground Steel Fuel Oil Piping 150 prig
<br />2. Vent, Gauge, and Fill Piping: 100 psig
<br />3. Fuel Storage Tank: 5 psig
<br />4. Fuel Storage Tank, Secondary Containment Shell Walls: 5 psig
<br />5. Fuel Control/Operating Valves: 250psi
<br />6. Jet Tank Fuel Unloading Rate: 200pgm
<br />7. Avgas Tank Fuel Unloading Rate: 200gpm
<br />8. Jet Tank Recirculation Rate: 200gpm
<br />9. Avgas Tank Recirculation Rate: 200gpm
<br />10. Jet Bulkloading Rate: 200gpm
<br />11. Avgas Bulkloading Rate: 180gpm
<br />12. Avgas Aircraft Dispensing Rate: 18gpm
<br />DELIVERY, INSTALLATION AND START-UP:
<br />1. Contractor shall provide safe installation of tanks and equipment
<br />2. Contractor shall provide qualified service representative to supervise installation, start-up, functional
<br />testing, acceptance inspection by Owner and Authority Having Jurisdiction
<br />3. Complete System shall be placed into service to complete satisfaction of the owner
<br />ABA -CON -
<br />AVIATION SERVICES
<br />ABA -CON INC.
<br />P.O. BOX 308
<br />TITUSVILLE, FL 32781
<br />PHONE: (321) 567-4967
<br />FAX: (321) 607 6805
<br />WEB:
<br />www.aba-con.com
<br />PROPRIETARY AND CONFIDENTIAL
<br />The information contained in this drawing is the sole
<br />property of ABA -CON Aviation Services. Any reproducton
<br />in part or as a whole is prohibited without written
<br />permission of ABA -CON Aviation Services.
<br />PROJECT CONTRACTOR:
<br />ADAMS TANK & LIFT, INC.
<br />4568 131 STAVE NORTH
<br />CLEARWATER, FL 33762
<br />V )
<br />W
<br />I—
<br />O
<br />Z
<br />W
<br />I —
<br />DATE: 6/18/2021
<br />_ ------ -- ........
<br />- --
<br />REVISIONS
<br />...........
<br />DATE 1DESCRIPTION
<br />CALE:XX:XX
<br />CLIENT:
<br />ZEPHYRHILLS
<br />MUNICIPAL
<br />AFRPORT
<br />ZEPHYIRHILLS,
<br />FLORIDA
<br />DESIGN TEAM TITLE:
<br />ADAMS TANK AND LIFT INC.
<br />4568 131 ST AVE N
<br />CLEARWATER, FL 33762
<br />727-540-0931
<br />NO.
<br />DATE
<br />REVISION DESCRIPTION
<br />This item has been digitally signed and sealed by Soumya Chakrabarti, PE,
<br />on date shown. Printed copies of this document are not considered signed
<br />and sealed and the signature must be verified on any electronic copies.
<br />CHAtK,Q'''
<br />* ; No. 66380 ;
<br />F
<br />:,�0 • 4 D R P F
<br />/0
<br />'ram
<br />S�J�ti�
<br />YA C AKRABARTI
<br />FL. REG # 66380
<br />TANK AND P 1 P I N:G
<br />PLA14S & DETAILS
<br />SITE DESIGNATIONS:
<br />FUEL FARM
<br />REPLACEMENT
<br />SCALE: AS NOTED
<br />JOB # 01
<br />DATE:
<br />09-23-2021
<br />DESIGNED BY:
<br />DRAWN BY:
<br />SS
<br />FILE NAME:
<br />CHECKED BY:
<br />DRAWING TITLE:
<br />NOTES
<br />SHEET NO:
<br />TA-1
<br />.i nld
<br />
|