GENERAL: <br />A. PROVIDE SHALL MEAN FURNISH AND INSTALL. <br />B. THE COMPLETE ELECTRICAL SYSTEM WHICH SHALL BE PROVIDED BY THE CONTRACTOR SHALL INCLUDE ALL WORK, <br />MATERIALS AND APPARATUSES SPECIFIED HEREINAFTER AND INDICATED ON THE DRAWINGS. ALL WORKMANSHIP SHALL <br />BE OF THE HIGHEST QUALITY AND NO SUBSTANDARD WORK WILL BE ACCEPTED. <br />C. PROVIDE ALL WORK AND ELECTRICAL SYSTEMS COMPONENTS REQUIRED TO SERVE LOADS AS SPECIFIED <br />HEREINAFTER AND INDICATED ON THE DRAWINGS. THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL ELECTRICAL <br />SYSTEMS AT THE COMPLETION OF THE WORK AND MAKING ANY CHANGES AND ADJUSTMENTS NECESSARY FOR THE <br />PROPER FUNCTIONING OF THE SYSTEMS. <br />D. MAKE A THOROUGH EXAMINATION OF THE SITE AND THE CONTRACT DOCUMENTS PRIOR TO EXECUTING THE <br />CONTRACT. NO CLAIM FOR ADDITIONAL COMPENSATION WILL BE RECOGNIZED FOR DIFFICULTIES ENCOUNTERED <br />WHICH AN EXAMINATION OF SITE CONDITIONS AND CONTRACT DOCUMENTS WOULD HAVE REVEALED. <br />E. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED ABOVE THE FLOODPLAIN ELEVATION. CONTRACTOR SHALL <br />COORDINATE FLOODPLAIN ELEVATION AND EQUIPMENT REQUIREMENTS WITH OWNER PRIOR TO ROUGH -IN. <br />F. THE PLANS ARE GENERALLY DIAGRAMMATIC. COORDINATE ALL WORK WITH OTHER TRADES AS REQUIRED TO AVOID <br />INTERFERENCES BETWEEN TRADES (i.e. BEAMS, CONDUITS, EQUIPMENT, DUCTWORK, ETC). <br />WORK PERFORMANCE: <br />A. JOB SITE SAFETY AND WORKER SAFETY IS THE RESPONSIBILITY OF THE CONTRACTOR. <br />B. ARRANGE, PHASE AND PERFORM ALL WORK DURING TIME PERIODS SCHEDULED WITH AND ACCEPTABLE TO THE <br />OWNER BEFORE PROCEEDING. NO ADDITIONAL COMPENSATION WILL BE AUTHORIZED FOR WORK NECESSITATED BY <br />ILL-TIMED, DEFECTIVE, OR NON -CONFORMING WORK. <br />C. THE CONTRACTOR SHALL ENSURE THAT ALL SYSTEMS OPERATE AS DESIGNED AND/OR REQUIRED AND SHALL REVIEW <br />THEIR OPERATION WITH THE OWNER UPON COMPLETION OF CONSTRUCTION AND TESTING. COMPILE COMPLETE AND <br />UPDATED AS -BUILT DRAWINGS/DOCUMENTS AND ISSUE ONE (1) SET TO THE OWNER. <br />D. ELECTRICAL WORK SHALL BE ACCOMPLISHED WITH ALL AFFECTED CIRCUITS OR EQUIPMENT DE -ENERGIZED. WHEN AN <br />ELECTRICAL OUTAGE CANNOT BE ACCOMPLISHED IN THIS MANNER FOR THE REQUIRED WORK, THE FOLLOWING <br />REQUIREMENTS ARE MANDATORY: <br />1. ELECTRICIANS MUST USE AND WEAR FULL PROTECTIVE EQUIPMENT (PPE) (i.e. CERTIFIED AND <br />TESTED INSULATING MATERIAL TO COVER EXPOSED ENERGIZED ELECTRICAL COMPONENTS, <br />CERTIFIED AND TESTED INSULATED TOOLS, ETC.) WHILE WORKING ON ENERGIZED SYSTEMS IN <br />ACCORDANCE WITH NFPA 70E. THE LEVEL OF PPE SHALL BE DETERMINED BY A COMPUTER <br />GENERATED ARC FLASH CALCULATION PROVIDED AND PAID FOR BY THE CONTRACTOR. THE ARC <br />FLASH DATA SHALL BE PRESENTED WITH THE SUBMITTAL BELOW. <br />2. WORK ON ENERGIZED CIRCUITS OR EQUIPMENT CANNOT BEGIN UNTIL PRIOR WRITTEN APPROVAL IS <br />OBTAINED FROM THE OWNER. <br />E. ENSURE THAT ELECTRICAL SERVICE REMAINS UNINTERRUPTED FOR OTHER BUILDINGS AND FACILITIES AT ALL <br />TIMES. PERFORM ALL TEMPORARY WORK NECESSARY TO MAINTAIN CONTINUITY OF ELECTRICAL SERVICE WHEN <br />CONNECTION IS MADE TO EXISTING SYSTEMS. EXISTING SERVICE SHALL NOT BE INTERRUPTED WITHOUT PRIOR <br />CONSENT OF THE OWNER AND MAYBE INTERRUPTED ONLY AT AND FOR THE SPECIFIED TIME DESIGNATED BY <br />THE OWNER. THE CONTRACTOR SHALL BE GUIDED BY THE OWNER AT ALL TIMES IN MATTERS AFFECTING THE <br />EXISTING FACILITIES. <br />F. ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUTDOORS. EQUIPMENT SHALL BE STORED IN AN <br />OWNER/ENGINEER APPROVED MEDIUM AND LOCATION. <br />CODES & STANDARDS: <br />A. PERFORM WORK IN COMPLIANCE WITH THE LATEST EDITION OF ALL APPLICABLE, FEDERAL, STATE AND LOCAL CODES, <br />REGULATIONS AND STANDARDS, TO INCLUDE THOSE LISTED BELOW, ADOPTED BY THE AUTHORITY HAVING <br />JURISDICTION. WHERE DIFFERENCES MAY OCCUR THE MORE STRINGENT REQUIREMENTS SHALL GOVERN. IN CASE OF <br />CONFLICT PROVIDE WRITTEN NOTIFICATION AND OBTAIN A DECISION FROM THE ARCHITECT. <br />1. NFPA 70: NATIONAL ELECTRICAL CODE (2014) <br />2. NFPA 70E: STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE (2018) <br />3. NFPA 101: LIFE SAFETY CODE (2015) <br />4. NFPA 110: STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS (2010) <br />5. NFPA 241: STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION AND DEMOLITION <br />OPERATIONS (2013) <br />6. NFPA 780: INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2014) <br />7. FBC: FLORIDA BUILDING CODE (2017) <br />OSHA PART 1910: OCCUPATIONAL SAFETY AND HEALTH STANDARDS <br />OSHA PART 1926: SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION <br />WARRANTY: <br />A. CONTRACTOR SHALL WARRANTY ALL WORK FOR A PERIOD OF ONE (1) YEAR FROM DATE OF SUBSTANTIAL <br />COMPLETION. CONTRACTOR SHALL RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR WORKMANSHIP AND PAY <br />FOR ANY DAMAGE TO OTHER WORK RESULTING THEREFROM WITHIN SAID PERIOD. THE OWNER WILL GIVE NOTICE OF <br />DEFECTS WITH REASONABLE PROMPTNESS. <br />B. PROVIDE COMPLETE WARRANTY INFORMATION FOR EACH ITEM TO INCLUDE PRODUCT OR EQUIPMENT; DATE OR <br />BEGINNING OF WARRANTY OR BOND; DURATION OF WARRANTY OR BOND; AND NAMES, ADDRESSES, AND TELEPHONE <br />NUMBERS AND PROCEDURES FOR FILING A CLAIM AND OBTAINING WARRANTY SERVICES. <br />SUBMITTALS: <br />A. SUBMIT FIVE (5) COMPLETE BOUND HARDCOPY SETS OR ONE (1) ELECTRONIC PDF COPY. THE ENGINEER WILL RETURN <br />MINIMUM ONE (1) COPY OF SUBMITTAL AND/OR SUBMITTAL REVIEW COMMENTS NO LATER THAN 21 CALENDAR DAYS OF <br />RECEIPT. <br />B. APPROVAL SHALL BE OBTAINED FOR ALL EQUIPMENT AND MATERIAL BEFORE DELIVERY TO THE JOB SITE. DELIVERY, <br />STORAGE OR INSTALLATION OF EQUIPMENT OR MATERIAL WHICH HAS NOT HAD PRIOR APPROVAL, WILL NOT BE <br />PERMITTED AT THE JOB SITE. <br />C. SUBMITTALS SHALL INCLUDE ADEQUATE DESCRIPTIVE LITERATURE, CATALOG CUTS, SHOP DRAWINGS AND OTHER <br />DATA NECESSARY FOR THE ARCHITECT/ENGINEER TO ASCERTAIN THAT THE PROPOSED EQUIPMENT AND MATERIALS <br />COMPLY WITH SPECIFICATION REQUIREMENTS. CATALOG CUTS SUBMITTED FOR APPROVAL SHALL BE LEGIBLE AND <br />CLEARLY IDENTIFY EQUIPMENT BEING SUBMITTED. <br />D. SUBMITTALS FOR INDIVIDUAL SYSTEMS AND EQUIPMENT ASSEMBLIES WHICH CONSIST OF MORE THAN ONE ITEM OR <br />COMPONENT SHALL BE MADE FOR THE SYSTEM OR ASSEMBLY AS A WHOLE. PARTIAL SUBMITTALS WILL NOT BE <br />CONSIDERED FOR APPROVAL <br />E. SUBMITTAL OF SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES WILL BE ACCEPTED ONLY WHEN SUBMITTED BY THE <br />CONTRACTOR. DATA SUBMITTED FROM SUBCONTRACTORS AND MATERIAL SUPPLIERS DIRECTLY TO THE <br />ARCHITECT/ENGINEER WILL NOT BE PROCESSED. <br />F. SUBMITTALS SHALL BE MARKED TO SHOW SPECIFICATION REFERENCE INCLUDING THE SECTION AND PARAGRAPH <br />NUMBERS. SUBMIT EACH SECTION SEPARATELY AND INCLUDE THE FOLLOWING: <br />1. INFORMATION THAT CONFIRMS COMPLIANCE WITH CONTRACT REQUIREMENTS. INCLUDE THE <br />MANUFACTURER'S NAME, MODEL OR CATALOG NUMBERS, CATALOG INFORMATION, TECHNICAL DATA <br />SHEETS, SHOP DRAWINGS, PICTURES, NAMEPLATE DATA AND TEST REPORTS AS REQUIRED. <br />2. PARTS LIST WHICH SHALL INCLUDE THOSE REPLACEMENT PARTS RECOMMENDED BY THE EQUIPMENT <br />MANUFACTURER, QUANTITY OF PARTS, CURRENT PRICE AND AVAILABILITY OF EACH PART. <br />G. MANUALS: SUBMIT IN ACCORDANCE WITH "A" ABOVE FOR REVIEW AND COMMENT. <br />1. MAINTENANCE AND OPERATION MANUALS: SUBMIT AS REQUIRED FOR SYSTEMS AND EQUIPMENT <br />SPECIFIED IN THE TECHNICAL SECTIONS. FURNISH THREE (3) COPIES, BOUND IN HARDBACK BINDERS, <br />(MANUFACTURER'S STANDARD BINDERS) OR AN APPROVED EQUAL. FURNISH ONE COMPLETE MANUAL AS <br />SPECIFIED IN THE TECHNICAL SECTION BUT IN NO CASE LATER THAN PRIOR TO PERFORMANCE OF <br />SYSTEMS OR EQUIPMENT TEST, AND FURNISH THE REMAINING MANUALS PRIOR TO CONTRACT <br />COMPLETION. <br />2. INSCRIBE THE FOLLOWING IDENTIFICATION ON THE COVER: THE WORDS "MAINTENANCE AND OPERATION <br />MANUAL," THE NAME AND LOCATION OF THE SYSTEM, EQUIPMENT, BUILDING, NAME OF CONTRACTOR, AND <br />CONTRACT NUMBER. INCLUDE IN THE MANUAL THE NAMES, ADDRESSES, AND TELEPHONE NUMBERS OF <br />EACH SUBCONTRACTOR INSTALLING THE SYSTEM OR EQUIPMENT AND THE LOCAL REPRESENTATIVES FOR <br />THE SYSTEM OR EQUIPMENT. <br />MATERIALS AND METHODS: <br />A. MATERIALS AND APPARATUSES SHALL COMPLY WITH ALL APPLICABLE TESTS, RATINGS, SPECIFICATIONS, AND <br />REQUIREMENTS OF THE IEEE, NEMA, NFPA AND UL, SHALL BEAR THE UL LABEL OF APPROVAL AND BE LISTED FOR THE <br />PROPOSED APPLICATION. <br />B. FINISHED PRODUCTS SHALL BE FACTORY PRIMED AND FINISH COATED WITH THE MANUFACTURER'S PRIME COAT AND <br />STANDARD FINISH UNLESS SPECIFIED OTHERWISE BY THE ARCHITECT. <br />C. UNLESS OTHERWISE SPECIFIED, UNFINISHED PRODUCTS SHALL BE GALVANIZED, COATED OR PLATED TO RESIST <br />CORROSION. <br />D. INSTALLATIONS SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES, AS RECOMMENDED BY THE MANUFACTURER <br />AND AS CLOSE AS PRACTICABLE TO LOCATIONS INDICATED ON DRAWINGS. <br />E. INSTALLATIONS SHALL FACILITATE MAINTENANCE AND REPAIR OR REPLACEMENT OF EQUIPMENT COMPONENTS. <br />ACCESS, WORKING SPACES AND CLEARANCES SHALL NOT BE LESS THAN SPECIFIED BY THE NEC FOR ALL VOLTAGES <br />SPECIFIED. <br />F. PROVIDE APPROVED FIRE STOPPING MATERIALS AT ALL CHASES TO PREVENT DRAFTS. <br />G. FIRE RATING: RESTORE FIRE RATING WHERE PIERCING OCCURS THROUGH FIRE RATED CEILINGS OR BETWEEN FIRE <br />RATED WALLS. FIRESTOP MATERIALS SHALL BE AS MANUFACTURED BY 3M COMPANY AND UL LISTED FOR USE IN THE <br />CONSTRUCTION ASSEMBLY IN WHICH IT IS TO BE USED. REFER TO ARCHITECTURAL PLANS FOR LOCATIONS OF FIRE <br />RATED WALLS AND CEILINGS. <br />DRAWING SPECIFICATIONS <br />IDENTIFICATION: <br />A. WIRING IN JUNCTION BOXES, WIREWAYS AND PANELBOARD GUTTERS SHALL BE LABELED IDENTIFYING CIRCUIT <br />NUMBER AND/OR EQUIPMENT SERVED. <br />B. JUNCTION BOXES SHALL BE LABELED IN A PERMANENT MANNER REFLECTING PANELBOARD/CIRCUIT NUMBER OF <br />BRANCH CIRCUIT WIRING CONTAINED WITHIN. <br />C. PANELBOARD DIRECTORIES SHALL BE TYPEWRITTEN REFLECTING RECORD CONDITIONS, INCLUDING CIRCUIT NUMBER, <br />TYPE AND LOCATION OF LOADS. <br />D. EQUIPMENT SHALL BE LABELED WITH PLASTIC PLACARDS REFLECTING, EQUIPMENT NAME/NUMBER AND RATING. <br />RACEWAYS: <br />A. RACEWAYS: <br />1. INTERIOR EXPOSED, CONCEALED IN WALLS OR ABOVE CEILINGS: ELECTRICAL METALLIC <br />TUBING (EMT) <br />2. INTERIOR CONNECTIONS TO MOTORS, TRANSFORMERS AND VIBRATING EQUIPMENT: <br />FLEXIBLE METAL CONDUIT (FMC) <br />4. EXTERIOR EXPOSED: GALVANIZED STEEL RIGID METAL CONDUIT (RMC). WHERE <br />PROTECTED, SCHEDULE 40 POLYVINYL CHLORIDE CONDUIT (PVC). <br />5. EXTERIOR CONNECTIONS TO MOTORS, TRANSFORMERS AND VIBRATING EQUIPMENT: <br />6. LIQUIDTIGHT FLEXIBLE METAL CONDUIT (LFMC) <br />7. UNDERGROUND: SCHEDULE 40 PVC <br />8. PENETRATIONS THROUGH CONCRETE SLABS SHALL BE MADE WITH PVC COATED RIGID <br />GALVANIZED STEEL CONDUIT. <br />B. SCHEDULE 40 PVC WILL BE PERMITTED WHERE ALLOWED BY APPLICABLE CODES AND AS OUTLINED <br />ABOVE. PVC SHALL NOT BE USED IN WALL OR CEILING SPACES. ALL BENDS IN PVC LARGER THV NOMINAL <br />TRADE SIZE SHALL BE MADE WITH PVC COATED RIGID METAL CONDUIT. <br />C. PROPERLY ALIGN, GROUP AND SUPPORT ALL CONDUITS. INSTALL EXPOSED CONDUITS <br />PERPENDICULAR AND PARALLEL TO PRINCIPAL STRUCTURAL MEMBERS. CONDUITS SHALL BE SUPPORTED <br />MINIMUM 18" FROM BENDS AND OUTLET BOXES, AT INTERVALS NOT EXCEEDING V-0" AND SHALL NOT SPAN <br />ANY SPACE UNSUPPORTED. CONDUITS SHALL BE SUPPORTED INDEPENDENTLY FROM OTHER TRADES. <br />D. UNDERGROUND CONDUITS SHALL BE INSTALLED WITH MINIMUM 30" COVER. <br />E. THIN WALL CONDUIT SHALL BE UL APPROVED GALVANIZED EMT. COUPLINGS AND CONNECTORS <br />SHALL BE STEEL HEX -NUT, ZINC OR CADMIUM PLATED SET SCREW TYPE FITTINGS. <br />F. FMC IN DRY LOCATIONS SHALL BE UL APPROVED, ZINC COATED, SINGLE STRIP TYPE. FITTINGS SHALL BE AS <br />MANUFACTURED BY THOMAS AND BETTS "TITE-BITE" OR APPROVED EQUAL. <br />G. PROVIDE NYLON PULL CORD AND LEAVE IN PLACE IN EACH EMPTY CONDUIT. <br />H. PROVIDE EXPANSION FITTINGS IN CONDUIT RUNS CROSSING EXPANSION JOINTS IN THE STRUCTURE. <br />BOXES: <br />A. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE SCREW FASTENED COVERS. OPEN <br />KNOCK -OUTS OR HOLES SHALL BE PLUGGED WITH A SUITABLE BLANKING DEVICE. <br />B. EXTERIOR BRANCH BOXES SHALL BE WEATHERPROOF CAST "FS" BOXES OR ENGINEER APPROVED EQUAL. <br />C. HANDHOLES AND COVERS SHALL BE HUBBELL QUAZITE OR EQUAL, UL LISTED TIER 15 RATED, LOCKABLE COVERS, <br />OPTIONS AS NEEDED, STAINLESS STEEL BOLTS. <br />CONDUCTORS: <br />A. UNLESS OTHERWISE INDICATED, BRANCH CIRCUIT CONDUCTORS SHALL BE NO. 12 AWG. BRANCH CIRCUIT RUNS <br />OVER 75 FEET IN LENGTH, MEASURED ONE WAY FROM THE FIRST OUTLET TO THE PANELBOARD, SHALL BE NO. 10 <br />AWG FOR THE ENTIRE CIRCUIT. <br />B. CONDUCTORS SHALL BE COPPER WITH THHN/THWN-2 90°C INSULATION. THE FOLLOWING SYSTEMS OF COLOR <br />CODING SHALL BE STRICTLYADHERED TO AND SHALL BE CONSISTENTLY FOLLOWED THROUGHOUT: <br />1. GROUND WIRES: GREEN <br />2. GROUNDED NEUTRAL WIRES: WHITE <br />3. 208/120 VOLT, UNGROUNDED PHASE WIRES: BLACK, RED AND BLUE <br />4. 480/277 VOLT, UNGROUNDED PHASE WIRES: BROWN, ORANGE AND YELLOW <br />C. WIRING IN AIR PLENUMS OR PLENUM SPACES NOT IN CONDUIT SHALL BE UL LISTED AS SUITABPLENUM <br />USE. <br />D. CONDUITS AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL BE SEALED TO MAINTAIN FIRE <br />RATING AND INTEGRITY OF SEPARATION. <br />E. UNDERGROUND SPLICES, JOINTS, TERMINATIONS, ETC. SHALL BE WATERPROOF. <br />F. MULTIPLE CIRCUITS IN SAME CONDUIT SHALL NOT SHARE NEUTRAL CONDUCTORS. <br />G. INSTALL SPLIT BOLT CONNECTORS FOR COPPER CONDUCTOR SPLICES AND TAPS, 6 AWG ,LARGER. <br />H. INSTALL SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR COPPER CONDUCTOR <br />SPLICES AND TAPS, 8 AWG AND SMALLER. <br />I. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER CONDISPLICES AND <br />TAPS, 10 AWG AND SMALLER. <br />J. "PUSH -IN" OR "STAB" TYPE CONNECTORS ARE NOT ACCEPTABLE. <br />GROUNDING: <br />A. THE ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS REQUIRED BY THE NEC AND AS <br />SPECIFIED HEREINAFTER. <br />B. METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE AT ALL JOINTS, AT ALL BOXES, <br />CABINETS, FITTINGS, AND EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A DIRECT GROUND AT THE <br />POINT OF ELECTRICAL SERVICE ENTRANCE AND SHALL BE ELECTRICALLY CONTINUOUS THROUGHOUT THE ENTIRE <br />SYSTEM. <br />C. GROUNDING CONDUCTORS SHALL BE INSULATED COPPER UON. <br />D. RACEWAYS WITH NO. 12 OR 10 AWG PHASE CONDUCTORS FOR BRANCH CIRCUITS SHALL BE PROVIDED WITH A <br />PARITY SIZED GREEN EQUIPMENT GROUNDING CONDUCTOR. GROUNDING CONDUCTOR SHALL BE INSTALLED IN ENTIRE <br />RACEWAY SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE CONNECTIONS TO LIGHTING FIXTURES. FOR <br />EQUIPMENT GROUNDING CONDUCTOR SIZES OF CIRCUITS WITH PHASE CONDUCTORS LARGER THAN NO. 12 AWG <br />REFER TO DRAWINGS. GROUNDING CONDUCTORS SHALL BE CONNECTED TO GROUND BUS IN PANELBOARDS. <br />E. INSULATED EQUIPMENT GROUNDING CONDUCTORS SHALL BE TERMINATED WITH GROUNDING LUG, BUS, OR BUSHING. <br />CONDUCTORS LOOPED UNDER SCREW OR BOLT HEADS WILL NOT BE PERMITTED. <br />F. INSTALL CLAMP -ON CONNECTORS ON CLEAN METAL CONTACT SURFACES TO ENSURE ELECTRICAL CONDUCTIVITY <br />AND CIRCUIT INTEGRITY. <br />G. TEST THE GROUNDING SYSTEM TO ASSURE CONTINUITY AND THAT RESISTANCE TO GROUND DOES NOT EXCEED 25 <br />OHMS UNLESS OTHERWISE NOTED. TEST EACH GROUND ROD FOR RESISTANCE TO GROUND BEFORE MAKING ANY <br />CONNECTIONS TO THE ROD; THEN TIE ENTIRE GROUNDING SYSTEM TOGETHER AND TEST FOR RESISTANCE TO <br />GROUND. MAKE RESISTANCE MEASUREMENTS IN NORMALLY DRY WEATHER, NOT LESS THAN 48 HOURS AFTER <br />RAINFALL. MAKE GROUND RESISTANCE MEASUREMENTS WITH A GROUND RESISTANCE TEST METER CALIBRATED <br />WITHIN THE LAST TWELVE MONTHS. <br />SWITCHES & RECEPTACLES: <br />A. RECEPTACLES SHALL BE THE GROUNDING TYPE WITH GROUNDING CONNECTION MADE THROUGH AN EXTRA POLE <br />WHICH SHALL BE PERMANENTLY CONNECTED TO A GROUNDING CONDUCTOR. <br />B. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW TERMINAL. WHEN STRANDED <br />CONDUCTORS ARE USED IN LIEU OF SOLID, USE CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT <br />PLACE BARE STRANDED CONDUCTORS DIRECTLY UNDER DEVICE SCREWS. <br />C. GFCI RECEPTACLES SHALL MEET CURRENT UL 943 REQUIREMENTS WITH AUTO -MONITORING OR SELF -TEST <br />FUNCTIONALITY; IF THE SELF -TEST FUNCTION DETECTS A PROBLEM, THE UNIT MUST DENY POWER OR PROVIDE <br />VISUAL AND/OR AUDIBLE INDICATION. <br />D. GFCI RECEPTACLES LOCATED IN DAMP, WET OR EXTERIOR LOCATIONS SHALL BE WEATHER -RESISTANT TYPE TO <br />COMPLY WITH NEC 406.9. <br />E. RECEPTACLES FOR 20 AMPERE, 120 VOLT APPLICATION SHALL BE SPECIFICATION GRADE THREE -WIRE, TWO POLE, <br />RATED 20 AMPERES AT 125 VOLTS, PASS & SEYMOUR OR APPROVED EQUAL. <br />F. LIGHT SWITCHES SHALL BE SPECIFICATION GRADE, 120/277 VOLTS, PASS & SEYMOUR OR APPROVED EQUAL. <br />G. PROVIDE WALL PLATES FOR SINGLE AND COMBINATION DEVICES OF TYPES, SIZES, AND WITH GANGING AND <br />CUTOUTS AS INDICATED. SELECT PLATES WHICH MATE AND MATCH WIRING DEVICES TO WHICH ATTACHED. <br />CONSTRUCT WITH METAL SCREWS FOR SECURING PLATES TO DEVICES; SCREW HEADS COLOR TO MATCH FINISH OF <br />PLATES, WALL PLATES COLOR TO MATCH DEVICES, COLOR BY ARCHITECT. <br />H. WEATHERPROOF COVER PLATES SHALL BE NEMA 250 COMPLYING WITH TYPE 3R, WEATHER RESISTANT, DIE-CAST <br />ALUMINUM, WHILE IN USE COVER. COVER SHALL HAVE NOTCH FOR CORD. <br />LIGHTING FIXTURES: <br />A. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE IN ALL RESPECTS ALL LIGHTING FIXTURES AND <br />APPURTENANCES AS INDICATED ON THE PLANS. <br />B. PROPERLY AND CAREFULLY ALIGN FIXTURES. FIXTURE BOTTOMS, EDGES, AND ENDS SHALL BE EVEN AND TRIMS <br />SHALL BE SNUG TO THE SURFACE. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL NECESSARY HARDWARE, <br />ETC. FOR A COMPLETE FIXTURE INSTALLATION. FIXTURES SHALL BE SUPPORTED INDEPENDENTLY FROM CEILING AND <br />OTHER TRADES. <br />C. RECESSED FIXTURES SHALL BE CONNECTED WITH A MAXIMUM 6 FOOT FLEXIBLE WHIP. <br />F. LAMPS: <br />1. LAMPS APPROVED MANUFACTURERS SHALL BE: SYLVANIA. PHILIPS OR GENERAL ELECTRIC, NO SUBSTITUTIONS <br />PERMITTED. <br />SHALL HAVE A MI 41 K T N OTHERWISE, ALL LAMPS SHALL BE <br />2. FLUORESCENT LAMPS SHA MINIMUM 85 CRI AND 00 CC UON, O , <br />TCLP' COMPLIANT. <br />HALL BE LEAN AND LENSES HALL BE CLEAR OF FINGERPRINTS. <br />G. FIXTURESS C S <br />H. REPLACE NON -OPERATING LAMPS WITH NEW AND REPLACE MISMATCHED COLOR LAMPS WITH SAME COLOR <br />LAMPS PRIOR TO FINAL OBSERVATION BY ENGINEER. <br />EQUIPMENT: <br />A. APPROVED MANUFACTURERS SHALL BE: SQUARE-D, CUTLER -HAMMER, GENERAL ELECTRIC AND SIEMENS. <br />B. EQUIPMENT BUSES SHALL BE COPPER. <br />C. OUTDOOR EQUIPMENT SHALL BE NEMA 3R OR NEMA 4X AS REQUIRED. <br />D. PANELBOARDS: <br />1. PANELBOARDS SHALL BE SQUARE-D: NQ, NF, I -LINE OR APPROVED EQUAL, SERIES RATED <br />PANELBOARDS WILL NOT BE PERMITTED. <br />2. FULL SIZE, COPPER NEUTRAL BUS (UON), MOUNTED ON INSULATED SUPPORTS. <br />3. COPPER GROUND BUS WITH SUFFICIENT TERMINALS FOR ALL GROUNDING CONDUCTORS. <br />BUSES BRACED FOR THE AVAILABLE SHORT CIRCUIT CURRENT, BUT NOT LESS THAN 10,000 AMPERES <br />SYMMETRICAL FOR 208/120 VOLT PANELBOARDS AND 14,000 AMPERES SYMMETRICAL FOR 480/277 VOLT <br />PANELBOARDS. <br />4. MAIN CIRCUIT BREAKER MOUNTING SHALL BE VERTICAL, AHEAD OF BUSES; HORIZONTAL <br />MOUNTING WILL NOT BE ACCEPTED. <br />5. FOR RECESSED PANELBOARDS, PROVIDE MINIMUM (5) SPARE 3/4" CONDUITS STUBBED <br />OUT TO ABOVE ACCESSIBLE CEILING. IDENTIFY EACH CONDUIT AS "SPARE". <br />E. CIRCUIT BREAKERS SHALL BE BOLT -ON TYPE. <br />F. PROVIDE DISCONNECTING MEANS OR SAFETY SWITCH NEAR AND WITHIN SIGHT OF EACH MOTOR. <br />G. SAFETY SWITCHES SHALL BE HEAVY DUTY TYPE LION. <br />H. FUSES SHALL BE CLASS RK1 UON. <br />L. SURGE PROTECTIVE DEVICE MANUFACTURERS SHALL BE: PQ PROTECTION, LEA INTERNATIONAL, ATLANTIC <br />SCIENTIFIC, OR CURRENT TECHNOLOGY. <br />Renna Enterprises, Inc. <br />P.E. # 85232 Irving Ho, P.E. <br />AUTH. # 00008631 Consulting Engineers <br />3231 Drone Field Road Ph. (863) 646 1258 <br />Lakeland, FI 33811 Fax. (863) 646 8881 <br />V� <br />a' <br />o <br />(7D <br />U <br />00c)) <br />N <br />1­1 <br />c`M <br />0 <br />= <br />V <br />QJ <br />� <br />N <br />s <br />O <br />0 <br />cc <br />m <br />V <br />ca <br />O <br />5 <br />o <br />� <br />� <br />W <br />o� <br />Q <br />Z U) <br />W <br />Z <br />m~ <br />VJ <br />oW <br />W <br />O <br />H <br />2Q <br />IX a <br />�- <br />LU J <br />Oz <br />W <br />0 <br />LL- <br />W <br />Lj_j <br />ow <br />T <br />�j� <br />W LL <br />F J <br />O <br />w J_ <br />� _ <br />W <br />Q <br />=2 <br />~ <br />LL <br />o�0�^o-04 <br />UZ <br />VJ <br />Q <br />LoN <br />IIIII111111 <br />E2 <br />URUA <br />