ACCESSIBILITY STANDARDS
<br />SIGNAGE SHOULD COMPLY W/ RELEVANT GUIDELINES AS FOLLOWS.
<br />A. ALL PERMANENT ROOM AND SPACE IDENTIFICATION SIGNAGE SHALL COMPLY
<br />WITH SECTIONS 1 THROUGH 5.
<br />B. ALL DIRECTIONAL AND INFORMATIONAL SIGNAGE SHALL COMPLY
<br />WITH SECTIONS 1 & 2.
<br />C. ALL IDENTIFICATION, INFORMATIONAL OR DIRECTIONAL SIGNAGE ABOUT
<br />ACCESSIBLE ELEMENTS AND FEATURES SHALL COMPLY WITH SECTIONS 1
<br />THROUGH 5.
<br />SIGNAGE DESIGN CRITERIA:
<br />1. FINISH AND CONTRAST:
<br />CHARACTER, SYMBOLS, BACKGROUNDS SHALL HAVE A NON -GLARE FINISH.
<br />CHARACTER & SYMBOLS SHALL CONTRAST A MIN. OF 70% W/ THEIR
<br />BACKGROUND.
<br />LRV FINISH (LIGHT REFLECTANCE VALUE) OF MATERIAL FINISHES SHALL BE
<br />ASTM E1349-90 OR EQUAL.
<br />2. PROPORTIONS:
<br />CHARACTERS ARE TO HAVE A WIDTH -TO -HEIGHT RATIO OF 3:5 TO 1:1.
<br />CHARACTER STROKE WIDTH -TO -HEIGHT OF 1:5 TO 1:10.
<br />3. RAISED CHARACTERS AND PICTORAL SIGN SYMBOLS:
<br />CHARACTER TYPE:
<br />1/32" RAISED (MIN.)
<br />SANS SERIF UPPERCASE WITH GRADE 2 BRAILLE.
<br />CHARACTER SIZE:
<br />MIN.5/8" AND MAX. 2" HIGH
<br />PICTOGRAMS:
<br />ACCOMPANY W/ VERBAL DESCRIPTION PLACED DIRECTLY BELOW THE
<br />PICTOGRAM.
<br />OUTSIDE DIMENSION OF PICTOGRAM FIELD TO BE MIN. 6" HEIGHT.
<br />CHARACTER PLACEMENT:
<br />CHARACTERS AND BRAILLE SHALL BE IN HORIZONTAL FORMAT
<br />BRAILLE SHALL BE PLACED 3/8" (MIN.) & 1/2" (MAX.) DIRECTLY BELOW THE
<br />TACTILE CHARACTERS (FLUSH LEFT OR CENTER).
<br />IF TACTILE TEXT IS MULTILINE, ALL BRAILLE SHALL BE PLACED
<br />TOGETHER BELOW ALL LINES OF TACTILE TEXT.
<br />4. BRAILLE:
<br />CONTRACTED GRADE 2 BRAILLE SHALL BE USED WHEREVER APPLICABLE
<br />STANDARDS REQUIRE BRAILLE.
<br />DOTS SHALL BE 1/10" ON CENTERS IN EACH CELL W/ 2/10" SPACE BETWEEN
<br />CELLS, MEASURED FROM THE SECOND COLUNMN OF DOTS IN THE FERST
<br />CELL TO THE FIRST COLUMN OF DOTS IN THE SECOND CELL.
<br />DOTS SHALL BE RAISED A 1/40" MIN ABOVE THE BACKGROUND.
<br />DOTS SHALL BE DOMED OR ROUNDED.
<br />5. MOUNTING LOCATION AND HEIGHT:
<br />INSTALL ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR.
<br />WHERE NO WALL SPACE EXISTS ON THE LATCH SIDE OF THE DOOR (INCL.
<br />DOUBLE LEAFS), PLACE SIGN ON THE NEAREST ADJACENT WALL,
<br />PREFERABLY TO THE RIGHT SIDE.
<br />HEIGHT: 60" ABOVE FINISH FLOOR TO THE CENTERLINE OF THE SIGN.
<br />LOCATION: PLACE SO THE APPROACHING PERSON MAY APPROACH WITHIN
<br />3" OF SIGNAGE WITHOUT WNCOUNTERING PROTRUDING OBJECTS OR
<br />STANDING WITHIN THE SWINGING DOOR PATH.
<br />DOORS
<br />A. LATCHES AND LOCKSETS: PROVIDE LEVER TYPE, PUSH-PULL OR PANIC TYPE
<br />HARDWARE 30 INCHES TO 44 INCHES ABOVE FLOOR.
<br />B. MAXIMUM FORCE TO OPERATE DOORS SHALL BE 5 LBS. PRESSURE. FIRE
<br />DOORS SHALL BE 15 LBS. MAXIMUM.
<br />C. FLOOR SHALL BE LEVEL AT ALL DOORS.
<br />1. THRESHOLDS: THE FLOOR OR LANDING SHALL NOTE BE MORE THAN 1/2-INCH
<br />LOWER THAN THE THRESHOLD OF THE DOOR WAY. CHANGE IN LEVEL
<br />BETWEEN 1/4-INCH AND 1/2-INCH SHALL BE BEVELED WITH A SLOPE NO
<br />GREATER THAN 1:2. (SEE BELOW).
<br />2. LEVEL FLOOR OR LANDING: THERE SHALL BE A LEVEL AND CLEAR AREA ON
<br />EACH SIDE ON AN EXIT DOOR. THE LEVEL AREA SHALL BE AS ILLUSTRATED IN
<br />FIGURE A. THE SPACE BETWEEN THE TWO CONSECUTIVE DOOR OPENING
<br />(VESTIBULE) SHALL PROVIDE 48-INCHES OF CLEAR SPACE FROM ANY DOOR
<br />OPENING INTO SUCH SPACE. (SEE BELOW)
<br />D. DOOR WIDTH AND HEIGHT: 3-FEET WIDE AND 6-FEET-8-INCHES HIGH. CLEAR
<br />WIDTH: 32-INCHES MINIMUM WITH DOOR OPEN 90-DEG. MEASURED FROM THE
<br />FACE OF THE DRR TO THE OPPOSITE SIDE.
<br />E. THE BOTTOM 10 INCHES OF ALL DOORS EXCEPT AUTOMATIC AND SLIDING
<br />SHALL HAVE A SMOOTH UNINTERUPTED SURFACE TO ALLOW THE DOOR TO BE
<br />OPENED BY A WHEELCHAIR FOOT - REST WITHOUT CREATING A TRAP OR
<br />HAZARDOUS CONDITION.
<br />EACH GRADE LEVEL EXTERIOR DOOR SHALL BE IDENTIFIED BY A TACTILE EXIT WITH
<br />THE WORDS 'EXIT.
<br />EACH EXIT DOOR THAT LEADS DIRECTLY TO A GRADE -LEVEL EXTERIOR EXIT MY
<br />MEANS OF A STAIRWAY OR RAMP SHALL BE INDENTIFIED BY A TACTILE EXIT SIGN
<br />WITH THE FOLLOWING WORDS AS APPROPRIATE:
<br />1. 'EXIT STAIRS DOWN'
<br />2. 'EXIT RAMP DOWN'
<br />3. 'EXIT STAIR UP'
<br />4. 'EXIT RAMP UP'
<br />EACH EXIT DOOR THAT LEADS DIRECTLY TO A GRADE -LEVEL EXTERIOR EXIT BY
<br />MEANS OF AN
<br />EXIT ENCLOSURE OR AN EXIT PASSAGEWAY SHALL
<br />BE IDENTIFIED BY A TACTILE EXIT SIGN WITH THE WORDS 'EXIT ROUTE'.
<br />EACH EXIT ACCESS DOOR FROM AN INTERIOR ROOM OR AREA TO A CORRIDOR OR
<br />HALLWAY THAT IS REQUIRED TO HAVE A VISUAL EXIT SIGN SHALL BE INDENTIFIED BY
<br />A TACTILE EXIT SIGN WITH THE
<br />WORDS 'EXIT ROUTE'.
<br />EACH EXIT DOOR THROUGH A HORIZONTAL EXIT SHALL BE IDENTIFIED BY A SIGN
<br />WITH THE WORDS 70 EXIT'.
<br />INTERIOR METAL STUD SCHEDULE
<br />SIZE
<br />GA.
<br />TYPE
<br />16" O.C.
<br />24" O.C.
<br />MAX. UNSUPPORTED HT
<br />NOTES 1,2,3
<br />25
<br />CSJ
<br />12'-7"
<br />11'-0"
<br />3 5/8"
<br />20
<br />CSJ
<br />15'-5"
<br />13'-5"
<br />18
<br />CSJ
<br />19'-1"
<br />16-8"
<br />20
<br />CSJ
<br />23'-2"
<br />20'-3"
<br />6"
<br />18
<br />CSJ
<br />28'-4"
<br />24'-9"
<br />NOTES:
<br />1. BASED ON INTERIOR NONBEARING PARTITIONS WITH ONE LAYER OF GYPSUM
<br />BOARD EACH SIDE; USE GAUGE, TYPE AS SCHEDULED UNLESS NOTED
<br />OTHERWISE ON DRAWINGS.
<br />2. RUNNER TRACK GAUGE TO MATCH STUD.
<br />3. ALL WALLS SHALL HAVE 1-1/2" X16 GA, COLD ROLLED CHANNEL HORIZONTAL
<br />BRIDGING SPACED AT V-0".
<br />4. HEADERS SHALL BE BUILT UP TYPE W/(2}12"X12GA BOX HEADER. PROVIDE
<br />12"X12GA WEB STIFFENERS @ EACH END. ALL HEADERS SHALL BE
<br />SUPPORTED BY (2) TRIMMER STUDS ADJACENT TO (2) FULL HEIGHT STUDS,
<br />UNLESS NOTED OTHERWISE.
<br />PROTRUDING OBJECTS
<br />A. PROJECTIONS FROM WALLS WITH A LEADING EDGE BETWEEN 27 INCHES AND
<br />80 INCHES ABOVE FLOOR MAY PROJECT 4 INCHES MAXIMUM. LEADING EDGE
<br />AT OR BELOW 27 INCHES MAY PROJECT ANY AMOUNT. FREESTANDING
<br />PROJECTIONS WITH LEADING EDGE BETWEEN 27 INCHES AND 80 INCHES
<br />ABOVE FLOOR MAY PROJECT 12 INCHES MAX. PROJECTIONS MAY NOT
<br />REDUCE MANEUVERING SPACE, OR CLEAR WIDTH OF AN ACCESSIBLE ROUTE.
<br />B. PROVIDE MINIMUM OF 80 INCHES HEAD ROOM.
<br />ELECTRICAL
<br />A. ELECTRICAL RECEPTACLES (15, 20, AND 30 AMPS) SHALL BE AT LEAST 15
<br />INCHES ABOVE THE FLOOR.
<br />B. SWITCHES AND CONTROLS FOR LIGHTS, APPLIANCES, COOLING, HEATING AND
<br />VENTILATING EQUIPMENT SHALL BE NOT LESS THAN 36" AND NO MORE THAN
<br />48" A.F.F.
<br />C. FIRE ALARM INITIATING DEVISES SHALL BE 48" ABOVE THE FLOOR, GROUND OR
<br />SIDEWALK.
<br />SANITARY FACILITIES
<br />A. GEOMETRIC SYMBOLS
<br />1. SYMBOLS
<br />A) MEN'S SANITARY FACILITIES SHALL BE IDENTIFIED BY AN EQUILATERAL
<br />TRIANGLE 1/4" THICK WITH SIDE 12" LONG AND VERTEX POINTING
<br />UPWARD.
<br />B) WOMEN'S SANITARY FACILITIES SHALL BE IDENTIFIED BY A CIRCLE 1/4"
<br />THICK, 12" DIAMETER.
<br />C) UNISEX SANITARY FACILITIES SHALL BE IDENTIFIED BY A CIRCLE 1/4" THICK,
<br />12" DIAMETER, WITH A 1/4" THICK EQUILATERAL TRIANGLE
<br />SUPERIMPOSED ON THE CIRCLE AND WITHIN THE 12 INCH DIAMETER.
<br />2. GEOMETRIC (CIRCLE AND TRIANGLE) SYMBOLS ON SANITARY DOORS SHALL BE
<br />CENTERED ON THE DOOR AT A HEIGHT OF 60" AND THEIR COLOR AND
<br />CONTRAST SHALL BE DINSTINCTLY DIFFERENT FROM THE COLOR AND
<br />CONTRAST OF THE DOOR.
<br />3. RAISED LETTERS SHALL BE PROVIDED AND SHALL BE ACCOMPAINED BY
<br />BRAILLE IN CONFORMANCE WITH SECTION 1117B.5.6. THEY SHALL BE
<br />INSTALLED ON THE WALL ADJACENT TO THE LATCH OUTSIDE OF THE DOGE.
<br />WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE, INCLUDING AT DOUBLE
<br />LEAF DOORS, SIGNS SHALL BE PLACED ON THE NEAREST ADJACENT WALL,
<br />PREFERABLY ON THE RIGHT. MOUNTNG HEIGHT SHALL BE 60 INCHES ABOVE
<br />THE FINISH FLOOR TO THE CENTER OF THE SIGN. MOUNTING LOCATION SHALL
<br />BE DETERMINED SO THAT A PERSON MAY APPROACH WITHIN 3 INCHES OF
<br />SIGNAGE WITHOUT ENCOUNTERING PROTUDING OBJECTS OR STANDING
<br />WITHIN THE SWING OF THE DOOR.
<br />SECTION 1117B.5.6
<br />A) LETTER TYPE: LETTERS AND NUMBERS ON SIGNS SHALL BE RAISED 1/32
<br />INCH (0.794mm) MINIMUM AND SHALL BE SANS -SERIF UPPERCASE
<br />CHARACTERS ACCOMPANIED BY GRADE 2 BRAILLE.
<br />B) SYMBOL SIZE: RAISED CHARACTERS OR SYMBOLS SHALL BE MINIMUM OF 5/8
<br />INCH (15.9mm) HIGH.
<br />C) PICTORAL SYMBOL SIGNS (PICTOGRAMS): PICTORAL SYMBOL SIGNS SHALL
<br />BE ACCOMPANIED BY THE EQUIVELANT VERBAL DESCRIPTION PLACED
<br />DIRECTLY BELOW THE PICTOGRAM. THE BORDER DIMENSION OF THE
<br />PICTOGRAM SHALL BE A MINIMUM OF 6 INCHES (152mm) IN HEIGHT.
<br />B. ACCESSIBLE COMPARTMENT DOORS SHALL BE EQUIPPED WITH AN AUTOMATIC
<br />CLOSING DEVICE. THE INSIDE AND OUTSIDE OF THE COMPARTMENT DOOR
<br />SHALL BE EQUIPPED WITH A LOOP OR U-SHAPED HANDLE IMMEDIATELY BELOW
<br />THE LATCH. THE LATCH SHALL BE FLIP -OVER STYLE, SLIDING OR OTHER
<br />HARDWARE NOT REQUIREING THE USER TO GRASP OR TWIST.
<br />C. WATER CLOSET: FLUSH CONTROLS ARE TO BE OPERABLE BY AN OSCILLATING
<br />HANDLE WITH A MINIMUM OPERATING FORCE OF 3 LB./F OR BY A LOW
<br />VOLTAGE BUTTON. THE HANDLE OR BUTTON IS TO BE LOCATED ON THE WIDE
<br />SIDE SO AS TO BE OPERABLE WITHOUT REQUIREING EXCESSIVE BODY
<br />MOVEMENT.
<br />D. URINALS: PROVIDE ALL WALL HUNG URINALS WITH ELONGATED RIM. FLUSH
<br />CONTROLS ARE TO BE HAND OPERATED AND ARE TO MEET THE SAME
<br />REQUIREMENTS AS THE FLUSH CONTROLS FOR THE WATER CLOSET AND ARE
<br />TO BE A MAXIMUM OF 44 INCHES ABOVE THE FLOOR. RIM ELEVATION TO BE 17
<br />INCHES A.F.F.
<br />E. LAVATORY: PROVIDE AT LEAST 29 INCHES FROM THE FLOOR TO THE BOTTOM
<br />OF THE APRON WITH KNEE CLEARANCE UNDER THE FRONT LIP EXTENDING A
<br />MINIMUM OF 30 INCHES WIDE. TO 8 INCHES MINIMUM DEPTH AT THE TOP.
<br />PROVIDE FOR THE CLEARANCE AT LEAST 30 INCHES WIDE. TO 9 INCHES ABOVE
<br />THE FLOOR AND 17 INCHES DEEP FROM THE FRONT OF THE LAVATORY.
<br />PROVIDE A CLEAR FLOOR SPACE 30 INCHES x 48 INCHES IN FRON T OF THE
<br />LAVAOTRY. THE CLEAR SPACE MAY EXTEND INTO KNEE AND TOE SPACE
<br />UNDERNEATH THE LAVATORY. INSULATE HOT WATER AND DRAIN PIPES UNDER
<br />LAVATORIES. NO SHARP OR ABRASIVE SURFACES ARE ALLOWED UNDER
<br />LAVATORIES. FAUCET CONTROLS ARE REQUIRED TO BE OPEARABLE WITH
<br />ONE HAND AND CANNOT REQUIRE GRASPING, PINCHING, OR TWISTING OF THE
<br />WRIST. THE FORCE NECESSARY TO OPERATE CONTROLS IS NOT TO EXCEED 5
<br />LB./F.
<br />F. ACCESSORIES: WHERE TOWEL, SANITARY NAPKIN AND WASTE RECEPTACLES
<br />AND SIMILAR DISPENSING AND DISPOSAL FIXTURES ARE PROVIDED, AT LEAST
<br />ONE OF EACH TYPE IS TO BE LOCATED WITH ALL OPERABLE PARTS, INCLUDING
<br />COIN SLOTS, WITHIN 40 INCHES FROM THE FLOOR.
<br />1. MOUNT MIRRORS WITH THE BOTTOM EDGE NO MORE THAN 40 INCHES A.F.F.
<br />2. LOCATE TOILET TISSUE DISPENSERS ON THE WALL WITHIN 12 INCHES OF THE
<br />FRONT EDGE OF THE TOILET SEAT.
<br />G. THE STRUCTURAL STRENGTH OF GRAB BARS, FASTENERS AND MOUNTING
<br />DEVICES SHALL MEET THE SPECIFICATIONS OF THE AMERICAN DISABILITES
<br />ACT AND THE STATE OF CALIFORNIS TITLE 24.
<br />H. SINGLE ACCOMODATION: A CLEAR FLOOR SPACE OF AT LEAST 60 INCHES IN
<br />DIAMETER IS REQUIRED FOR SINGLE ACCOMODATION TOILET ROOMS.
<br />SECTION TAG:
<br />DETAIL TAG:
<br />DOOR TAG:
<br />SHEET NOTE:
<br />FINISH TAG:
<br />00/A0.0
<br />7
<br />SYMBOLS LEGEND
<br />ROOM TAG: ROOM NAME
<br />PARTITION TYPE: F
<br />DATUM TAG:
<br />INTERIOR
<br />ELEVATION TAG
<br />FINISH FLOOR
<br />-0-
<br />0'-0" A.F.F.
<br />/400%
<br />�-o
<br />DRINKING FOUNTAINS
<br />CLEAR FLOOR SPACE.
<br />A. A CLEAR FLOOR SPACE COMPLYING WITH SECTION 305, POSITIONED FOR A
<br />FORWARD APPROACH TO THE DRINKING FOUNTAIN, SHALL BE PROVIDED. KNEE
<br />AND TOE SPACE COMPLYING WITH SECTION 306 SHALL BE PROVIDED. THE
<br />CLEAR FLOOR SPACE SHALL BE CENTERED ON THE DRINKING FOUNTAIN.
<br />EXCEPTIONS:
<br />A. DRINKING FOUNTAINS FOR STANDING PERSONS.
<br />B. DRINKING FOUNTAINS PRIMARILY FOR CHILDREN'S USE SHALL BE PERMITTED
<br />WHERE THE SPOUT IS 30 INCHES (760 MM) MAXIMUM ABOVE THE FLOOR, AND A
<br />PARALLEL APPROACH COMPLYING WITH SECTION 305, CENTERED ON THE
<br />DRINKING FOUNTAIN, IS PROVIDED.
<br />C. IN EXISTING BUILDINGS, EXISTING DRINKING FOUNTAINS PROVIDING A
<br />PARALLEL APPROACH COMPLYING WITH SECTION 305, CENTERED ON THE
<br />DRINKING FOUNTAIN, SHALL BE PERMITTED.
<br />D. WHERE SPECIFICALLY PERMITTED BY THE ADMINISTRATIVE AUTHORITY, A
<br />PARALLEL APPROACH COMPLYING WITH SECTION 305, CENTERED ON THE
<br />DRINKING FOUNTAIN, SHALL BE PERMITTED FOR DRINKING FOUNTAINS THAT
<br />REPLACE EXISTING DRINKING FOUNTAINS WITH A PARALLEL APPROACH
<br />OPERABLE PARTS
<br />A. OPERABLE PARTS SHALL COMPLY WITH SECTION 309.
<br />SPOUT OUTLET HEIGHT.
<br />A. SPOUT OUTLETS OF WHEELCHAIR ACCESSIBLE DRINKING FOUNTAINS SHALL
<br />BE 36 INCHES (915 MM) MAXIMUM ABOVE THE FLOOR. SPOUT OUTLETS OF
<br />DRINKING FOUNTAINS FOR STANDING PERSONS SHALL BE 38 INCHES (965 MM)
<br />MINIMUM AND 43 INCHES (1090 MM) MAXIMUM ABOVE THE FLOOR.
<br />SPOUT LOCATION
<br />A. THE SPOUT SHALL BE LOCATED 15 INCHES (380 MM) MINIMUM FROM THE
<br />VERTICAL SUPPORT AND 5 INCHES (125 MM) MAXIMUM FROM THE FRONT EDGE
<br />OF THE DRINKING FOUNTAIN, INCLUDING BUMPERS. WHERE ONLY A PARALLEL
<br />APPROACH IS PROVIDED, THE SPOUT SHALL BE LOCATED 31/2 INCHES (89 MM)
<br />MAXIMUM FROM THE FRONT EDGE OF THE DRINKING FOUNTAIN, INCLUDING
<br />BUMPERS.
<br />FIG. 308.2.1 UNOBSTRUCTED
<br />FORWARD REACH
<br />nnw
<br />FIG. 308.3.1 UNOBSTRUCTED
<br />SIDE REACH
<br />_nn nrw
<br />FIG. 308.2.2 OBSTRUCTED
<br />HIGH FORWARD REACH
<br />FIG. 308.3.2 OBSTRUCTED
<br />HIGH SIDE REACH
<br />LOOSE LINTEL SCHEDULE
<br />INTERIOR WALLS
<br />CLEAR SPAN
<br />SIZE PER 4" WYTHE
<br />0' TO 2'-8"
<br />SEE NOTE 3 BELOW
<br />2'-9" TO 4'-0"
<br />1-3jx3jx6
<br />4'-1" TO 5'-6"
<br />L4x34x6 LLV
<br />5'-7" TO T-6"
<br />L5x3jx6 LLV
<br />T-7" TO 9'-6"
<br />1-541 LLV
<br />EXTERIOR WALLS
<br />CLEAR SPAN SIZE PER 4" WYTHE REMARKS 8" 12"
<br />BACKUP BACKUP
<br />0' TO 4'-0" L3*x3�x16 BOT R 8"
<br />4'-1" TO 5'-6" L4x3*x6 LLV BOT R. 8"
<br />5'-7" TO T-6" L5x3jxj LLV BOT R "TZ
<br />T-7" TO 9'-6" L6x34x8 LLV BOT R 8"
<br />9'-7" TO 1 V-0" L7x4)j LLV BOT R. 8"
<br />NOTES:
<br />1. PROVIDE MINIMUM 3/8" THICKNESS FOR EXTERIOR ANGLES.
<br />2. PROVIDE A MINIMUM BEARING LENGTH OF 8" ON V-4" MIN. HT. OF GROUTED SOLID
<br />MASONRY.
<br />3. GALVANIZE ALL LINTELS THAT ARE EXPOSED TO WEATHER.
<br />4. AT EXTERIOR WALLS, STOP BOTTOM PLATE 1/16" SHORT AT EACH END OF MASONRY
<br />OPENING LENGTH.
<br />5. PROVIDE A MINIMUM BEARING LENGTH OF 8"
<br />6. FILL VOID BETWEEN VENEER & LINTEL WITH MORTAR TO TOP OF ANGLE.
<br />7. ANGLE MATERIAL: ASTM A36.
<br />8. REFER TO STRUCTURAL DRAWINGS FOR DETAILS OF ALL EXTERIOR WALL OPENINGS.
<br />E N 18 min 12 min �� o
<br />\ M5 305 iy
<br />(a) - front approach, pull side (b) - front app ach, push de, door
<br />provided with b6th closer d latch
<br />E N E O
<br />\ 36 min \ 42 min
<br />\ ses \ 1055
<br />(c) - hinge approach, pull side (d) - hinge approach, pull side
<br />c 22 min D c \
<br />sso I
<br />N 12 min * � F \ 24 min
<br />v � v \ sho
<br />0!
<br />(f)5latch
<br />min. (1370) if closer I de
<br />4provided
<br />(e) - hinge approach, push side 24 min E 8
<br />` If both closer and latch are provided 510 �v
<br />** 48" min. (1220) if both closer and
<br />latch provided
<br />Fig. 404.2.4.1 (g)7min
<br />approach rser
<br />h side
<br />Maneuvering Clearance at * 41 0) if provided
<br />Manual Swinging Doors
<br />Fig. 404.2.6
<br />Two Doors in a Series
<br />= 1M.
<br />(c)
<br />NLO
<br />E
<br />Vf
<br />00
<br />00
<br />`_
<br />N
<br />•
<br />q
<br />FENEI
<br />h N
<br />d L
<br />Z
<br />O
<br />H
<br />U)
<br />W
<br />0
<br />W
<br />Q
<br />W
<br />aaa i
<br />L0J
<br />J
<br />L.0
<br />W
<br />Z
<br />W
<br />ISSUED FOR:
<br />PERMIT
<br />03.14.19
<br />BID
<br />03.14.19
<br />CONSTRUCTION
<br />00.00.00
<br />REVIEW SET
<br />03.14.19
<br />PROJECT MANAGER DESIGNER
<br />SS SS
<br />E: JOB NO.
<br />18390