D <br />in <br />SECTION 260100 ELECTRICAL GENERAL PROVISIONS <br />A. THE PROVISIONS OF THE INSTRUCTION TO BIDDERS, GENERAL CONDITIONS, <br />SUPPLEMENTARY CONDITIONS, ALTERNATES, ADDENDA, AND DIVISION 1 ARE A <br />PART OF THIS SPECIFICATION. A REQUIREMENT OCCURRING IN ONE IS AS <br />BINDING AS THOUGH OCCURRING IN ALL. THEY ARE INTENDED TO BE <br />COMPLEMENTARY AND TO DESCRIBE AND PROVIDE FOR A COMPLETE WORK. <br />CONTRACTORS AND SUBCONTRACTORS SHALL EXAMINE SAME AS WELL AS <br />OTHER DIVISIONS OF THE SPECIFICATIONS WHICH AFFECT WORK UNDER THIS <br />DIVISION. <br />B. MATERIAL OR LABOR WHICH IS NOT INDICATED ON THE DRAWINGS OR <br />SPECIFICATION BUT WHICH IS OBVIOUSLY NECESSARY TO COMPLETE THE WORK <br />(AND IS USUALLY INCLUDED IN SIMILAR WORK) SHALL BE PROVIDED. DRAWINGS <br />AND SPECIFICATIONS ARE TO BE CONSIDERED AS SUPPLEMENTING EACH <br />OTHER. WORK SPECIFIED BUT NOT INDICATED, OR INDICATED BUT NOT <br />SPECIFIED, SHALL BE PROVIDED AS THOUGH MENTIONED IN BOTH <br />SPECIFICATIONS AND DRAWINGS. <br />C. IN THE EVENT OF DISCREPANCIES BETWEEN THE CONTRACT DOCUMENTS <br />(DRAWINGS AND SPECIFICATIONS), THE CONTRACTOR SHALL ADHERE TO THE <br />MORE STRINGENT REQUIREMENT. <br />D. VISIT THE SITE OF THE WORK AND BECOME FAMILIAR WITH CONDITIONS <br />AFFECTING THE INSTALLATION. SUBMISSION OF A PROPOSAL SHALL <br />PRESUPPOSE KNOWLEDGE OF SUCH CONDITIONS AND NO ADDITIONAL <br />COMPENSATION SHALL BE ALLOWED WHERE EXTRA LABOR OR MATERIALS ARE <br />REQUIRED BECAUSE OF IGNORANCE OF THESE CONDITIONS. <br />E. DEFINITIONS <br />1. "CONTRACTOR" AS USED WITHIN THE ELECTRICAL SPECIFICATIONS SHALL <br />REFER TO THE ELECTRICAL CONTRACTOR. <br />2. "EQUAL" OR "EQUIVALENT" SHALL BE UNDERSTOOD TO MEAN OF THE SAME <br />QUANTITY, SIZE, NUMBER, VALUE, DEGREE, INTENSITY AND THE ITEMS ARE <br />SIMILAR IN ALL RESPECTS. THE ENGINEER WILL MAKE THE FINAL DECISION <br />OF ACCEPTANCE OF THESE ITEMS. <br />3. "CONTRACT DOCUMENTS" SHALL BE UNDERSTOOD TO ENCOMPASS <br />DRAWINGS AND SPECIFICATIONS FOR ARCHITECTURAL, STRUCTURAL, CIVIL, <br />MECHANICAL, ELECTRICAL AND ALL OTHER PERTINENT DISCIPLINES. <br />4. "PROVIDE" SHALL BE INTERPRETED TO MEAN THE CONTRACTOR SHALL <br />FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SUPPLIES INCLUDING <br />TESTS AND INSPECTIONS NECESSARY TO INSTALL, CONNECT, APPLY, ERECT, <br />CONSTRUCT, AND PLACE IN OPERATING CONDITION. <br />5. "FURNISH" SHALL BE INTERPRETED TO MEAN THE CONTRACTOR SHALL <br />SUPPLY AND DELIVER TO THE JOB SITE SPECIFIED MATERIAL, EQUIPMENT, <br />AND SUPPLIES. <br />6. "INSTALL" SHALL BE INTERPRETED TO MEAN ASSEMBLING, PLACING, <br />ERECTING, WIRING AND TO MAKE FULLY OPERATIONAL. <br />F. INCLUDE ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, TRANSPORTATION, <br />INSURANCE, TEMPORARY PROTECTION, SUPERVISION, SERVICES FOR THE <br />PROPER COMPLETION OF ALL ELECTRICAL WORK. ITEMS OMITTED, BUT <br />NECESSARY TO MAKE THE ELECTRICAL SYSTEM COMPLETE AND WORKABLE, <br />SHALL BE UNDERSTOOD TO FORM PART OF THE WORK. SECURE AND PAY FOR <br />ALL PERMITS AND INSPECTIONS REQUIRED AND TURN OVER ALL CERTIFICATES <br />OF APPROVAL TO THE OWNER. <br />G. TEMPERATURE CONTROLS ARE PROVIDED AND WIRED BY A CONTROLS <br />CONTRACTOR PER MECHANICAL SPECIFICATIONS. LINE VOLTAGE (120 VOLT) <br />CONTROL DEVICES SUCH AS THERMOSTATS AND AQUA STATS THAT CONTROL <br />FRACTIONAL HORSEPOWER, 120V MOTOR SHALL BE PROVIDED BY THE <br />MECHANICAL CONTRACTOR AND SHALL BE WIRED BY THE ELECTRICAL <br />CONTRACTOR. <br />H. WORK SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE PROVISIONS <br />OF LOCAL AND STATE CODES AS WELL AS THE NATIONAL ELECTRICAL CODE <br />(NEC), AS INTERPRETED BY THE LOCAL AUTHORITY HAVING JURISDICTION. <br />1. AFTER INSTALLATION BUT PRIOR TO ENERGIZATION, PERFORM TESTS FOR <br />GROUNDS, SHORT CIRCUITS AND PROPER FUNCTION. FAULTS IN THE <br />INSTALLATION SHALL BE CORRECTED. <br />J. PROVIDE NAMEPLATES ON PANEL BOARDS, DISTRIBUTION PANELS, MOTOR <br />STARTERS, SAFETY SWITCHES, CONTROL PANELS, CONTROL DEVICES, <br />JUNCTION AND PULL BOXES. LETTERING SHALL INCLUDE NAME OF EQUIPMENT, <br />HORSEPOWER, VOLTAGE RATING AND SERVICE DESIGNATION. NAMEPLATES <br />SHALL BE LAMINATED PHENOLIC WITH A BLACK SURFACE AND WHITE CORE. <br />NAMEPLATES MAY BE ATTACHED TO WALL ADJACENT TO EQUIPMENT IF AREA <br />FOR ATTACHMENT IS TOO SMALL. IDENTIFICATION WITH A DYMO TYPE <br />INSTRUMENT IS NOT PERMISSIBLE. <br />K. BEFORE FINAL PAYMENT, DEMONSTRATE TO THE OWNER'S SATISFACTION THE <br />PROPER OPERATION OF EACH OF THE SYSTEMS COMPRISING THIS CONTRACT. <br />INSTRUCT THE OWNER'S MAINTENANCE PERSONNEL IN THE OPERATION AND <br />MAINTENANCE OF ALL ELECTRICAL EQUIPMENT AND CONTROLS. <br />L. AFTER ALL TESTS HAVE BEEN COMPLETED, CLEAN ALL EQUIPMENT LEAVING <br />EVERYTHING IN WORKING ORDER AT THE COMPLETION OF THIS WORK. ALL <br />ELECTRICAL EQUIPMENT SHALL BE COMPLETELY CLEANED INSIDE AND OUT <br />PRIOR TO INITIAL ENERGIZING. <br />M. AVOID CUTTING INTO THE WORK OF OTHERS BY USING SLEEVES, INSERTS, <br />CHASES AND SIMILAR ITEMS NECESSARY FOR THE INSTALLATION. EXCEPT <br />WHERE OTHERWISE SPECIFIED OR NOTED ON DRAWINGS, THE ELECTRICAL <br />CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING OF THE BUILDING <br />AS REQUIRED TO INSTALL SLEEVES, INSERTS, CONDUITS AND ELECTRICAL <br />EQUIPMENT. PATCHING SHALL BE DONE BY SKILLED MECHANICS. WORK SHALL <br />MATCH THE GENERAL CONSTRUCTION WORK. ALL CUTTING SHALL BE DONE IN A <br />MANNER TO RETAIN THE STRUCTURAL INTEGRITY OF THE UNIT BEING CUT. <br />WHERE EXISTING EQUIPMENT IS REMOVED OR RELOCATED, PATCH TO MATCH <br />THE EXISTING BUILDING FINISHES (WALLS, CEILINGS, FLOORS, ETC.). <br />N. GUARANTEE ALL WORKMANSHIP AND MATERIALS PROVIDED UNDER THE <br />CONTRACT FOR ONE YEAR AFTER ACCEPTANCE BY THE OWNER AND <br />COMPLETION OF ALL PUNCH LIST ITEMS. REPAIR OR REPLACE ANY DEFECT <br />WITHOUT COST TO THE OWNER. <br />O. PROVIDE TEMPORARY ELECTRIC SERVICE OF SUFFICIENT CAPACITY TO SUPPLY <br />THE ELECTRIC LIGHT AND POWER REQUIREMENTS OF CONSTRUCTION SITE. <br />SECTION 260500 BASIC MATERIALS AND METHODS <br />A. EQUIPMENT AND MATERIAL USED ON THIS PROJECT SHALL BE NEW AND U.L. <br />LABELED FOR -THE APPLICATION. <br />B. DEDICATED EQUIPMENT SPACE SHALL BE PROVIDED FOR PANELBOARDS. <br />PRIOR TO INSTALLING PANELBOARDS AND THEIR ASSOCIATED <br />INCOMING/DISTRIBUTION FEEDERS AND BRANCH CIRCUITS, CONTRACTOR <br />SHALL COORDINATE PANELBOARD LOCATIONS WITH HVAC AND PLUMBING <br />CONTRACTORS TO ENSURE DEDICATED SPACE IS MAINTAINED PER NEC <br />ARTICLE 110.26. <br />C. CONDUIT SHALL BE RIGID GALVANIZED, OR EMT. ALL OTHER INTERIOR <br />CONDUITS SHALL BE EMT. CONDUITS SHALL BE 3/4" TRADE SIZE MINIMUM, <br />UNLESS OTHERWISE NOTED ON THE DRAWINGS OR IN THESE <br />SPECIFICATIONS. <br />D. MAKE CONDUIT CONNECTIONS TO MOTORS AND TRANSFORMERS WITH <br />FLEXIBLE METAL CONDUIT, AS SPECIFIED HEREIN, OF THE SAME SIZE AS THE <br />FEEDER CONDUIT, AND MAKE SUCH CONNECTION AS SHORT AS PRACTICAL. <br />E. WIRE AND CABLE FOR POWER AND LIGHTING FEEDERS LARGER THAN #6AWG <br />SHALL BE COPPER STRANDED 600 VOLT TYPE THHN/THWN OR XHHW COPPER. <br />WIRE AND CABLE FOR POWER AND LIGHTING BRANCH CIRCUITS SHALL BE <br />THHN/THWN COPPER FOR #10 AND SMALLER AND THHW OR XHHW COPPER <br />FOR #8 AND LARGER. MINIMUM WIRE SIZE FOR POWER AND LIGHTING <br />CIRCUITS SHALL BE #12. <br />F. METAL CLAD (TYPE MC) CABLE OR ARMORED (TYPE AC) CABLE MAY BE <br />UTILIZED, ONLY IF LOCAL JURISDICTION ALLOWS, IN LIEU OF BRANCH CIRCUIT <br />EMT CONDUIT. INSTALLATION OF MC CABLE SHALL COMPLY WITH ARTICLE <br />330 OF THE NATIONAL ELECTRICAL CODE. ALL BRANCH CIRCUIT HOMERUNS <br />SHALL BE INSTALLED IN TYPE EMT CONDUITS WITHIN THE CEILING SPACE TO <br />RESPECTIVE PANELBOARDS. WIRING SHALL BE AS SPECIFIED ELSEWHERE IN <br />THIS SECTION. A GREEN EQUIPMENT GROUNDING CONDUCTOR SHALL BE <br />PROVIDED IN ALL MC CABLE OR AC CABLE SYSTEMS. <br />G. ALL BOXES SHALL BE RIGIDLY SUPPORTED FROM BUILDING STRUCTURE <br />INDEPENDENT OF THE CONDUIT SYSTEM. ALL BOXES SHALL BE 4" SQUARE <br />BOXES MINIMUM WITH RAISED COVERPLATE SUITABLE FOR WALL MATERIAL <br />TO ALLOW -BOX TO BE FLUSH. <br />H. LOCAL LIGHT SWITCHES SHALL BE BACK AND SIDE WIRED, 20 AMPERE, 120/277 <br />VOLTS, AC SPECIFICATION GRADE. HUBBELL #HBL-1221 SERIES. APPROVED <br />ALTERNATES: EQUIVALENT SERIES BY PASS & SEYMOUR, LEVITON, BRYANT, <br />AND ARROW HART. COLORS SHALL BE SELECTED BY ARCHITECT. <br />1. DUPLEX RECEPTACLES SHALL BE "SPECIFICATION GRADE" 20 AMPERES, 125 <br />VOLT, 3 WIRE, GROUNDING TYPE. HUBBELL #HBL 5362. APPROVED <br />ALTERNATES: EQUIVALENT SERIES BY PASS & SEYMOUR, LEVITON, BRYANT, <br />ARROW HART. <br />J. INDOOR AND OUTDOOR RECEPTACLES, WHERE REQUIRED BY LOCAL CODE, <br />SHALL HAVE INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER OR GROUND <br />FAULT CIRCUIT INTERRUPTER CIRCUIT BREAKER PROTECTION. GROUND <br />FAULT CIRCUIT INTERRUPTER RECEPTACLES, WHERE REQUIRED, SHALL BE <br />HUBBELL #GF5362. <br />K. ALL COVER PLATES SHALL BE SMOOTH HIGH IMPACT COMMERCIAL GRADE <br />THERMOPLASTIC OR SMOOTH NYLON WHITE FINISH. IN UNFINISHED AREAS, <br />USE CADMIUM PLATED, ROUND CORNER, STEEL COVER PLATES FOR <br />SURFACE MOUNTED OUTLET BOXES. BOTH THE WIRING DEVICES AND THE <br />COVER PLATES SHALL BE BY THE SAME MANUFACTURER. <br />L. SAFETY SWITCHES SHALL BE HEAVY-DUTY UNFUSED OR FUSED AND SHALL <br />BE INSTALLED WHERE INDICATED ON THE DRAWINGS AND/OR WHERE <br />REQUIRED BY CODE AND SHALL BE SUITABLE FOR VOLTAGE AND CURRENT <br />RATING AS SHOWN ON THE DRAWINGS. ACCEPTABLE MANUFACTURERS <br />SHALL BE: SQUARE D, GENERAL ELECTRIC, EATON/CUTLER-HAMMER, OR <br />SIEMENS. <br />M. ALL CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS <br />SHALL BE PROTECTED BY MATERIALS TESTED IN ACCORDANCE WITH <br />UL1479/ASTM E-814. INSTALLATION SHALL FOLLOW MANUFACTURER'S <br />INSTRUCTIONS AND MAINTAIN THE FIRE RATING OF WALLS AND/OR FLOORS <br />AFFECTED. PROVIDE HILTI C5240 FIRESTOP SEALANT, CSFM LISTING NO. <br />4060-1200:100, OR EQUIVALENT STATE FIRE MARSHAL APPROVED AND LISTED <br />MATERIAL. <br />SECTION 260529 GROUNDING AND BONDING <br />A. GROUND ALL CONDUITS, CABINETS, MOTORS, PANELS, FIXTURES, AND OTHER <br />EXPOSED NON -CURRENT CARRYING METAL PARTS OF ELECTRICAL EQUIPMENT <br />IN ACCORDANCE WITH ALL PROVISIONS OF THE NATIONAL ELECTRIC CODE AND <br />LOCAL CODES. <br />B. GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF AN <br />INSULATED GROUNDING CONDUCTOR INSTALLED WITH CIRCUIT CONDUCTORS IN <br />ALL CONDUITS. GROUNDING CONDUCTORS SHALL BE SIZED IN ACCORDANCE <br />WITH N.E.C. 250.122 AND SHALL RUN FROM GROUNDING BUS OF SERVING PANEL <br />TO GROUND BUS OF SERVED PANEL, GROUNDING TERMINAL OF RECEPTACLES, <br />LIGHTING FIXTURE HOUSINGS, GROUNDING TERMINAL OF LIGHT SWITCHES OR <br />METAL ENCLOSURES OF SERVED EQUIPMENT. <br />C. INSTALL BONDING JUMPERS ACROSS ALL BUILDINGS, EXPANSION JOINTS, AND <br />ACROSS CONDUIT EXPANSION FITTINGS. <br />SECTION 260573 FAULT CURRENT, COORDINATION STUDY, AND ARC FLASH <br />A. ELECTRICAL CONTRACTOR SHALL CONDUCT A FAULT CURRENT CALCULATION <br />AND COORDINATION STUDY TO ENSURE THE CORRECT AIC RATING OF NEW <br />ELECTRICAL EQUIPMENT INCLUDING SWITCHBOARDS, DISTRIBUTION PANELS, <br />BRANCH CIRCUIT PANELBOARDS, ETC. AND TO DETERMINE THE APPROPRIATE <br />SETTINGS OF ANY ADJUSTABLE BREAKERS. THE RESULTS OF THESE STUDIES <br />SHALL BE SUBMITTED WITH THE ELECTRICAL EQUIPMENT SHOP DRAWINGS. <br />B. ELECTRICAL CONTRACTOR SHALL PROVIDE AN ARC -FLASH STUDY AND LABEL <br />ALL EQUIPMENT AS REQUIRED PER THE N.E.C. <br />SECTION 262416 BRANCH CIRCUIT BREAKER PANELS <br />B. PANELBOARD BUS STRUCTURE AND MAIN LUG/MAIN CIRCUIT BREAKER SHALL <br />HAVE THE CURRENT RATING AS SHOWN ON THE CONTRACT DRAWINGS. <br />C. PANELBOARD BUSSING SHALL BE COPPER, (TIN-PLATED COPPER). <br />D. BUS BAR CONNECTIONS SHALL ACCEPT BOLT -ON CIRCUIT BREAKERS. <br />PANELBOARDS SHALL BE DEAD FRONT SAFETY TYPE. <br />E. BUS BARS SHALL HAVE ANTI -TURN SOLDERLESS LUG CONNECTIONS FOR <br />ATTACHING FEEDERS. <br />F. PANELBOARDS SHALL BE EQUIPPED WITH CIRCUIT BREAKERS OF THE FRAME <br />& TRIP RATING AS SPECIFIED HEREIN & AS SHOWN ON THE CONTRACT <br />DRAWINGS. <br />G. WHERE MULTI -POLE CIRCUIT BREAKERS ARE REQUIRED, THEY SHALL BE <br />COMMON TRIP TYPE. <br />H. ALL PANELBOARDS SHALL BE LOCKABLE AND KEYED ALIKE. <br />I. PANEL ENCLOSURES SHALL BE AT LEAST 20 INCHES WIDE. <br />J. CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC, MOLDED CASE BOLT -ON <br />TYPE. <br />K. PROVIDE A SEPARATE NEUTRAL CONDUCTOR PROPERLY SIZED FOR EVERY <br />BRANCH CIRCUIT. SHARING OF A NEUTRAL CONDUCTOR BETWEEN MULTIPLE <br />CIRCUITS SHALL NOT BE PERMITTED. <br />L. BRANCH CIRCUIT PANELBOARDS (AS A COMPLETE UNIT, INCLUDING <br />BREAKERS) SHALL HAVE A MINIMUM SHORT CIRCUIT RATING OF 208(240Y120 - <br />22,000 AIC FOR BIDDING PURPOSES, UNLESS OTHERWISE NOTED. AIC <br />RATINGS SHALL BE MODIFIED AS REQUIRED TO MEET OR EXCEED THE <br />AVAILABLE FAULT CURRENT AT THEIR CONNECTION POINT(S) AS A RESULT OF <br />THE FAULT CURRENT STUDY REPORT. <br />M. PANELBOARDS SHALL BE LISTED BY UNDERWRITERS LABORATORIES AND <br />BEAR THE "UL" LABEL. PANELBOARDS SHALL BE MANUFACTURED BY SQUARE <br />D, SIEMENS, GENERAL ELECTRIC, OR EATON/CUTLER-HAMMER. <br />N. WHEN WORK IS COMPLETE, BALANCE THE CONTINUOUS LOAD ON EACH <br />PHASE OF ALL PANELBOARDS. <br />O. A GLAZED DIRECTORY FRAME SHALL BE PROVIDED INSIDE THE DOOR AND <br />SHALL BE OF SUFFICIENT SIZE TO GIVE DESCRIPTION OF EACH CIRCUIT. <br />TYPED DIRECTORY CARDS SHALL BE PROVIDED LISTING EACH CIRCUIT <br />SERVED. <br />P. PROVIDE ENGRAVED NAMEPLATE MATCHING PANELBOARD DESIGNATION ON <br />THE DRAWINGS. <br />SECTION 262413 CIRCUIT BREAKER DISTRIBUTION PANELS <br />A. DISTRIBUTION PANELBOARD BUS STRUCTURE AND MAIN LUGS/MAIN CIRCUIT <br />BREAKER SHALL HAVE THE CURRENT RATING AS SHOWN ON THE CONTRACT <br />DRAWINGS. BUS BAR CONNECTION SHALL ACCEPT BOLT -ON CIRCUIT <br />BREAKERS. <br />B. DISTRIBUTION PANELBOARD SHALL BE OF THE FULLY RATED DEAD FRONT <br />SAFETY TYPE. <br />C. BUS BARS SHALL HAVE ANTI -TURN SOLDERLESS LUG CONNECTIONS FOR <br />ATTACHING FEEDERS. <br />D. PROVIDE DISTRIBUTION PANELBOARD EQUIPPED WITH CIRCUIT BREAKERS OF <br />THE FRAME AND TRIP RATING AS SPECIFIED HEREIN AND AS SHOWN ON THE <br />CONTRACT DRAWINGS. <br />E. WHERE MULTI -POLE CIRCUIT BREAKERS ARE REQUIRED, THEY SHALL BE <br />COMMON TRIP TYPE. <br />F. ALL PANELBOARDS SHALL BE LOCKABLE AND KEYED ALIKE. <br />G. DISTRIBUTION PANEL ENCLOSURES SHALL BE 32" WIDE BY 12.75" DEEP. <br />TOTAL AVAILABLE CIRCUIT SPACE SHALL BE 45" WITH FULL LENGTH BUSSING. <br />H. DISTRIBUTION PANELBOARD BUSSING SHALL BE COPPER, (TIN-PLATED <br />COPPER). <br />I. MULTIPLE SECTION PANELBOARDS SHALL COMPRISE OF MATCHING <br />ENCLOSURES, SIZED IDENTICALLY AND ABUTTED TO ONE ANOTHER. COVERS <br />AND TRIMS SHALL BE IDENTICAL AND SUITABLE FOR SURFACE TUBS. <br />J. CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC, MOLDED CASE, -BOLT-ON- <br />TYPE. <br />K. DISTRIBUTION PANELBOARD (AS A COMPLETE UNIT, INCLUDING BREAKERS) <br />SHALL HAVE MINIMUM SHORT CIRCUIT RATING OF: 208/12OV : (65,000) AIC. <br />L. PROVIDE UNINSULATED GROUND BUSSING WITH NECESSARY QUANTITY OF <br />TERMINALS TO ACCEPT GROUNDING CONDUCTORS. <br />M. PROVIDE A (100%) RATED NEUTRAL BUSSING WITH NECESSARY QUANTITY TO <br />TERMINALS TO ACCEPT NEUTRAL CONDUCTORS. <br />N. DISTRIBUTION PANELBOARDS SHALL BE LISTED BY UNDERWRITERS <br />LABORATORIES AND BEAR THE "UL" LABEL. PANELBOARDS SHALL BE <br />MANUFACTURED BY SQUARE D, SIEMENS, GENERAL ELECTRIC OR EATON <br />ELECTRIC (CUTLER -HAMMER). <br />O. DISTRIBUTION PANELBOARDS SHALL BE WALL MOUNTED AS INDICATED ON <br />THE DRAWINGS. DISTRIBUTION PANELBOARDS SHALL BE MOUNTED SO THAT <br />THE HIGHEST CONTROL DEVICE IS BELOW 6'-7" FROM THE FLOOR. <br />P. PROVIDE NAMEPLATES FOR EACH BRANCH DEVICE TO GIVE DESCRIPTION OF <br />EACH CIRCUIT OR FEEDER. <br />Q. PROVIDE ENGRAVED NAMEPLATE MATCHING PANELBOARDS DESIGNATION ON <br />THE DRAWINGS. <br />SECTION 265100 LIGHTING <br />A. FLUORESCENT FIXTURES SHALL HAVE THERMALLY PROTECTED, HIGH POWER <br />FACTOR (>99%), U.L. LISTED, CLASS P, CBM, ETL, AND CSA CERTIFIED, ONE, TWO, <br />THREE, AND/OR FOUR LAMP (AS REQUIRED), RAPID START, PARALLEL, HIGH <br />FREQUENCY, T-8, ELECTRONIC (<10% THD) BALLASTS, WITH 5 YEAR MINIMUM <br />WARRANTY. APPROVED MANUFACTURERS SHALL BE MAGNETEK/TRIAD HP, OR <br />ADVANCE CENTIUM. <br />B. COMPACT FLUORESCENT AND/OR T-5 FLUORESCENT FIXTURES SHALL HAVE <br />THERMALLY PROTECTED, HIGH POWER FACTOR (>98%), U.L. LISTED, CLASS P, <br />CBM, ETL, AND CSA CERTIFIED, ONE, TWO, AND/OR THREE LAMP (AS REQUIRED), <br />RAPID START, PARALLEL, HIGH FREQUENCY, ELECTRONIC (<20%) BALLASTS. <br />APPROVED MANUFACTURERS SHALL BE MOTOROLA, ENERGY SAVING INC., OR <br />ROBERTSON. <br />C. LAMPS <br />1. PROVIDE ALL LAMPS REQUIRED. AT THE CONCLUSION OF THE WORK, EACH <br />FIXTURE MUST BE EQUIPPED WITH THE PROPER NUMBER OF NEW LAMPS OF <br />THE CORRECT SIZE AND TYPE, ALL IN GOOD OPERATING CONDITION. <br />2. INCANDESCENT LAMPS SHALL BE 130 VOLT ONLY. <br />3. FLUORESCENT LAMPS SHALL BE T-8, SP35 MEDIUM BI-PIN LAMPS WITH A <br />CRI-85 TRI-PHOSPHOR COATING. APPROVED FLUORESCENT LAMP <br />MANUFACTURERS SHALL BE G.E., PHILIPS, OR OSRAM/SYLVANIA. <br />D. WHERE LIGHTING FIXTURES ARE INSTALLED IN LAY -IN CEILINGS, EACH FIXTURE <br />SHALL BE PROVIDED WITH CLIPS (4 REQUIRED) OR EQUIVALENT MEANS TO <br />PREVENT THE ACCIDENTAL DISENGAGEMENT OF THE FIXTURE FROM THE <br />CEILING SUPPORT OR "T-BAR". IN ADDITION, ALL FLUORESCENT LIGHTING <br />FIXTURES SHALL BE SUPPORTED AT EACH CORNER WITH FOUR (4) #12 AWG <br />GALVANIZED STEEL WIRES AND SECURED TO THE BUILDING STRUCTURE IN <br />ACCORDANCE WITH N.E.C. REQUIREMENTS. <br />A. PERFORMANCE REQUIREMENTS: COMPLY WITH TIA/EIA-568-B.1 <br />B. COMPLY WITH NFPA 70, "NATIONAL ELECTRICAL CODE." <br />C. COMPLY WITH THE TIA-EIA-569-A, "COMMERCIAL BUILDING STANDARD FOR <br />TELECOMMUNICATIONS PATHWAYS AND SPACES." <br />D. COMPLY WITH ANSI-J-STD-607-A, "COMMERCIAL BUILDING GROUNDING <br />(EARTHING) AND BONDING REQUIREMENTS FOR TELECOMMUNICATIONS." <br />E. COORDINATE LAYOUT AND INSTALLATION OF TELECOMMUNICATIONS <br />PATHWAYS AND CABLING WITH TENANTS TELECOMMUNICATIONS AND LAN <br />EQUIPMENT AND SERVICE SUPPLIERS. <br />F. COORDINATE TELECOMMUNICATIONS OUTLET/CONNECTOR LOCATIONS WITH <br />LOCATION OF POWER RECEPTACLES AS EACH WORK AREA. <br />G. CABLE SUPPORT: NRTL LABELED FOR SUPPORT OF CATEGORY 6 CABLING, <br />DESIGNED TO PREVENT DEGRADATION OF CABLE PERFORMANCE AND PINCH <br />POINTS THAT COULD DAMAGE CABLE. <br />H. CONDUIT AND BOXES: SHALL BE A MINIMUM OF 2" W X 3" H X 2-1/2" DEEP. <br />I. BACKBOARDS SHALL BE 3/4" X 48" X 96" WITH TWO (2) COATS OF GRAY <br />FIRE -RETARDANT PAINT ON ALL SIDES AND EDGES AND SHALL BE MOUNTED <br />VERTICALLY. <br />J. ALL COMMUNICATION CABLING SHALL BE CATEGORY 5E, PLENUM RATED, AND <br />MANUFACTURED BY WEST PENN, OR APPROVED EQUIVALENT. <br />K. ALL COMMUNICATION CABLES ROUTED IN UNFINISHED SPACES ALONG WALLS <br />SHALL BE ROUTED IN EXPOSED CONDUIT. ALL COMMUNICATION CABLING <br />ROUTED IN UNFINISHED SPACES ALONG CEILINGS SHALL BE SUPPORTED <br />WITH CABLE SUPPORTS SUCH AS J-HOOKS A MINIMUM OF 4'-0" ON CENTER. <br />L. ALL COMMUNICATION CONDUITS SHALL BE PROVIDED WITH RADIUS ELBOWS <br />SIZE AS RECOMMENDED BY CABLING MANUFACTURER TO ENSURE THAT <br />CABLING INSULATION IS NOT DAMAGED DURING INSTALLATION. <br />M. ALL COMMUNICATION CABLING INSTALLED IN FINISHED SPACES WITH <br />EXPOSED CEILING STRUCTURE SHALL BE ROUTED IN CONDUIT AND <br />CONCEALED IN NEW WALL CONSTRUCTION. ALL COMMUNICATION CONDUITS <br />ROUTED ALONG CEILING STRUCTURE SHALL BE INSTALLED AT 4" MINIMUM <br />FROM CEILING, SUPPORTED EVERY 6-0" AND SHALL BE ROUTED PARALLEL OR <br />PERPENDICULAR TO WALLS. <br />N. ALL COMMUNICATION CABLING INSTALLED IN FINISHED SPACES WITH LAY -IN <br />CEILINGS SHALL BE INSTALLED IN CONDUIT AND CONCEALED IN NEW WALL <br />CONSTRUCTION AND STUBBED ABOVE ACCESSIBLE CEILING. SUPPORT <br />EVERY 4'-0" MAXIMUM WITH J-HOOKS OR OTHER METHOD TYPICALLY USED AS <br />AN INDUSTRY STANDARD. <br />O. PROVIDE PLASTIC BUSHING ON EACH END OF CONDUIT RUN. <br />P. SURFACE RACEWAY SHALL ONLY BE PERMITTED TO BE INSTALLED IN <br />FINISHED AREAS IF SPECIFICALLY APPROVED BY ARCHITECT IN ADVANCE OF <br />COMMENCING WORK. <br />Q. IDENTIFICATION PRODUCTS SHALL COMPLY WITH TIA/EIA 606-a, AND SHALL <br />MEET UL 969 FOR LABELING MATERIALS, INCLUDING LABEL STOCKS, <br />LAMINATING ADHESIVES, AND INKS USED BY LABEL PRINTERS. <br />R. PROVIDE MACHINE PRINTED ADHESIVE TAPE LABEL ON EACH END OF <br />COMMUNICATION CABLE WITH IDENTIFICATION TAGGING REQUIRED BY <br />TENANT. LABELS SHALL BE PRINTED WITH PRINTING AREA AND TYPE COLOR <br />THAT IS CONTRASTING WITH CABLE JACKET COLOR, BUT STILL COMPLYING <br />WITH TIVEIA-606-A. <br />S. PROVIDE SINGLE -GANG DEEP BACKBOX AT ALL WALL PHONE DEVICE <br />LOCATIONS AND ROUTE 3/4" CONDUIT BACK TO SOURCE. <br />T. PROVIDE TWO -GANG DEEP BACKBOX AT ALL OTHER DATA OUTLET <br />BACKBOXES AND ROUTE 1" MINIMUM CONDUIT TO EACH. <br />U. INSTALLATION OF CABLES SHALL COMPLY WITH TIA-EIA-B.1 AND <br />TIA/EIA-568.B.2. <br />V. PROVIDE COMMUNICATION OUTLETS AS DIRECTED BY TENANT (SUCH AS <br />OUTLETS WITH RJ45 CONFIGURATION) WITH ASSOCIATED FACEPLATES. <br />PROVIDE TERMINATIONS REQUIRED TO COMPLY WITH BICSI ITSIM, CH. 6, <br />"CABLE TERMINATION PRACTICES." <br />W. CONSOLIDATION POINTS FOR CABLING MAY BE USED ONLY FOR MAKING A <br />DIRECT CONNECTION TO TELECOMMUNICATIONS OUTLET/CONNECTORS. <br />X. TERMINATE CONDUCTORS; NO CABLE SHALL CONTAIN UNTERMINATED <br />ELEMENTS. MAKE TERMINATIONS ONLY AT INDICATED OUTLETS, TERMINALS, <br />AND CROSS -CONNECT AND PATCH PANELS. <br />Y. CABLES MAY NOT BE SPLICED. SECURE AND SUPPORT CABLES AT INTERVALS <br />NOT EXCEEDING 30" AND NOT MORE THAN 6" FROM CABINETS, BOXES, <br />FITTINGS, OUTLETS, RACKS, FRAMES, AND TERMINALS. <br />Z. AFTER COMPLETION OF ALL COMMUNICATION CABLING, CONTRACTOR SHALL <br />CONDUCT ALL TESTING REQUIRED AND SHALL RECORD RESULTS OF THE <br />TEST AND PROVIDE TO TENANT FOR FUTURE REFERENCE. ANY DEFICIENCIES <br />FOUND SHALL BE RECORDED AND ANY CORRECTIVE MEASURES COMPLETED <br />SHALL ALSO BE NOTED ON THE REPORT. <br />AA. CONTRACTOR SHALL PROVIDE ALL OUTLETS WITH CONFIGURATIONS AS <br />SELECTED BY TENANT. ALL OUTLETS SHALL BE PROVIDED WITH MATCHING <br />FACEPLATES AND PROPER ICON IDENTIFICATION TABS FOR FACEPLATES. <br />1--lo kam� <br />ENTECH <br />ENGINEERING INC. <br />5301 VIRGINIA WAY SUITE 140 <br />BRENTWOOD, TN 37027 <br />v. 615.373.2640 f. 615.373.4837 <br />email®entechtn.com entechtn.com <br />_O <br />H <br />a_ <br />U) <br />W <br />W <br />H <br />Q <br />W <br />WAN 2R�PF a <br />WE Or <br />'•.. UL•• <br />3115119 <br />N <br />LLo <br />M <br />_J <br />J <br />~�J <br />_ _ <br />W �- <br />N= <br />w <br />N <br />U) <br />J z <br />Q0 <br />U�- <br />I..L Q <br />�0 <br />ULL <br />Wv <br />W m <br />W <br />ISSUED FOR: <br />PERMIT 03.14.19 <br />BID 03.14.19 <br />CONSTRUCTION - <br />REVIEW SET - <br />PROJECT MANAGER DESIGNER <br />JOB NO. <br />18390 <br />ES1 mO <br />