Laserfiche WebLink
STRUCTURAL GENERAL NOTES - FBC 2014 <br />O <br />r <br />0 <br />1. GENERAL <br />a.Provide construction conforming to the 2014 Florida Building Code. Reference to other standards, <br />specifications, or codes means the latest standard or code published and adopted. <br />b.Materiai tests and inspections are required per Chapter 17 of the 201.7 International Building Code. <br />Refer to the project Statement of Special Inspections for required tests and inspections. Special <br />inspection reports and a final report in accordance with Section 1704,1.2 of the 2014 Florida Building <br />Code at the time the building is approved fear occupancy. <br />c, The structural general notes apply except where indicated otherwise on the drawings or in the <br />specifications. A detail shown for one condition applies for all like or similar conditions even though not <br />specifically indicated on the drawings. <br />d.Verify all existing conditions, dimensions, and elevations before starting work. Notify the Architect and <br />Structural Engineer- of Record in writing of any discrepancy. <br />e.The Contractor is solely responsible for the design, adequacy, and safety of erection bracing, shoring, <br />temporary supports, and all other means, methods, techniques, sequences, and procedures of <br />construction. <br />f. Coordinate the structural contract documents with architectural, mechanical, electrical, plumbing, civil, <br />and all other consultants. Notify the Architect and Structural Engineer of Record in writing of any conflict <br />and/ or omission. <br />• :z r <br />g.Coordinate and verify floor and roof opening sizes and locations with architectural, mechanical, plumbing, <br />and electrical drawings. For additional openings not shown on the structural drawings refer to the <br />architectural and mechanical drawings. <br />h. Review of the submittals and/or shop drawings by the Structural Engineer of Record is only for general <br />conformance with the contract documents and does not relieve the Contractor of the responsibility to <br />review and check shop drawings before submittal to the Structural Engineer of Record. The Contractor <br />must review and stamp all submittals prior to submission. The Contractor remains solely responsible for <br />� � tuber sizes <br />errors and omissions associated with the preparation of shop drawings as they pertain to me , <br />details, and dimensions specified in the contract documents. Do not begin fabrication until shop <br />drawings are completed and reviewed by the Structural Engineer of Record. <br />r . <br />.: , r-c` documents or referencing the contract <br />i. Do not make shop drawings using. reproductions or thy, contract a � do_ g <br />documents. <br />2. EXISTING CONDITIONS <br />a.Renovation of existing structures requires thorough coordination of the contract documents with existing <br />conditions. The Contractor must verify all relevant existing conditions, dimensions, and details prior to <br />beginning construction. Report any deviations from conditions or dimensions shown on the contract <br />documents to the Architect and Structural Engineer of Record for review of the design and possible <br />revision of the contract documents. <br />b. The nature of .structural demolition and stabilization is inherently uncertain. The exact condition and <br />capacity of each structural element cannot be verified prior to the commencement of work. As a result, <br />it is imperative to report any discrepancies between the contract documents and actual field conditions, <br />as well as any element of questionable structural integrity immediately to the Architect and Structural <br />Engineer of Record for review. <br />c. No attempt has been made to define each specific structural element that must be removed, enhanced, <br />or replaced. It is the responsibility of the Contractor to review the condition of individual elements, <br />Particularly rafters, joists, and structural deck boards, to determine which elements can be salvaged, <br />which elements must be replaced, and which elements are questionable. The Contractor should consult <br />with the Architect and Structural Engineer of Record to determine the appropriate procedure for handling <br />elements in questionable condition, <br />3, MASONRY <br />a.Provide concrete masonry conforming to the following standards: <br />ACI 530-11/ASCE 5-11/TMS 402-11, Building Code Requirements for Concrete Masonry Structures <br />ACI 530.1-11/ASCE 6-11/TMS 602-11, Specifications for Concrete Masonry Structures <br />b.Load bearing masonry walls are designed in accordance with Chapters 1. and 2 of ACI 530, <br />c. Brick veneer is designed in accordance with Chapter 6 of ACI 530, <br />d,Provide light -weight, hollow, load bearing concrete masonry units conforming to ASTM C 90 with a <br />compressive strength of masonry (f'm) of 1500 PSI and a net strength of 2000 PSI on the net <br />cross -sectional area of CMU determined in accordance with ASTM C :1.40, <br />e.Provide mortar conforming to ASTM C 270, Type M or S. Standard mortar bed joint thickness is 3/8" and <br />must not exceed 5/8". , <br />f. Unless noted otherwise, provide grout for reinforced masonry conforming to ASTM C 476 with minimum <br />compressive strength of 2.500 PSI. Pea gravel concrete with a rninimurn compressive strength of 3000 <br />PSI may be substituted for grout only with approval of the Structural Engineer of Record, <br />g.Uniess noted otherwise, lay masonry units in running bond. <br />h. Provide ladder type horizontal joint reinforcing conforming to ASTM A 82. Unless noted otherwise, place <br />9 gage or heavier, zinc coated ladder type horizontal joint reinforcing at 16" on center. Lap horizontal <br />joint reinforcing minimum 12". Use prefabricated 'L 's and 'T's at corners and intersections. <br />i, For grouted walls, the maximum height of grout lifts must not exceed 5'-0". The maximurn ungrouted <br />height of 8" or thicker CMU walls prior to grouting must not exceed 12'-0". Refer to Table 7 of ACI 530,1 <br />for the maximum ungrouted height of CMU walls thinner than 8". Consolidate and reconsolidate grout in <br />accordance with paragraph 3.5.E of ACI 530.1. Walls higher than 5'-0" must have inspection holes at <br />the base of the wall. <br />j. Lap vertical masonry wall reinforcing as follows: <br />#4 Bars 25„ <br />#5 Bars 31" <br />k. Provide vertical control joints in all masonry weans not retaining earth. Unless noted otherwise on the <br />architectural drawings, place vertical control joints at three times the wall height, but not closer than <br />25'-0" on center or farther than 50'-0" on center. <br />I. Unless noted otherwise, provide minimum (1) #5 vertical bar, grouted full height, at each side of <br />openings and at all corners and ends of walls, including both sides at ends of wall panels at vertical <br />control joints. <br />m. Unless noted otherwise, anchor sides and tops of masonry wall panels to the structure by dovetail <br />anchors, metal straps, or equivalent. <br />n.Place ties for brick veneers at not more than 16" vertically or 24" horizontally. <br />4. REINFORCED CONCRETE <br />a.Provide reinforced concrete conforming to the following standards: <br />ACI 301-11, Specifications for Structural Concrete for Buildings <br />ACI 318-10, Building Cade Requirements for Reinforced Concrete <br />ACI 302.1R-04, Guide for Concrete Floor and Slab Construction <br />ACI 360R-10, Design of Slabs -on -Ground <br />b. Unless noted otherwise, provide normal weight concrete with 3000 PSI compressive strength at 28 days. <br />c. Provide 411% to 6% entrained air by volume in concrete permanently exposed to weather. <br />d.Provide concrete with a maximum water-to-cementitious materials ratio of 0.50. <br />e.Fully document and submit for review the proposed materials and rnix design for all concrete. The <br />Contractor is responsible for obtaining the required design strength. All concrete test data must be <br />available at the job site. <br />f. The use of calcium chloride, chloride ions, or other salts is not permitted. <br />g.Place concrete at a slump of 5" ± 1", <br />h. Unless noted otherwise, provide construction or contraction joints in slabs -on -grade such that the <br />maximum area between joints does :lot exceed 225 square feet with the length not exceeding twice the <br />width. <br />i, Chamfer or round all exposed carriers a rninirnurn of 3/4". <br />j. Detail concrete reinforcement accor=ding to ACI SP-66 detailing ;manual. Submit shop drawings for <br />approval, showing all fabrication dimensions and locations for placing concrete reinforcing and <br />accessories. Do not begin fabrication until shop drawings are completed and reviewed by the Structural <br />Engineer of Record. Unless specifically approved otherwise, detail all concrete walls and beams in <br />elevation. <br />k. Unless noted otherwise, provide reinforcing steel conforming to ASTM A 6.15, Grade 60. <br />I. Provide welded wire fabric (mesh) in flat sheets (rolls not permitted) conforming to ASTM A 185 and <br />ASTM A 82. Lap welded wire fabric a minimum of 6" at each splice. Place welded wire fabric I" below <br />the tap of slabs -on -grade. <br />m. Fiber reinforcing may be substituted for welded wire fabric in slabs -on -grade with the approval of the <br />Structural Engineer of Record. Provide fiber reinforcing conforming to ASTM C 1116, Type III. Use only <br />1.0011/c, virgin polypropylene fibrillated fibers with a minimum of 1.5 pounds per cubic yard of concrete <br />unless otherwise directed by the fiber reinforcing manufacturer. <br />n.Unless noted otherwise, 44 n 12" o/c in 8" thick slabs on grade. Place rebar 2" below the top of the <br />slab. <br />o.Tie all. reinforcing steel and embedded items securely in place prior to placing concrete. Provide <br />sufficient supports to maintain the position of the reinforcement within specified tolerances during all <br />construction activities. "Sticking" dowels, anchor rods, or other embedded items into wet concrete is not <br />permitted, <br />p.Provide corner bars at all corners and intersections of all footings, beams, and walls. <br />q,Provide basic class "B" tension laps in all reinforcing bars indicated as continuous. <br />r. The placement of all reinforcing steel must be: reviewed by a professional engineer registered in the state <br />of Florida or by a representative responsible to him (Ref: ACI 318, 1.3.1). <br />s. Unless noted otherwise, provide the following concrete cover on all reinforcing steel: <br />Concrete against earth (not formed): <br />t. Do not place pipes or ducts with a maximum dimension exceeding one-third the slab or wall thickness <br />within the slab or wall unless specifically shown and detailed on the structural drawings. <br />u.Do not weld or tack weld reinforcing steel unless approved or directed' by the Structural Engineer of <br />Record. Provide reinforcing steel conforming to ASTM A 706, Grade 60 where welding is approved or <br />directed. <br />5, STRUCTURAL STEEL <br />a.Provide structural steel conforming to the following standards: <br />AISC Manual of Steel Construction, 14th Edition <br />AISC 360-10, Specification for Structural Steel Buildings <br />AISC 303-10, Code of Standard Practice for Structural Steel Buildings and Bridges <br />AISC 326-09, Detailing for Steel Construction, 2nd Edition <br />b. Unless noted otherwise, provide steel shapes made of material conforming to the following standards: <br />Wide flange and WT shapes: ASTM A 992 <br />Angles, plates, and channels: ASTM A 36 <br />Hollow Structural Sections (HSS): ASTM A 500, Grade B <br />c. Unless noted otherwise, provide anchor rods conforming to ASTM F 1554, Grade 36. <br />r �• f <br />d.Unless noted otherwise, make all connections with 3; 4 „ diameter AST"M A ..2.� bolts. Assemble and <br />inspect bolted connections in accordance with AISC "Specification for Joints Using .ASTM A 325 or ASTM A <br />490 Bolts", 2009, <br />e.Make all welded connections in accordance with AWS D1.1-04 "Structural Welding Code", using type <br />E70XX electrodes. Use only certified welders. Proof of certification must be maintained at the job site. <br />f. Unless specifically detailed on the contract documents, provide the following beam connections: <br />1. Where beam reactions are shown, provide connections to develop the reaction shown. <br />2. Where beam reactions are not shown, provide connections to develop one-half the total uniform load <br />capacity shown in the Maximum Total Uniform Load Tables, in Part 3 of the AISC Manual. <br />3, Where reactions are subject to eccentricity, the eccentricity must be accounted for', <br />g.Submit shop drawings prepared in accordance with AISC 326-09. Provide complete welding information <br />using AWS symbols. Use prequalified welded joints per AISC and AWS D1.1 "Structural Welding <br />r <br />t� <br />rill drawings are completed and reviewed b the Structural <br />Code." Do not begin fabrication .� shop g p y <br />Engineer of Record. <br />h.Do not use gas cutting torches to correct fabrication errors in structural steel framing. <br />i. Provide temporary bracing for structural steel framing until all permanent bracing, moment connections, <br />and floor/roof decks (diaphragms) are completely installed. <br />j. Paint structural steel in accordance with the project specifications. Do not paint steel surfaces to be <br />encased in concrete, surfaces to receive fireproofing, connections designated as friction type, surfaces to <br />be welded, or surfaces receiving welded studs or DBA's in the field. <br />k. Provide an allowance of 3% of structural/miscellaneous steel to be fabricated and placed during progress <br />of work as may be directed by the Structural Engineer of Record in addition to all steel indicated on the <br />contract documents. Credit any unused quantity at the end of the project. <br />6. OPEN WEB STEEL JOISTS, JOIST GIRDERS, AND STEEL DECKING <br />a. Provide steel joists and joist girders conforming with the fallowing standards: <br />SJI JG-1.1-10, Standard Specification for Joist Girders <br />SJI K-1.1-10, Standard Specification for Open Web Steel Joists, K-Series <br />SJI LH/DLH-1.1-10, Standard Specification for Longspan Steel Joists, LH Series and Deep Longspan <br />Steel Joists, DLH Series <br />b. Provide fabrication and erection of steel decking conforming to the following standards: <br />SDI Design Manual for Composite Decks, Form Decks, and Roof Decks <br />c. Provide bridging in accordance with SJI recommendations. Add 'X' bridging to the second panel at each <br />end of each run of horizontal bridging, and every sixth panel in between. Provide one continuous run of <br />'X' bridging near mid -span where four or more roves of bridging are required, <br />d.Unless noted otherwise, design steel joists for a minimum net uplift of 15 PSF over the entire roof area. <br />Install bridging immediately after erection and permanent fastening of joists. Install bridging before <br />construction loads are applied to joists. Permanently attach lines of bridging to walls or beams where <br />bridging terminates. Weld bridging to joists. <br />e.Coordinate joist spacing with mechanical requirements. The average space between any three joists <br />must not exceed the spacing shown on the drawings, and the spacing between any two roof joists must <br />not exceed X'-X". <br />OR <br />Support for the mechanical roof top units has been designed specifically for the unit listed on the <br />structural drawings or specified on the mechanical drawings. If any substitutions occur, notify the <br />Structural Engineer of Record immediately so that the structural support may be revised if necessary. <br />f. Provide double joists under masonry walls parallel to the joist framing for rnasonry vvalls supported on <br />steel framed floors. <br />g.Unless noted otherwise, provide double joists Linder all mechanical equipment supported by the roof. <br />h.Provide steel deck of the type and gage indicated on the design documents. <br />i. Unless noted otherwise, provide steel decking primed and painted or with a G60 galvanized coating, <br />j. Install steel decking in accordance with the manufacturers recommendation. Do not install steel decking <br />until supporting joists are braced, bridged, and permanently fastened, <br />k. Install decking such that it is continuous over a minimum of three spans. <br />I. Unless noted otherwise, fasten steel roof deck to supporting structure according to the following options: <br />(Roof exterior zones are areas of the roof within X'-X" of the roof perimeter-. All other zones are <br />interior zones.) <br />1. Fasten to Supports with #12 TEK screws in a 36/7 pattern at exterior zones and in a 36/3 pattern at interior <br />zones. Fasten side laps with #10 TEK screws at 6 inches on center at roof perimeter, (3) #10 TEK screws <br />per span at exterior zones, and (3) #10 TEK screws per span at interior zones. <br />2. Fasten to supports with 5/8" puddle melds in a 36/7 pattern at exterior zones and in a 36/3 pattern at <br />interior zones. Fasten side laps with rx10 TEK screens or 5./8" puddle welds at 6 inches on center at roof <br />perimeter, (3) # 10 TEK screws or (3) 5/8" puddle welds per span at exterior zones, and (3) #10 TEK screws <br />or (3) 5/8" puddle welds per span at interior zones. <br />7, COLD FORMED METAL FRAMING <br />a.Provide cold -farmed metal framing conforming with the following standards: <br />NAS-01, AISI North American Specification for the Design of Cold -Formed Steel Structural Members <br />b. Provide studs, runner track, and associated accessories of the type and thickness indicated on the <br />drawings or as recommended by the manufacturer for the indicated application. <br />c. Provide studs, joists, runner track, and accessories manufactured of hot clip galvanized ASTM A 1003 <br />steel with the following yield strength: <br />33,000 PSI 33-mil (20 gage) and 43-mil (18 gage) members <br />50,000 PSI 54-mil 0_6 gage), 68-mil (14 gage), and 97-mil (12 gage) members <br />d.Provide minimum S-12 screws (cadmium or zinc coated). <br />e.Install all cold --formed metal framing in accordance with the manufacturer's recormendations, <br />f. Provide reinforcement for any member cut for the installation of plumbing or wiring such that the <br />member is of equal strength to the member prior to cutting. <br />g.Provide lateral bridging in load bearing walls consisting of 1 1/2" cold -rolled channels at 4'-0" on center <br />vertically. Insert channels through stud web holes and screw or weld to each stud using 1. 1/2" x I." x <br />54-mil (16 gage) clip angles. Provide clip angles :1/4" less than the stud width. <br />h.Provide joist bridging at 8'-0" on center maximum. Install joist bridging in accordance with the <br />manufacturer's recommendations. <br />i. Provide unpunched material for all joists and headers. <br />j. Provide solid blocking behind all horizontal panel joints of exterior wall sheathing and interior shear wall <br />sheathing. <br />k. Design of exterior walls subject to wind pressures is based on lateral bracing of stud flanges provided by <br />sheathing. If sheathing is not applied to both faces of the wall, provide bracing in accordance with SSMA <br />Technical Note No. 2, published March 2005. <br />8. OTHER COMPONENTS <br />a.Provide shop drawings for construction of all applicable specialty items including but not limited to <br />concrete pilings, curtain wall glazing systems, light gage steel framing, ornamental guardrails, guards, <br />handrails, pre-engineered wood trusses, skylights, and signage. Shop drawings must indicate the <br />required materials, sizes, and locations for all posts and pickets including anchorage at the base of the <br />posts. Shop drawings must be sealed by a professional engineer registered in the state of Florida. <br />b. Provide curtain wall glazing system shop drawings that clearly indicate the attachment to the structure <br />on all sides of the exterior glazing system required to adequately resist the applicable wind design <br />pressures. <br />c. The glazing Contractor must provide engineering calculations to document compliance with 2012 <br />International Building Code, Sections 2403.2 through 2303.4 for butt joined glazing. <br />d.The design of special connections between steel framing components (including but not limited to braced <br />end connections, moment -resisting connections, modified beam seat connections, and member splice <br />connections) not designed by the Structural Engineer of Record must be performed by a professional <br />engineer registered in the state of Florida. <br />9. FOUNDATIONS <br />a.The Owner must commission a geotechnical exploration of the site by a properly insured professional <br />engineer registered in the state of Florida and forward the Geotechnical Engineer's report to the <br />Structural Engineer of Record. The Geotechnical Engineer's report must conform to section 1802.6 of the <br />2014 Florida Building Code. The design of foundations is based on the following assumed soil criteria: <br />Allowable Soil Bearing Pressure: 2000 PSF <br />Equivalent Lateral Fluid Pressure - Active Case: 40 PSF/FT <br />Equivalent Lateral Fluid Pressure - At -Rest Case: 60 PSF/FT <br />Equivalent Lateral Fluid Pressure - Passive Case: 300 PSF/FT <br />Coefficient of Sliding Friction: 0.35 <br />Soil Density: 110 PCF <br />Redesign of foundations my be required if the recommendations in the Geotechnical Report are different <br />than the values listed above. The following conditions could also result in redesign of foundations: <br />presence of expansive soils, high water table, potential for large settlements, or any other <br />recommendations stated in the Geotechnical Engineer's report. <br />b. The Geotechnical Engineer must verify the condition and/or adequacy of all subgrades, fills, and backfills <br />prior to the placement of foundations, footings, slabs, walls, etc. <br />c. If any interference appears between existing foundations and the specified design, notify the Architect so <br />that the foundations may be redesigned as required. <br />d.Coordi€nate top of footing elevations with the requirements of other trades (plumbing, electrical, etc.). <br />e. Place all column footings and wall footings monolithically with adjacent footings at the same elevation. <br />f. All footings must bear on original undisturbed soil where possible. <br />g.Remove all organic soils and replace with clean structural fill at the direction of the Geotechnical <br />Engineer. Place fill soils in 6" maximum (loose) lifts at moisture contents as described in the <br />geotechnical report. Compact all fill within 10'-0" of the building limit to 95% Standard Proctor. Field <br />density tests must be made as described in the geotechnical report to verify adequate compaction and <br />design bearing pressure. <br />h. Sides of foundations must be formed unless conditions permit earth forming. Foundations placed against <br />the earth require the following precautions: slope sides of excavations as approved by the Geotechnical <br />Engineer and clean up sloughing before and during concrete placement. <br />i. Where footing steps are necessary, slope no steeper than one vertical to two horizontal. <br />j. Do not backfill against basement walls (walls supported at the top and bottom) until slabs, framing, and <br />diaphragms are in place to provide support at top and bottom of wall. Concrete diaphragms must reach <br />65% of their design 28 day compression strength prior to backfilling. <br />k. Deposit backfill evenly against both sides of the wall until the louver finished grade is reached. <br />I. Unless noted otherwise, place all slabs on grade on a 10 mil polyethylene vapor retarder and a crushed <br />stone base over a properly compacted subgrade. <br />10. DESIGN LOADS <br />a. Live Loads: <br />Roof 20 PSF <br />b. Dead Loads: <br />Roof 5 PSF <br />c. Wind Design Data: <br />6. Ultimate Wind Speed (3 second gust): 146 MPH <br />7. Wind Risk Category: Category III <br />S. Wind Exposure: Exposure B <br />9. Internal pressure Coefficient: t 0.1.8 <br />10.Components and Cladding Pressures: See Table <br />------------- <br />COMPONEN COMPONENTS & CLADDING PRESSURE SCHEDULE (NOTE 1) <br />EFFECTIVE <br />ROOF <br />ROOF OVERHANG <br />WALL <br />PARAPET <br />WIND <br />AREA <br />ZONE 1 <br />ZONE 2 <br />ZONE 3 <br />ZONE 1 OVHG <br />ZONE 2 OVHG <br />ZONE 3 OVHG <br />ZONE 4 <br />(NOTE 2) <br />ZONE 4 <br />(NOTE 2) <br />+16.0 PSF <br />+38.3 PSF <br />i +3$.3 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+35.1 PSF <br />+35.1 PSF <br />+87.7 PSF <br />+87.7 PSF <br />10 SF <br />-38.3 PSF <br />-64.3 PSF <br />-64.3 PSF <br />-61.1 PSF <br />-61.1 PSF <br />-96.8 PSF <br />-38.0 PSF <br />-46.8 PSF <br />-61.4 PSF <br />-70.2 PSF <br />+16.0 PSF <br />+36.1 PSF <br />+36.1 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+33.0 PSF <br />+33.0 PSF <br />+76.6 PSF <br />+76.6 PSF <br />25 SF <br />-37.1 PSF <br />-55.3 PSF <br />-55.3 PSF <br />-59.8 PSF <br />-59.8 PSF <br />-71.0 PSF <br />-36.0 PSF <br />-42.7 PSF <br />-57.3 PSF <br />-64.0 PSF <br />+16.0 PSF <br />+34.3 PSF <br />+34.3 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+31.5 PSF <br />+31.5 PSF <br />+68.2 PSF <br />+68.2 PSF <br />50 SF <br />-36.1 PSF <br />-48.4 PSF <br />-48.4 PSF <br />-58.8 PSF <br />-58.8 PSF <br />-51.4 PSF <br />-34.4 PSF <br />-39.6 PSF <br />-54.2 PSF <br />-59.4 PSF <br />+16.0 PSF <br />_ +32.6 PSF <br />+32.6 PSF <br />+15.,, PSF <br />+16,0 PSF <br />+16.0 PSF <br />+29.9 PSF <br />+29.9 PSF <br />+59.8 PSF <br />+59.8 PSF <br />100 SF <br />-35.1 PSF <br />-41.6 PSF <br />-41.6 PSF <br />-57.8 PSF <br />-57.8 PSF <br />-31.8 PSF <br />-32.9 PSF <br />-36.5 PSF <br />-51.1 PSF <br />-54.7 PSF <br />+16.0 PSF <br />+28.6 PSF <br />+28.6 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+16.0 PSF <br />+26.3 PSF <br />+26.3 PSF <br />+56.2 PSF <br />+56.2 PSF <br />500 SF <br />€ -35.1 PSF <br />i <br />-41.6 PSF <br />-41.6 PSF <br />-41.6 PSF <br />-41,6 PSF <br />-31.8 PSF <br />-292 PSF <br />-29.2 PSF <br />-43.9 PSF <br />-43.9 PSF <br />NOTES: <br />1. (+j AND () SIGNES INDICATE PRESSURES ACTING TOWARD AND AWAY FROM <br />THE BUILDING SURFACE, RESPECTIVELY. <br />2. PRESSURES APPLY 8'-10" FROM PROMINENT BUILDING CORNER IN EACH DIRECTION. <br />9 <br />FAI <br />H <br />r, <br />�! al 00 <br />00 <br />CD <br />co <br />W CD D Lo <br />� CD <br />w ►'� U� <br />) I-- <br />13, <br />�WCCLLJ Lo <br />W�CD <br />LIJ <br />r <br />-� to <br />d N <br />c� 0 C\J <br />4= J <br />LL <br />• <br />• <br />®�m®t ��1 J�'Iv9Ft "� <br />No 76433 <br />f <br />$T TE OF LU: <br />O R 0 %N <br />'iOE�'t��*� <br />F111111 <br />2016-02-19 <br />r <br />CONTRACT DATE: 01.05.2016 <br />BUILDING TYPE: N/A <br />PLAN VERSION: DEC 2015 <br />SITE NUMBER: N/A <br />STORE NUMBER: N;'A <br />5935 GALL BLVD <br />ZEPHYRHILLS, FL 33541 <br />REMODEL <br />PHASE 1 <br />r r t <br />1 iN <br />• <br />PLOT DATE: <br />1111=1EMIrm <br />