ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />comer counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />�?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />77 <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />116 <br />EXHAUST FAN <br />,I <br />EXHAUST FAN/LIGHT COMBINATION <br />rD <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />P13 <br />PUSH BUTTON SWITCH (OPTIONAL) <br />�[]aD <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />a <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />TV 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />�M <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ROUGH-IN FOR <br />T J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANEL CENTER <br />#14 to lights & outlets <br />NEMA 1 #12 to appliances and GFI <br />160 AMP/ <br />200 AMP 00 #10 to WH <br />10 #6 to Range <br />10 #6 to HVAC <br />7 <br />MAIN <br />200 amp <br />150 amp <br />UNDERGROUND IDis <br />SERVICE BY POWER CO.---_ <br />INTERSYSTEM <br />BONDING o <br />TERMINATION PER 71 <br />200=4/0 in 2" Conduit <br />4 Bare Cu Ground <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />LANAAI-----�' <br />/e I <br />AC PAD I �� <br />DISC. GFI WP <br />I GFF1 <br />�Q I <br />r7=-= _, �. <br />II ALT II — <br />I I <br />I -- <br />I i <br />i <br />l AC PAD <br />I <br />WP DINING -- <br />LI H AS <br />OPT. 5'-0" SP C <br />D — to / r- <br />- <br />5' <br />LIGHT AS PER li <br />SPECSol <br />PENDANT <br />LIGHT PER <br />SPECS <br />GREAT RM r <br />IGFI p I <br />a ROUGH -IN � U.C. OUTLET I I <br />FOR OPT. o <br />li�`yo1 <br />IIL__J. <br />U.C. OUTLET <br />r 0 1 <br />I <br />SWITCH FOR FII a <br />DISPOSAL I <br />II <br />II <br />Il <br />N. <br />w <br />IGF <br />I® <br />NO <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />SPEC 3 & 4 KITCHEN <br />SCALE: %4'=1'-0" <br />cc <br />s SWITCH FOR ( [E' <br />iF�1��1■ <br />OPT. CLG. FAINI/ DISPOSAL-3, <br />LIGHT PRE -WIRE/ <br />' <br />,..== <br />929i `M'r <br />Y <br />GFI @ 44" �� / <br />A.F.F. �/ <br />I <br />J <br />I <br />I <br />_ <br />DGBW <br />- <br />\� GARAGE -t - <br />>- <br />GFI <br />LIGHT AS <br />PER SPECS <br />I I <br />- <br />w W <br />I <br />- <br />> w <br />GARAGE, <br />1 k5F GARAG E <br />I I <br />ENTRY <br />DOOR <br />�_ <br />GFI <br />II--�----- <br />I <br />-------------------------- <br />- - - - - - - <br />I I IRRIGATION GFI <br />-------_ <br />I @ 44" A.F.F. <br />I ' 1 <br />I 1 <br />I I <br />I � I <br />I � I <br />------------------------------ <br />------------ COAUHTCfGRTS----------- <br />OR PREWIRE AS <br />PER SPECS <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />0 <br />ED <br />--------I <br />I I <br />I I <br />I I <br />t I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I ! <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L------------------------------------ J <br />RECEPT. FOR <br />ALARM SYSTEM <br />PROVIDE PHONE / CABLE <br />AND OUTLET AT TECH <br />CENTER <br />GFI @ <br />44" A.F.F. <br />III 3" VTR 1.5" VTR <br />I III <br />I I, <br />I I <br />I I <br />I I <br />� I I <br />_III 3" VTR <br />! � I I� <br />I I <br />PLUMBING RISER_ <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />ELECTRICAL PLAN <br />SCALE: %4"=1'-0" <br />C`1 <br />'•cs <br />CIA <br />Cn <br />y W <br />C tc c-1 <br />d3c <br />t?:.i .�.. C; <br />c <br />' - e8 <br />a � <br />N <br />a� <br />o ' <br />w <br />N <br />C`J <br />0 <br />N <br />ti <br />N <br />to <br />0 <br />To the as of the Enginee s knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code <br />- <br />Residentlal 7th Edition. Engineers signature and seal <br />is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />E <br />O N S <br />v <br />® <br />p <br />a) O 0) 9 ti <br />_ <br />00 <br />N <br />di <br />U.) to <br />rnr�� <br />CD � LL <br />M <br />Q <br />R <br />C U. <br />w <br />(' <br />to U_ w 5 a <br />_ w <br />Z <br />a N <br />two <br />W01 <br />w o <br />o <br />M <br />Z <br />IL <br />°) m w-- <br />o <br />�p <br />to ) Z J F <br />N <br />O U o <br />z <br />to <br />W <br />13� <br />Cl)(Dz <br />� <br />a C' <br />Z co <br />N <br />z oC' <br />� <br />� <br />fl- <br />v'1 <br />M <br />z <br />v <br />W � <br />a <br />U <br />QO <br />' /� <br />y ' <br />gJim <br />N <br />h— fn <br />U <br />w m <br />Nowak <br />Mfg <br />m 3 <br />z� <br />link <br />C� o y <br />m <br />C to <br />_ <br />Q <br />O <br />cfl <br />w <br />M <br />w� <br />o <br />z <br />� <br />CL 0 <br />oz <br />a�� <br />zo <br />o� <br />ca <br />B <br />O00 <br />&a <br />0 U <br />a <br />ZCDG <br />c <br />N <br />a) <br />qz <br />o <br />wz <br />o <br />L <br />to <br />U3 C <br />OY <br />U <br />mm <br />o <br />O¢ <br />Z <br />Z <br />Q) <br />4 W <br />3 <br />0¢ <br />Z 0 <br />3 <br />W <br />Q <br />U <br /><o <br />a <br />0 W <br />G <br />J <br />z <br />¢'< <br />0 <br />>° <br />o <br />co <br />z �d <br />aF <br />01 <br />c 0 <br />0 <br />0 <br />C9 <br />CID <br />r <br />Q <br />Cr <br />U <br />r <br />r^ <br />W s <br />N <br />a--+ m <br />Lo <br />� <br />0 <br />� <br />M <br />N <br />C) <br />N <br />LO <br />ai <br />C`V <br />LO <br />o <br />Z <br />ld <br />Z <br />E Ir— <br />N <br />N <br />C <br />d <br />U <br />Q 0 <br />� <br />JOB <br />NO: <br />22-06452 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />