ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance With R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />$4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />0 <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />® <br />EXHAUST FAN <br />EXHAUST FAN/LIGHT COMBINATION <br />�D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PI3 <br />PUSH BUTTON SWITCH (OPTIONAL) <br />D3 <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />TELEVISION (OPTIONAL) <br />2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />C� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />., <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANEL CENTER <br />#14 copper to lights & outlets <br />N1 <br />150 #12 copper to 20 amp ckts <br />AM AMP/ <br />200 AMP #10-2 copper to WH <br />#10-3 copper to Dryer <br />2!0 or 4!0 SER Alu <br />200 amp <br />150 amp <br />UNDERGROUND Disconnect <br />POWER CO. FEED <br />INTERSYSTEM 4 Bare Cu Ground <br />BONDING O #4 GROUNDING WIRE <br />TERMINATION PER WITH CODE APPROVI <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF NEC 17. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 04.06.21 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-17, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER CO. <br />1.5" VTR <br />lil <br />I <br />I <br />III 3" VTR <br />I\ � <br /><� I I <br />t I 14" \rrR <br />SWITCH FOR <br />DISPOSAL <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />I C <br />11DW _ / <br />tj_ _ / <br />KITCHEN <br />DEDICATED <br />RECEPTACLE FOR <br />ICROWAVE RANGE <br />HOOD PER SPECS <br />A/C PAD <br />GFI WP DISC. <br />�B <br />/ I <br />/ I <br />ENTRYWP <br />DB & GFI TO I GFI <br />BE ALIGNED — — — — — — — <br />VERTICALL <br />I <br />I <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />IX Cr <br />W LU <br />t— 0 <br />W J <br />� O m <br />�UT_ <br />�o � <br />COACH LIGHTS COACH LIGHTS <br />OR PREWIRE AS OR PREWIRE AS <br />PER SPECS / PER SPECS <br />SPEC 3 & 4 KITCHEN FIRST FLOOR ELECTRICAL PLAN — ELEV—B <br />SCALE: %4'=1'-0" <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I I <br />I I <br />I I <br />I I <br />I I <br />L— — — — — — — — — — <br />I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L- — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — J <br />SECOND FLOOR ELECTRICAL PLAN <br />ELEV—B <br />70 <br />N <br />0 <br />X <br />N <br />Q <br />J ('7 <br />1. <br />r. <br />sa -- <br />M <br />ILL t= <br />tc5 a) O O <br />L � L <br />0- © W <br />CV <br />N <br />0 <br />N <br />C14 <br />N <br />N <br />0 <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seat is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />W <br />W <br />Q <br />d E m <br />O O <br />N it LL <br />Q <br />C <br />cv u°ri xt " w <br />ills <br />� N 0 u_ a Y <br />°' <br />Q <br />a' �n <br />, a = <br />Z <br />Z <br />0 <br />o <br />Lmv 0 <br />0 0 <br />C t of OJ W <br />W <br />m <br />in��rn ¢ co <br />Z <br />LL <br />° a <br />N cNi Z W 0 <br />O 0 U _j in <br />Z <br />W <br />❑0❑ <br />V M t�2 <br />o g <br />z N <br />z <br />Q) <br />�N <br />o <br />_04-1 <br />Q A <br />t0 <br />U <br />OLLJ <br />N <br />�N <br />O <br />Ly N <br />In <br />U <br />E <br />U o' <br />c <br />" <br />Q <br />N � <br />/0 <br />\� <br />ti <br />o <br />Q0 <br />w <br />M <br />�+ = <br />Z <br />Z <br />_j <br />U_ <br />Q E <br />w� <br />�o <br />Z <br />tru no <br />04 @ <br />�a <br />a� <br />° <br />o2 <br />ww <br />N I— <br />o <br />6 <br />¢ <br />L <br />ro <br />� L <br />-� <br />O <br />ox <br />U <br />'m'<w <br />m 0 <br />0 <br />Oil <br />z <br />Z <br />� J <br />�b <br />irn <br />a_ <br />8 <br />LL� <br />g° <br />W <br />W <br />U <br />az <br />J w <br />'IS <br />O <br />wa <br />¢a <br />a <br />0 <br />c Q <br />> M <br />I1/ <br />I..L <br />rn <br />m <br />m <br />U <br />L <br />d. <br />C0 d' <br />N <br />:3 T <br />Y <br />) U <br />vo <br />in <br />o <br />� <br />o <br />M <br />N <br />N <br />Lo <br />Q <br />N <br />T <br />ai <br />m <br />N <br />N <br />o <br />z <br />Z <br />E N <br />N <br />CU <br />a <br />o <br />U _j <br />ai <br />Q p <br />JOB <br />NO : <br />22-02370 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />