ELECTRICAL EQUIPMENT SPECIFICATIONS <br />PANELS: SQUARE D TYPE NQODCU RECESSED MOUNTED COPPE BUS, BOLTED CIRCUIT <br />BREAKER PANELBOARD, 120/208 VOLT, 3PH., 4 WIRE OR EQUIVALENT. <br />TIME CLOCK: COORDINATE WITH ELECTRICAL CONTRACTOR <br />DUPLEX RECEPTACLES: HUBBELL #5262-WHI. UNLESS OTHERWISE NOTED. <br />DUPLEX RECEPTACLES: HUBBELL #5262-BL. UNLESS OTHERWISE NOTED. <br />QUAD RECEPTACLE: TWO (2) HUBBELL #5262-WHI DUPLEX RECEPTACLES IN COMMON <br />JUNCTION BOX WITH 4 GANG COVER PLATE UNLESS OTHERWISE NOTED. <br />ISOLATED GROUND RECEPTACLES: HUBBELL #IG-5262-WHI UNLESS OTHERWISE NOTED. <br />ISOLATED GROUND QUAD RECEPTACLES: TWO (2) HUBBELL MG-5262-WHI DUPLEX <br />RECEPTACLES IN COMMON JUNCTION BOX WITH 4 GANG COVER PLATE UNLESS <br />OTHERWISE NOTED. <br />GROUND FAULT RECEPTACLE: HUBBELL #GF-5252-WA UNLESS OTHERWISE NOTED. <br />SINGLE POLE SWITCHES: HUBBELL #HBL-1221-WHI. <br />ELECTRICAL NOTES <br />REMOVE ALL EXISTING LIGHTING FIXTURES, SWITCHES, JUNCTION BOXES, CONDUIT, <br />WIRING, ETC., NOT REQUIRED FOR REUSE. <br />THE EXISTING 200 AMP 120/208 VOLT 3 PHASE SERVICE SHALL BE REUSED. ELECTRICAL <br />CONTRACTOR SHALL EXTEND THE EXISTING SERVICE TO THE NEW PANEL LOCATION. BASE BID <br />SHALL INCLUDE ANY ADDITIONAL CONDUIT AND WIRING AND CONNECTIONS OF THE ELECTRICAL <br />EQUIPMENT, ETC. <br />THE EXISTING SERVICE DISTRIBUTION EQUIPMENT INCLUDING THE METER AND THE 200 AMP <br />MAIN DISCONNECT SWITCH SHALL REMAIN AND BE REUSED. VERIFY AND CHANGE AS <br />REQUIRED TO ADEQUATELY PROTECT THE FEEDER TO THE SPACE. IF ANY ISSUES ARISE WITH <br />REGARD TO REUSE OF SERVICE AND EQUIPMENT, CONTACT ARCHITECT AND/OR ENGINEER PRIOR <br />TO BID FOR DISPOSITION. THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY AND VIEW ALL <br />EXISTING CONDITIONS BEFORE SUBMITTING A PROPOSAL FOR THE WORK AS DESCRIBED AND <br />SHOWN. EXTRAS WILL NOT BE PERMITTED FOR FAILURE TO MAKE THIS VISIT. <br />THE INTENT OF THE WORK WITH REGARD TO ELECTRICAL DISTRIBUTION AS INDICATED ON <br />THE DRAWINGS IS AS FOLLOWS: <br />A. ALL EXISTING ELECTRICAL EQUIPMENT NOT CURRENTLY BEING USED TO FEED <br />ANYTHING AND NOT REQUIRED AS PART OF THIS REMODEL SHALL BE REMOVED. <br />B. EXISTING ELECTRICAL EQUIPMENT CURRENTLY BEING USED TO FEED LIGHTING, <br />EQUIPMENT, ETC, SHALL BE REUSED. A DETAILED FIELD INSPECTION OF THE <br />EXISTING EQUIPMENT SHALL BE INCLUDED IN THE BASE BID TO DETERMINE ITS <br />CONDITION AND COSTS TO PERFORM MAINTENANCE SERVICE. INSPECTION SHALL <br />INCLUDE THE FOLLOWING: <br />1. CHECK ENTIRE INSTALLATION FOR CODE COMPLIANT CLEARANCES. <br />MODIFY INSTALLATION AND EQUIPMENT LOCATION AS REQUIRED. <br />2. CHECK CONDUITS FOR PROPER INSTALLATION, I.E. TIGHT <br />CONNECTIONS, PROPER FITTINGS, RUSTING, CREASING, BENDING, <br />ETC. REPAIR OR REPLACE AS REQUIRED. <br />3. CHECK FOR BARE WIRING. COVER OR REPLACE AS REQUIRED. <br />4. CHECK FOR PROPER GROUNDING OF SYSTEM AND EQUIPMENT. CORRECT <br />AS REQUIRED. <br />5. CHECK FOR CIRCUIT OVERLOADING AND/OR TRIPPING. REPLACE <br />BREAKERS AND/OR FUSES AS REQUIRED. REDISTRIBUTE CIRCUITING <br />OF EQUIPMENT AND/OR LIGHTING AS REQUIRED. <br />6. REPAIR ANY RUSTED AREAS ON EQUIPMENT CASINGS. REPAINT AS <br />REQUIRED. <br />7. VERIFY THE SIZES OF THE EQUIPMENT IN FIELD AS SHOWN AND <br />CALLED FOR - IF EQUIPMENT IS NOT SIZED AS REQUIRED, CONTACT <br />THE ARCHITECT/ENGINEER. <br />AN ALTERNATE PROPOSAL SHALL BE SUBMITTED TO REPLACE ANY AND/OR ALL EXISTING <br />EQUIPMENT, IF THE EQUIPMENT IS DETERMINED TO BE IN NEED OF REPLACEMENT AFTER <br />THE INSPECTION AT THE JOB SITE. ALTERNATE PROPOSAL SHALL BE COMPLETE. <br />FURNISH AND INSTALL NEW ELECTRICAL PANELS AS REQUIRED. <br />FURNISH AND INSTALL TYPEWRITTEN PANEL DIRECTORIES AS SHOWN. <br />CIRCUITS SHALL BE CONNECTED TO THE PANELS AND ARRANGED TO COMPLY WITH THE <br />NUMBERS SHOWN ON THE DRAWINGS. UNUSED CIRCUITS SHALL BE UTILIZED AS SPARES. <br />PROVIDE ADEQUATE TEMPORARY POWER AND LIGHTING. <br />MAINTAIN ALL REQUIRED CLEARANCES AT ALL ELECTRICAL EQUIPMENT AND COMPLY WITH <br />N.E.C. ARTICLE 110. <br />TIME CLOCK AND OTHER MISCELLANEOUS ELECTRICAL COMPONENTS SHALL NOT BE INSTALLED <br />ON THE TELEPHONE TERMINAL BOARD. <br />FURNISH AND INSTALL NEW FIRE ALARM SYSTEM (IF REQUIRED). COORDINATE WITH LANDLORD. <br />TEMPERATURE CONTROL EXCLUDED FROM ELECTRICAL CONTRACT. <br />CONTRACTOR SHALL NOTIFY THE ARCHITECT AND/OR ENGINEER OF ERRORS, OMISSIONS OR <br />DISCREPANCIES BEFORE CONSTRUCTION OR FABRICATION OF AFFECTED WORK, OR, FAILING <br />SUCH NOTICE, SHALL BE RESPONSIBLE FOR CORRECTING SAME WITHOUT COST TO TENANT, <br />ARCHITECT OR ENGINEER. <br />WORK SHALL INCLUDE START UP OF ALL SYSTEMS. PROVIDE ONE YEAR LABOR WARRANTY ON <br />ENTIRE INSTALLATION AND ONE YEAR PARTS WARRANTY ON ALL EQUIPMENT SUPPLIED BY <br />SUB -CONTRACTOR. FURNISH ALL MANUALS, MAINTENANCE INSTRUCTIONS, AND WARRANTIES <br />TO CONTRACTOR. <br />MOUNT SWITCHES 4'-0" ABOVE FLOOR UNLESS OTHERWISE NOTED. <br />ALL CONDUITS FOR USE BY OTHERS SHALL BE CONTINUOUS, CONTAIN PULL STRINGS, AND <br />HAVE PULL BOXES AS NECESSARY. <br />ALL RECEPTACLE LOADS ARE BASED ON 180 WATTS FOR DUPLEX DEVICES AND 360 WATTS FOR <br />QUAD DEVICES. <br />ALL PANEL LOCK DEVICES MUST BE U.L. LABELED -LISTED. <br />ALL ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE SUITABLE FOR INSTALLATION AND USE IN <br />CONFORMITY WITH NEC 110.3(A)(1). <br />SEAL AROUND ALL ELECTRICAL PENETRATIONS OF FIRE RATED WALLS PER NEC 300.21. <br />PANEL EXISTING P1 LUGS 225 AMP <br />120/208 VOLT 3 PHASE 4 WIRE AIC RATING:22,000 MAIN BREAKER 200 AMP <br />ORTIZ-3mgm <br />m <br />EX COND #1 <br />�■■�omm <br />�■■ <br />COND #3 In <br />Ron <br />no <br />a <br />11100 <br />11100 <br />` <br />® <br />®' <br />so�M® <br />ME <br />n <br />EQUIP RECPT <br />11100 <br />Wes■■�■■�on�n <br />- • - <br />11100 <br />` <br />m_■■�■■�®_®®' <br />11100 <br />PANEL P2_ FEED- <br />11100 <br />® <br />■■ <br />®0 <br />� <br />_ <br />1 <br />' <br />®IMME■■�■■�■■MO <br />' <br />11100 <br />11100 <br />_ <br />` <br />MISSES <br />■�■■�■■MO <br />_ A. <br />11100 <br />_ <br />` <br />®_■■�■■�■■_® <br />` <br />11100 <br />®INNI■■�■■�■■IMMEm <br />' <br />11100 <br />• • <br />®_■■�■■�■■_ <br />® <br />• _ <br />11100 <br />� <br />®�■■�■■�■■MO <br />� <br />11100 <br />.:. <br />OMEN <br />■■ <br />m <br />. _ . <br />11100 <br />"*" INDICATES PANEL LOCKS <br />PHASE A: <br />26912 <br />WATTS <br />PHASE B: <br />26424 <br />WATTS <br />PHASE C: <br />25980 <br />WATTS <br />TOTAL <br />79316 <br />WATTS <br />BALANCE 3.46% <br />CONNECTED <br />79,316 W. <br />220.3 A. <br />PANEL EXISTING P2 LUGS 100 AMP <br />120/208 VOLT 3 PHASE 4 WIRE AIC RATING:22,000 MAIN BREAKER 100 AMP <br />WIRE <br />SIZE <br />USE <br />CKT. <br />NO. <br />LOAD <br />KVA <br />BKR <br />SIZE <br />A B C <br />BKR <br />SIZE <br />LOAD <br />KVA <br />CKT. <br />NO. <br />USE <br />WIRE <br />SIZE <br />SPARE <br />1 <br />20/1 <br />20/1 <br />2 <br />SPARE <br />SPARE <br />3 <br />4 <br />SPARE <br />SPARE <br />5 <br />250 <br />6 <br />SIGN <br />LIGHTING <br />7 <br />432 <br />1080 <br />8 <br />LOBBY RECPT <br />LIGHTING <br />9 <br />174 <br />360 <br />10 <br />RECEPTION RECPT <br />LIGHTING <br />11 <br />350 <br />360 <br />12 <br />GROOMING GFCI <br />LIGHTING <br />13 <br />650 <br />180 <br />14 <br />GROOMING RECPT <br />LIGHTING <br />15 <br />312 <br />180 <br />16 <br />1 GROOMING RECPT <br />LIGHTING <br />17 <br />342 <br />180 <br />18 <br />GEN RECPT <br />SPARE <br />19 <br />720 <br />20 <br />OFFICE RECPT <br />SPARE <br />21 <br />1080 <br />22 <br />STOCKROOM FGCI <br />SPARE <br />23 <br />1080 <br />24 <br />1 KENNEL RECPT <br />SPARE <br />25 <br />900 <br />26 <br />1 KENNEL RECPT <br />SPARE <br />27 <br />28 <br />SPARE <br />SPARE <br />29 <br />180 <br />30 <br />RESTROOM GFCI <br />SPARE <br />31 <br />32 <br />SPARE <br />SPARE <br />33 <br />34 <br />SPARE <br />SPARE <br />35 <br />36 <br />SPARE <br />SPARE <br />37 <br />180 <br />38 <br />WASHER <br />SPARE <br />39 <br />30/2 <br />2250 <br />40 <br />DRYER <br />SPARE <br />41 <br />L <br />_F2250 <br />42 <br />"*" INDICATES PANEL LOCKS <br />PHASE A: 4142 WATTS <br />PHASE B: 4356 WATTS <br />PHASE C: 4992 WATTS <br />TOTAL 13490 WATTS <br />BALANCE 17.03% <br />CONNECTED <br />67,332 W. <br />187.0 A. <br />EXISTINGDISC SW #1 <br />60/50, NEMA 3R <br />EXISTING COND #1 <br />ON GROUND <br />P1-16 <br />WR 20A. GFCI RECEPTACLE - <br />IN WEATHER RESISTANT BOX <br />3-#6 CU, 1 #8 GRD. 1 "C. <br />NEW DISC SW #2 <br />60/50, NEMA 3R <br />I I \ <br />NEW COND #1 <br />ON GROUND <br />P1-16 <br />WR 20A. GFCI RECEPTACLE - <br />IN WEATHER RESISTANT BOX <br />3-#6 CU, 1 #8 GRD. 1 "C. <br />NEW DISC SW #3 <br />30/30, NEMA 3R <br />NEW COND #2 <br />ON GROUND <br />WR 20A. GFCI RECEPTACLE - <br />IN WEATHER RESISTANT BOX <br />EXISTING DISC SW #4 <br />100/70, NEMA 1 <br />P1-16 <br />3-#4 CU, 1 #8 GRD. 1-1 /4"C. <br />EXISTING AHU #1 <br />SUSPENDED <br />WR 20A. GFCI RECEPTACLE <br />IN WEATHER RESISTANT BOX <br />NEW DISC SW #5 <br />100/70, NEMA 1 <br />P1-16 <br />3-#4 CU, 1 #8 GRD. 1-1 /4"C. <br />NEW AHU #2 <br />SUSPENDED <br />WR 20A. GFCI RECEPTACLE <br />IN WEATHER RESISTANT BOX <br />NEW DISC SW #6 <br />100/70, NEMA 1 <br />P1-16 11 11 P1-16 <br />3-#6 CU, 1 #8 GRD. 1 "C. I I I-- 3-#4 CU, 1 #8 GRD. 1-1 /4"C. <br />EXTERIOR OF BUILDING I HOUNDSTOWN <br />FIRST FLOOR <br />4-#3/0 CU, 11 #4 GRD., 2"C. <br />EXISTING TO REMAIN <br />4-#3/0 CU, 1 #4 GRD., 2"C. <br />EXISTING 200 AMP <br />DISCONNECT SWITCH <br />WITH 200 AMP FUSES <br />CONNECT TO <br />EXISTING <br />O <br />' <br />R <br />EXISTING <br />225 AMP <br />120/208V. <br />EXISTING <br />100 AMP <br />120/208V. <br />200A. <br />PNL "P1" <br />PNL "P2" <br />200 AMP <br />100 AMP <br />BREAKER <br />BREAKER <br />RELOCATED <br />RELOCATED <br />EXISTING METER SOCKET TO REMAIN <br />NEW METER BY E.C. <br />4-#3 CU, 1 #4 GRD., 1-1 /4"C. <br />RISER DIAGRAM NOTES <br />1. OBTAIN AVAILABLE FAULT CURRENT RATING AND PROVIDE <br />PROTECTION FOR MAIN CIRCUIT BREAKER AND ALL <br />BRANCH DEVICES. <br />2. MAINTAIN ALL REQUIRED CLEARANCES PER ARTICLE <br />110-26 NEC <br />POWER RISER DIAGRAM. <br />NOT TO SCALE <br />NEW AHU #3 <br />SUSPENDED <br />WR 20A. GFCI RECEPTACLE <br />IN WEATHER RESISTANT BOX <br />2 <br />O <br />_ <br />N <br />� � � � Z <br />W <br />uj U <br />w <br />m NW%.:j <br />Z <br />I z <br />�o <br />Wo <br />ON <br />¢ o <br />o 0)co <br />tTm�:QO <br />o� <br />L2LZ <br />mal <br />CERTIFIED BY: <br />6440 FORT KING <br />ZEPHYRHILLS, FL <br />33542 <br />DARREN & LUANN <br />Owner <br />LJANSEN GEHRING <br />317.747.0555 <br />ZEPHYR HILLS <br />ELECTRICAL <br />SPECIFICATIONS <br />E101 <br />