Laserfiche WebLink
I!I <br />BASIC MECHANICAL REQUIREMENTS <br />Section 15050 Me <br />chanical & Methods <br />PART 1 GENERAL: <br />1.01 Description of Work: The work to be performed under this Division includes all labor, <br />materials, equipment and services necessary to design and install the complete mechanical <br />system as shown on the drawings and herein specified. <br />1.02 Quality Assurance: All work shall be done in a workman like manners in accordance with <br />good practice, manufacturers? recommendations, and in compliance with 2004 and 2006 Florida <br />Mechanical Code including all local codes and regulation. <br />1.03 Other Specified Work: See electrical and plumbing specification for work to be done in <br />conjunction with the mechanical work. All control and hardware to complete the HVAC <br />control systems shall be furnished and installed under Division 15 of Mechanical, of this <br />contract documents. <br />1.04 Manufacturers: Manufacturer name and model numbers listed in the specification or on the <br />schedules are for the purpose of establishing a quality of products or a specific design <br />configuration. Equal products, as approved by the Architect/Engineer, will be acceptable <br />from other manufacturers. <br />1.05 Quality Assurance: <br />A. Manufacturer: Firms regularly engaged in manufacture of packaged cooling units, of type <br />sizes and capacities required, whose products have been in satisfactory use in similar <br />service for not less than five years. <br />B. Installers: A firm with at least five years of successful installation experience on projects <br />with packaged and split system cooling units. <br />C. Codes and standards: The latest version of the following codes and standards apply to all <br />or part of the products for procedures covered in this specification. <br />National Fire Protection Association (NFPA) <br />Air Movement and Control Association (AMCA) <br />Air Conditioning and Refrigeration Institute (ARI) <br />Underwriters Laboratories (UL) <br />American National Standards Institute, Inc. American Society of Heating, <br />refrigerating and air-conditioning Engineers (ANSI-ASHRAE) <br />2004 Florida Building Code <br />National Electric Code (NEC) <br />Standard Mechanical Code <br />Standard Fire Prevention Code <br />Americans with Disabilities Act (ADA) <br />SMACNA Ductwork Standards <br />ASRAE Standard 62-89 and latest revisions. <br />All other local, City, County and State Codes <br />1.06 Equipment: All equipment, etc., unless otherwise noted, shall be new and of the best <br />quality free of defects as shown on the drawings and as indicated in these specifications. <br />1.07 Workmanship: All materials shall be fabricated and installed in a neat and workman like <br />manners with the coordination of all involved trades to avoid interference and delay due to <br />lack of coordination. No allowances will be given for reworks due to lack of <br />coordination or interference between trades. <br />1.08 Access Doors: Provide access doors for all dampers, valves, etc. where floors, walls, and <br />ceilings must be penetrated to access mechanical equipment. Provide fire rated access <br />doors in rated construction. <br />1.09 Submittal: Submittal data is required for all HVAC equipment, plumbing equipment, <br />ductwork, hangers, etc. Partial submittal will not be accepted. Submittal shall be <br />presented in six individual binders with the project name listed on the front cover. Submit <br />maintenance data and parts list for each cooling unit, control, and accessory, including <br />troubleshooting and maintenance guides. <br />1.10 Fire Dampers: Fire dampers shall be type "b" curtain type, suitable for either vertical or <br />horizontal installation, with 20 gauge steel channel frames, 24 gauge steel blades, and 18 <br />gauge steel enclosure with Duct collars. All parts galvanized mill finish. <br />Fire dampers shall be equal to Ruskin type DIBD for walls up to two hours. <br />Install in accordance with NFPA-90a, tested in accordance with UL safety standard 555. <br />1-1/2 hour and 4-hour protection, 165 fusible links. <br />1.11 Warranty/guarantee: The contractor shall warranty/guarantee and maintain the stability of <br />work and materials and keep the some in perfect repair and condition of the period of one <br />year. <br />Defects of any kind due to faulty work or materials appearing during the above -mentioned <br />period must be immediately made good by the contractor at his own expense to the entire <br />satisfaction of the owner and architect and engineer. Such reconstruction and repairs shall <br />include all damage to the finish or furnishing of the building resulting from the original <br />defect or repairs thereto. <br />PART 2 EXECUTION: <br />All locations of equipment, ductwork, piping, etc., indicated on the drawings are diagrammatic <br />and shall be followed as closely as possible to the plans subject to building construction and <br />interference with other trades. All work shall be installed to insure maximum headroom. <br />Balanced operation and suitable aesthetic appearance. The contractor is responsible for any field <br />measurements required providing an approved and functional installation. <br />Not all components required for a complete installation are shown on these drawings. Refer to <br />equipment installations, schedules and applicable codes for additional information, including <br />required connection location, types, and size. Provide isolation valves and unions at equipment <br />and as indicated on drawings. <br />The contractor shall be responsible for furnishing and installing adequate and proper insulation <br />and moisture -seal in a manner that will permanently prevent the accumulation of any objectionable <br />moisture on the exterior of air-conditioning units, refrigerant -piping, condensate drain piping, air <br />ducts or other parts of the system. He shall correct the cause of any condensation and fully <br />repair, without cost to the owner, any damages to building surfaces, furnishings or equipment <br />caused by condensation from this system, for the full period of the guarantee. <br />2.01 Cleaning, Testing And Adjusting: Clean and Adjust: Upon completion of work, the <br />contractor shall clean, oil and grease all fans, motors and other running equipment and <br />apparatus which he installs and make certain all such apparatus and mechanisms are in <br />proper working order and ready for tests. <br />Testing: Upon completion of installation of units and connection to competed air <br />distribution system, start-up and test equipment in accordance with ARI Standards; <br />operate units to demonstrate capability and compliance with requirements. Where <br />possible, field -correct malfunctioning units, then retest to demonstrate compliance. <br />2.02 Excavation and Backfill Provide all excavation and trenching, to the correct elevations, <br />for the installation of all piping, manholes, catch basins and foundations included under <br />this division of the work. <br />Provide all backfill in strict accordance with the "excavation and backfill" section of <br />division 1 specifications. <br />2.03 Training Services: Thoroughly instruct the owner?s representative in the operation of all <br />equipment furnished and location of all valves and control devices. <br />Train building owner's personnel during normal working hours on start-up and shut down <br />procedures, troubleshooting procedures, servicing and preventive maintenance schedules <br />and procedures. Review with the owner's personnel the data contained in the operating <br />and maintenance manual. Schedule training with the owner, provide at least 7-days prior <br />notice to architect/engineer. <br />Section 15161 Vibration Isolation: <br />All blower units and vibrating type equipment shall be properly fitted with mason industries <br />vibration isolation equipment sized in accordance with equipment weight and duty. <br />Provide flexible connectors at all supply and return connections to air handling equipment <br />consisting of heavy canvas or neoprene fabric with airtight seams and connections to the <br />equipment. <br />Section 15190 Equipment Identification: <br />Equipment Identification: Provide identification labels on or near each piece of major equipment <br />and each operational device and disconnects. The labels shall be constructed of engraved plastic <br />laminate sign or plastic equipment marker permanently secured to equipment. The lettering shall <br />be a minimum of 2 inch high for equipment name and 3/8 inches for equipment information. <br />Section 15530 Refrigerant Piping <br />A. Refrigerant piping shall be Type "L" hard drawn copper, jointed with Sil FOS brazing <br />alloy backed up with 60-40 tin lead solder. <br />B. Refrigerant piping insulation shall be "Armstrong Armaflex pipe insulation" or approved <br />equal, sizes as follow: <br />3/8" thru 2-5/8" ID =3/4" <br />Armaflex pipe insulation shall be installed with all seams and joints sealed with Armstrong 520 <br />Adhesive. Since 520 adhesives are a contact adhesive, it must be applied to both surfaces. <br />Applications must be coated with Armstrong Armaflex Finish or protective coating approved by <br />the manufacturer. <br />Section 15855 Air-conditioning and Heating: <br />A. General: The general mechanical specifications apply to the work specified in this section. <br />B. Description of Work: Furnish and install complete air conditioning systems as indicated on <br />the design drawings and as outlined within these specifications. Work shall include but <br />not be limited to the fabrication and/or installation of the scheduled air conditioning units, <br />exha <br />ust fans air distribution and ductwork. <br />C. Equipment: Air conditioning units - units shall be split system <br />air-to-air electric air conditioning units as scheduled on the design <br />drawings. Units with integral electric resistance heaters shall have a single -point electric <br />connection. <br />Total cooling capacity of the units shall be as scheduled on drawings. Unit cabinets shall be <br />constructed of galvanized steel. Bonderized and coated with baked enamel. Cabin insulation <br />shall comply with Florida Energy Code. <br />Refrigeration system - the units shall contain hermetic compressors with service valves and <br />vibration isolation. Units shall have dual compressors and dual refrigeration circuits or capacity <br />reduction steps where indicated on equipment schedules. <br />Fans and motors - the indoor air fans shall be of the forward -curved centrifugal class 1 type.The <br />outdoor air fans shall be of the propeller type, each directly driven by an inherently protected <br />motor. Motor and drive to provide higher fan output when job requirements exceed standard fan <br />capacity shall be provided. <br />Safety controls - cooling system shall be protected by: loss of charge protection, high and low <br />pressurestat. A compressor motor overloads, and a timing device Which will prohibit the <br />r n once ever five minutes. <br />'n subjected to a starting current more than compressor motor from being sub�e e g y <br />Three phase units shall have phase- loss protection. <br />Controls - provide wall mounted, heat/cool on -off -auto thermostat and firestat for each unit. <br />Air filters - Filters shall be fiberglass media throw -away type in a rigid frame with a supportin,g <br />maze across both enteringand leaving surfaces. Supply one complete set of filters after owners <br />final acceptance. Farr 30,730 or equal. <br />D. Warranties: Provide a one (1) year warranty on the complete system and an additional <br />four (4) year factory warranty on all compre sors. Loss of refrigerant will be replaced at <br />no cost to the owner for a period of one (1) year. <br />Condensate drains: type, I PVC Route to roof drain. <br />Install per manufacturers recommendations. <br />2.01 ACCEPTABLE MANUFACTURERS: Provide products by one of the following: <br />1. Aaon <br />2. Lennox <br />3. Trane <br />4. Carrier <br />Section 15870 Power Ventilators (Exhaust Fans): <br />PART 1 GENERAL <br />1.01 Related Documents: Basic Mechanical Requirements govern the work specified in this <br />section. <br />1.02 Description of Work: The extent of power ventilator work is shown on drawings and <br />schedules, and by the requirements of this section and includes the following: <br />1. Ceiling ventilators. <br />PART 2 B Products: <br />2.01 ACCEPTABLE MANUFACTURERS: Provide products by one of the following: <br />1. Nutone <br />2. Penn. <br />3. Greenheck. <br />4. Carnes. <br />5. Acme. <br />6. Broon. <br />2.02 Ventilator Units: <br />A. General: <br />1. Provide standard prefabricated power ventilator units of the type and size shown, <br />modified as necessary to comply with requirements, and as requlied for a complete <br />installation. <br />2. Provide motor and electrical accessories complying with NEMA standards. <br />3. Bird Screen: Nonmagnetic galvanized steel �? mesh, unless otherwise indicated. <br />4. Fasteners: Nonmagnetic stainless screws, bo s and rivets of standard type and <br />sizes. <br />B. Power Ventilators: <br />1. Electrical: Provide factory -wired non -fusible type disconnect switch at motor in <br />fan housing. Provide thermal overload protection in fan motors. Provide conduit <br />chases within the unit for electrical connection. <br />2. Dampers: Provide gravity actuated louvered dampers in curb bases or wall sleeves <br />as required. <br />3. Provide power ventilators with AMCA certified rating in accordance with ACMA <br />standards and tested in accordance with UL 705 Power Ventilators: <br />PART 3 - EXECUTION <br />3.01 Inspection: The installer must examine conditions under which power ventilators are to be <br />installed, and notify the Architect in writing of conditions detrimental to proper <br />completion of the work. <br />3.02 Installation <br />A. General: Except as otherwise indicated or specified, install ventilators in accordance with <br />manufacturers installation instructions and recognized industry practices to insure that <br />ventilators serve their intended function. <br />B. Furnish exhaust fans with performance and capacities as listed on the design drawings. <br />Section 15891 Ductwork: <br />PART 1 GENERAL <br />1.01 Fibrous Glass Ductwork <br />A. General: The finished duct system shall meet the requirements of NFPA 90A by complying <br />with the requirements of Underwriters Laboratory Standard for Safety UL181 for Class I <br />arid Florida energy code, latest addition Air Duct. <br />1) Dimensions shown on the plan are finished inside dimensions. Fabrication and <br />installation shall conform to the manufacture?s recommendations and to the requirements <br />of the latest edition of the SMACNA Fibrous Glass Duct Construction Standard. <br />2) Grooves and shiplaps shall be made using sppecific tools and/or machines designed <br />for that purpose. Ends shall mate so that s iplaps meet flush without ridges or rough <br />edges. <br />B. Delivery and Storage of Materials: Deliver all materials and/or fabricated duct sections and <br />fittings to the job site and store in a safe dry placewith all labels in tact and legible. Use <br />all means necessary at the job site to protect materials from dust, dirt, moisture and <br />physical damage before, during and after installation, and to protect the installed work. <br />1.02 Sheet Metal Ductwork (An option by the owner) <br />A. This Contractor shall furnish and install all sheet metal work in connection with the <br />heating, cooling and ventilating systems. Provide prime quality sheet steel, galvanized <br />ductwork, lock -forming with double locked seams of the following thickness: <br />UQ to 12" wide 26 USSG <br />13 to 30" wide 24 gauge <br />31" to 54" wide 22 gauge <br />55" to 84" wide 20 gauge <br />85" to 96" wide 18 gauge <br />B. Round Ductwork shall conform to the following: <br />Up to 12"O round 26 gauge <br />13" to 18" round 24 gauge <br />19" to 28" round 22 gauge <br />29" to 36" round 20 gauge <br />PART 2 PRODUCTS:: <br />A. Insulated Duct Systems: <br />1) All supply and Return ducts and related fittin s of a J§" span or less operating at <br />pllus or minus 2 inches W.G. shall bg fabricated Irom 1 1 minimum super -duct rated. <br />Owen Corning Fiberglass duct board.( Min. R-6.0 . <br />2) The facing shall be foil-kraft laminate reinforced <br />B. Closure Materials: <br />�rressure <br />All �jooints, whether made in the shop or in the field, shall be stapled with minimum <br />. outward clinching steel staples and sealed with a UL181 listed closure system. <br />sensitive tapes shall be identified by the tape manufacturer?fs "name, date of <br />manufacturer and product name/number. Tapes shall be at least 2 r� wide. <br />2) As an alternative closure system, one of the U.L. listed 3"wide heat sealable tape <br />closure may be used in all applications expect in bonding to sheet metal. Heat sealing <br />equipment must be capable of maintaining a temperature of 550 degree F at the duct <br />surface. Staples may be omitted when closures are made by machine using heat sealable <br />tape. <br />3) Mastics as listed by Owens -Corn in Fiberglass and appplied in conjunction with 3" <br />wide glass fabric tape, shall be used o seal duple board to steel metal ducts an/or <br />equipment where operating pressures are over 1 W. G. <br />PART 3 EXECUTIONS: <br />Inspection: <br />1 � Prior to all work of this section, carefully inspect the installed work of other trades <br />and verify that such work is complete to the point where duct system installation may <br />5Coperly be started. <br />Z Verify that the duct system may be installed in accordance with project drawings <br />and Owens-Corning installation instructions. <br />B. Closure: <br />1) Flaps on all field joints shall be stapled 2" on center with minimum ? outward <br />clinching staples near the edge of the flap. On fitting join where stop trig flaps cannot be <br />d f f in length sFiall be ed. Tabs <br />include as part of the construction, tape tabs o 6 to 8us <br />s all be centered over the joint, a minimum of one tab per duct side on/or 12 on center. <br />2� On field joints, all taping surfaces shall be wiped clean before sealing. Oil and <br />grease contaminated surfaces shall be cleaned with a solvent recommended by the tape <br />3anufacturer. <br />) Mastics, when used, shall be applied in accordance with application instructions on <br />the container. <br />4) Mechanical fasteners of the type shown in Construction Standard shall be used to <br />connect the duct board to the sheet metal. <br />C. Hanging: <br />11The duct system shall be supported at all fitting and at a maximum recommended by <br />ACNA standards. <br />2,) Hangers shall be minimum I" x 2" x I" x 22 gaga galvanized channel supported by <br />1 wide by 22 ga. Or heavier straps, 'A" rods, or 12 gaga hanger wires, where local <br />codes permit. Al?f hanger systems must be capable of wit'hstandmg a load of three times <br />the an load. <br />D. Reinforcement: All ducts must be reinforced per manufacturer's recommendation to <br />erevent balloonin , collapsing or sagging. <br />E. Accessories: Boors coils, dampers, registers, grills, diffusers air forming vanes air <br />volume extractors and other accessories shall be installed as detailed in the SMANA <br />Fibrous Glass Duct Ygt struction Standard. All 90 degree elbows shall contain air turning <br />vanes spaced at 3 A maximum intervals, mounted in accordance with the vane <br />manufacturers instructions. If air volume extractors or splitter dampers are required on <br />side take -off and split duct connections, they shall be fabricated using appropriate <br />hardware. <br />F Inspection: <br />1) Upon completion of duct system installation and before operation is to commence, <br />visually inspect the system and verify that it has been correctly installed. <br />2) Open all system dampers and turn on fans to blow all scraps and other loose <br />material out of the duct system. Allow for a means of removal of such material. <br />G. Check duct system to ensure there are no air leaks through joints, at reinforcement <br />locations or through tears or punctures of the air barrier facing. If tears or punctures <br />found, repair these using one of the U.L. approved closure systems. <br />NOTE: All duct work sizes called for on the Plans are inside dimension and do not <br />reflect allowance for internal insulation. If fibrous glass duct work is used, sizes <br />must be increased accordingly. <br />H. Flexible Connections: Provide flexible connections in all connections between air handling <br />equipment and duct. Fabricate collars of Neoprene coated glass fabric, fire, water and <br />weather resistant, approyjmotelYY"4 long and install with g0ficient slack. Secure <br />rectan ular collars with I x 1/S flat bars fastened at 8 intervals or with slip joint. Tightly <br />crimp abric into joint. <br />I. Support of Ductwork: Ductwork shall be supported from the building structure. Install <br />malleable <br />Ilea le iron inserts in concrete duringconstruction. <br />n. Where the construction is steel <br />'n ductwork shall not be <br />I attached to beams channels joints; etc. frame, steel clamps shall be a ) , <br />supported by the finished ceiling or other building components than the structure <br />Section 15910 Support of Ductwork: <br />Ductwork shall be supported from the building structure. Install malleable iron inserts in concrete <br />during construction. Where the construction is steel frame, steel clamps shall be attached to <br />beams, channels, joists, etc. Ductwork shall not be supported by the finished ceiling or other <br />building components than the structure. Support shall be in accordance with the following <br />schedules: <br />Section 15936 Air Outlets and Inlets: <br />PART 1 GENERAL <br />A. Description of Work <br />1) Extent of air outlets and inlets is indicated by drawings and schedules and the <br />requirements of this section. <br />2) Air outlets and inlets required for this project include: <br />1. Diffusers. <br />2. Registers and grilles. <br />3. Door grilles. <br />4. Louvers. <br />5. Air intakes. <br />B. Ceiling Air Diffusers: <br />1) General: Expect as otherwise indicated provide manufacturers standard ceiling air <br />ddiffusers where shown of size, shape, capacity and type indicated' constructed of materials <br />and components as indicated, and as required for complete installation. <br />2) Performance: Provide ceiling air diffusers that have, as minimum, temperature and <br />velocity traverses, throw and drop, and noise criteria ratings for each size device as listed <br />irl manufacturer's current data. <br />3). Ceiling Compatibility. Provide diffusers with border styles that are specifically <br />manufactured to fit into ceiling module with accurate fit and adequate support. Refer to <br />general construction drawings and specifications for type of ceiling systems, which contain <br />e ch type of ceiling air diffuser. <br />43 Type:. Provide ceiling diffusers of type, capacity, and performance and with <br />a cessories and finishes as listed on air distribution schedule, or approved equal. <br />5� Insulation: Provide insulated blanket by manufacturer of grille on back of each <br />ceiling grill where installed in ceiling. <br />C. WALL REGISTERS AND GRILLES <br />1) General: Except as otherwise indicated, provide manufacturer's standard wall <br />registers and grilles where shown; of size shape, capacity and type indicated; constructed <br />of materials and components as indicated and as required for complete installation. <br />2) Performance: Provide wall registers and grilles that have, as minimum, temperature <br />and velocity traverses, throw and drop, and noise criteria ratings for each size device as <br />listed in manufacturers current data. <br />3) Wall Compatibility. Provide registers and grilles with border styles that are <br />compatible with adjacent wall systems and that are specifically manufactured to fit into <br />wall construction with accurate fit and adequate support. Refer to general construction <br />drawings and specifications for types of wall construction which will contain each type of <br />wall register and grille. <br />4) Types: Provide wall registers and grilles of type, capacity, and with accessories and <br />fi ishes as listed on Air Distribution Schedule. <br />5� Manufacturer: Subject to compliance with requirements, provide wall registers and <br />grilles by one of the following: <br />Price Manufacturing <br />Krueger Mfg. Co. <br />Titus Products Div., Philips Industries, Inc. <br />Tuttle & Bailey series by Hart & Cooley. <br />Metalaire, Metal Industries, Inc. <br />D. Louvers: <br />1) Except as otherwise indicated, provide manufacturer's standard louvers where <br />shown; of size, shape capacity and type indicated; constructed of materials and <br />c m onents as indicated, and as required for complete installation. <br />2) Performance: Provide louvers that have rrlaximum free area, and minimum pressure <br />drop for each type as listed in manufacturers current data, complying with louv2r <br />schedule. <br />3) Substrate Compatibility. Provide louvers with frame and sill styles that are <br />compatible with adjacent substrate, and that are specifically manufactured to fit into <br />construction openings with accurate fit and adequate support for weatherproof <br />installation. Refer to general construction drawings and specifications for types of <br />substrate which will contain each type of louver. <br />MECHANICAL NOTES: <br />1. ALL MECHANICAL WORKS AND AND INSTALLATIONS SHALL COMPLY <br />WITH FLORIDA BUILDING/MECHANICAL CODES, 2004 W/2006 UPDATE EDITION. <br />2' THESE DRAWINGS ARE DIAGRAMMATIC AND ARE PROVIDED TO CONVEY <br />THE INTENT OF T1 E DESIGN. CONTRACTOR IS REQUIRED TO FIELD VERIFY <br />THE EXISTING CONDITIONS AND SHALL CONSULT WITH THE <br />ARCHITECT/ENGINEER OR HIS REPRESENTATIVE CONCERNING FIELD <br />CONDITIONS THAT PRECLUDE THE CONSTRUCTION OF THESE PLANS. <br />MODIFICATIONS DUE TO FIELD CONDITIONS SHALL BE MADE ONLY <br />AFTER THE ARCHITECT/ENGINEER OR HIS REPRESENTATIVE HAS GIVEN <br />HIS APPROVAL <br />3. COORDINATE DIFFUSER AND GRILLE LOCATIONS WITH OTHER TRADES. <br />4. ALL AIR CONDITIONING AND HEATING DUCT WORK SHALL BE CONSTRUCTED OF <br />FIBERGLASS DUCT BOARD (R-6.0) IN ACCORDANCE WITH SMCANA STANDARDS <br />, SEAMS SHALL BE STAPLED OR TAPED AND SEALED WITH GLASS FABRIC <br />N IMBEDDED I MASTIC. USE OF PRESSURE SENSITIVE TAPES AS THE ONLY DUCT <br />CLOSURE METHOD IS PROHIBITED. DUCTWORK SHALL BE SUPPORTED WITH 1 1/2" <br />WIDE GALVANIZED CHANNEL, STRAPPED TO STRUCTURE WITH 1-1/2" WIDE, 18 <br />GAUGE GALVANIZED STEEL BANDS. WITH BANDS SHALL BE SECURED DIRECTLY <br />TO THE STRUCTURE USING SCREWS, RIVETS, OR BOLTS. MAXIMUM DISTANCE <br />BETWEEN SUPPORTS SHALL BE PER SMACNA AND FMC STANDARDS. <br />FLEXIBLE DUCT WORK SHALL BE CONSTRUCTED OF U.L CLASS I POLYESTER <br />LINED, METAL HELIX SUPPORTED, INSULATED FIBERGLASS FLEXIBLE DUCT (R-6.0). <br />DUCT WORK SHALL BE SUPPORTED WITH 1-1/2" WIDE, 18 GAUGE GALVANIZED <br />STEEL BANDS. BANDS SHALL BE SECURED DIRECTLY TO THE STRUCTURE USING <br />SCREWS RIVETS, OR BOLTS. MAXIMUM DISTANCE BETWEEN SUPPORT SHALL BE <br />5'-0" WITH MAXIMUM ALLOWABLE DUCT DROOP IS 1 INCH IN 10 FEET. <br />5. ALL EXHAUST AND OUTSIDE AIR DUCT TO BE SHEET METAL MATERIAL <br />6. ALL NEW DUCTWORK TO BE CONSTRUCTED AND INSTALLED IN ACCOR- <br />DANCE WITH ASHRAE GUIDE AND SMACNA STANDARDS AND FL CODES. <br />7. COORDINATE ALL MECHANICAL WORK, INCLUDING EQUIPMENT, DUCTWORK <br />OR PIPING, WITH ARCHITECT AND OTHER TRADES PRIOR TO WORK. <br />8. ALL INSULATION, MATERIAL, COVERINGS, ADHESIVES, VAPOR BARRIERS <br />NOT TO EXCEED 25 AND SMOKE DEVELOPMENT NOT TO EXCEED 50. <br />9. ALL DUCTWORK SHALL BE INSTALLED PER THE LATEST SMACNA MANUAL <br />AND TAPES SHALL CONFORM TO NFPA 90A, FLAMESPREAD CLASSIFICATION <br />10. ALL EQUIPMENT INSTALLATION SHALL COMPLY WITH THE MANUFACTURER'S <br />SPECIFICATIONS AND CLEARANCE REQUIREMENTS. <br />11. CONTRACTOR SHALL VISIT THE PROJECT SITE PRIOR TO THE BIDDING. <br />12. UNLESS OTHERWISE NOTED. INSTALL DUCTWORK AS HIGH AS POSSIBLE <br />OF STRUCTURE. COORDINATE DUCT ELEVATION WITH OTHER TRADES AND <br />MODIFY AS REQUIRED TO CLEAR OBSTRUCTIONS. <br />13. ALL DUCT SIZES SHOWN AS INSIDE DIMENSION. IN CASE OF CONFLICT <br />WITH STRUCTURAL MEMBER, DUCT CROSS -SECTIONAL AREA SHOULD <br />BE KEPT THE SAME. <br />14. COORDINATE T-STAT LOCATIONS WITH OWNER. <br />15. ALL DUCTWORK MATERIALS AND INSTALLATION SHALL CONFORM TO <br />APPLICABLE STATE, COUNTY AND LOCAL CODES. DUCT MATERIAL SHALL <br />BE ALL NEW AND IN GOOD CONDITION. <br />16. AIR CONDITIONING UNIT SIZES AND CAPACITIES SHALL BE AS SCHEDULED. <br />17. UNITS SHALL HAVE NON-FERROUS COILS AND FINS. UNITS SHALL BE <br />EQUIPPED WITH ELECTRIC RESISTANCE HEATING, HERMETIC COMPRESSORS. <br />18. PROVIDE FIRE S'TAT IN RETURN AIR DUCT. <br />19. PROVIDE SINGLE POINT CONNECTION FOR ELEC. HEATER AND RTU'S UNITS. <br />20. PROVIDE 1" - 30% EFFICIENCY THROWAWAY FILTERS, FARR 30/30 OR <br />EQUAL. <br />21. ALL FIBERGLASS DUCT AND DUCT WRAP SHALL BE SEALED WITH GLASS <br />FAB AND MASTIC. <br />22• PROVIDE ALL REQUIRED STARTERS AND LOCAL DISCONNECT AS PART <br />THE PACKAGED EQUIPMENT. FIELD COORDINATE WITH ELECTRICAL WORK. <br />MECHANICAL LEGENDS: <br />® SUPPLY AIR DIFFUSER - ARROWS INDICATE <br />PATTERN. NO PATTERN SHOWN EQUALS 4-WAY. <br />Z RETURN AIR GRILLE <br />® EXHAUST GRILLE <br />SUPPLY AIR SLOT <br />23. THIS CONTRACTOR SHALL COORDINATE CLEARANCE AROUND UNIT AND EXACT <br />DIMENSIONS OF WALL OPENINGS WITH ARCHITECTURAL AND STRUCTURAL <br />PLAN PRIOR TO CONSTRUCTION AND WITH GENERAL CONTRACTOR DURING <br />CONSTRUCTION. <br />24. CONTRACTOR TEST AND BALANCE AIR DISTRIBUTION CFM AS LISTED. <br />25. ALL FLOOR, WALL AND ROOF OPENING SHALL BE SEALED <br />WITH 3M FIRE SAFE MATERIAL OR EQUAL <br />26. CONTRACTOR SHALL NOT CUT STRUCTURAL WORK IN A MANNER <br />RESULTING IN A REDUCTION OF LOAD CARRYING CAPACITY OR LOAD/ <br />DELETION RATION. NOTIFY ARCHITECT OF ALL STRUCTURAL CUTS <br />PRIOR TO EXECUTION TO OBTAIN APPROVAL <br />27. CONDENSATE DRAIN LINES SHALL BE PVC PIPING SCHEDULES 40 <br />PVC PIPING WITH SOLVENT WELD JOINTS. PROVIDE A CONDENSATE <br />TRAP AT A/C UNIT. THE TRAP SHALL BE <br />CONSTRUCTED IN ACCORDANCE WITH THE MANUFACTURERS <br />REQUIREMENTS. PROVIDE CAPPED TEES ON THE ENTERING AND <br />LEAVING SIDE OF THE TRAP FOR CLEANOUTS AND PROVIDE <br />ADDI <br />TIONAL CLEANOUTS AT EVERY CHANGE OF DIRECTION AND <br />EVERY 30 FEET OF PIPING LENGTH. CONDENSATE DRAINS SHALL <br />BE INSULATED, PIPING TO BE SUPPORT PER FMC REQUIREMENTS. <br />28. DISPOSE OF AIR CONDITIONING CONDENSATE AS NOTED ON THE PLANS. <br />FIELD ROUTE DRAIN LINES IN A MANNER AS REQUIRED BY LOCAL CODE <br />REQUIREMENTS AND IN A MANNER MEETING THE APPROVAL OF THE <br />AUTHORITY HAVING JURISDICTION. CONDENSATE DRAIN DISCHARGE TO <br />BE MIN. 1 FOOT FROM EXTERIOR WALL, FIELD VERIFY. <br />29. ALL HVAC SYSTEMS SHALL BE BALANCED TO THE AIR QUANTITIES SHOWN <br />AGAINST THE ACTUAL STATIC PRESSURE REQUIREMENTS OF THE INSTALLED <br />SYSTEMS. CONTRACTOR SHALL PROVIDE POSITIVE MEANS FOR BALANCING EACH <br />INDIVIDUAL AIR OUTLET AND INLET. <br />30. UNFORESEEN CONDITIONS MAY EXIST AND NEW WORK MAY NOT BE FIELD <br />LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COOPERATION WITH OTHER <br />TRADES IN ROUTING AND/OR D BURIAL DEPTHS AS DETERMINED DURING <br />CONSTRUCTION AND AS DIRECTED BY THE ARCHITECT/ENGINEER MAY BE <br />NECESSARY. IT IS INTENDED THAT SUCH DEVIATIONS SHALL BE CONSIDERED <br />AS PART OF THIS CONTRACT. FIELD VERIFY ALL CONDITIONS AND NOTIFY <br />THE ARCHIETCT/ENGINEER WITH ANY DEVIATIONS. <br />31. PROVIDE ALL ELECTRICAL WORK REQUIRED TO PLACE THE NEW <br />MECHANICA SYSTEM IN OPERATION. ALL WORK SHALL BE IN <br />ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND LOCAL CODE <br />REQUIREMENTS. ELECTRICAL REQUIREMENTS INCLUDE MECHANICALLY <br />RELATED CONTROL WIRING. FURNISH DUCT SMOKE DETECTOR. <br />32. ALL EQUIPMENT INSTALLED OUTSIDE SHALL COMPLY WITH WIND RESISTANCE <br />REQUIREMENTS AND WIND LOADS OF FLORIDA BUILDING CODES 2004. <br />CH.3 AND 16. <br />33. DO NOT SCALE THESE DRAWINGS. <br />34. GENERAL CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTARY STEEL <br />REQUIRED TO SUPPORT ALL MECHANICAL EQUIPMENT. <br />35. PROVIDE SUPPLY AIR FLEXIBLE DUCT CONNECTION WITH SPIN IN FITTING <br />EQUIPPED WITH BALANCING VOLUME DAMPER. <br />36. INSTALL CLEANOUTS AT EVERY 90-DEGREE TURN ON AIR CONDITIONING <br />CONDENSATE DRAIN ONES. <br />37. PROVIDE ALL EXHAUST AIR DUCTS WITH BACK DRAFT DAMPER. <br />38. WHERE DIFFERENCES OCCUR BETWEEN WORKING CLEARANCE AND ACTUAL <br />PROPOSED LOCATION Tl NOTIFY ARCHITECT IMMEDIATELY BEFORE ANY WORK. <br />39• THE CONTRACTOR SHALL VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE <br />BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, <br />SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT <br />WILL AFFECT EXECU11ON OF THE WORK. SUBMISSION OF PROPOSAL WILL <br />INDICATE THAT SUCH EXAMINATION BY THE CONTRACTOR HAS BEEN MADE. <br />LATER CLAIMS FOR LABOR EQUIPMENT OR MATERIALS REQUIRED BECAUSE <br />OF DIFFICULTIES ENCOUNTERED WILL NOT BE RECOGNIZED. <br />40. FIELD VERIFY ALL MECHANICAL SYSTEM ELECTRICAL'S REQUIREMENTS WITH <br />ELECTRICAL PANELS AND DRAWINGS TO ENSURE CORRECT REQUIREMENTS. <br />NOTIFY ARCHITECT/ENGINEER IF ANY DISREFENCIES. <br />41. INSTALL FIRE DAMPER AND FIRE/SMOKE DAMPER FOR DUCT PRNETATiNG <br />RATED PARTITION, REFER TO ARCHITECTURAL DRAWINGS FOR FIRE/SMOKE <br />RATING, FIELD VERIFY. <br />o <br />RETURN AIR SLOT <br />120 <br />ROUND DUCTWORK. DIAMETER INDICATED IN INCHES. <br />20/12 <br />RECTANGULAR DUCTWORK NET FREE AREA. SIZE INDICATED IN <br />INCHES, FIRST NUMBER IS SIDE SHOWN. <br />DASHED LINES INDICATE ACOUSTICAL LINER. SEE <br />SPECIFICATIONS FOR THICKNESS. <br />OFtTTM <br />FLEXIBLE DUCT <br />_f <br />® <br />SUPPLY OR OUTSIDE AIR DUCT <br />RETURN AIR DUCT. <br />® <br />RELIEF OR EXHAUST AIR DUCT. <br />''% OR N <br />TURNING VANES <br />RADIUS DUCTWORK ELBOW - <br />ROUND OR RECTANGULAR. <br />RECTANGULAR DUCTWORK BRANCH TAKE -OFF <br />WITH 45 DEGREE BRANCH INLET. <br />FLARED SPIN -IN WITH DAMPER AND <br />d�:, <br />FLEX DUCT (DIFFUSER CONNECTION). <br />ROUND DUCT BRANCH TAKE -OFF FROM <br />RECTANGULAR MAIN WITH CONICAL TAP. <br />0:m <br />DUCTWORK SIZE TRANSITION. <br />DUCTWORK SIZE TRANSITION FROM <br />RECTANGULAR TO ROUND <br />nH n DUCT MOUNTED HUMIDIFIER <br />S POINT OF CONNECTION OR DISCONNECTION <br />�---- , MOTORIZED DAMPER <br />DAMPER TYPE: VOLUME DAMPER <br />SD -SMOKE DAMPER <br />BD -COUNTER BALANCE <br />BACKDRAFT DAMPER <br />SB - SECURITY BARS Q THERMOSTAT <br />FSD -FIRE/SMOKE DAMPER <br />NO MARK INDICATES FIRE DAMPER <br />i <br />a) O <br />c <br />N <br />C <br />• - <br />0 <br />L. <br />O0) <br />c <br />C <br />c <br />C7 <br />C1 <br />U <br />0 <br />D U <br />u <br />N <br />:t: <br />0 So. 0 <br />12 a, <br />r- <br />tU <br />W ci <br />_J V <br />�"r` <br />W , <br />;R -� W <br />z � <br />w <br />ax M <br />r`i <br />W <br />0 <br />U W <br />Z rn a as t•- v <br />v XL,�Q_~a <br />W <br />(c copyright <br />revisions: <br />OI- �T 110 <br />L0 Nil <br />O <br />' ' O <br />u7 <br />0 <br />00 00 N <br />I <br />00 <br />14- ,I- <br />0 a <br />O <br />s <br />a <br />a) 00 <br />:0 C14 <br />c M <br />N <br />> 0 <br />0 _0 <br />N O <br />c <br />v C) <br />�-0 <br />c <br />X O <br />L0 in O <br />N <br />,,I- <br />LO <br />" M <br />0 <br />> (:3 <br />N -p <br />O O <br />v N <br />0)s <br />11O >. <br />%O -C <br />O W <br />NO N <br />drawn: HD <br />checked : HD <br />date: 03-21-08 <br />prof. no: P07-15 <br />M = 1 <br />