ROOF TOP PACKAGE UNIT SCHEDULE
<br />UNIT NO.
<br />(MARK)
<br />TOTAL
<br />SUPPLY
<br />(CFM)
<br />OUTSIDE
<br />AIR
<br />(CFM)
<br />EXT./TOT.
<br />S.P.
<br />(IN. W.G.)
<br />TOTAL
<br />CAPACITY
<br />(MBH)
<br />SENSIBLE
<br />CAPACITY
<br />(MBH)
<br />HEATING
<br />CAPACITY
<br />(MBH)
<br />ELEC. HEAT
<br />(KW/STEPS)
<br />E.A.T.(°F)
<br />L.A.T.(°F)
<br />INDOOR FAN
<br />MCA/MFS
<br />ELECTRICAL
<br />DATA
<br />(V/PH/HZ)
<br />EER
<br />DESIGN
<br />MANUF.
<br />MODEL
<br />NOTES
<br />D.B./W.B.
<br />D.B,/W.B.
<br />DRIVE
<br />HP
<br />RPM
<br />RTU-1
<br />4,500
<br />1,200
<br />0.35/-
<br />1 51 .0
<br />87.1
<br />92.2
<br />27.0/2
<br />80.8/70.0
<br />58.0/57.2
<br />BELT
<br />3.0
<br />778
<br />108/1 1 0
<br />208/3/60
<br />9.8
<br />TRANE
<br />TCD 1 51 D3
<br />1 ,2,4
<br />RTU-2
<br />2,400
<br />360
<br />0.40/-
<br />73.8
<br />39.2
<br />46.1
<br />13.5/1
<br />78.1 /66.5
<br />58.0/56.6
<br />BELT
<br />1.0
<br />909
<br />53.1 /60
<br />208/3/60
<br />1 1 .2
<br />TRANE
<br />TSC072E3
<br />1 ,2,4
<br />RTU-3
<br />2,900
<br />820
<br />0.55/-
<br />93.2
<br />52.1
<br />46.1
<br />13.5/1
<br />81 .7/70.8
<br />58.0/57.1
<br />BELT
<br />2.0
<br />856
<br />54.8/60
<br />208/3/60
<br />1 1 .2
<br />TRANE
<br />TSC092E3
<br />1 ,2,3,4
<br />NOTES:
<br />1. PROVIDE 7 DAY PROGRAMMABLE THERMOSTATS LOCATION
<br />SHOWN ON PLAN.
<br />2. PROVIDE 100% OUTSIDE AIR ECONOMIZER.
<br />3. PROVIDE BAROMETRIC RELEIF DAMPER HOOD.
<br />4. PROVIDE WITH MANUFACTURER'S ROOF CURB.
<br />AIR BALANCE SCHEDULE
<br />UNIT NO,
<br />(MARK)
<br />SUPPLY
<br />CFM
<br />RETURN
<br />CFM
<br />❑UTSIDE
<br />CFM
<br />EXH,
<br />CFM
<br />TRANSFER
<br />CFM
<br />RELIEF
<br />CFM
<br />EXFIL,
<br />CFM
<br />RTU-1
<br />4,500
<br />3,300
<br />1,200
<br />0
<br />1,000
<br />0
<br />200
<br />RTU-2
<br />2,400
<br />2,040
<br />360
<br />0
<br />300
<br />0
<br />60
<br />RTU-3
<br />2,900
<br />2,400
<br />820
<br />0
<br />500
<br />320
<br />0
<br />EF-1
<br />0
<br />0
<br />0
<br />2,100
<br />0
<br />0
<br />0
<br />EF-2
<br />0
<br />0
<br />0
<br />1,000
<br />0
<br />0
<br />0
<br />EF-3
<br />0
<br />0
<br />0
<br />300
<br />0
<br />0
<br />0
<br />SF-1
<br />0
<br />0
<br />1,600
<br />0
<br />0
<br />0
<br />0
<br />VENTILATION RATE TABLE
<br />BASIS: ASHRAE STANDARD 62.1 -2004
<br />RTU-1
<br />DINNING ROOM: 1,804 SQ. FT. X 0.18 CFM/SQ. FT. = 324.7 CFM
<br />116 PEOPLE X 7.5 CFM/PERSON = 870 CFM
<br />TOTAL OUTSIDE AIR REQUIRED: 1,194.7 CFM
<br />RTU-2
<br />DINNING ROOM: 560 SO. FT. X 0.18 CFM/SQ. FT. = 100.8 CFM
<br />35 PEOPLE X 7.5 CFM/PERSON = 260 CFM
<br />TOTAL OUTSIDE AIR REQUIRED: 360.8 CFM
<br />RTU-3
<br />KITCHEN: 39 PEOPLE X 20 CFM/PERSON = 780 CFM
<br />DINNING ROOM: 95 SO. FT. X 0.18 CFM/SQ. FT. = 17.1 CFM
<br />3 PEOPLE X 7.5 CFM/PERSON = 22.5 CFM
<br />TOTAL OUTSIDE AIR REQUIRED: 819.6 CFM
<br />EXHAUST FAN SCHEDULE
<br />UNIT NO.
<br />(MARK)
<br />CFM
<br />EXT. S.P.
<br />(IN H20)
<br />MOTOR
<br />RPM
<br />MAX.
<br />SONES
<br />DRIVE
<br />TYPE
<br />DESIGN
<br />MANUF.
<br />MODEL
<br />NOTES
<br />V/PH/HZ
<br />HP
<br />EF-3
<br />1 3001
<br />0.25
<br />1 1 5/1 /60
<br />1 /1 2
<br />1,550
<br />7.2
<br />DIRECT
<br />INLINE
<br />GREENHECK
<br />SQ-80-D
<br />1,2
<br />1. PROVIDE WITH UNIT MOUNTED DISCONNECT AND GRAVITY BACKDRAFT DAMPER.
<br />2. INTERLOCK FAN WITH RTU-1 .
<br />AIR DISTRIBUTION DEVICE SCHEDULE
<br />MARK
<br />SERVICE
<br />DESCRIPTION
<br />MATERIAL
<br />MANUF.
<br />MODEL
<br />NOTES
<br />S-1
<br />SUPPLY
<br />SQUARE CONE DIFFUSERS
<br />ALUMINUM
<br />EH PRICE
<br />SCD
<br />1 ,2,3
<br />R-1
<br />RETURN
<br />LOUVERED FACE RETURN
<br />ALUMINUM
<br />EH PRICE
<br />630
<br />1 ,2,3
<br />E-1
<br />EXHAUSTI
<br />LOUVERED FACE EXHAUST
<br />ALUMINUM
<br />EH PRICE
<br />630
<br />1 ,2,3
<br />1, PROVIDE OPPOSED BLADE VOLUME DAMPER.
<br />2. STANDARD BAKED -ON WHITE ENAMEL FINISH.
<br />3. PROVIDE 24X24 CEILING MODULE AS REQUIRED
<br />1
<br />1
<br />1
<br />1
<br />1
<br />I
<br />1
<br />1
<br />1
<br />DESIGN CONDITIONS
<br />SUMMER
<br />WINTER
<br />DB('F)
<br />WB(`F)
<br />DB('F)
<br />OUTDOOR
<br />91.4
<br />77.5
<br />36.6
<br />INDOOR
<br />75.0
<br />62.6
<br />68.0
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1
<br />1 1
<br />1
<br />i
<br />1
<br />1
<br />1
<br />1
<br />KITCHEN HOOD SCHEDULE
<br />EXHAUST
<br />SUPPLY
<br />DESCRIPTION
<br />MARK
<br />VOLUME
<br />(CFM)
<br />SP
<br />(IN WC)
<br />DUCT COLLAR
<br />VELOCITY (FT/M)
<br />FILTER FACE
<br />VELOCITY (FT/M)
<br />VOLUME
<br />(CFM)
<br />SP
<br />(IN WC)
<br />DUCT COLLAR
<br />VELOCITY (FT/M)
<br />LENGTH
<br />WIDTH
<br />H-1
<br />2,100
<br />0.50
<br />1,700
<br />175
<br />1,600
<br />0.1
<br />750
<br />10'-0"
<br />7'-0"
<br />FAN SCHEDULE
<br />UNIT NO.
<br />(MARK)
<br />CFM
<br />S.P.
<br />(IN H20)
<br />SF-1
<br />1,600
<br />0.40
<br />EF-1
<br />2,100
<br />1 0.90
<br />EF-2
<br />11,000
<br />1 0.40
<br />1
<br />i
<br />NOTE: KITCHEN HOOD SCHEDULE IS PROVIDED
<br />FOR REFERENCE ONLY. KITCHEN HOODS WILL 1
<br />BE PROVIDED BY THE OWNER. REFER TO HOOD 1
<br />MANUFACTURER'S DRAWINGS FOR COORDINATION. 1
<br />1
<br />1
<br />HVAC LEGEND:
<br />GENERAL NOTES:
<br />SUPPLY, RETURN, AND EXHAUST DUCT
<br />1. INSTALLATION SHALL COMPLY WITH ALL LOCAL, STATE AND FLORIDA ENERGY CODES.
<br />2. CONTRACTOR SHALL INSTALL ALL EQUIPMENT, PIPING AND DUCTWORK SUCH THAT
<br />FLEXIBLE SUPPLY AND RETURN DUCT
<br />MANUFACTURERS' RECOMMENDED CLEARANCES ARE MET FOR ALL ACCESS PANELS, COILS, MOTORS,
<br />FANS, BELTS, FILTERS, AND AIR INTAKES.
<br />SUPPLY GRILLE
<br />3. PROVIDE ACCESS PANELS IN ALL NON -ACCESSIBLE CONSTRUCTIONS (INCLUDING CEILING, WALLS,
<br />RETURN AND EXHAUST GRILLE
<br />ETC.) SIZED AND LOCATED AS REQUIRED TO PROVIDE PROPER SERVICE ACCESS IN ACCORDANCE
<br />WITH THE MANUFACTURERS RECOMMENDATION FOR ALL HVAC EQUIPMENT INCLUDING DAMPERS.
<br />COLLAR TAKE -OFF WITH DAMPER
<br />AIR DISTRIBUTION NOTES:
<br />OPPOSED BLADE VOLUME DAMPER
<br />1. DUCTWORK SHALL BE FABRICATED, INSTALLED AND INSULATED PER "SMACNA" STANDARDS
<br />AND ALL LOCAL AND STATE CODES.
<br />UNDERCUT DOOR 3/40
<br />2. DUCT SIZES ARE INSULATED SHEET METAL SIZES AND ARE "CLEAR" INSIDE DIMENSIONS. ALL DUCT
<br />3/4"
<br />SHALL BE EXTERNALLY INSULATED WITH 2.2" THICK KNAUF DUCTWRAP WITH R=6.0 VALUE.
<br />TT
<br />THERMOSTAT
<br />3. ROUND RUNOUTS TO GRILLES (AND BACKS OF GRILLES) TO BE WRAPPED WITH 2.2" THICK KNAUF
<br />DUCTWRAP WITH R=6.0 AND FSK JACKET (OR EQUAL).
<br />SD
<br />SMOKE DETECTOR
<br />4. FLEXIBLE DUCTWORK TO BE ATCO RUBBER PRODUCTS (OR EQUAL) INSULATED FLEX DUCT WITH
<br />R=6.0 VALUE.
<br />X-1
<br />DIFFUSER TAG X = S-SUPPLY
<br />CFM
<br />X = R-RETURN
<br />5. CONTRACTOR SHALL VERIFY CLEARANCE SPACE AVAILABLE, OFFSETS REQUIRED, STRUCTURAL
<br />INK
<br />NK = NECK SIZE X = E-EXHAUST
<br />OPENINGS, AND WORK BY OTHER TRADES PRIOR TO FABRICATION OF DUCTWORK. COORDINATE
<br />WITH ROOF TRUSSES/STRUCTURE. PRESSURE TEST ALL DUCTWORK FOR LEAKS. RETURN DUCT
<br />X-#
<br />EQUIPMENT TAG
<br />SHALL BE TESTED UNDER NEGATIVE PRESSURE.
<br />X = EF - EXHAUST FAN
<br />X = H - KITCHEN HOOD
<br />EQUIPMENT NOTES:
<br />X = SF - SUPPLY FAN
<br />X = RTU - PACKAGE UNIT
<br />1. PROVIDE FULL SIZE INSULATED CONDENSATE DRAINS FROM ALL UNITS TO NEAREST OUTLET.
<br />2. PROVIDE A TRAP ON ALL CONDENSATE DRAIN OUTLETS. SLOPE ALL CONDENSATE DRAIN PIPING
<br />DETAIL NUMBER
<br />1 /8" INCH PER FOOT.
<br />#
<br />3. CONTRACTOR SHALL INSTALL ALL EQUIPMENT, PIPING AND DUCTWORK SUCH THAT MANUFACTURERS'
<br />RECOMMENDED CLEARANCES ARE MET FOR ALL ACCESS PANELS, COILS, MOTORS, FANS, BELTS,
<br />#
<br />FILTERS, AND AIR INTAKES.
<br />SHEET NUMBER
<br />WHERE SHOWN
<br />4. ALL SMOKE DETECTION DEVICES SHALL BE INSTALLED PER LOCAL AND STATE CODES.
<br />MECHANICAL PERMIT DOCUMENTS©2007
<br />AIRCO MECHANICAL, INCORPORATEDjl_�
<br />DESIGN.
<br />Certificate of Authorization No.: 27407
<br />BUILD.
<br />N 0
<br />RC
<br />THESE MECHANICAL DOCUMENTS, DESIGNS, NOTES,
<br />DETAILS, CONCEPTS ARE THE
<br />AIRCO
<br />-
<br />SOLUTION.
<br />PROPERTY OFME
<br />SOLE CHANICAL, INC. AND
<br />M E C H A N I c A L_ -
<br />SHALL NOT BE REPRODUCED, RE -USED OR COPIED FOR
<br />OR HERFE MR°tPETCMC.
<br />WRITTEN IOF`JASSON
<br />6334 118TH AVENUE N. P: 727-547-9700
<br />CONSENTS.
<br />M.M.
<br />BY THE ENGINEER
<br />RIGHTS ARE RESEREWITH
<br />LARGO, FLORIDA 33773 F: 727-547-9754
<br />RECORD IN ACCORDANCEALL
<br />U.S. COPIRIGHTOAND
<br />PATUSEENT
<br />VVM.AIRCO-MECHANICAL.COM
<br />WILL BESPROSECUTEDITODTHEPRODUCTINULL EXTOENTND
<br />OF
<br />THE LAW.
<br />N
<br />'t
<br />r
<br />aj N
<br />V
<br />U
<br />°°
<br />C
<br />0 co
<br />CU coo
<br />�w
<br />a
<br />�
<br />U04
<br />JT
<br />N
<br />U
<br />J
<br />0
<br />00
<br />C
<br />Lw
<br />a
<br />>
<br />..
<br />o
<br />2
<br />C;
<br />co
<br />C
<br />s
<br />N
<br />0
<br />o�Q
<br />_
<br />`C
<br />a
<br />J"
<br />06LL
<br />E
<br />UL
<br />a
<br />0
<br />O
<br />N
<br />0
<br />0
<br />0
<br />0
<br />_
<br />c
<br />Q
<br />N
<br />J
<br />O�
<br />O
<br />J
<br />o
<br />_J
<br />J
<br />U
<br />0
<br />M
<br />0
<br />0
<br />0
<br />N
<br />Q
<br />N
<br />It
<br />M
<br />CM
<br />OLL
<br />z
<br />o
<br />Q
<br />N
<br />mp
<br />Q
<br />0
<br />CO
<br />0
<br />UJ
<br />o
<br />o
<br />�
<br />U
<br />Z]
<br />(�
<br />00
<br />(�
<br />J
<br />U_
<br />J
<br />W
<br />N
<br />Revisions:
<br />W
<br />J �
<br />Z
<br />Cl W
<br />_ (D
<br />W W
<br />� J
<br />Q Q
<br />U_
<br />Z U)
<br />Q W
<br />=0
<br />W Z
<br />2
<br />Project Number
<br />163
<br />Date
<br />11-16-07
<br />Sheet Number
<br />M -4