1
<br />M2.0
<br />►•'FAU lli
<br />HVAC DETAIL
<br />SCALE: NOT TO SCALE
<br />l'�
<br />1A X 1A ISM
<br />MOMP
<br />Ni uwi
<br />.=.
<br />b
<br />WD
<br />1 RTU DETAIL
<br />M 2.0 / SCALE: NOT TO SCALE
<br />or tr �Wll
<br />DINATE DUCT ROUTING
<br />JGH OPEN WEB JOISTS.
<br />PROVIDE CHASE I1�
<br />H.V.A.C. DUCT TO
<br />ELECTRICAL ROOM.
<br />FLOOR FRAMING
<br />OFFICE AND
<br />ROOFTOP OHEAT
<br />PUMP
<br />M P
<br />UNIT
<br />SCHEO LE
<br />UNIT
<br />DESCRPTTON
<br />ST R
<br />c NG CAPACITY
<br />HEATING CAPACITY
<br />POWER
<br />TRANE MODEL
<br />REMARKS
<br />SUPPLY
<br />OA MIN
<br />TOTAL
<br />SENSIBLE
<br />KW
<br />OUTPUT
<br />MTR HP
<br />VOLTAGE
<br />MCA/MCOP
<br />RTU-1
<br />PACKAGED ROOFTOP UNIT W/ HEAT PUMP
<br />4000 CFM
<br />550 CFM
<br />0.5 IN
<br />121.0 MBH
<br />94.8 MBH
<br />9.59
<br />108 MBH
<br />2 HP
<br />208-3-60
<br />50.4/60
<br />WSC120A3
<br />1, 2, 3, 4, 5
<br />RTU-2
<br />PACKAGED ROOFTOP UNIT W/ HEAT PUMP
<br />4000 CFM
<br />550 CFM
<br />0.5 IN
<br />121.0 MBH
<br />94.8 MBH
<br />9.59
<br />108 MBH
<br />2 HP
<br />208-3-60
<br />50.4/60
<br />WSC120A3
<br />1, 2, 3, 4, 5
<br />REMARKS:
<br />1. PROVIDE UNIT WITH ROOF CURB, DISCONNECT, 115V GFI SERVICE OUTLET, AND LOW AMBIENT
<br />COOLING
<br />CONTROL.
<br />2. RTU'S FAN SHALL BE SET TO RUN IN CONTINUOUS MODE.
<br />3. COOLING/HEATING RATED AT 80/67 T AND AMBIENT 95 'F.
<br />4. PROVIDE RTU UNIT WITH ELECTRONIC PROGRAMMABLE THERMOSTAT.
<br />5. REFER TO SPECIFICATION FOR ADDITINAL INFORMATION.
<br />EXHAUST FAN
<br />SCHEDULE
<br />ELECTRICAL
<br />OPER
<br />MARK
<br />LOCATION
<br />MFR
<br />MODEL
<br />CFM
<br />S.P.
<br />WT
<br />REMARKS
<br />H.P.
<br />VOLT/PH/HZ
<br />IN W.G.
<br />LBS
<br />EF-1
<br />WOMENS RESTROOM
<br />LOREN COOK
<br />GC-164
<br />100
<br />0.625
<br />145 WATTS
<br />120 1 60
<br />15
<br />1,2,3,4
<br />EF-2
<br />MEN'S RESTROOM
<br />LOREN COOK
<br />GC-164
<br />100
<br />1 0.625
<br />1 145 WATTS
<br />120 1 60
<br />15
<br />1,2,3,4
<br />REMARKS:
<br />1. PROVIDE FACTORY INSTALLED DISCONNECT SWITCH AND BACKDRAFT DAMPER.
<br />2. CONNECT THE EXHAUST FAN TO THE LIGHT SWITCH
<br />3. PROVIDE GEMINI MODEL ROOF CAP.
<br />4. FAN SHALL BE INTERLOCKED WITH LIGHT SWITCH
<br />DIFFUSERS REGISTERS
<br />GRILLES
<br />& LOUVERS
<br />UNIT
<br />SIZE
<br />THROW
<br />MODEL
<br />OUTLET
<br />DAMPER
<br />FINISH
<br />FRAME
<br />REMARKS
<br />INCHES
<br />(1)
<br />CONNECTION
<br />(4)
<br />SA -A
<br />12X12
<br />4 WAY
<br />SMD 1 4A/B12/SR3
<br />10"
<br />YES
<br />WHITE
<br />SM
<br />1,2,3,4
<br />SA-B
<br />10x10
<br />2 WAY
<br />SMD/1 /4A/B1 2/SR3
<br />10"
<br />YES
<br />WHITE
<br />SM
<br />1,2,3,4
<br />REMARKS:
<br />1. E.H. PRICE.
<br />2. PROVIDE SQUARE TO ROUND NECK ADAPTER WITH DAMPER. EH PRICE MODEL SR3.
<br />3. INDEPENDENTLY SUPPORT ALL DIFFUSERS, REGISTERS, AND GRILLES FROM STRUCTURE.
<br />DO NOT REPLY ON CEILING TILE OR GRID.
<br />4. TB=LAY-IN TEE BAR OR SM=CUT-IN SURFACE MOUNTED W/FLANGE AS REQUIRED. FIELD VERIFY.
<br />GENERAL NOTES:
<br />1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL
<br />POSSIBLE CONDITIONS. IT IS INTENDED THAT A COMPLETE HVAC SYSTEM BE PROVIDED WITH
<br />ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS COMPLETELY COORDINATED
<br />WITH ALL DISCIPLINES. ALL MECHANICAL EQUIPMENT AND INSTALLATIONS SHALL CONFORM
<br />WITH THE REQUIREMENTS OF ALL STATE BUILDING CODES, THE NFPA 90A, 101 AND ALL
<br />LOCAL AUTHORITIES AND THESE CONTRACT DOCUMENTS. THESE ITEMS SHALL BE FURNISHED
<br />WITHOUT INCURRING ANY ADDITIONAL COST TO THE OWNER. THE WORD "PROVIDE" SHALL
<br />MEAN FURNISH AND INSTALL. CAREFULLY REVIEW ALL CONTRACT DOCUMENTS AND THE
<br />DESIGN OF OTHER TRADES BEFORE PREPARING SHOP DRAWINGS.
<br />2. PRIOR TO PURCHASING ANY MATERIALS OR STARTING ANY WORK, CONTRACTOR SHALL FIELD
<br />VERIFY ALL EXISTING CONDITIONS, DUCTWORK SIZES AND LOCATIONS, EQUIPMENT, ETC. SHOWN
<br />ON THE DRAWINGS OR AFFECTING THIS WORK AND SHALL REPORT ANY DEVIATIONS TO THE
<br />ARCHITECT.
<br />3. CONTRACTOR SHALL COORDINATE ELECTRICAL CHARACTERISTICS AND REQUIREMENTS OF ALL
<br />MECHANICAL EQUIPMENT WITH ELECTRICAL DRAWINGS PRIOR TO ORDERING EQUIPMENT OR
<br />SUBMITTING SHOP DRAWINGS, AND SHALL FURNISH EQUIPMENT WIRED FOR THE VOLTAGES
<br />SHOWN THEREIN.
<br />4. ALL MECHANICAL EQUIPMENT REQUIRING ELECTRICAL POWER SHALL BE INSTALLED WITH
<br />DISCONNECT SWITCHES AT EACH PIECE OF EQUIPMENT. COORDINATE SWITCH TYPE (FUSED OR
<br />NON -FUSED) WITH EQUIPMENT CHARACTERISTICS, MANUFACTURER'S RECOMMENDATIONS AND
<br />ELECTRICAL DRAWINGS.
<br />5. ALL REQUIRED CONTROL WIRING NOT SHOWN ON THE ELECTRICAL DRAWINGS SHALL BE
<br />INCLUDED AS PART OF THE MECHANICAL WORK.
<br />6. UNLESS NOTED OTHERWISE, STARTERS, SMOKE DETECTORS, TRANSFORMERS, CONTROLS AND
<br />CONTROL WIRING REQUIRED FOR ALL MECHANICAL SYSTEMS SHALL BE FURNISHED AND
<br />INSTALLED BY THE MECHANICAL CONTRACTOR.
<br />7. ALL FANS SUPPLYING MORE THAN 2000 CFM OF AIR TO ANY SPACE AND ALL RECIRCULATING
<br />FAN SYSTEMS SERVING AREAS OF EGRESS SHALL BE INSTALLED WITH A SMOKE DETECTOR IN
<br />THE SUPPLY DUCTWORK. THE SMOKE DETECTOR SHALL BE WIRED TO STOP THE FAN UPON
<br />DETECTION OF SMOKE, AND SIGNAL THE BUILDING FIRE ALARM CONTROL PANEL (IF BUILDING
<br />IS SO EQUIPPED). IF THE BUILDING IS NOT PROVIDED WITH A FIRE ALARM SYSTEM, THE
<br />SMOKE DETECTOR SHALL CAUSE A VISIBLE AND AUDIBLE ALARM SIGNAL IN A NORMALLY
<br />OCCUPIED AREA. SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE INDICATED VISUALLY OR
<br />AUDIBLY IN A NORMALLY OCCUPIED AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
<br />TROUBLE. IF A BUILDING FIRE ALARM SYSTEM IS INSTALLED, THE SMOKE DETECTOR SHALL BE
<br />FURNISHED BY THE FIRE ALARM SYSTEM CONTRACTOR, MOUNTED IN THE DUCT BY THE
<br />MECHANICAL CONTRACTOR, AND WIRED BY THE ELECTRICAL CONTRACTOR. IF A BUILDING FIRE
<br />ALARM SYSTEM IS NOT INSTALLED, THE SMOKE DETECTOR AND AUDIBLE/VISIBLE ALARM
<br />SHALL BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.
<br />8. INSTALL FIRE DAMPERS IN ALL RATED THROUGH WALLS, FLOOR AND CEILING PENETRATIONS.
<br />REFER TO THE ARCHITECTURAL DRAWINGS FOR LOCATIONS OR RATED AREAS. PROVIDE
<br />ACCESS DOORS IN DUCTWORK AT EACH FIRE DAMPER LOCATION. INSTALL SMOKE DAMPERS IN
<br />ALL DUCT PENETRATIONS THROUGH SMOKE RATED WALLS. WHERE DUCTS PENETRATE WALLS
<br />THAT CARRY BOTH FIRE AND SMOKE RATINGS, THE DAMPERS INSTALLED SHALL BE
<br />COMBINATION FIRE AND SMOKE DAMPERS. ALL DAMPERS SHALL BE U.L. LABELED.
<br />9. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S
<br />RECOMMENDATIONS.
<br />10. ALL MECHANICAL EQUIPMENT AND SYSTEMS SHALL BE GUARANTEED FOR A PERIOD OF ONE
<br />YEAR AFTER CERTIFICATE OF OCCUPANCY.
<br />11. EXHAUST DUCTWORK SHALL BE SHEET METAL AND SHALL NOT BE INSULATED UNLESS NOTED
<br />OTHERWISE.
<br />12. ALL DUCTWORK SHALL BE SUPPORTED BY THE BUILDING STRUCTURE AND SHALL NOT REST
<br />ON CEILING TILES OR CEILING STRUCTURE. DUCT SUPPORTS AND ATTACHMENT TO STRUCTURE
<br />SHALL BE AS PER SMACNA STANDARDS.
<br />13. FLEXIBLE DUCTWORK SHALL BE SIZED TO MATCH DEVICE NECK, PROVIDE ROUND GALVANIZED
<br />STEEL DUCT RUNOUTS TO MAINTAIN MAXIMUM FLEXIBLE DUCT OF 5'-0" LONG. FLEXIBLE
<br />DUCTWORK SHALL BE INSTALLED AS STRAIGHT AS POSSIBLE, AND SHALL BE ROUTED AND
<br />SUPPORTED WITHOUT FORMING CRIMPS OR OTHER AIR FLOW RESTRICTIONS. PROVIDE SQUARE
<br />TO ROUND ADAPTERS OR BOOTS TO CONNECT TO AIR DEVICE NECK WHEN REQUIRED.
<br />14. ROUND AND FLEXIBLE DUCTWORK SHALL BE CONNECTED TO MAIN DUCTS WITH SPIN -IN
<br />FITTINGS WITH AIR EXTRACTORS AND BALANCING DAMPERS.
<br />15. PORTIONS OF DUCTWORK VISIBLE THROUGH AIR DISTRIBUTION DEVICES IN FINISHED AREAS
<br />SHALL BE PAINTED FLAT BLACK.
<br />16. DUCTWORK DIMENSIONS SHOWN ON THE DRAWINGS ARE INSIDE CLEAR DIMENSIONS.
<br />CONTRACTOR SHALL ADJUST DUCT DIMENSIONS WHERE DUCT LINER IS USED M MAINTAIN
<br />INSIDE CLEAR DIMENSIONS SHOWN ON DRAWINGS.
<br />17. THE CONDENSATE SHALL DRAIN TO A SANITARY SEWER DRAIN TROUGH AN INDIRECT WASTE,
<br />STORM SEWER DRAIN OR AN APPROVED FRENCH DRAIN. THE APPROVED
<br />CORROSION -RESISTANT DISCHARGE PIPING SHALL NOT BE SMALLER THAN THE DRAIN PAN
<br />CONNECTION ON THE APPROVED EQUIPMENT AND SHALL MAINTAIN A MINIMUM HORIZONTAL
<br />SLOPE IN THE DIRECTION OF DISCHARGE OF NOT LESS THAN 1/8 UNIT VERTICAL IN 12 UNITS
<br />HORIZONTAL (17.).
<br />18. AFTER CONSTRUCTION, THE ENTIRE HVAC SYSTEM SHALL BE TESTED, ADJUSTED, AND
<br />BALANCED TO DELIVER THE AIR QUANTITIES SHOWN ON THE DRAWINGS. SUBMIT CERTIFIED
<br />TEST AND BALANCE REPORT TO ARCHITECT FOR APPROVAL.
<br />19. MANUAL OVER -RIDE CONTROL (EMERGENCY SHUT -DOWN) SWITCHES FOR ALL HVAC UNITS
<br />SHALL BE LOCATED IN LOCKING COVER ADJACENT TO FIRE ALARM ANNUNCIATOR PANEL OR
<br />OTHER LOCATION APPROVED BY LOCAL AUTHORITY HAVING JURISDICTION.
<br />20. ALL WORK SHALL BE COORDINATED AND PERFORMED WITH PRIOR APPROVAL FROM THE
<br />OWNER TO SUIT HIS OPERATING CONDITIONS.
<br />21. ANY WALL, FLOOR, OR CEILING SURFACE THAT IS DISTURBED DURING THE COURSE OF THE
<br />HVAC WORK SHALL BE REPAIRED TO MATCH NEW AND/OR EXISTING.
<br />22. CONTRACTOR SHALL COORDINATE THE INSTALLATION OF ALL MECHANICAL EQUIPMENT,
<br />DUCTWORK, ETC. TO FIT WITHIN THE SPACE ALLOWED BY THE ARCHITECTURAL AND
<br />STRUCTURAL CONDITIONS. CUTTING OR OTHERWISE ALTERING ANY STRUCTURAL MEMBERS
<br />SHALL NOT BE PERMITTED WITHOUT WRITTEN PERMISSION FROM THE ARCHITECT.
<br />23. MOUNT THERMOSTATS 48" AFF UNLESS NOTED OTHERWISE. PROVIDE CLEAR LOCKING COVER
<br />ASSEMBLIES FOR ALL THERMOSTATS.
<br />24. LOCATIONS OF GRILLES, REGISTERS, & DIFFUSERS SHOWN ON THE DRAWINGS ARE
<br />APPROXIMATE. COORDINATE EXACT LOCATIONS WITH LIGHTS, CEILING GRID, SPRINKLER HEADS
<br />ETC.
<br />25. SLOPE ALL HORIZONTAL GAS FLUE PIPING MINIMUM 1/4" PER FOOT.
<br />26. GAS FLUE PIPING SHALL BE TYPE "B" DOUBLE WALL FLUE, U.L. LISTED, EXCEPT FOR INDUCED
<br />OR FORCED DRAFT EQUIPMENT, WHICH SHALL BE TYPE PS, METALBESTOS OR EQUAL.
<br />27. TERMINATE ALL GAS FLUE PIPING THRU ROOF WITH TALL CONE FLASHING, STORM COLLAR,
<br />AND WEATHER CAP.
<br />28. PROVIDE ACCESS PANELS IN NON -ACCESSIBLE CEILINGS AND IN WALL STRUCTURE TO ALLOW
<br />ADEQUATE ROOM FOR MAINTENANCE OF EQUIPMENT AND BALANCING OF SYSTEM.
<br />Greenberghrrow
<br />1430 West Peachtree Street
<br />Atlanta, GA 30309
<br />t: 404 6014000 f. 404 (601 3980
<br />COPYRIGHT NOTICE
<br />This drawing is the property of the above
<br />referenced Professional and is not to be used
<br />for any purpose other than the specific
<br />project and site named herein, and cannot
<br />be reproduced in any manner without the
<br />express written permission from the Professional
<br />ISSUE/REVISION RECORD
<br />DATE DESCRIPTION
<br />12/5/07 ISSUED FOR PERMIT
<br />T i%rv, c-oA 4- t6007==
<br />PROFESSIONAL SEAL
<br />PROFESSIONAL IN CHARGE
<br />JUSTIN HARDY, P.E. 67084
<br />PROJECT MANAGER
<br />STEVE ALLEN
<br />QUALITY CONTROL
<br />AMY HADLOW P.E.
<br />DRAWN BY
<br />STEVE ALLEN
<br />PROJECT NAME
<br />NAPA AUTO
<br />PARTS
<br />ZEPHYRHILLS
<br />FLORIDA
<br />6901 GALL BOULEVARD
<br />41APA
<br />r-
<br />PROJECT NUMBER
<br />20070208
<br />SHEET TITLE
<br />MECHANICAL
<br />DETAILS AND
<br />SCHEDULES
<br />SHEET NUMBER