FIRE ALARM
<br />CONTROL UNIT
<br />•
<br />DEDICATED 120V
<br />G ~j) 20 AMP CIRCUIT
<br />REPLACE CONTROL PANEL ALL EXISTING
<br />DEVICES REMAIN THE SAME
<br />N2-01
<br />115cd
<br />C
<br />M
<br />N2.02
<br />N2.03
<br />115cd
<br />115cd
<br />N2.04 EOL
<br />C
<br />C
<br />110cd
<br />8S1BO
<br />M001 D002 M002 M003
<br />N3.01 N3.02 N3.03
<br />115cd 115cd 115cd N3.04 N3.05 N3.06 N3.07 N3.08 N3.09 EOL
<br />C C C 110cd 15cd 15cd 110cd p 110cd 75cd
<br />ANN•1
<br />ANNUNCIATOR
<br />•
<br />4UX1.01
<br />WF
<br />M005 M006 M007 M008 M009
<br />A- AIM lA i r l V' - F�-- A- - AIM V- AIM
<br />FBO FBO
<br />�SS� VS
<br />I
<br />i
<br />l
<br />N1.01 N1.02 N1-03 EOL
<br />75cd 75cd 115cd
<br />C WP C
<br />_,,_4
<br />SYSTEM RISER
<br />1 N.T.S.
<br />NAPCO CELLULAR DIALER
<br />NA -.�
<br />Total stand by current 0.08500
<br />X Stand by hours 24
<br />Stand by amp/hours 2.04
<br />Total Alarm Current 0.40
<br />X alarm Minutes (5)/60 0.083
<br />AlarmTotal amp/hours 0.03
<br />Total Amp/hours 2.07
<br />X Derating factor of 20% 1.2
<br />Minimum Battery Size 2.49
<br />Battery Selected
<br />COMMUNICATOR CALCULATIONS
<br />2 N.T.S.
<br />BATTERY CALCULATION
<br />(SECONDARY POWER SOURCE REQUIREMENTS)
<br />STANDBY CURRENT (AMPS)
<br />SECONDARY ALARM CURRENT (AMPS)
<br />QTY
<br />PART NO.
<br />DESCRIPTION
<br />CURRENT DRAW (A)
<br />TOTAL (A)
<br />CURRENT DRAW (A)
<br />TOTAL
<br />FIRE ALARM CONTROL
<br />PANEL COMPONENTS
<br />1
<br />6808 MAIN BOARD
<br />PANEL MAIN BOARD SK
<br />0.17
<br />0.17
<br />0.365
<br />0.365
<br />PROTOCOL
<br />CIRCUIT
<br />SYMBOL
<br />QTY
<br />PART NO
<br />DESCRIPTION
<br />CURRENT DRAW (A)
<br />TOTAL (A)
<br />CURRENT DRAW (A)
<br />TOTAL (A)
<br />ANN
<br />IFAAI
<br />1
<br />5860R
<br />ANNUNCIATOR
<br />0.02
<br />0.02
<br />0.025
<br />0.025
<br />AUX1
<br />cE
<br />1
<br />SLE-LTEVI-CFB-PS
<br />Wireless Commercial Fire
<br />0.071
<br />0.071
<br />0.2
<br />0.2
<br />Alarm Communicator
<br />FBO
<br />1
<br />DUCT DETECTOR
<br />0
<br />0
<br />0
<br />0
<br />AIM
<br />5
<br />SK-MONITOR
<br />ADDRESSABLE MONITOR
<br />0.000375
<br />0,001875
<br />0.000375
<br />0.001875
<br />MODULE
<br />M33
<br />O
<br />2
<br />SK-PHOTO
<br />ADDRESSABLE
<br />PHOTOELECTRIC SMOKE
<br />0.0003
<br />0.0006
<br />0.0003
<br />0.0006
<br />DETECTOR
<br />ADDRESSABLE MANUAL
<br />4
<br />SK-PULL-DA
<br />PULL STATION,
<br />0.000375
<br />0.0015
<br />0.000375
<br />0.0015
<br />DOUBLE -ACTION
<br />2-Wire Horn Strobe,
<br />Wp
<br />1
<br />P2RK
<br />Standard cd, Outdoor 75cd
<br />0
<br />0
<br />0.176
<br />0.176
<br />N1
<br />1
<br />PC2RL
<br />2-Wire, Horn Strobe; Red
<br />0
<br />0
<br />0.143
<br />0.143
<br />C
<br />75cd
<br />1
<br />PC2RL
<br />2-Wire, Horn Strobe, Red
<br />0
<br />0
<br />0.187
<br />0.187
<br />C
<br />115cd
<br />1
<br />P2RL
<br />2-Wire, Horn Strobe, Red
<br />0
<br />0
<br />0.162
<br />0,162
<br />110cd
<br />N2
<br />3
<br />PC2RL
<br />2-Wire, Horn Strobe, Red
<br />0
<br />0
<br />0.187
<br />0.561
<br />C
<br />115cd
<br />1
<br />P2RL
<br />2-Wire, Horn Strobe, Red
<br />0
<br />0
<br />0.121
<br />0.121
<br />75cd
<br />3
<br />P2RL
<br />2-Wire, Horn Strobe, Red
<br />0
<br />0
<br />0.162
<br />0.486
<br />N3
<br />11 0cd
<br />3
<br />PC2RL
<br />2-Wire, Horn Strobe; Red
<br />0
<br />0
<br />0.187
<br />0.561
<br />C
<br />115cd
<br />2
<br />SRL
<br />Strobe, Red 15cd
<br />0
<br />0
<br />0.043
<br />0.086
<br />TOTAL STANDBY (A)
<br />0.264975
<br />TOTAL ALARM (A)
<br />3.076975
<br />REQUIRED STANDBY TIME = 24 HOURS
<br />REQUIRED ALARM TIME = 5 MINUTES
<br />SECONDARY STANDBY LOAD (A)
<br />0.264975
<br />24
<br />I 6.36
<br />SECONDARY ALARM LOAD (A)
<br />3.076975
<br />0,08
<br />1 0.26
<br />STANDBY AND ALARM SUBTOTAL (AMP HOURS)
<br />6.62
<br />DERATING FACTOR
<br />1.2
<br />SECONDARY LOAD REQUIREMENTS (AMP HOURS)
<br />7.94
<br />PROVIDE (2) 12V 12AH BATTERIES
<br />*BATTERY BOX SIZE CAPACITY NOT SPECIFIED. REFER TO MANUFACTURER DOCUMENTATION.
<br />AUX1 LUMP SUM REPORT
<br />CIRCUIT SETTINGS
<br />TOTALS
<br />Starting Calculation Voltage:
<br />20A
<br />Max. Voltage Drop:
<br />0
<br />Min. Operational Voltage:
<br />16
<br />End Of Line Voltage:
<br />20.4
<br />Max. Circuit Current (A):
<br />3
<br />Voltage Drop Percent:
<br />0.02 %
<br />Wire Resistance (t2/kFt):
<br />3.07
<br />Total Circuit Current (A):
<br />0.2
<br />Circuit Wiring Properties 'P' 14/2 FPLP/R (AUX) 14 AWG, 2 Cond. Solid Copper FPLP/R Unshielded
<br />Total Circuit Length (Ft):
<br />3
<br />Spare Current (A):
<br />2.8
<br />Distance measured using drawn segment lengths with 10,00 % additional length calculated
<br />Total Circuit Resistance (Q):
<br />0.019699
<br />Spare Current (A) Percent:
<br />93.33 %
<br />DEVICE TOTALS
<br />Symbol
<br />Part No.
<br />Description
<br />Qty.
<br />Device Current (A)
<br />Total Current (A)
<br />c-
<br />SLE-LTEVI-CFB-PS
<br />Wireless Commercial Fire
<br />Alarm Communicator
<br />1
<br />0.2
<br />0.2
<br />Calculation Methods:
<br />Total Resistance (D) = Wire Resistance (O/Ft) x 2 x Total Circuit Length (Ft)
<br />Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A)
<br />N1 LUMP SUM REPORT
<br />CIRCUIT SETTINGS
<br />TOTALS
<br />Starting Calculation Voltage:
<br />20.4
<br />Max. Voltage Drop:
<br />0.34
<br />Min. Operational Voltage:
<br />16
<br />End Of Line Voltage:
<br />20.06
<br />Max. Circuit Current (A):
<br />3
<br />Voltage Drop Percent:
<br />1.67 %
<br />Wire Resistance (.0/kFt):
<br />3.07
<br />Total Circuit Current (A):
<br />0.506
<br />Circuit Wiring Properties: 'V' 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
<br />Total Circuit Length (Ft):
<br />110
<br />Spare Current (A):
<br />2.494
<br />Distance measured using drawn segment lengths with 10.00 % additional length calculated
<br />Total Circuit Resistance (0):
<br />0.673903
<br />Spare Current (A) Percent:
<br />83.13 %
<br />Symbol
<br />PartNo.
<br />Description
<br />Qty,
<br />Device Current (A)
<br />Total Current (A)
<br />C
<br />PC2RL
<br />2-Wire, Horn Strobe, Red
<br />75cd
<br />1
<br />0.143
<br />0.143
<br />DEVICE TOTALS
<br />Wp
<br />P2RK
<br />2-Wire Horn Strobe, 1
<br />Standard cd, Outdoor 75cd
<br />1
<br />0.176
<br />0.176
<br />C
<br />PC2RL
<br />2 Wire, Horn Strobe, Red
<br />115cd
<br />1
<br />0.187
<br />0.187
<br />Calculation Methods:
<br />Total Resistance (0) = Wire Resistance (4/Ft) x 2 x Total Circuit Length (Ft)
<br />Total Voltage Drop = Total Resistance (0) x Total Circuit Current (A)
<br />N2 LUMP SUM REPORT
<br />CIRCUIT SETTINGS
<br />TOTALS
<br />Starting Calculation Voltage:
<br />20A
<br />Max. Voltage Drop:
<br />0.74
<br />Min. Operational Voltage:
<br />16
<br />End Of Line Voltage:
<br />19.66
<br />Max. Circuit Current (A):
<br />3
<br />Voltage Drop Percent:
<br />3.63 %
<br />Wire Resistance (t2/kFt):
<br />3.07
<br />Total Circuit Current (A):
<br />0.723
<br />Circuit Wiring Properties: 'V 14/2 FPLP/R (NAC) 14 AWG, 2 Cond. Solid Copper FPLP/R Analog Unshielded
<br />Total Circuit Length (Ft):
<br />167
<br />Spare Current (A):
<br />2.277
<br />Distance measured using drawn segment lengths with 10.00 % additional length calculated
<br />Total Circuit Resistance (0):
<br />1.025244
<br />Spare Current (A) Percent:
<br />75.90 %
<br />DEVICE TOTALS
<br />Symbol
<br />Part No.
<br />Description
<br />Qty.
<br />Device Current (A)
<br />Total Current (A)
<br />P2RL
<br />2-Wire, Horn Strobe, Red
<br />110cd
<br />1
<br />0.162
<br />0.162
<br />C
<br />PC2RL
<br />2-Wire, Horn Strobe, Red
<br />115cd
<br />3
<br />0187
<br />0.561
<br />Calculation Methods:
<br />Total Resistance (0) = Wire Resistance ((2/Ft) x 2 x Total Circuit Length (Ft)
<br />Total Voltage Drop = Total Resistance (Q) x Total Circuit Current (A)
<br />N3 LUMP SUM REPORT
<br />CIRCUIT SETTINGS
<br />TOTALS
<br />Starting Calculation Voltage:
<br />20A
<br />Max. Voltage Drop:
<br />1.87
<br />Min. Operational Voltage:
<br />16
<br />End Of Line Voltage:
<br />18.53
<br />Max. Circuit Current (A):
<br />3
<br />Voltage Drop Percent:
<br />9.18 %
<br />Wire Resistance (0/kFt):
<br />3.07
<br />Total Circuit Current (A):
<br />1.254
<br />Circuit Wiring Properties. 'V 14/2 FPLP/R (NAC) 14 AWG, 2 Cond, Solid Copper FPLP/R Analog Unshielded
<br />Total Circuit Length (Ft):
<br />243
<br />Spare Current (A):
<br />1.746
<br />Distance measured using drawn segment lengths with 10.00 % additional length calculated
<br />Total Circuit Resistance (0),
<br />1,492773
<br />Spare Current (A) Percent:
<br />58.20 %
<br />Symbol
<br />Part No.
<br />Description
<br />Qty.
<br />Device Current (A)
<br />Total Current (A)
<br />SRL
<br />Strobe, Red 15cd
<br />2
<br />0.043
<br />0.086
<br />DEVICE TOTALS
<br />P2RL
<br />2-Wire, Horn Strobe, Red
<br />75cd
<br />1
<br />0.121
<br />0.121
<br />P2RL
<br />2-Wire, Horn Strobe, Red
<br />110cd
<br />3
<br />0.162
<br />0.486
<br />C
<br />PC2RL
<br />2-Wire, HornStrobe, Red
<br />cd
<br />3
<br />0.187
<br />0.561
<br />Calculation Methods:
<br />Total Resistance (D) = Wire Resistance (Q/Ft) x 2 x Total Circuit Length (Ft)
<br />Total Voltage Drop = Total Resistance (Q) x Total Circuit Current (A)
<br />�F
<br />Commercial
<br />4221 W JOHN CARPENTER FWY
<br />IiIN, T. 77
<br />Web.- dt,Com/'com m rci l
<br />FRESH
<br />ENCOUNTER INC.
<br />I SAVE A LOT #468 .
<br />7320 GALL BLVD
<br />FIRE LA Y TF
<br />PREPARED BY:
<br />This fire alarm shop drawing was prepared
<br />for equipment application only. The
<br />informatian' contained herein' is intended
<br />to aid in, the instailation;of this system. No
<br />design changes have been made,to the
<br />engineer of recort3s contract documents.
<br />JODY CONGLETON, SET
<br />FIIREEA ARM6SYSTEMS LVL IV `Try GJ�l�~f%Jir
<br />EXPIRES 06/01/2024 1/9/2023
<br />REVISIONS
<br />NO.
<br />DATE
<br />REVISION
<br />BY:
<br />�'•.
<br />BY:
<br />BY:
<br />41
<br />BY:
<br />-
<br />5
<br />BY:
<br />BY:
<br />7.
<br />BY:
<br />-
<br />PREPARED BY: J LC
<br />CHECKED BY:
<br />PROJECT MANAGER:
<br />DATE: 01 /09/2
<br />PROJECT NO:
<br />TITLE:
<br />RISER AND
<br />CALCULATIONS
<br />SHEET:
<br />Fool