IL <br />0 <br />MECHANICAL SPECIFICATIONS <br />SCOPE: THE CONTRACTOR SHALL VISIT THE SITE AND EXAMINE THE DRAWINGS AND SPECIFICATIONS BEFORE SUBMITTING A PROPOSAL. <br />ALL WORK SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODES SEVENTH EDITION (2020), WITH ALL AMENDMENTS, AND LOCAL CODES AND ORDINANCES. INSTALLATION <br />SHALL COMPLY WITH THE CODE REFERENCED STANDARDS SET BY NFPA, ASHRAE, ASPE, SMACNA, NEC AND UL. THE SYSTEMS, EQUIPMENT, DEVICES AND ACCESSORIES SHALL BE <br />INSTALLED, FINISHED, TESTED AND ADJUSTED FOR CONTINUOUS AND PROPER OPERATION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR HIS WORK FITTING IN PLACE AND SHALL <br />COORDINATE WITH OTHER TRADES TO AVOID INTERFERENCE WITH THEIR WORK. THE INFORMATION GIVEN HEREIN AND ON THE DRAWINGS IS AS EXACT AS COULD BE SECURED, BUT <br />ITS EXTREME ACCURACY IS NOT GUARANTEED. THE DRAWINGS ARE DIAGRAMMATIC, INTENDED TO SHOW GENERAL ARRANGEMENT, CAPACITY AND LOCATION OF VARIOUS COMPONENTS, <br />EQUIPMENTS, AND DEVICES. IF WORK IS REQUIRED IN A MANNER TO MAKE IT IMPOSSIBLE TO PRODUCE FIRST CLASS WORK, OR SHOULD DISCREPANCIES APPEAR AMONG THE <br />CONTRACT DOCUMENTS, OR BETWEEN THE CONTRACT DOCUMENTS AND THE MANUFACTURER'S RECOMMENDATIONS,THE CONTRACTOR SHALL REQUEST INTERPRETATION BEFORE <br />PROCEEDING WITH WORK. CONTRACTOR SHALL FURNISH AND INSTALL ALL MINOR ITEMS WHICH ARE OBVIOUSLY AND REASONABLY NECESSARY TO COMPLETE THE INSTALLATION <br />WHETHER OR NOT SPECIFIED IN THE DOCUMENTS. <br />REQUIRED COORDINATION: ALL WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN DUCTS AND PIPING (INCLUDING DIVIDED DUCTS) AND TRANSITIONS AROUND <br />OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE OWNER. <br />CONSTRUCTION PLANS: IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY AND SHOULD NOT BE SCALED. <br />REQUIRED ACCESS: CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT AND DEVICES THAT REQUIRE REPLACEMENT, SERVICING, ADJUSTING OR MAINTENANCE SHALL BE LOCATED TO <br />ALLOW EASY ACCESS AND SPACE FOR REMOVAL OF INTERNAL ASSEMBLIES, IF REQUIRED. CONTRACTOR SHALL PROVIDE ACCESS PANELS WHERE REQUIRED TO ALLOW ACCESS, EVEN <br />IF NOT INDICATED ON 'THE DRAWINGS AT NO ADDITIONAL COST TO OWNER. <br />WIND RESISTANCE: ALL EQUIPMENT, APPLIANCE AND SUPPORTS LOCATED EXTERIOR OF THE FACILITY SHALL BE INSTALLED TO RESIST WIND LOADS AS DETAILED IN THE BUILDING <br />CODE. <br />CUTTING AND PATCHING: ALL OPENINGS AROUND DUCT OR PIPE PENETRATIONS THROUGH SMOKE OR FIRE RATED FLOORS, CEILINGS OR WALLS SHALL BE SEALED AIRTIGHT WITH <br />MATERIALS HAVING A RATING EQUAL TO THE MATERIAL OF THE WALL, CEILING OR FLOOR PENETRATED. <br />EQUIPMENT TAGS: ALL EQUIPMENT WILL HAVE A PERMANENTLY FIXED ENGRAVED PHENOLIC LABEL CORRESPONDING TO THE EQUIPMENT TAG ON THE ENGINEER'S DRAWINGS. <br />FIRESTOPPING: UL APPROVED MATERIALS AND METHODS SHALL PROTECT THE PENETRATIONS OF FIRE AND/OR SMOKE RATED WALLS, CEILINGS OR FLOORS. THE RATING OF THE <br />FIRESTOPPING SHALL EQUAL THE RATING OF THE RATED ASSEMBLY. ALL INSULATION SHALL HAVE COMPOSITE FIRE AND SMOKE HAZARD RATINGS AS TESTED BY PROCEDURE ASTM <br />E-84, NFPA-225, UL-723 NOT EXCEEDING: <br />FLAME SPREAD 25 <br />SMOKE DEVELOPED 50 <br />FUEL DISTRIBUTED 50 <br />ACCESSORIES SUCH AS ADHESIVE, MASTIC, CEMENTS AND TAPES SHALL HAVE THE SAME COMPONENT RATING AS LISTED ABOVE. <br />START-UP: CONTRACTOR SHALL STARTUP ALL EQUIPMENT AND FOLLOW THE MANUFACTURER'S START-UP PROCEDURES. <br />OPERATING AND MAINTENANCE DATA: SUBMIT THREE COPIES OF MANUFACTURER'S OPERATING AND MAINTENANCE INSTRUCTIONS AND SPARE PARTS LIST FOR EACH PIECE OF <br />EQUIPMENT. <br />CONDENSATE DRAIN PIPING: CONDENSATE DRAIN PIPING SHALL BE PVC TYPE DWV. DRAINS SHALL BE PITCHED NOT LESS THAN 1 PERCENT. RUNS SHALL BE AS SHORT AS <br />POSSIBLE WITHOUT ANY DIPS TO TRAP WATER AND INTERFERE WITH PROPER DRAINAGE. PROVIDE TRAPS AND CLEANOUTS AT DRAIN PAN CONNECTIONS. RUN CONDENSATE DRAIN <br />PER PLANS. INSULATE CONDENSATE LINE INSIDE BUILDINGS WITH 1" ARMAFLEX (ASTM E-84). <br />DIMENSIONAL DATA: ALL DUCTWORK DIMENSIONS SHOWN ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. <br />SUPPLEMENTARY SUPPORTS: CONTRACTOR SHALL PROVIDE ALL SUPPLEMENTARY STEEL REQUIRED TO SUSPEND MECHANICAL EQUIPMENT AND MATERIALS, IN ORDER TO PROVIDE A <br />"VIBRATION -FREE" RIGID INSTALLATION. <br />DUCTWORK - GENERAL: FABRICATE AND INSTALL ALL DUCTWORK AND DUCT ACCESSORIES IN ACCORDANCE WITH THE LATEST EDITION OF APPLICABLE SMACNA STANDARDS, THE <br />LATEST NFPA STANDARDS, AND THIS SPECIFICATION. THE MOST STRINGENT OF THESE SHALL BE THE MINIMUM STANDARD. MINIMUM OF 1" PRESSURE CLASS RATING FOR ALL <br />DUCTWORK. <br />ALL RECTANGULAR SUPPLY AND RETURN DUCTWORK TO BE R-6.0 RIGID FIBERGLASS DUCTSOARD (UL-181 AND 181A) WITH CLEANABLE AIRSIDE SURFACE AND EPA -APPROVED <br />BIOCIDE (ANTI -MICROBIAL AGENT) IMPREGNATED IN MATTED AIR -SIDE SURFACE. <br />KITCHEN HOOD GREASE EXHAUST DUCTWORK SHALL BE PREFABRICAGTED DOUBLE -WALL ROUND STAINLESS STEEL DUCTWORK. <br />OPTION FOR KITCHEN GREASE DUCT IS 16-GAUGE BLACK STEEL, WELDED LIQUIDTIGHT PER NFPA-96, AND INSULATED WITH 2-HOUR LISTED FIRE BARRIER TO MAINTAIN ZERO <br />CLEARANCES TO COMBUSTIBLES AND LIMITED COMBUSTIBLES. <br />ALL RESTROOM EXHAUST DUCTWORK SHALL BE GALVANIZED SHEET METAL STEEL OF LOCKFORMING GRADE CONFORMING TO ASTM A653 AND ASTM A924. <br />DUCTWORK INSTALLATION: ALL INTERIOR DUCTWORK SHALL BE SEALED TO SMACNA CLASS (B) REQUIREMENTS WITH UL-181 MASTIC. PROVIDE DOUBLE THICKNESS TURNING VANES IN <br />ALL NINETY (90) DEGREE SQUARE ELBOWS. <br />CONTRACTOR SHALL FURNISH AND INSTALL ALL DUCT OFFSETS AS REQUIRED TO CLEAR INTERFERENCES WITH EXISTING BUILDING STRUCTURE, PIPES AND ELECTRICAL CONDUITS. <br />FURNISH AND INSTALL ALL MISCELLANEOUS STEEL SUPPORTS REQUIRED FOR HANGING AND SUPPORTING DUCTWORK UNLESS OTHERWISE NOTED. <br />VOLUME DAMPERS: DAMPERS SHALL BE PROVIDED IN THE BRANCHES OF THE DUCT SYSTEMS WHERE SHOWN ON DRAWINGS AND AS REQUIRED TO PROPERLY REGULATE THE VOLUME <br />OF AIR DELIVERED TO OR WITHDRAWN FROM THE OUTLETS. <br />FLEXIBLE DUCTWORK: FLEXIBLE DUCTWORK MAY BE USED FOR THE FINAL RUNOUTS TO AIR OUTLETS, AND SHALL BE SIZED TO MATCH AIR OUTLET NECK. FLEXIBLE DUCTS SHALL <br />NOT EXCEED 8-FEET LENGTHS. NO FLEXIBLE DUCTS SHALL PENETRATE FIRE -RATED WALLS OR CEILINGS. FLEXIBLE DUCTS SHALL COMPLY WITH THE PROVISIONS OF UL-181 CLASS <br />1 AIR DUCT MATERIAL. DUCTS SHALL BE FACTORY MADE AND COMPOSED OF: AN INNER FIBERGLASS WOVEN LINER, ENCAPSULATED HELIX COIL, A FIBERGLASS INSULATING BLANKET <br />AND OUTER VAPOR BARRIER OF FIBERGLAS REINFORCED METALIZED FILM LAMINATE. PROVIDE THERMAFLEX MK-C FLEXIBLE DUCT OR APPROVED EQUAL (MIN. OF R-6.0). CARE IS <br />TO BE TAKEN THAT ALL RUNOUTS OF FLEXIBLE DUCTS ARE INSTALLED AS STRAIGHT AS PRACTICAL AND FASTENED SO AS TO ELIMINATE AIR LEAKAGE. THE INSTALLATION SHALL <br />CONFORM TO THE TECHNIQUES SHOWN IN THE UL APPROVED AND FACTORY -SUPPLIED INSTRUCTIONS. <br />INSULATION: ASSURE ALL DUCTWORK IS SEALED PRIOR TO INSTALLING INSULATION. <br />ALL METAL SUPPLY, RETURN, AND FRESH AIR (OUTSIDE AIR) DUCTWORK SHALL BE WRAPPED WITH 2" THICK FIBERGLASS BLANKET INSULATION WITH FSK (ASJ) FACING, MINIMUM <br />INSTALLED R VALUE OF 6.0, AND FLAME SPREAD/SMOKE DEVELOPED RATINGS OF 25/50 BY ASTM E-84. INSTALL INSULATION ON DUCTWORK USING ADHESIVE AND/OR WELD PINS <br />WITH WASHERS. SEAL ALL INSULATION JOINTS, SEAMS AND FASTENER PIN PENETRATIONS WITH VAPOR RETARDING PRESSURE SENSITIVE TAPE OR WITH GLASS FABRIC AND MASTIC. <br />INSTALL TAPERED INSULATION TO THE TOP OF ALL EXTERIOR HORIZONTAL RECTANGULAR DUCTS WIDER THAN 24" BEFORE APPLYING THE FINISH INSULATION TO CAUSE A 1 /2" PER <br />FOOT SLOPE OF FINISH INSULATION TO SHED WATER. <br />BRANCH DUCT RUNOUTS: SHALL BE GALVANIZED ROUND (SNAPLOCK) SEAM LOCKED DUCTWORK WITH EXTERNAL FIBERGLASS WRAP INSULATION (R-6.0). <br />NOTE: BRANCH DUCT RUNOUTS & FLEXIBLE DUCTS SHALL BE THE SAME SIZE DUCT AS THE DIFFUSER NECK CONNECTED TO, AS LISTED ON THE FLOOR PLAN. <br />GRILLES AND DIFFUSERS: ALL GRILLES AND DIFFUSERS SHALL BE INSTALLED WITH AN INSULATED BOOT OR BLANKET. PROVIDED A METHOD OF VOLUME CONTROL BY DEVICE <br />ADJUSTABLE AT DIFFUSER FACE OR MANUAL VOLUME DAMPERS AT TAKEOFF BRANCHES. COORDINATE DIFFUSER AND GRILLE LOCATIONS WITH ELECTRICAL LIGHTING LAYOUT AND <br />ARCHITECTURAL REFLECTED CEILING PLAN. <br />DUCT SMOKE DETECTORS: INSTALL SMOKE DETECTORS AS RECOMMENDED BY MANUFACTURER TO ACQUIRE PROPER READINGS. LOCATION OF DUCT MOUNTED SMOKE DETECTORS ARE <br />FOR REFERENCE LOCATION ONLY. FINAL PLACEMENT SHALL MEET ALL REQUIREMENTS IN THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. PROVIDE 12"X12" ACCESS DOOR FOR <br />INSPECTION AND SERVICE. SMOKE DETECTORS SHALL BE FURNISHED & WIRED BY FIRE ALARM INSTALLER AND INSTALLED BY HVAC CONTRACTOR. SMOKE DETECTORS SHALL BE <br />WIRED TO SHUTOFF UNIT WITH THE DETECTION OF SMOKE. <br />CONTROLS: PROVIDE CONTROLS COMPLETE TO SUIT THE EQUIPMENT PROVIDED AND TO ACCOMPLISH THE SEQUENCE OF OPERATION AS REQUIRED BY PLANS AND SYSTEMS. LOCATE <br />THERMOSTATS 48" ABOVE FINISHED FLOOR, UNLESS OTHERWISE NOTED. THERMOSTATIC CONTROLS SHALL BE PROGRAMMABLE TO INCLUDE ALL ITEMS REQUIRED BY FBC-ENERGY <br />CODE SIXTH EDITION AND SHALL HAVE LOCKOUT FUNCTION WITH PASSWORD. <br />MINIMUM FUNCTIONALITY SHALL INCLUDE: 7-DAY A WEEK PROGRAMMABLE CONTROLLER WITH SETBACKS UP TO 85-F AND DOWN TO 55-F, 10-HOUR BATTERY BACKUP, MANUAL <br />OVERRIDE FOR 2-HOURS, AND AUTOMATIC STARTING (OPTIMUM START) ADJUSTABLE DAILY START TIMES. <br />TESTING AND BALANCING: THE CONTRACTOR SHALL ENSURE THAT ALL DEVICES AND SYSTEMS ARE COMPLETE, TESTED AND BALANCED, AND READY FOR OPERATION WHEN THE FACILITY <br />IS HANDED OVER THE OWNER. THE AIR CONDITIONING SYSTEM SHALL BE TESTED IN ACCORDANCE WITH CURRENT AABC OR NEBB OR NBC PROCEDURES. A CERTIFIED, WRITTEN <br />REPORT SHALL BE SUBMITTED TO MECHANICAL ENGINEER FOR APPROVAL. THE CONTRACTOR SHALL RECTIFY DISCREPANCIES BETWEEN THE ACTUAL INSTALLATION AND CONTRACT <br />DOCUMENTS WHEN IN THE OPINION OF THE T&B AGENCY OR THE ENGINEER, THAT THE DISCREPANCIES WILL AFFECT SYSTEM BALANCE AND PERFORMANCE. <br />SUBMITTALS REQUIRED: <br />SUBMIT SHOP DRAWINGS FOR ALL MATERIALS, EQUIPMENT, AND SYSTEMS REQUIRED BY THESE DOCUMENTS (SEE ARCH. PLANS/SPECS FOR SPECIFIC FORMATTING), INCLUDING: <br />ROOFTOP UNIT <br />TEST/BALANCE REPORT <br />EXHAUST FANS <br />DIFFUSERS AND GRILLES <br />DUCTWORK, INSULATION AND ACCESSORIES (CONNECTIONS, MASTICS, ETC.) <br />THERMOSTATS & CONTROLS <br />SUBSTITUT10i4S: -CONTRACTOR SHALL PAY FOR ANY AND ALL ADDED COSTS ASSOCIATED WITH ANY SUBSTITUTION, INCLUDING SUBSTITUTIONS THAT REQUIRE CHANGES TO THE OTHER <br />BUILDING COMPONENTS, SUCH AS ELECTRICAL, STRUCTURAL REINFORCING, CEILINGS, WALLS, ROOFS, ETC. THIS WILL INCLUDE ANY ENGINEERING/ARCHITECTURAL RE -DESIGN COSTS <br />AS A RESULT OF SAID SUBSTITUTION. THESE COSTS SHALL NOT BE BORNE BY THE OWNER, ARCHITECT, NOR ENGINEER, REGARDLESS OF ACCEPTABILITY OF SUBSTITUTION. <br />ENGINEER RESERVES THE RIGHT TO ACCEPT OR DENY ANY SUBSTITUTION THAT HE DOES NOT DEEM TO BE EQUIVALENT, AND CONTRACTOR SHALL PROVIDE SPECIFIED OR EQUIVALENT <br />MATERIALS/EQUIPMENT AT NO ADDITION COST TO OWNER, SHOULD A SUBSTITUTION BE DENIED. <br />GUARANTEE: THE ONE-YEAR GUARANTEE PERIOD SHALL NOT START UNTIL THE PROJECT IS FULLY COMPLETED AND THE CONTRACTOR HAS RECEIVED THE FINAL PAYMENT AND <br />CERTIFICATION OF OCCUPANCY. ALL EQUIPMENT AND ALL WORK SHALL BE FULLY GUARANTEED, PARTS AND LABOR, FOR ONE YEAR FROM THE DATE OF THE CERTIFICATE OF <br />COMPLETION. REPAIRS MADE DURING THIS PEROID MUST BE FULLY GUARANTEED FOR AN ADDITIONAL ONE YEAR PERIOD FROM THE DATE OF REPAIRS. IN ADDITION, THE �- <br />CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING, AND ITS CONTENTS OR OTHER EQUIPMENT, CAUSED BY DEFECTS OR IMPROPER INSTALLATION <br />OF EQUIPMENT OR MATERIAL INSTALLED. A 5-YEAR WARRANTY IS REQUIRED FOR COMPRESSORS. <br />HVAC LEGEND <br />® <br />SUPPLY AIR DIFFUSER OR GRILLE <br />® ® <br />RETURN/EXH. AIR REGISTER OR GRILLE <br />NEW DUCTWORK, WITH SIZE LISTED <br />FLEXIBLE DUCT <br />DUCT SMOKE DETECTOR <br />--- <br />FIRE DAMPER <br />--� <br />SMOKE/FIRE DAMPER <br />CD <br />CONDENSATE DRAIN <br />RFT <br />REFRIGERANT LINE SET <br />QT <br />THERMOSTAT BASE <br />H@ <br />HUMIDITY SENSOR <br />FT <br />REMOTE TEMPERATURE SENSOR <br />CARBON DIOXIDE SENSOR <br />C® <br />CARBON MONOXIDE SENSOR <br />GNITROGEN <br />DIOXIDE SENSOR <br />9 <br />HYDROGEN SENSOR <br />4+ <br />AIRFLOW DIRECTION <br />'ld <br />1" DOOR UNDERCUT <br />0 1 ROUND, DIAMETER <br />AFF I ABOVE FINISHED FLOOR <br />CFM <br />CUBIC FEET PER MINUTE <br />TYP <br />TYPICAL - ITEM OR METHOD <br />BD <br />BAROMETRIC DAMPER <br />—p <br />GRAVITY BACK -DRAFT DAMPER <br />VD / l� <br />MANUAL VOLUME DAMPER (W/HANDLE) <br />MD @G) <br />MOTORIZED DAMPER <br />DOUBLE THICK VANES <br />SUPPLY DUCT TAKE -OFF WITH VD <br />SUPPLY DUCT TAKE -OFF WITH SCOOP <br />SIDE DIFFUSER WITH VD <br />(N) <br />NEW <br />(E) <br />EXISTING <br />® SWITCH <br />CONNECT NEW TO EXISTING <br />® WAVE GUIDE <br />— CONDENSATE LINE ON ROOF SUPPORTS <br />DIFFUSER TAG EQUIPMENT TAG <br />/; AIRFLOW EQUIPMENT <br />400 CFM TYPE <br />RTU-1 <br />CQ-12 0 :EQUIPMENT <br />MARK-/ -NECK NUMBER <br />SIZE <br />NOTE TO CONTRACTOR <br />ON EXISTING CONDITIONS: <br />1. CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID <br />AND SURVEY ALL EXISTING CONDITIONS AND <br />EQUIPMENT PRIOR TO SUBMITTING BID FOR WORK <br />REQUIRED BY THESE DOCUMENTS. THIS <br />INCLUDES ABOVE THE CEILING AND ON TOP OF <br />THE ROOF. <br />2. CONTRACTOR SHALL REFER TO AND READ <br />THROUGH ALL OF THE "CONTRACTOR'S SCOPE OF <br />WORK" AS DEFINED IN THE BID SPECIFICATIONS <br />AND DOCUMENTS AS PART OF THE BID PROCESS. <br />I IF AT ANY TIME. THERE IS DISCREPANCY BETWEEN <br />THE PLANS & SPECS. OR CONFUSION/CONCERN <br />OVER REQUIRED WORK. CONTRACTOR SHALL <br />IMMEDIATELY NOTIFY ARCHITECT. ENGINEER. &/OR <br />OWNER AND GET DIRECTION BEFORE PROCEEDING <br />WITH WORK IN QUESTION, <br />4. FOR ALL NEW ROOF PENETRATIONS, CONTRACTOR <br />SHALL INCLUDE IN HIS BID THE COST TO HIRE <br />THE ROOFING FIRM HOLDING THE WARRANTY TO <br />PROVIDE ROOF PENETRATIONS. <br />5. FOR ALL EXISTING EQUIPMENT TO BE <br />RE -LOCATED &/OR RE -USED, CONTRACTOR <br />SHALL BE RESPONSIBLE FOR DISCONNECTION, <br />SAFE STORAGE, & RE -CONNECTION OF SAID <br />EQUIPMENT COMPLETELY. <br />6. FOR ALL EXISTING EQUIPMENT TO BE <br />DEMOLISHED (I.E. DEMO) CONTRACTOR SHALL BE <br />RESPONSIBLE FOR DISCONNECTION, REMOVAL, & <br />DISPOSAL OFF -SITE PER CODE, OF SAID <br />EQUIPMENT COMPLETELY. <br />RTU CABINET <br />BALANCING HOT GAS <br />DAMPER REHEAT ELECTRIC <br />MERV-7 (30%) COOLING COIL IF SUPPLY HEATING <br />FILTER COIL SPECIFIED FAN COIL <br />OUTSIDE AIR <br />SEOUBCE OF O iAT10N 6100FfOP LINTS) <br />A: SUPPLY FANS, <br />THE EVAPORATOR FAN WILL RUN <br />CONTINUOUSLY DURING OCCUPIED HOURS AND/OR <br />IF KEF-2 IS RUNNING AND CYCLE ON/OFF WITH <br />COOLING / HEATING /VENTILATION IN UN -OCCUPIED <br />MODE AS PROGRAMMED AND SUBJECTED TO FIRE <br />ALARM (DUCT SMOKE DETECTOR) SHUTDOWN. <br />B: OUTSIDE AIR DAMPER, <br />THE MOTORIZED DAMPER CLOSES WHEN THE UNIT <br />IS OFF. DAMPER SHALL OPEN FULLY WHEN SUPPLY <br />FAN STARTS. <br />C: COOLING COIL, <br />THE DX REFRIGERANT COIL AND COMPRESSORS <br />SHALL ENERGIZE IN STAGES (IF APPLICABLE) TO <br />MAINTAIN SPACE COOLING SETPOINT. (75-F <br />OCCUPIED/ 80-F UNOCCUPIED) <br />D: HEATING COIL (IF APPLICABLE), <br />THE ELECTRIC HEAT WILL ENERGIZE IN STAGES TO <br />MAINTAIN HEATING SETPOINT. (68-F OCCUPIED/60'1` <br />UNOCCUPIED). <br />E: HUMIDITY CONTROL, <br />WHEN THE COOLING TEMPERATURE SETPOINT IS <br />SATISFIED BUT THE HUMIDITY SETPOINT IS <br />UNSATISFIED, THE UNIT SHALL GO INTO <br />DEHUMIDIFICATION MODE, BY CLOSING THE FRESH <br />AIR DAMPER AND ACTIVATING THE COMPRESSORS <br />AND THE REHEAT COIL IN STAGES TO PREVENT <br />OVERCOOLING UNTIL HUMIDITY SETPOINT IS <br />SATISFIED. (50% OCCUPIED/60% UNOCCUPIED). <br />F: EXHAUST FANS, <br />RESTROOM FANS WILL START AND RUN FULL SPEED <br />WHEN RESTROOM IS OCCUPIED AS DETERMINED BY <br />THE INTERLOCKED LIGHT SWITCHES. THE <br />BREAKROOM FAN SHALL START AND RUN FULL <br />SPEED WHEN SWITCH IS ENGAGED AND RUN ON 10 <br />MINUTE TIMER. <br />DUCT SMOKE DETECTOR <br />SD <br />SUPPLY <br />RETURN AIR AIR <br />MANUAL BALANCE DAMPERS ADJUSTABLE <br />SPACE <br />SPACE MOUNT HUMIDITY SENSOR <br />THERMOSTAT <br />FM-# CONSTANT VOLUME CONTROL SCHEMATIC <br />NO SCALE <br />�1111111 <br />MCO M <br />V) V) LO <br />ao <br />., o r- <br />cp <br />w Q <br />Y ((n N � <br />(/) w <br />W o-1'�� a <br />ZQ W�� <br />CL. p w 0 <br />LijZ nevi J <br />in ••Z5 Q <br />w <br />Q <br />a- <br />ao <br />119 <br />L <br />Q <br />� <br />LL <br />c <br />E <br />�j <br />E <br />a <br />L V <br />o. <br />o > <br />o.o <br />" <br />a <br />Q <br />�a <br />E <br />I .l a <br />(L <br />Q <br />0 <br />Q <br />>O <br />� <br />0 <br />6 <br />WLL- <br />� <br />CL <br />a/Q< <br />J <br />L <br />o <br />J <br />I <br />n <br />C� <br />col <br />I <br />� <br />� <br />N <br />W <br />ti <br />AH <br />a <br />,%ti"1 U 11111"I, <br />�% �v_Vd D. ��i <br />No 56189 <br />�. STATE OF <br />0,< <br />. • k <br />Date: 4. 25. 22 <br />Checked by: MI, <br />Drawn: TJ/K13 <br />Job: 21-042 <br />Sheet <br />moor <br />ti <br />LIl 55 D <br />