<br />DIVISION 16 - ELECTRICAL SPECIFICATIONS
<br />PART I. GENERAL PROVISIONS
<br />1. SCOPE: PROVIDE ALL LABOR, MATERIAL, AND EQUIPMENT IN
<br />ACCORDANCE WITH THESE SPECIFICATIONS, AND THE ACCOMPANYING
<br />DRAWINGS TO PROVIDE A COMPLETE AND PROPERLY OPERATING
<br />ELECTRICAL SYSTEM FOR THE BUILDING.
<br />A. THE CONTRACTOR SHALL FURNISH AND INSTALLALL OF THE
<br />FOLLOWING MATERIAL AND EQUIPMENT UNDER THIS DIVISION OF THE
<br />SPECIFICATIONS, UNLESS NOTED OTHERWISE: PANELBOARDS;
<br />LIGHTING FIXTURES; LAMPS; RACEWAYS; 600 VOLT WIRE AND CABLE;
<br />WIRING DEVICES; DEVICE PLATES; DEVICE, PULL, AND JUNCTION
<br />BOXES; SAFETY SWITCHES; MOTOR STARTERS; LIGHTING CONTROLS;
<br />CIRCUIT BREAKERS; FUSES; TIME CLOCKS; EQUIPMENT IDENTIFICATION
<br />(NAMEPLATES AND DIRECTORIES); WIRE AND CABLE TERMINATIONS;
<br />CONNECTIONS TO INDIVIDUAL UNITS OF EQUIPMENT FOR THE WALK-IN
<br />FREEZERS AND COOLERS; AND TEMPORARY POWER.
<br />B. THE FOLLOWING MATERIAL AND EQUIPMENT WILL BE FURNISHED
<br />AND/OR INSTALLED BY OTHERS, OR UNDER OTHER DIVISIONS OF THE
<br />SPECIFICATIONS, UNLESS NOTED OTHERWISE: LOW VOLTAGE (24 VOLT)
<br />WIRE AND CABLE, COMMUNICATION DEVICES, SECURITY EQUIPMENT,
<br />POINT OF SALE (POS) EQUIPMENT, SIGNAGE, CONCRETE BASES FOR
<br />SITE LIGHTING POLES.
<br />C. THE FOLLOWING MATERIALAND EQUIPMENT WILL BE FURNISHED
<br />BY OTHERS, OR UNDER OTHER DIVISIONS OF THE SPECIFICATIONS, AND
<br />INSTALLED BY THE CONTRACTOR, UNLESS NOTED OTHERWISE: SITE
<br />LIGHTING FIXTURES AND POLES.
<br />2. GENERAL REQUIREMENTS: ALL WORK SHALL BE PERFORMED BY
<br />SKILLED LICENSED ELECTRICIANS IN ACCORDANCE WITH THE BEST
<br />PRACTICES OF THE TRADE, MEETING THE REQUIREMENTS OF THE
<br />LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, APPLICABLE
<br />FEDERAL, STATE AND LOCAL CODES, AND THE REQUIREMENTS OF THE
<br />ELECTRICAL UTILITY COMPANY FURNISHING THE SERVICES. ALL
<br />NECESSARY CONSTRUCTION PERMITS AND CERTIFICATES OF
<br />INSPECTION SHALL BE PURCHASED AND OBTAINED UNDER THIS
<br />CONTRACT.
<br />A. COORDINATION: ALL OUTLETS MUST BE ACCURATELY LOCATED,
<br />PARTICULARLY APPLIANCE OUTLETS WHICH SHALL BE LOCATED FROM
<br />THE DIMENSIONS GIVEN ON THE DRAWING AND FIELD VERIFIED.
<br />REVIEW THE ARCHITECTURAL, PLUMBING AND HEATING AND
<br />VENTILATING PLANS IN ORDER TO COORDINATE THIS WORK WITH
<br />OTHER TRADES, AND COOPERATE WITH THEM IN THE ENTIRE
<br />INSTALLATION.
<br />3. SERVICE VOLTAGE: THESE DRAWINGS ARE FOR A METERED,
<br />UNDERGROUND BUILDING SERVICE OF 120/208 VOLT, THREE PHASE,
<br />FOUR WIRE, 60 HERTZ. ALL KITCHEN AND AIR CONDITIONING EQUIPMENT
<br />HAS BEEN DESIGNED AND PURCHASED FOR USE ON THIS ELECTRICAL
<br />SYSTEM. THE CONTRACTOR SHALL CONTACT THE ELECTRICAL UTILITY
<br />AND VERIFY ALL OF THE ABOVE SERVICE CHARACTERISTICS, AND THE
<br />AVAILABLE FAULT CURRENT.
<br />4. SERVICE EQUIPMENT: THE SERVICE SHALL BE LOCATED AS
<br />SHOWN ON THE SITE PLAN, OR AS INDICATED IN THE INSTRUCTIONS TO
<br />BIDDERS. UTILITY POLES, PADS FOR UTILITY TRANSFORMERS, CURRENT
<br />TRANSFORMER ENCLOSURES, METERING EQUIPMENT, SERVICE MASTS,
<br />AND OTHER RELATED MATERIALS AND EQUIPMENT SHALL BE
<br />APPROVED, FURNISHED, AND INSTALLED AS REQUIRED. INCLUDE THE
<br />COST OF ALL THE ABOVE ITEMS, SERVICE CONNECTIONS, AND METER
<br />CHARGES IN THE BASE BID. MAIN SERVICE SWITCHES AND CURRENT
<br />TRANSFORMER CABINETS SHALL BE INCLUDED IN THE BASE BID.
<br />UNLESS NOTED OTHERWISE, A MAIN SERVICE SWITCH WITH CURRENT
<br />LIMITING FUSES MAY BE USED WHEN THE AVAILABLE FAULT CURRENT
<br />(AFC) IS EXCESSIVE, IN ORDER TO USE STOCK PANELBOARDS, WITH
<br />10K OR 22K AIC RATINGS.
<br />PART II. MATERIALS
<br />1. MATERIALS: ALL MATERIALS SHALL BE NEW AND OF THE QUALITY
<br />INDICATED BY THE SPECIFIED BRAND NAMES. SUBSTITUTIONS OF
<br />MATERIAL OF EQUAL QUALITY BY OTHER MAJOR MANUFACTURERS OF
<br />COMMERCIAL EQUIPMENT MAY BE ACCEPTABLE PROVIDED A LIST OF
<br />SUCH SUBSTITUTIONS IS APPROVED IN WRITING BY POPEYE'S
<br />ARCHITECTURE AND ENGINEERING DEPARTMENT. THE CONTRACTOR
<br />SHALL SUBMITA SUBSTITUTION LIST IN TRIPLICATE AT LEAST FIVE DAYS
<br />PRIOR TO THE BID OPENING.
<br />A. PANELBOARDS: PANELBOARDS SHALL BE BOLT -IN CIRCUIT
<br />BREAKER TYPE, AS SHOWN ON THE PLANS. PANELS SHALL BE OF
<br />PANELBOARD CONSTRUCTION, 20 INCHES WIDE (MINIMUM), 5-3/4" TO
<br />6-1/2" DEEP, UL LISTED, AND MEET UL 67, UL 50, AND FEDERAL
<br />SPECIFICATION W-P-115B AS TYPE 1, CLASS 1, WITH BOLT -ON CIRCUIT
<br />BREAKERS, COPPER BUS BARS, NEUTRAL BUS, GROUND BUS, AND A
<br />HINGED LOCKABLE DOOR. CABINETS SHALL BE CODE GAUGE,
<br />GALVANIZED STEEL, MOUNTED AS SHOWN. PROVIDE TYPEWRITTEN
<br />CIRCUIT DIRECTORIES WITH CLEAR PLASTIC PROTECTORS IN ALL
<br />PANELS. ALL WIRES SHALL BE TAGGED WITH PANEL AND CIRCUIT
<br />NUMBERS. PANEL "MP" SHALL BE UL LISTED AND LABELED AS
<br />SUITABLE FOR USE AS SERVICE ENTRANCE EQUIPMENT. APPROVED
<br />MANUFACTURERS OF PANELS ARE SQUARE D/TELEMECHANIQUE,
<br />CUTLER -HAMMER, GENERAL ELECTRIC, WESTINGHOUSE, AND SIEMENS
<br />(I-T-E).
<br />B. LIGHTING FIXTURES: ALL LIGHTING FIXTURES SHALL BE UL
<br />LISTED, COMMERCIAL QUALITY. REFER TO NATIONAL ACCOUNT
<br />SCHEDULE. REVIEW AT: WWW.POPEYESDEVELOPMENTCOM;
<br />PASSWORD: lagniappe
<br />C. LAMPS: ALL NEW FLUORESCENT LAMPS (F40T8) SHALL BE COOL
<br />WHITE, OR COLOR IMPROVED COOL WHITE, WITH A 4100 DEGREE K
<br />COLOR TEMPERATURE, 2950 MIN INITIAL LUMENS, 20,000 HOURS RATED
<br />LIFE, AND 62 MIN CRI, UNLESS NOTED OTHERWISE.
<br />D. WIRING DEVICES: ALL WIRING DEVICES SHALL BE UL LISTED,
<br />COMMERCIAL SPECIFICATION GRADE. SWITCHES SHALL BE RATED 20
<br />AMPS AT 120/277 VOLTS, AC. STANDARD RECEPTACLES SHALL BE 20
<br />AMP, DUPLEX, GROUNDING TYPE, IN NEMA CONFIGURATIONS, UNLESS
<br />NOTED OTHERWISE. SWITCHES IN THE SAME LOCATION SHALL BE
<br />GANGED BEHINDASINGLE PLATE. DEVICE PLATES IN THE KITCHEN
<br />AREA SHALL BE METAL, ALUMINUM OR STAINLESS STEEL. DEVICE
<br />PLATES IN THE DINING AREA SHALL BE THERMOPLASTIC PLASTIC
<br />(NYLON) OR METAL, COLOR AS APPROVED BY THE ARCHITECT OR
<br />OWNER. APPROVED MANUFACTURERS OF SWITCHES AND
<br />RECEPTACLES ARE HUBBELL, ARROW HART, BRYANT, LEVITON, PASS &
<br />SEYMOUR, GENERAL ELECTRIC, SLATER, OR EQUAL.
<br />1. SWITCHES:
<br />a. SINGLE POLE: HUBBELL HBL1221-I, OR EQUAL.
<br />b. THREE WAY: HUBBELL HBL1223-I, OR EQUAL.
<br />2. RECEPTACLES:
<br />a. NEMA 5-20R: HUBBELL 53621, OR EQUAL.
<br />b. NEMA 5-20R-IG: HUBBELL IG-5362, OR EQUAL.
<br />c. NEMA 5-20R-IG/SS: HUBBELL IG-5362-OS, OREQUAL.
<br />d. NEMA 5-20R-GFCI: HUBBELL GF5362-I, OR EQUAL.
<br />e. NEMA 6-20R: HUBBELL 5462-I, OR EQUAL.
<br />f. OTHERS: COMMERCIAL OR INDUSTRIAL GRADE, UL LISTED,
<br />FEDERAL SPECIFICATION WC596F.
<br />3. WP PLATES: WEATHERPROOF COVERS ARE PERMITTED UNDER
<br />NEC ARTICLE 406.8(B)(1).
<br />4. NATIONALACCOUNT REFER TO THE NATIONAL ACCOUNT
<br />DIRECTORY. THE FOLLOWING EQUIPMENT MAY BE AVAILABLE: MAIN
<br />SERVICE PANELBOARD WITH BREAKERS INSTALLED, LIGHTING AND
<br />DISTRIBUTION PANELBOARDS WITH BREAKERS INSTALLED, ROOF -TOP
<br />DISCONNECTS FOR HVAC UNITS AND KITCHEN HOOD FANS, LIGHTING
<br />CONTACTOR PANEL, AND SHUNT TRIP SYSTEMS (IF REQUIRED PER
<br />LOCAL CODE).
<br />5. EXCAVATIONS: PERFORM ALL NECESSARY EXCAVATING AND
<br />BACK -FILLING REQUIRED FOR THIS INSTALLATION. ALL EXCAVATIONS
<br />BELOW THE BOTTOM OF FOOTINGS SHALL BE BACKFILLED WITH 3000
<br />PSI CONCRETE. WHERE DITCHES ARE CUT FOR OUTSIDE RUNS OF
<br />CONDUIT, REPLACE AND TAMP THE EARTH IN 12" LAYERS AND LEAVE
<br />THE GROUND LEVEL AND EQUAL TO ITS ORIGINAL CONDITION.
<br />6. CONDUITAND FITTINGS: CONDUIT PERMITTED: (A) RIGID
<br />GALVANIZED STEEL (RGS), (B) EMT, (C) PVC, AND (D) ENT TYPES UTILIZED
<br />SHALL BE RUN ONLY AS PERMITTED PER CODE. ALL WIRING SHALL BE
<br />RUN IN CONDUIT. CONDUIT PLACED IN CONCRETE OR RUN
<br />UNDERGROUND SHALL BE RIGID GALVANIZED CONDUIT OR PVC. IF PVC IS
<br />USED, ALL ELBOWS, SWEEPS AND STUB -UPS SHALL BE RGS. CONDUIT
<br />EXPOSED OR RUN IN MASONRY WALLS ABOVE GRADE MAY BE PVC OR
<br />EMT WHERE ALLOWED BY LOCAL CODES. IF EMT IS NOT PERMITTED,
<br />RIGID SCREWED GALVANIZED PIPE CONDUIT AND FITTINGS SHALL BE
<br />USED. IF SHIELDED CABLE IS REQUIRED FOR CONTROL CIRCUITRY, IT
<br />SHALL BE TAN, GREY OR ANY NEUTRAL COLOR OTHER THAN THAT AS
<br />SPECIFIED FOR POWER DISTRIBUTION. NO CONDUIT SMALLER THAN
<br />3/4" SHALL BE INSTALLED EXCEPT FOR TWO -WIRE SWITCH LEGS. ALL
<br />CONDUIT BENDS SHALL BE FREE FROM DENTS AND KINKS. ALL
<br />CONDUITS SHALL BE ELECTRICALLY CONTINUOUS FROM THE SERVICE
<br />EQUIPMENT TO ALL OUTLETS, AND SHALL BE SECURED TO ALL METAL
<br />BOXES WITH ONE LOCK NUT OUTSIDE, AND ONE INSIDE THE BOX WITH
<br />A REINFORCED BAKELITE BUSHING. IF PVC, OR ENT, IS USED, THEN
<br />APPROPRIATE SIZED, ELECTRICALLY CONTINUOUS, BOND WIRES
<br />SHALL BE RUN FROM THE SERVICE EQUIPMENT TO ALL OUTLETS, AND
<br />SHALL BE SECURED TO EACH WIRING DEVICE PER THE NATIONAL
<br />ELECTRICAL CODE. WHERE CONNECTIONS ARE TO BE MADE BETWEEN
<br />CONDUIT TERMINATIONS AND MOTORS, EQUIPMENT, OR APPARATUS
<br />NECESSITATING FLEXIBLE CONNECTIONS, APPROVED FLEXIBLE CONDUIT
<br />SHALL BE USED. OUTDOOR CONNECTIONS TO FANS, HVAC UNITS, OR
<br />ROTATING EQUIPMENT SHALL B MADE WITH HELICAL WOUND,
<br />LIQUIDTIGHT, FLEXIBLE STEEL CONDUIT. EXPOSED CONDUIT SHALL BE
<br />SUITABLY SUPPORTED AT INTERVALS NOT TO EXCEED FIVE (5) FEET.
<br />DURING CONSTRUCTION, CONDUIT SHALL BE KEPT FREE OF ALL
<br />FOREIGN MATTER BY USE OF CAPPED BUSHINGS ON ALL TURNED UP
<br />ENDS. PAPER OR WOOD PLUGS ARE NOT ACCEPTABLE FOR THIS
<br />PURPOSE.
<br />7. WIRE AND CABLES: ALL WIRE AND CABLES SHALL BE
<br />UNDERWRITERS LABORATORIES' LISTED, AND LABELED, AND CONFORM
<br />WITH APPLICABLE STANDARDS OF UL (44, AND 83), NEMA (WC-5, AND
<br />WC-7), IPCEA (S-61-402, AND S-66-524), FEDERAL SPECIFICATIONS
<br />(J-C-30A(1), AND HH-1-595C), ANSI, AND OTHER APPLICABLE INDUSTRY
<br />STANDARDS. CONNECTORS AND LUGS SHALL MEET UL PUBLICATION
<br />486. ALL BRANCH CIRCUIT WIRING SHALL BE 600 VOLT, COPPER, 75
<br />DEGREE C (MIN), TYPE THHN/THWN WITH A MINIMUM SIZE OF #12 AWG,
<br />UNLESS NOTED OTHERWISE. WIRE SIZES OF #8 AWG AND LARGER SHALL
<br />BE STRANDED. SERVICE AND FEEDER CABLES SHALL BE 600 VOLT,
<br />STRANDED COPPER, 75 DEGREE C (MIN), TYPE XHHW. ALL CIRCUITS
<br />SHALL HAVE A SEPARATE GROUND CONDUCTOR. PROVIDE
<br />GREEN -INSULATED GROUND WIRE IN ALL RACEWAYS, CABLE
<br />ASSEMBLIES, AND WHERE NOTED. SIZE EQUIPMENT GROUNDS PER
<br />TABLE 250-122 OF THE NATIONAL ELECTRICAL CODE. INSULATION
<br />COLOR CODES SHALL BE BLACK, RED, AND BLUE (PHASE), WHITE
<br />(NEUTRAL), AND GREEN (GROUND).
<br />A. ALL WIRING SHALL BE INSTALLED IN CONDUIT, EXCEPT WHERE
<br />SPECIFICALLY SHOWN ON THE DRAWINGS. NON-METALLIC SHEATHED
<br />(TYPE NM) CABLE IS NOT PERMITTED.
<br />B. ALL BRANCH CIRCUIT, COMMUNICATION, SIGNALING, AND CONTROL
<br />WIRING TO KITCHEN, FIRE PROTECTION, AND OTHER EQUIPMENT SHALL
<br />BE ROUTED ABOVE THE CEILING. VERIFY WHETHER OR NOT THE SPACE
<br />ABOVE THE CEILING IS USED AS A SPACE FOR RETURN AIR FOR THE
<br />ENVIRONMENTAL AIR SYSTEM. IF IT IS USED FOR RETURN AIR, PROVIDE
<br />APPROVED RACEWAYS FOR ALL OVERHEAD WIRING PER NEC ARTICLE
<br />300-22(B). IF IT IS NOT "OTHER SPACE USED FOR ENVIRONMENTAL AIR",
<br />APPROVED LOW VOLTAGE CABLES MEETING THE REQUIREMENTS OF
<br />NEC ARTICLES 725 AND 760 MAY BE RUN WITHOUT RACEWAYS, UNO. ALL
<br />SAFETY CONTROL WIRING FOR FIRE PROTECTION SYSTEMS, SHUNT
<br />TRIPS, ETC. SHALL BE RUN IN A RACEWAY IN ACCORDANCE WITH NEC
<br />ARTICLES 725.25 AND 725.28.
<br />8. SITE LIGHTING: THE G.C. WILL FURNISH THE SITE LIGHTING
<br />PACKAGE, AS REQUIRED FOR THE SPECIFIC LOCATION. UNDER THIS
<br />SPECIFICATION SECTION, PROVIDE 1" RIGID GALVANIZED STEEL
<br />ELECTRICAL CONDUIT, AND THE REQUIRED WIRING FROM THE PANEL TO
<br />THE POLE. SET FIXTURES AND POLES ON CONCRETE BASES, AS
<br />PROVIDED UNDER SPECIFICATION SECTION 3A: CONCRETE.
<br />GROUND/BOND ALL SITE LIGHTING FIXTURES/POLES PER THE NEC. THE
<br />BRANCH CIRCUIT CONDUCTORS SHALL BE INCREASED FROM #10 AWG TO
<br />#8 AWG IF THE HORIZONTAL DISTANCE FROM THE PANEL TO THE POLE IS
<br />GREATER THAN EIGHTY (80) FEET. ALL SITE LIGHTING SHALL BE
<br />CONTROLLED THROUGH THE LIGHTING CONTROL SYSTEM SHOWN ON
<br />THE DRAWINGS. REFER TO THE SITE PLAN FOR QUANTITYAND
<br />LOCATION OF ALL SITE LIGHTING. SET FIXTURES AS SPECIFIED, AND AIM
<br />AFTER DARK FOR UNIFORM LIGHT DISTRIBUTION.
<br />9. SIGNAGE LIGHTING: PROVIDE A 1" RIGID GALVANIZED STEEL
<br />ELECTRICAL CONDUIT, AND WIRING, FROM THE PANEL TO ALL
<br />ILLUMINATED SIGNS AS SHOWN ON THE LIGHTING AND SITE PLANS.
<br />GROUND/BOND EACH SIGN. SIGNS WILL BE FURNISHED AND INSTALLED
<br />BY THE OWNER, OR UNDER A SEPARATE CONTRACT, UNO. POWER AND
<br />WIRING SHALL BE FURNISHED AND INSTALLED UNDER THIS SECTION OF
<br />THE SPECIFICATIONS.
<br />OTHER WIRING:
<br />A. FURNISH AND INSTALLALL POWER WIRING AND CONDUITAS
<br />INDICATED ON THE DRAWINGS FOR ROOF -TOP HVAC EQUIPMENT,
<br />KITCHEN HOOD FANS, AND WALK-IN FREEZERAND COOLER EQUIPMENT.
<br />DISCONNECT SWITCHES, AVAILABLE FROM THE NATIONAL ACCOUNT,
<br />SHALL BE FURNISHED AND INSTALLED FOR EACH UNIT OF HVAC
<br />EQUIPMENT, AND FOR KITCHEN EQUIPMENT WITHOUT ACORD AND PLUG.
<br />BEFORE ENERGIZING ANY EQUIPMENT, VERIFY THAT THE CORRECT
<br />POWER SUPPLY VOLTAGE, AMPACITY, AND PHASING HAS BEEN
<br />PROVIDED AT THE LOAD SIDE OF THE DISCONNECT.
<br />B. FURNISH AND INSTALL THE LIGHTING CONTACTOR PANEL, AND ALL
<br />ASSOCIATED POWER WIRING, AS INDICATED. THE LIGHTING CONTACTOR
<br />PANEL IS CUSTOM BUILT, AND AVAILABLE FROM THE NATIONAL ACCOUNT.
<br />10. EMPTY CONDUIT: LEAVE A#12 AWG PULL WIRE IN ALL EMPTY
<br />CONDUITS.
<br />11. BOXES AND WIREWAYS: ALL JUNCTION BOXES, PULL BOXES,
<br />WIREWAYS, ETC, SHALL BE SIZED IN ACCORDANCE WITH THE NATIONAL
<br />ELECTRICAL CODE.
<br />12. EQUIPMENT IDENTIFICATION: PROVIDE NAMEPLATES FOR ALL
<br />PANELBOARDS, CONTROLS, AND OTHER ELECTRICAL EQUIPMENT.
<br />EQUIPMENT VISIBLE TO THE PUBLIC SHALL BE IDENTIFIED WITH
<br />ENGRAVED LAMINATED NAMEPLATES ATTACHED WITH STAINLESS STEEL
<br />FASTENERS. ELECTRICAL EQUIPMENT NOT VISIBLE TO THE PUBLIC MAY
<br />BE NEATLY IDENTIFIED WITH BLACK PERMANENT MARKERS.
<br />PART III. EXECUTION
<br />1. TESTS: MAKE ALL TESTS NECESSARY TO ENSURE THAT THE
<br />ENTIRE INSTALLATION IS FREE FROM IMPROPER GROUNDS, AND FROM
<br />SHORTED AND/OR OPEN CONDUCTORS. VOLTAGE, CURRENT, AND
<br />ROTATION TESTS SHALL BE MADE BEFORE ANY MOTORS ARE PLACED
<br />IN OPERATION. ALL LOADS SHALL BE BALANCED ACROSS PHASES.
<br />CHECK TO SEE THAT ALL LIGHTS WORK, AND ARE CONTROLLED BY
<br />SWITCHES INDICATED ON DRAWINGS, OR CIRCUIT BREAKERS SO
<br />INDICATED ON PANEL SCHEDULE.
<br />2. GUARANTEE: FURNISH A GUARANTEE IN WRITING TO THE
<br />OWNER THAT ALL WORK EXECUTED UNDER THIS SECTION IS FREE
<br />FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF
<br />ONE (1) YEAR FROM DATE OF FINAL ACCEPTANCE. IN ADDITION,
<br />DURING THE TERM OF THIS GUARANTEE, THE REPAIR AND/OR
<br />REPLACEMENT OF ANY DEFECTIVE WORK, AND ALL RESULTING
<br />DAMAGES SHALL BE MADE AT NO ADDITIONAL EXPENSE TO THE
<br />OWNER.
<br />3. TEMPORARY POWER: AT THE PROJECT SITE, PROVIDE A 100
<br />AMP, 120/240 VOLT, SINGLE PHASE, SERVICE WITH POWER OUTLETS
<br />ADEQUATE FOR TEMPORARY CONSTRUCTION POWER. TEMPORARY
<br />LIGHTING SHALL BE MAINTAINED IN ALL AREAS OF THE BUILDING UNTIL
<br />PERMANENT POWER SOURCES HAVE BEEN ENERGIZED. TEMPORARY
<br />SERVICE SHALL BE PROVIDED UNDER SECTION 1A OF THESE
<br />SPECIFICATIONS.
<br />4. CLEAN-UP: LEAVE THE ELECTRICAL PORTION OF THE WORK IN A
<br />CLEAN AND FINISHED CONDITION.
<br />5. SHOP DRAWINGS: PROVIDE SHOP DRAWINGS FOR THE
<br />FOLLOWING ITEMS: PANELBOARDS, LIGHTING FIXTURES.
<br />6. AS -BUILT DRAWINGS: MAINTAIN AS -BUILT DRAWINGS, UPDATED
<br />DAILY DURING CONSTRUCTION, AND PRESENT THE OWNER WITH ONE
<br />SET UPON COMPLETION. PROVIDE THE OWNER'S PERSONNEL WITH
<br />ON -SITE INSTRUCTION IN THE OPERATION AND MAINTENANCE OF THE
<br />COMPLETED ELECTRICAL SYSTEM.
<br />SYMBOL LIST
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />00
<br />LIGHT FIXTURE, CEILING TYPE
<br />SEE FIXTURE
<br />LETTER INDICATES TYPE
<br />SCHEDULE
<br />SEE FIXTURE
<br />yyy
<br />TRACK LIGHTING
<br />SCHEDULE
<br />SWITCH, SINGLE POLE -LETTER
<br />48" AFF TO CL
<br />S
<br />INDICATES LIGHTS CONTROLLED
<br />OR AS NOTED
<br />S
<br />SWITCH, THREE WAY
<br />u
<br />AFF TO CL
<br />OR AS NOTED
<br />S
<br />DIMMER SWITCH
<br />48" AFF TO CL
<br />OR AS NOTED
<br />S
<br />SWITCH, DOUBLE POLE
<br />48" AFF TO CL
<br />OR AS NOTED
<br />SINGLE RECEPTACLE, 125V, 20A
<br />IS" AFF TO CL
<br />OR AS NOTED
<br />O
<br />SINGLE RECEPTACLE, 125V, 20A
<br />FLUSH WITH FLOOR
<br />(FLUSH FLOOR BOX)
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />24" AFF TO CL
<br />OR AS NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />46" AFF TO CL
<br />OR AS NOTED
<br />GFI
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />24" AFF TO CL
<br />GROUND FAULT
<br />OR AS NOTED
<br />WIP
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />IS" AFF TO CL
<br />WEATHERPROOF
<br />OR AS NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />46" AFF TO CL
<br />GROUND FAULT
<br />OR AS NOTED
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />FLUSH WITH CEILING
<br />C
<br />FLUSH CEILING BOX
<br />0__ 1
<br />QUADRAPLEX FRECEPTACLE, 125V, 20A
<br />24" AFF TO CL
<br />OR AS NOTED
<br />IG(5-
<br />DUPLEX RECEPTACLE, 125V, 20A
<br />24" AFF TO CL
<br />WITH ISOLATED GROUND
<br />OR AS NOTED
<br />QUADRAPLEX RECEPTACLE, 125V, 20A
<br />48" AFF TO CL
<br />OR AS NOTED
<br />O
<br />SPECIAL f;mCEPTACLE AS NOTED
<br />24" AFF TO CL
<br />OR AS NOTED
<br />-
<br />PANELBOARD 120/208V
<br />SEE PANEL
<br />SCHEDULE
<br />L
<br />DISCONNECT SWITCH
<br />•
<br />TOP 60" AFF
<br />SIZE/ FUSE/ OF POLES
<br />OR AS NOTED
<br />LIM
<br />COMBINATION MOTOR STARTER
<br />TOP 60" AFF
<br />DISCONNECT SWITCH
<br />OR AS NOTED
<br />4
<br />MOTOR
<br />AS NOTED
<br />SM
<br />MOTOR STARTER SWITCH WITH
<br />NOTED
<br />OVERLOAD RELAYS AS REQUIRED`
<br />ELECTRIC DUCT HEATER WITH
<br />AS NOTED
<br />DISCONNECT SWITCH
<br />■
<br />DEVICE AS NOTED
<br />AS NOTED
<br />0
<br />TRANSFORMER
<br />AS NOTED
<br />OUTLET BOX WITH FLEXIBLE
<br />AS NOTED OR
<br />CONDUIT CONNECTION TO EQUIPMENT
<br />REQUIRED
<br />©
<br />OUTLET, JUNCTION OR
<br />AS NOTED OR
<br />PULL BOX
<br />REQUIRED
<br />I
<br />DRIVEN GROUND, UNLESS
<br />I
<br />NOTED OTHERWISE
<br />CONDUIT CONCEALED IN CEILING
<br />NUMBER OF WIRES
<br />SPACE OR WALL
<br />INDICATED AS FOLLOWS
<br />TWO WIRES --�-
<br />CONDUIT IN FLOOR SLAB, CEILING
<br />SLAB OR UNDERGROUND
<br />THREE WIRES I.
<br />HOME RUN TO PANEL (HASH MARKS
<br />FOUR WIRES -
<br />INDICATE NUMBER OF WIRES)
<br />���
<br />CONDUIT RUN EXPOSED
<br />O O
<br />REFER TO LIKE NUMBERED NOTES
<br />D
<br />COMMUNICATIONS OUTLET
<br />24" AFF OR AS
<br />NOTED
<br />COMMUNICATIONS OUTLET
<br />48' AFF OR AS
<br />NOTED
<br />S
<br />DUCT TYPE SMOKE DETECTOR
<br />HVAC
<br />D
<br />RK
<br />DUCTWORK
<br />®
<br />FAN SHUT DOWN RELAY
<br />AS NOTED
<br />0
<br />DUCT DETECTOR TEST/RESET
<br />48 AFF OR AS
<br />NOTED
<br />©
<br />DOOR BUZZER
<br />AS NOTED
<br />�.
<br />DOOR BUZZER PUSHBUTTON
<br />AS NOTED
<br />NOTE ALL MOUNTING HEIGHTS SHOWN ARE TO THE CENTERLINE
<br />OF THE DEVICE UNLESS NOTED OTHERWISE.
<br />NOT ALL SYMBOLS APPEAR ON PLANS.
<br />ABBREVIATIONS
<br />AFF - ABOVE FINISHED FLOOR
<br />AHU - AIR HANDLING UNIT
<br />BFG - BELOW FINISHED GRADE
<br />C - CONDUIT
<br />CL - CENTERLINE
<br />CW - COOL WH 1 TE
<br />DACP - DOOR ALARM CONTROL PANEL
<br />DN - DOWN
<br />EF - EXHAUST FAN
<br />EG - EQUIPMENT GROUND
<br />ENCL - ENCLOSURE
<br />EWC - ELECTRIC WATER COOLER
<br />EWH - ELECTRIC WATER HEATER
<br />FCU - FAN COIL UNIT
<br />FHP - FRACTIONAL HORSE POWER
<br />FLA - FULL LOAD AMPERES
<br />G - GROUND
<br />GFI - GROUND FAULT INTERRUPTER
<br />HID - HIGH INTENSISTY DISCHARGE
<br />HORIZ - HORIZONTAL
<br />IG - ISOLATED GROUND
<br />LW - LIGHT WHITE
<br />HP - HORSEPOWER, HEAT PUMP
<br />HVAC - HEATING, VENTILATING, AIR CONDITIONING
<br />JB - JUNCTION BOX
<br />LRA - LOCKED ROTOR AMPERES
<br />MCB - MAIN CIRCUIT BREAKER
<br />MLO - MAIN LUGS ONLY
<br />N - NEUTRAL
<br />NL - NIGHT LIGHT
<br />OB - OUTLET BOX
<br />PB - PULL BOX, PUSHBUTTON
<br />PS - PAY STATION
<br />RECEPT - RECEPTACLE
<br />RLC - RELOCATED
<br />SPEC - SPECIFICATIONS
<br />TTB - TELEPHONE TERMINAL BOARD
<br />TVTB - TELEVISION TERMINAL BOARD
<br />VERT - VERTICAL
<br />WP - WEATHERPROOF
<br />uW - WARM WHITE
<br />XFMR - TRANSFORMER
<br />MANUFACTURER: SQUARE D
<br />MLO OR MCB:
<br />MLO
<br />PANEL: A
<br />TYPE: EXISTING
<br />FEED:
<br />BOTTOM
<br />VOLTAGE: 120/208V, 3 0, 4 WIRE
<br />MOUNTING: FLUSH
<br />CUORALWIRE:
<br />CU
<br />MAIN AMPS: 150AMP
<br />LOCATION: BACKWALL
<br />AICRATING:
<br />10,000AMPS
<br />FEEDER: 150 AMP
<br />BREAKER OPTIONS:
<br />NOTES:
<br />- EXISTING BREAKER NEW CIRCUIT
<br />I,-
<br />ISOLATED GROUND CIRCUIT
<br />& - PROVIDE BREAKER LOCK -OUT DEVICE
<br />CKT
<br />CKT
<br />NO.
<br />LOAD
<br />OPT
<br />CODE
<br />KVA
<br />WIRE
<br />BRKR
<br />PHASE
<br />BRKR
<br />WIRE
<br />KVA
<br />CODE
<br />OPT: LOAD
<br />NO.
<br />1
<br />RECEPTACLES DINING
<br />:#
<br />R
<br />0.54
<br />12
<br />20
<br />A
<br />20
<br />12
<br />1.08
<br />R
<br /># & : SECURITY CAMERA RECEPT
<br />2
<br />3
<br />RECEPTACLES DINING
<br />#
<br />R
<br />0.72
<br />12
<br />20
<br />B
<br />20
<br />12
<br />0.86
<br />E
<br /># : BAG-N-BOX CARBONATOR K42
<br />4
<br />5
<br />BEVERAGE DISP DINING K-32
<br />#
<br />E
<br />0.48
<br />12
<br />20
<br />C
<br />20
<br />12
<br />0.36
<br />R
<br /># & SECURITY SYSTEM OFFICE
<br />6
<br />7
<br />POS DRIVE THRU P-20 , P-30
<br /># !
<br />R
<br />0.54
<br />12
<br />20
<br />A
<br />20
<br />12
<br />0.50
<br />R
<br /># MUSIC SYSTEM OFFICE
<br />8
<br />9
<br />RECEPTS KITCHEN
<br />#
<br />R
<br />0.90
<br />12
<br />20
<br />B
<br />20
<br />12
<br />0.54
<br />R
<br /># ! POS SYSTEM OFFICE
<br />10
<br />11
<br />SAFE M30
<br /># &
<br />R
<br />0.60
<br />12
<br />20
<br />C
<br />20
<br />12
<br />0.50
<br />R
<br /># ! COMPUTER PRINTER OFFICE
<br />12
<br />13
<br />BEVERAGE DISP DRIVE TH K-31
<br />;#
<br />R
<br />0.18
<br />12
<br />20
<br />A
<br />20
<br />12
<br />0.36
<br />R
<br /># RECEPTS OFFICE
<br />14
<br />15
<br />REFRIGERATOR UPRIGHT B60
<br /># &
<br />E
<br />1.38
<br />12
<br />20
<br />B
<br />20
<br />12
<br />1.00
<br />E
<br /># DRIVE THRU AUDIO SYSTEM
<br />16
<br />17
<br />REFRIGERATOR UPRIGHT A54
<br /># &
<br />E
<br />1.38
<br />12
<br />20
<br />C
<br />20
<br />12
<br />1.00
<br />R
<br /># ! :VIDEO MONITORS
<br />18
<br />19
<br />ICE BATTER TABLE A47.4
<br /># &
<br />E
<br />0.30
<br />12
<br />20
<br />A
<br />20
<br />12
<br />0.10
<br />E
<br /># : DOOR BUZZER
<br />20
<br />21
<br />MARINATOR A31
<br />#
<br />E
<br />0.75
<br />12
<br />20
<br />B
<br />20
<br />12
<br />1
<br /># SPARE
<br />22
<br />23
<br />BREWER TEA COFFEE K71
<br />#
<br />K
<br />1.70
<br />12
<br />20
<br />C
<br />20
<br />12
<br />I
<br /># • SPARE
<br />24
<br />25
<br />POS DINING P-20 , P-30
<br /># !
<br />R
<br />0.72
<br />12
<br />20
<br />A
<br />20
<br />12
<br />1
<br /># SPARE
<br />26
<br />27
<br />RECEPT TELEPHONE BOARD
<br /># &
<br />R
<br />0.36
<br />12
<br />20
<br />B
<br />20
<br />12
<br />1
<br /># 'SPARE
<br />28
<br />29
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />C
<br />20
<br />12
<br />1
<br /># :SPARE
<br />30
<br />31
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />A
<br />20
<br />12
<br />1
<br /># :SPARE
<br />32
<br />33
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />B
<br />20
<br />12
<br />I
<br /># :SPARE
<br />34
<br />35
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />C
<br />2P
<br />15
<br />12
<br />1
<br /># :SPARE
<br />#
<br />36
<br />37
<br />SPARE #
<br />1
<br />12
<br />20
<br />A
<br />12
<br />1
<br />38
<br />39
<br />SPACE
<br />I
<br />B
<br />40
<br />41
<br />SPACE
<br />ClI
<br />42
<br />KVA PER PHASE=
<br />BUS A:
<br />4.32
<br />DEMAND
<br />BUS B:
<br />6.51
<br />KVA
<br />FACTOR
<br />DEMAND KVA
<br />BUS C:
<br />6.02
<br />(L) LIGHTING: 0.00
<br />X
<br />1.25 =
<br />0.00
<br />TOTAL KVA:
<br />16.85
<br />(R) RECEPTACLES: 8.90
<br />X
<br />1.00 =
<br />8.90
<br />(R) RECEPTACLES: 0.00
<br />X
<br />0.50 =
<br />0.00
<br />PANEL CALCULATIONS
<br />(H) HVAC: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DEMAND KVA:
<br />16.26
<br />(E) EQUIPMENT: 6.25
<br />X
<br />1.00 =
<br />6.25
<br />TIMES 1000
<br />JOB NAME:
<br />(K) KITCHEN EQUIPMENT: 1.70
<br />X
<br />0.65 =
<br />1.11
<br />DIVIDED BY 1.732
<br />Popeye's Zephyrhills
<br />(S) SUBFEED: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DIVIDED BY 208
<br />MPS #:
<br />LARGEST MOTOR: 0.00
<br />X
<br />0.25 =
<br />0.00
<br />213027
<br />TOTAL DEMAND KVA:
<br />16.26
<br />PANEL DEMAND AMPS:
<br />45.12 DATE LAST MODIFIED
<br />3/21/2013
<br />MANUFACTURER: SUQARE D
<br />MLO OR MCB:
<br />MLO
<br />PANEL: B
<br />TYPE: EXISTING
<br />FEED:
<br />BOTTOM
<br />VOLTAGE: 120/208V, 3 0, 4 WIRE
<br />MOUNTING: FLUSH
<br />CUORALWIRE:
<br />CU
<br />MAIN AMPS: 200AMPS
<br />LOCATION: BACK WALL
<br />AICRATING:
<br />10,000AMPS
<br />FEEDER: 200AMPS
<br />BREAKER OPTIONS:
<br />NOTES:
<br /># - EXISTING BREAKER NEW CIRCUIT
<br />% - EXISTING BREAKER EXISTING CIRCUIT
<br />A - WIRE CIRCUIT THROUGH LIGHTING
<br />CONTACTOR AS SPECIFIED ON PLAN
<br />& - PROVIDE BREAKER LOCK -OUT DEVICE
<br />CKT
<br />CKT
<br />NO.
<br />LOAD
<br />;OPT
<br />CODE
<br />KVA
<br />WIRE
<br />BRKR
<br />PHASE
<br />BRKR
<br />WIRE
<br />KVA
<br />CODE
<br />OPT; LOAD
<br />NO.
<br />1
<br />MENUBOARD DRIVE THRU Q20
<br /># A
<br />L
<br />1.00
<br />10
<br />20
<br />A
<br />20
<br />12
<br />0.65
<br />L
<br /># : LIGHTS DINING SWITCH a
<br />2
<br />3
<br />DIRECTION SIGNS
<br /># A
<br />L
<br />1.00
<br />10
<br />20
<br />B
<br />20
<br />12
<br />0.54
<br />L
<br /># : LIGHTS DINING SWITCH b
<br />4
<br />5
<br />LIGHTS COOLER FREEZER
<br />% &
<br />L
<br />1.00
<br />12
<br />20
<br />C
<br />20
<br />12
<br />0.58
<br />L
<br /># • LIGHTS DINING SWITCH c
<br />6
<br />7
<br />LIGHTING CONTACTOR CONTROL
<br /># &
<br />E
<br />0.25
<br />12
<br />20
<br />A
<br />20
<br />12
<br />1.19
<br />L
<br /># LIGHTS KITCHEN SWITCH d
<br />8
<br />9
<br />CANOPY LIGHTS
<br /># A
<br />L
<br />0.70
<br />10
<br />20
<br />B
<br />20
<br />12
<br />1.04
<br />L
<br /># LGTS KIT RESTROOM SWITCH a
<br />10
<br />11
<br />CANOPY LIGHTS
<br /># A
<br />L
<br />0.80
<br />10
<br />20
<br />C
<br />20
<br />12
<br />SPARE
<br />12
<br />13
<br />CANOPY LIGHTS
<br /># A
<br />L
<br />1.00
<br />10
<br />20
<br />A
<br />20
<br />12
<br />1
<br />SPARE
<br />14
<br />15
<br />MENUBOARD DINING Q10
<br />#
<br />L
<br />1.00
<br />12
<br />20
<br />B
<br />2P
<br />20
<br />10
<br />1.60
<br />L
<br />% A : PARKING LOT LIGHTS
<br />% A : EXISTING
<br />16
<br />17
<br />ROOF CAP %
<br />L
<br />0.50
<br />12
<br />20
<br />C
<br />10
<br />1.60
<br />L
<br />18
<br />19
<br />SPARE
<br />: #
<br />1
<br />12
<br />20
<br />A
<br />2P
<br />20
<br />10
<br />1.60
<br />L
<br />% A : PARKING LOT LIGHTS
<br />% A : EXISTING
<br />20
<br />21
<br />SPARE #
<br />1
<br />12
<br />20
<br />B
<br />10
<br />1.60
<br />L
<br />22
<br />23
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />C
<br />2P
<br />20
<br />10
<br />1.60
<br />L
<br />% A PARKING LOT LIGHTS
<br />% A EXISTING
<br />24
<br />25
<br />SPARE #
<br />1
<br />12
<br />20
<br />A
<br />10
<br />1.60
<br />L
<br />26
<br />27
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />B
<br />20
<br />12
<br />1.00
<br />L
<br /># A 'BUILDING MOUNTED SIGN
<br />28
<br />29
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />C
<br />20
<br />12
<br />1.00
<br />L
<br /># A BUILDING MOUNTED SIGN
<br />30
<br />31
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />A
<br />20
<br />12
<br />1.00
<br />L
<br /># A BUILDING MOUNTED SIGN
<br />32
<br />33
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />B
<br />20
<br />12
<br />1.00
<br />L
<br /># A : BUILDING MOUNTED SIGN
<br />34
<br />35
<br />SPARE
<br />: #
<br />1
<br />12
<br />20
<br />Ct20
<br />12
<br />1
<br />:SPARE
<br />36
<br />37
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />A
<br />12
<br />1
<br />SPARE
<br />38
<br />39
<br />PYLON SIGN
<br /># A
<br />L
<br />1.00
<br />10
<br />20
<br />8
<br />12
<br />1
<br />SPARE
<br />40
<br />41
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />C
<br />20
<br />12
<br />1
<br />SPARE
<br />42
<br />KVA PER PHASE=
<br />BUS A:
<br />8.29
<br />DEMAND
<br />BUS B:
<br />10.48
<br />KVA
<br />FACTOR
<br />DEMAND KVA
<br />BUS C:
<br />7.08
<br />(L) LIGHTING: 25,60
<br />X
<br />1.25 =
<br />32.00
<br />TOTAL KVA:
<br />25.65
<br />(R) RECEPTACLES: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />(R) RECEPTACLES: 0.00
<br />X
<br />0.50 =
<br />0.00
<br />PANEL CALCULATIONS
<br />(H) HVAC: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DEMAND KVA:
<br />32.25
<br />(E) EQUIPMENT: 0.25
<br />X
<br />1.00 =
<br />0.25
<br />TIMES 1000
<br />JOB NAME:
<br />(K) KITCHEN EQUIPMENT: 0.00
<br />X
<br />0.65 =
<br />0.00
<br />DIVIDED BY 1.732
<br />Popeye's Zephyrhills
<br />(S) SUBFEED: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DIVIDED BY 208
<br />MPS #:
<br />LARGEST MOTOR: 0.00
<br />X
<br />0.25 =
<br />0.a
<br />213027
<br />TOTAL DEMAND KVA:
<br />32.25
<br />PANEL DEMAND AMPS:
<br />89.52 DATE LAST MODIFIED
<br />X21/2013
<br />MANUFACTURER: SUQARE D
<br />MLO OR MCB:
<br />MLO
<br />PANEL: C
<br />TYPE: EXISTING
<br />FEED:
<br />BOTTOM
<br />VOLTAGE: 120/208V, 3 (0, 4 WIRE
<br />MOUNTING: FLUSH
<br />CUORALWIRE:
<br />CU
<br />MAIN AMPS: 150 AMPS
<br />LOCATION: BACK WALL
<br />AICRATING:
<br />10,000 AMPS
<br />FEEDER: 150 AMPS
<br />BREAKER OPTIONS:
<br />NOTES:
<br /># - EXISTING BREAKER NEW CIRCUIT
<br />$ - NEW BREAKER NEW CIRCUIT
<br />& - PROVIDE BREAKER LOCK -OUT DEVICE
<br />CKT
<br />CKT
<br />NO.
<br />LOAD
<br />:OPT
<br />CODE
<br />KVA
<br />WIRE
<br />BRKR
<br />PHASE
<br />BRKR
<br />WIRE
<br />KVA
<br />CODE
<br />OPT; LOAD
<br />NO.
<br />1
<br />HOLDING UNIT SIDES (D92)
<br />#
<br />#
<br />K
<br />1.67
<br />12
<br />2P
<br />20
<br />A
<br />2P
<br />20
<br />12
<br />1.75
<br />K
<br /># & :PRODUCTION COUNTER (H10.4PD)
<br /># & :
<br />2
<br />3
<br />K
<br />1.67
<br />12
<br />B
<br />12
<br />1.75
<br />K
<br />4
<br />5
<br />HOLDING UNIT SIDES (D92)
<br />#
<br />#
<br />K
<br />1.67
<br />12
<br />2P
<br />20
<br />C
<br />2P
<br />20
<br />12
<br />0.63
<br />K
<br /># & • HOT FOOD WELL (H10.4PD)
<br /># &
<br />6
<br />7
<br />K
<br />1.67
<br />12
<br />A
<br />12
<br />0.63
<br />K
<br />8
<br />9
<br />HOLDING UNIT (D94)
<br />$
<br />$
<br />K
<br />2.85
<br />10
<br />2P
<br />30
<br />B
<br />2P
<br />20
<br />12
<br />0.45
<br />E
<br /># & HEAT LAMPS (H10.4PD)
<br /># &
<br />10
<br />11
<br />K
<br />2.85
<br />1 10
<br />C
<br />1 12
<br />1 0.45
<br />E
<br />12
<br />13
<br />CHICKEN HOLDING UNIT (D93)
<br />$ &
<br />$ &
<br />K
<br />3.08
<br />8
<br />2P
<br />40
<br />A
<br />20
<br />12
<br />1.50
<br />K
<br /># ; TOASTER VERT C20
<br />14
<br />15
<br />K
<br />3.08
<br />8
<br />B
<br />20
<br />12
<br />0.78
<br />K
<br /># & SANDWICH FRIDGE C10.27
<br />16
<br />17
<br />UNDER COUNTER FRIDGE J40
<br /># &
<br />E
<br />0.58
<br />12
<br />20
<br />C
<br />20
<br />12
<br />0.55
<br />K
<br /># HOLDING UNIT C30
<br />18
<br />19
<br />PACK STATION DIP WELL (D30)
<br />: # &
<br /># &
<br />E
<br />0.62
<br />12
<br />2P
<br />20
<br />A
<br />2P
<br />30
<br />10
<br />2.00
<br />E
<br />$ : HOT WATER DISP (D70)
<br />$ :
<br />20
<br />21
<br />E
<br />0.62
<br />12
<br />B
<br />10
<br />2.00
<br />E
<br />22
<br />23
<br />MICROWAVE (D20)
<br />$
<br />$
<br />K
<br />2.00
<br />10
<br />2P
<br />30
<br />C
<br />2P
<br />30
<br />10
<br />2.00
<br />E
<br />$ HOT WATER DISP (D70)
<br />$
<br />24
<br />25
<br />K
<br />2.00
<br />10
<br />A
<br />10
<br />2.00
<br />E
<br />26
<br />27
<br />MICROWAVE (D20)
<br />$
<br />$
<br />K
<br />2.00
<br />10
<br />2P
<br />30
<br />B
<br />25
<br />10
<br />2.32
<br />K
<br />$ HOLDING CABINET D90
<br />28
<br />29
<br />K
<br />2.00
<br />10
<br />C
<br />2P
<br />20
<br />12
<br />1.24
<br />E
<br />$ ICE CUBER (K10)
<br />$
<br />30
<br />31
<br />BISCUIT HOLDING B65 #
<br />K
<br />1.00
<br />12
<br />20
<br />A
<br />12
<br />1.24
<br />E
<br />32
<br />33
<br />FLY FAN
<br />#
<br />E
<br />0.50
<br />12
<br />20
<br />B
<br />I
<br />SPACE
<br />34
<br />35
<br />SPARE
<br />20
<br />C
<br />I
<br />SPACE
<br />36
<br />37
<br />SPARE
<br />1
<br />20
<br />A
<br />I
<br />SPACE
<br />38
<br />39
<br />SPACE
<br />I
<br />B
<br />I
<br />SPACE
<br />40
<br />41
<br />SPACE
<br />I
<br />I
<br />ClI
<br />SPACE
<br />42
<br />KVA PER PHASE=
<br />BUS A:
<br />19.16
<br />DEMAND
<br />BUS B:
<br />18.02
<br />KVA
<br />FACTOR
<br />DEMAND KVA
<br />BUS C:
<br />13_97
<br />(L) LIGHTING: 0.00
<br />X
<br />1.25 =
<br />0.00
<br />TOTAL KVA:
<br />51.15
<br />(R) RECEPTACLES: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />(R) RECEPTACLES: 0.00
<br />X
<br />0.50 =
<br />0.00
<br />PANEL CALCULATIONS
<br />(H) HVAC: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DEMAND KVA:
<br />38.04
<br />(E) EQUIPMENT: 13.70
<br />X
<br />1.00 =
<br />13.70
<br />TIMES 1000
<br />JOB NAME:
<br />(K) KITCHEN EQUIPMENT: 37.45
<br />X
<br />0.65 =
<br />24.34
<br />DIVIDED BY 1.732
<br />Popeye's Zephyrhills
<br />(S) SUBFEED: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DIVIDED BY 208
<br />MPS #:
<br />LARGEST MOTOR: 0.00
<br />X
<br />0.25 =
<br />0.00
<br />213027
<br />TOTAL DEMAND KVA:
<br />38.04
<br />PANEL DEMAND AMPS:
<br />105.60 DATE LAST MODIFIED
<br />3/21/2013
<br />MANUFACTURER: SUQARE D
<br />MLO OR MCB:
<br />MLO
<br />PANEL: D
<br />TYPE: EXISTING
<br />FEED:
<br />BOTTOM
<br />VOLTAGE: 120/208V, 3 0, 4 WIRE
<br />MOUNTING: FLUSH
<br />CUORALWIRE:
<br />CU
<br />MAINAMPS: 400AMPS
<br />LOCATION: BACK WALL
<br />AICRATING:
<br />10,000 AMPS
<br />FEEDER: 400 AMPS
<br />BREAKER OPTIONS:
<br />NOTES:
<br />#- EXISTING BREAKER NEW CIRCUIT
<br />%- EXISTING BREAKER EXISTING CIRCUIT
<br />& - PROVIDE BREAKER LOCK -OUT DEVICE
<br />$ - NEW BREAKER NEW CIRCUIT
<br />CKT
<br />CKT
<br />NO.
<br />LOAD
<br />;OPT
<br />CODE
<br />KVA
<br />WIRE
<br />BRKR
<br />PHASE
<br />BRKR
<br />WIRE
<br />KVA
<br />CODE
<br />OPT; LOAD
<br />NO.
<br />1
<br />WALK IN COOLER
<br />; % &
<br />: % &
<br />: % &
<br />H
<br />1.44
<br />12
<br />3P
<br />15
<br />A
<br />20
<br />12
<br />1
<br /># : SPARE
<br />2
<br />3
<br />H
<br />1.44
<br />12
<br />B
<br />2P
<br />60
<br />6
<br />4.75
<br />K
<br />$ : CHUB WARMER (D81)
<br />$ :
<br />4
<br />5
<br />H
<br />1.44
<br />12
<br />C
<br />6
<br />4.75
<br />K
<br />6
<br />7
<br />WALK IN FREEZER
<br />% &
<br />°/a &
<br />% &
<br />H
<br />2.40
<br />10
<br />3P
<br />25
<br />A
<br />3P
<br />30
<br />10
<br />1.87
<br />K
<br />$ CONVECTION OVEN STACK
<br />$ 1 OF 2
<br />$
<br />8
<br />9
<br />H
<br />2.40
<br />10
<br />B
<br />10
<br />1.87
<br />K
<br />10
<br />11
<br />H
<br />1 2.40
<br />10
<br />C
<br />10
<br />1.87
<br />K
<br />12
<br />13
<br />ROOF RECEPTACLES
<br />; % &
<br />R
<br />0.36
<br />12
<br />20
<br />A
<br />3P
<br />30
<br />10
<br />1.87
<br />K
<br />$ CONVECTION OVEN STACK
<br />$ : 2 OF 2
<br />$
<br />14
<br />15
<br />HOOD EXHAUST FAN EF-2 #
<br />H
<br />1.50
<br />12
<br />20
<br />8
<br />10
<br />1.87
<br />K
<br />16
<br />17
<br />HOOD EXHAUST FAN EF-3 #
<br />H
<br />1.50
<br />12
<br />20
<br />C
<br />10
<br />1.87
<br />K
<br />18
<br />19
<br />HOOD CONTROLS F15
<br />#
<br />E
<br />0.50
<br />12
<br />20
<br />A
<br />3P
<br />15
<br />12
<br />1
<br /># :
<br /># SPARE
<br />#
<br />20
<br />21
<br />IRRIGATION TIMER %&
<br />E
<br />0.25
<br />12
<br />20
<br />B
<br />12
<br />1
<br />22
<br />23
<br />WATER HEATER CONTROLS : % &
<br />R
<br />0.18
<br />12
<br />20
<br />1 C
<br />12
<br />24
<br />25
<br />RTU-1
<br />%
<br />%
<br />%
<br />H
<br />7.56
<br />4
<br />3P
<br />80
<br />A
<br />3P
<br />15
<br />12
<br />#
<br /># SPARE
<br />#
<br />26
<br />27
<br />H
<br />7.56
<br />4
<br />B
<br />12
<br />28
<br />29
<br />H
<br />7.56
<br />4
<br />C
<br />12
<br />FR
<br />30
<br />31
<br />RTU-2
<br />%
<br />%
<br />%
<br />%
<br />%
<br />%
<br />H
<br />12.11
<br />210
<br />3P
<br />150
<br />A
<br />20
<br />12
<br />0.18
<br />% &; ROOF RECEPTACLE
<br />32
<br />33
<br />H
<br />12.11
<br />B
<br />20
<br />12
<br />0.50
<br />#& :ANSUL SYSTEM
<br />34
<br />35
<br />H
<br />12.11
<br />2/0
<br />C
<br />20
<br />12
<br /># : SPARE
<br />36
<br />37
<br />H
<br />-
<br />A
<br />20
<br />12
<br />1
<br /># SPARE
<br />38
<br />39
<br />H
<br />-
<br />2/O
<br />B
<br />20
<br />12
<br />1
<br /># -SPARE
<br />40
<br />41
<br />F H
<br />-
<br />C
<br />20
<br />12
<br />1 I
<br />1 # -SPARE
<br />42
<br />KVA PER PHASE=
<br />BUS A:
<br />28.29
<br />DEMAND
<br />BUS B:
<br />34.25
<br />KVA
<br />FACTOR
<br />DEMAND KVA
<br />BUS C:
<br />33_68
<br />(L) LIGHTING: 0.00
<br />X
<br />1.25 =
<br />0.00
<br />TOTAL KVA:
<br />96.22
<br />(R) RECEPTACLES: 0.72
<br />X
<br />1.00 =
<br />0.72
<br />(R) RECEPTACLES: 0.00
<br />X
<br />0.50 =
<br />0.00
<br />PANEL CALCULATIONS
<br />(H) HVAC: 73.53
<br />X
<br />1.00 =
<br />73.53
<br />DEMAND KVA:
<br />88.97
<br />(E) EQUIPMENT: 1.25
<br />X
<br />1.00 =
<br />1.25
<br />TIMES 1000
<br />JOB NAME:
<br />(K) KITCHEN EQUIPMENT: 20.72
<br />X
<br />0.65 =
<br />13.47
<br />DIVIDED BY 1.732
<br />Popeye's Zephyrhills
<br />(S) SUBFEED: 0.00
<br />X
<br />1.00 =
<br />0.00
<br />DMOED BY 208
<br />MPS #:
<br />LARGEST MOTOR: 0.00
<br />X
<br />0.25 =
<br />0.00
<br />213027
<br />TOTAL DEMAND KVA:
<br />88.97
<br />1 PANEL DEMAND AMPS:
<br />246.96 DATE LAST MODIFIED
<br />3/2112013
<br />MANUFACTURER: SUQARE D
<br />MLO OR MCB:
<br />MLO
<br />PANEL: H
<br />TYPE: EXISTING
<br />FEED:
<br />BOTTOM
<br />VOLTAGE: 120/208V, 3 m, 4 WIRE
<br />MOUNTING: FLUSH
<br />CU ORAL WIRE:
<br />CU
<br />MAIN AMPS: 100 AMPS
<br />LOCATION: BACK WALL
<br />AICRATING:
<br />10,000 AMPS
<br />FEEDER: 100 AMPS
<br />BREAKER OPTIONS:
<br />NOTES:
<br /># - EXISTING BREAKER NEW CIRCUIT
<br />$ - NEW BREAKER NEW CIRCUIT
<br />THIS PANEL IS FED THROUGH A CONTACTOR TO FACILITATE
<br />SHUTDOWN OF UNDER HOOD EQUIPMENT.
<br />CKT
<br />CKT
<br />NO.
<br />LOAD
<br />;OPT
<br />CODE
<br />KVA
<br />WIRE
<br />BRKR
<br />PHASE
<br />BRKR
<br />WIRE
<br />KVA
<br />CODE
<br />OPT; LOAD
<br />NO.
<br />1
<br />FRYER CONTROLS A18.U6
<br />: #
<br />E
<br />1.00
<br />12
<br />20
<br />A
<br />20
<br />12
<br />1
<br /># SPARE
<br />2
<br />3
<br />HEATED HOLDING UNIT (F15.1)
<br />: $
<br />: $
<br />E
<br />2.00
<br />10
<br />2P
<br />30
<br />B
<br />20
<br />12
<br />1
<br /># : SPARE
<br />4
<br />5
<br />E
<br />2.00
<br />10
<br />C
<br />20
<br />12
<br /># SPARE
<br />6
<br />7
<br />SPARE
<br />#
<br />I
<br />12
<br />20
<br />A
<br />20
<br />1 12
<br />1
<br /># SPARE
<br />8
<br />9
<br />SPARE
<br />#
<br />1
<br />12
<br />20
<br />B
<br />20
<br />12
<br />1
<br /># SPARE
<br />10
<br />11
<br />SPACE
<br />I
<br />C
<br />20
<br />12
<br />1
<br /># 'SPARE
<br />12
<br />13
<br />SPACE
<br />I
<br />A
<br />I
<br />SPACE
<br />14
<br />15
<br />SPACE
<br />I
<br />B
<br />I
<br />;SPACE
<br />16
<br />17
<br />SPACE
<br />I
<br />C
<br />I
<br />;SPACE
<br />18
<br />19
<br />SPACE
<br />I
<br />A
<br />I
<br />SPACE
<br />20
<br />21
<br />SPACE
<br />I
<br />B
<br />I
<br />SPACE
<br />22
<br />23
<br />SPACE
<br />I
<br />C
<br />I
<br />SPACE
<br />24
<br />25
<br />SPACE
<br />I
<br />A
<br />I
<br />'SPACE
<br />26
<br />27
<br />SPACE
<br />1
<br />B
<br />I
<br />SPACE
<br />28
<br />29
<br />SPACE
<br />I
<br />C
<br />I
<br />;SPACE
<br />30
<br />31
<br />SPACE
<br />I
<br />A
<br />I
<br />;SPACE
<br />32
<br />33
<br />SPACE
<br />I
<br />B
<br />I
<br />:SPACE
<br />34
<br />35
<br />SPACE
<br />I
<br />C
<br />I
<br />SPACE
<br />36
<br />37
<br />SPACE
<br />I
<br />A
<br />I
<br />:SPACE
<br />38
<br />39
<br />SPACE
<br />I
<br />B
<br />I
<br />SPACE
<br />40
<br />41
<br />SPACE
<br />1
<br />C
<br />I
<br />SPACE
<br />42
<br />KVA PER PHASE=
<br />BUS A: 1.00
<br />DEMAND
<br />BUS B: 2.00
<br />KVA
<br />FACTOR
<br />DEMAND KVA
<br />BUS C: 2.&
<br />(L) LIGHTING:
<br />0.00
<br />X
<br />1.25 =
<br />0.00
<br />TOTAL KVA: 5.00
<br />(R) RECEPTACLES:
<br />0.00
<br />X
<br />1.00 =
<br />0.00
<br />(R) RECEPTACLES:
<br />0.00
<br />X
<br />0.50 =
<br />0.00
<br />PANEL CALCULATIONS
<br />(H) HVAC:
<br />0.00
<br />X
<br />1.00 =
<br />0.00
<br />DEMAND KVA:
<br />5.00
<br />(E) EQUIPMENT.
<br />5.00
<br />X
<br />1.00 =
<br />5.00
<br />TIMES 1000
<br />JOB NAME:
<br />(K) KITCHEN EQUIPMENT:
<br />0.00
<br />X
<br />0.65 =
<br />0.00
<br />DIVIDED BY 1.732 Papaya's Zephyrhills
<br />(S) SUBFEED:
<br />0.00
<br />X
<br />1.00 =
<br />0.00
<br />DIVIDED BY 208 MPS #:
<br />LARGEST MOTOR:
<br />0.00
<br />X
<br />0.25 =
<br />0,00
<br />213027
<br />TOTAL DEMAND KVA:
<br />5.00
<br />PANEL DEMAND AMPS: 13.88 DATE LAST MODIFIED
<br />3/2112013
<br />SERVICE LOAD CALCULATION
<br />PANEL
<br />LIGHTS
<br />RECEPT.
<br />HVAC EQUIP. KITCHEN
<br />TOTALS
<br />PAN EL A
<br />0.00
<br />8.90
<br />0.00 6.25 1.70
<br />16.85
<br />KVA
<br />PANEL B
<br />25.60
<br />0.00
<br />0.00 0.25 0.00
<br />25.85
<br />KVA
<br />PANEL C
<br />0.00
<br />0.00
<br />0.00 13.70 37.45
<br />51.15
<br />KVA
<br />PANEL D
<br />0.00
<br />0.72
<br />73.53 1.25 20.72
<br />96.22
<br />KVA
<br />PANEL H
<br />0.00
<br />0.00
<br />0.00 5.00 0.00
<br />5.00
<br />KVA
<br />TOTALS
<br />25.60
<br />9.62
<br />73.53 26.45 59.87
<br />195.07
<br />KVA
<br />X 125%
<br />X 50%
<br />X 100% X 100% X 65%
<br />32.00
<br />4.81
<br />73.53 26.45 38.92
<br />175.71
<br />KVA
<br />RECEPTACLE ADJUSTMENT +5.00
<br />KVA
<br />LARGEST MOTOR
<br />9.10
<br />X DEMAND LOAD OF 25% PER NEC
<br />2.28
<br />KVA
<br />182.98
<br />KVA
<br />X
<br />1000
<br />DIVIDED BY
<br />1.73
<br />DIVIDED BY
<br />208
<br />507.92
<br />AMPS
<br />A 800 AMP, 120/208V, 3 PHASE, 4 WIRE SERVICE HAS BEEN PROVIDED
<br />EXISTING SWITCHBOARD SCHEDULE
<br />MFR: SQUARED
<br />SHORT CIRCUIT RATING: EXISTING MAIN: MLO 800 A VOLTAGE: 120/208 PHASE:
<br />30, 4W
<br />FEEDER NO.
<br />SERVING
<br />LOAD (KW)
<br />BREAKER
<br />WIRE
<br />CONDUIT
<br />POLES
<br />1
<br />PANELA
<br />16.26
<br />150A
<br />#1/0AWG
<br />1.511
<br />3
<br />2
<br />PANEL B
<br />32.25
<br />200A
<br />#3/0 AWG
<br />2.0"
<br />3
<br />3
<br />PANEL C
<br />38.04
<br />150A
<br />#1/0 AWG
<br />1.511
<br />3
<br />4
<br />PANEL D
<br />88.97
<br />400A
<br />#500 MCM
<br />3.511
<br />3
<br />5
<br />PANEL H
<br />5.01
<br />100A
<br />#3 AWG
<br />1.25"
<br />3
<br />CONTRACTOR SHALL VERIFY THE ABOVE MINIMUM FEEDER CONDUCTOR SIZES. CONTRACTOR SHALL NOTIFY ENGINEER IF ANY OF THE
<br />ABOVE CONDUCTORS ARE FOUND TO BE SMALLER THAN THE MINIMUM SPECIFIED IN THIS MOP SCHEDULE.
<br />101 ELECTRICAL SPECIFICAtIONS IOI EL�CTRIC,4L SYMBOLS I OI PANEL 3CHEDULEB 1
<br />REVISIONS
<br />BY
<br />V `0
<br />CD
<br />Y M N
<br />Q�-.
<br />O 0 ti E
<br />o
<br />_ ti v
<br />/
<br />N_a�r
<br />C U
<br />O U N cu
<br />>
<br />EE
<br />m o
<br />N !`
<br />3
<br />z N
<br />o ti
<br />/
<br />p :D c
<br />o1` o
<br />ba
<br />N
<br />U
<br />$1to
<br />0:�
<br />•
<br />c
<br />•�
<br />•
<br />6
<br />KJ
<br />,0 •••
<br />OJ IVj
<br />.`-
<br />*000 .•
<br />111
<br />O
<br />%f__
<br />Z
<br />fn
<br />LLJ
<br />0
<br />Y v
<br />O
<br />O
<br />m
<br />m
<br />V
<br />N
<br />O
<br />:E•�
<br />LLJ >.
<br />X
<br />> d
<br />W
<br />LLJ m
<br />i
<br />� N
<br />O
<br />•o
<br />m
<br />cL
<br />4-
<br />C
<br />Date:
<br />03. 28. 13
<br />Scale:
<br />AS NOTED
<br />Project Mgr: EJW
<br />Drawn: CAD
<br />Job:
<br />13-03
<br />Sheet
<br />El
<br />
|