SYSTEM NO. HW-D-0178 <br />ASSEMBLY RATING - 1 AND 2 HR <br />NOMINAL JOINT WIDTH - 1 IN <br />CLASS II MOVEMENT CAPABILITIES - 18.75% COMPRESSION OR EXTENSION <br />1. FLOOR ASSEMBLY - THE FIRE RATED FLUTED STEEL DECK/CONCRETE FLOOR ASSEMBLY SHALL BE <br />CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL FLOOR -CEILING DESIGN <br />IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: <br />A. STEEL FLOOR AND FORM UNITS* - MAX 3 IN. DEEP GALV STEEL FLUTED UNITS. <br />B. CONCRETE - MIN 2-1/2 IN. THICK REINFORCED CONCRETE, AS MEASURED FROM THE TOP PLANE OF THE FLOOR <br />UNITS. <br />2. WALL ASSEMBLY - THE 1 OR 2 HR FIRE RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE <br />CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U400 SERIES WALL AND <br />PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THEFOLLOWING <br />CONSTRUCTION FEATURES: <br />A. STEEL FLOOR AND CEILING RUNNERS - FLOOR AND CEILING RUNNERS OF WALL ASSEMBLY SHALL CONSIST OF <br />MIN NO. 25 GAUGE GALV STEEL CHANNELS SIZED TO ACCOMMODATE STEEL STUDS. CEILING RUNNER TO BE <br />PROVIDED WITH MIN 1-1/4 IN. FLANGES. CEILING RUNNER SECURED TO VALLEYS OF STEEL FLOOR UNITS WITH <br />STEEL FASTENERS OR BY WELDS SPACED MAX 12 IN. OC. <br />B. STUDS - STEEL STUDS TO BE MIN 3-1/2 IN. WIDE. STUDS CUT 5/8 IN. LESS IN LENGTH THAN ASSEMBLY HEIGHT <br />WITH BOTTOM NESTING IN AND RESTING ON FLOOR RUNNER AND WITH TOP NESTING IN CEILING RUNNER <br />WITHOUT ATTACHMENT. STUD SPACING NOT TO EXCEED 24 IN. <br />C. GYPSUM BOARD* - GYPSUM BOARD SHEETS INSTALLED TO A MIN TOTAL THICKNESS OF 5/8 IN. AND 1-1/4 IN. ON <br />EACH SIDE OF WALL FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY. WALL TO BE CONSTRUCTED AS <br />SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY, EXCEPT <br />THAT A NOM 1 IN. GAP SHALL BE MAINTAINED BETWEEN THE TOP OF THE GYPSUM BOARD AND THE BOTTOM OF <br />THE STEEL FLOOR UNITS AND THE TOP ROW OF SCREWS SHALL BE INSTALLED INTO THE STUDS 1 IN. BELOW THE <br />BOTTOM OF THE CEILING RUNNER. <br />THE HOURLY FIRE RATING OF THE JOINT SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL. <br />3. JOINT SYSTEM - MAX WIDTH OF JOINT (AT TIME OF INSTALLATION OF JOINT SYSTEM) IS 1 IN. THE JOINT <br />SYSTEM IS DESIGNED TO ACCOMMODATE A MAX 18.75 PERCENT COMPRESSION OR EXTENSION FROM ITS <br />INSTALLED WIDTH. THE JOINT SYSTEM SHALL CONSIST OF THE FOLLOWING: <br />A. FORMING MATERIAL* - MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION CUT TO THE SHAPE <br />OF THE FLUTED DECK, APPROX 20 PERCENT LARGER THAN THE AREA OF THE FLUTES AND COMPRESSED INTO <br />FLUTES OF THE STEEL FLOOR UNITS BETWEEN THE TOP OF THE CEILING RUNNER AND THE STEEL DECK AND <br />COMPRESSED IN THICKNESS TO BE FLUSH WITH VERTICAL LEG OF CEILING RUNNER ON BOTH SIDES. ADDITIONAL <br />PIECES OF MIN 4 PCF MINERAL WOOL BATT INSULATION ARE TO BE CUT TO THE CONTOUR OF THE FLUTES WITH <br />AN ADDITIONAL 1-3/8 IN. HIGH SECTION AT THE BOTTOM OF THE SHAPES TO FILL THE 1 IN. GAP BETWEEN THE TOP <br />OF THE WALLBOARD AND BOTTOM OF THE STEEL FLOOR UNITS. THE ADDITIONAL PIECES OF MINERAL WOOL ARE <br />TO BE CUT TO MIN 3/4 AND 1-1/2 IN. THICK FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY AND <br />COMPRESSED AND FIRMLY PACKED INTO THE FLUTES AND THE GAP BETWEEN THE TOP OF THE GYPSUM BOARD <br />AND BOTTOM OF THE STEEL FLOOR UNITS ON BOTH SIDES OF THE WALL AND COMPRESSED IN THICKNESS TO BE <br />RECESSED FROM EACH SURFACE OF THE WALL TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL <br />MATERIAL. <br />FIBREX INSULATION INC - FBX SAFING INSULATION <br />OWENS CORNING HT INC, DIV OF OWENS CORNING - SAFING INSULATION/MW <br />ROCK WOOL MANUFACTURING CO - DELTA SAFING BOARD <br />THERMAFIBER L L C - TYPE SAF <br />B. FILL,VOID OR CAVITY MATERIAL* - CAULK - MIN 1/4 IN. THICKNESS OF CAULK INSTALLED ON EACH SIDE OF THE <br />WALL IN THE FLUTES OF THE STEEL FLOOR UNITS AND BETWEEN THE TOP OF THE WALL AND THE BOTTOM OF <br />THE STEEL FLOOR UNITS, FLUSH WITH EACH SURFACE OF THE GYPSUM BOARD. AN ADDITIONAL MIN 1/8 IN. <br />THICKNESS OF CAULK TO OVERLAP ONTO GYPSUM BOARD A MIN 1/2 IN. <br />MINNESOTA MINING & MFG CO - FIREDAM 150+ <br />*BEARING THE UL CLASSIFICATION MARK <br />RATED PENETRATION DETAIL <br />SYSTEM NO. WW-D-0074 <br />DECEMBER 04, 2007 <br />ASSEMBLY RATING - 1 AND 2 HR (SEE ITEM 2) <br />L RATING AT AMBIENT - 4 CFM/LIN FT <br />L RATING AT 400OF - 6 CFM/LIN FT <br />NOMINAL JOINT WIDTH - 3/4 IN. <br />CLASS 11 MOVEMENT CAPABILITIES - 17% COMPRESSION OR EXTENSION <br />1. CONCRETE WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 <br />PCF) STRUCTURAL CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. <br />SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF <br />MANUFACTURERS. <br />2. GYPSUM WALL ASSEMBLY - THE 1 OR 2 H FIRE -RATED GYPSUM WALLBOARD/STEEL STUD WALL ASSEMBLY <br />SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U400 SERIES <br />WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING <br />CONSTRUCTION FEATURES: <br />A. STEEL RUNNERS - RUNNERS OF WALL ASSEMBLY SHALL CONSIST OF MIN NO. 25 GAUGE GALV STEEL <br />CHANNELS SIZED TO ACCOMMODATE STEEL STUDS (ITEM 2B). RUNNER TO BE PROVIDED WITH 1-1/4 IN. FLANGES. <br />RUNNER SECURED TO CONCRETE WALL ASSEMBLY WITH STEEL CONCRETE FASTENERS SPACED 12 IN. OC. <br />B. STUDS - STEEL STUDS TO BE MIN 3-5/8 IN. (92 MM) WIDE. STUDS CUT 1/2 TO 3/4 IN. (13 TO 19 MM) LESS IN <br />LENGTH THAN ASSEMBLY HEIGHT_ STUD SPACING NOT TO EXCEED 24 IN. (610 MM) OC. <br />C. GYPSUM BOARD* - GYPSUM BOARD SHEETS INSTALLED TO A MIN TOTAL THICKNESS OF 5/8 IN. (16 MM) AND <br />1-1/4 IN. (32 MM) ON EACH SIDE OF WALL FOR A 1 OR 2 HR RATED ASSEMBLIES, RESPECTIVELY. WALL TO BE <br />CONSTRUCTED AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN IN THE UL FIRE RESISTANCE <br />DIRECTORY, EXCEPT THAT A NOM 3/4 IN. (19 MM) GAP SHALL BE MAINTAINED BETWEEN THE SIDE OF THE <br />GYPSUM BOARD AND THE FACE OF THE CONCRETE WALL ASSEMBLY. <br />3. FILL, VOID OR CAVITY MATERIAL* - CAULK - MAX SEPARATION BETWEEN SIDE OF GYPSUM BOARD AND FACE <br />OF CONCRETE WALL ASSEMBLY IS 3/4 IN. (19 MM). THE JOINT SYSTEM IS DESIGNED TO ACCOMMODATE A MAX 17 <br />PERCENT COMPRESSION OR EXTENSION FROM ITS INSTALLED WIDTH. MIN 5/8 IN. (16 MM) THICKNESS OF FILL <br />MATERIAL INSTALLED ON EACH SIDE OF THE WALL BETWEEN THE SIDE OF THE GYPSUM BOARD AND THE FACE <br />OF THE CONCRETE WALL ASSEMBLY, FLUSH WITH EACH SURFACE OF GYPSUM BOARD. <br />3M COMPANY <br />3M FIRE PROTECTION PRODUCTS - FD-150+ <br />*BEARING THE UL CLASSIFICATION MARK <br />UL SYSTEM NO. W-L-2078 <br />XHEZ.W-L-2078 <br />THROUGH -PENETRATION FIRESTOP SYSTEMS <br />F RATINGS -1 AND 2 HR (SEE ITEM 1) <br />T RATINGS - 0, 1 AND 2 HR (SEE ITEMS 2 AND 3) <br />L RATING AT AMBIENT - 3 CFM/SQ FT <br />L RATING AT 400 F - LESS THAN 1 CFM/SQ FT <br />1. WALL ASSEMBLY - THE FIRE -RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE <br />MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300, U400 OR V400 SERIES WALL AND PARTITION <br />DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE CONSTRUCTION FEATURES NOTED <br />BELOW: <br />A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO <br />CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED MAX 16 IN. OC. STEEL STUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED <br />MAX 24 IN. OC. <br />B. GYPSUM BOARD* - NOM 5/8 IN. THICK GYPSUM BOARD, AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION <br />DESIGN. MAX DIAM OF OPENING IS 11-1/2 IN. <br />THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL <br />ASSEMBLY IN WHICH IT IS INSTALLED. <br />2. THROUGH -PENETRANTS - ONE NONMETALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE <br />FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PIPE AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT <br />CONTACT) TO MAX 1/2 IN. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. <br />THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES MAY BE USED: <br />A. POLYVINYL CHLORIDE (PVC) PIPE - NOM 10 IN. DIAM (OR SMALLER) SCHEDULE 40 SOLID -CORE OR CELLULAR <br />CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING <br />SYSTEM. <br />B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE - NOM 10 IN. DIAM (OR SMALLER) SDR13.5 CPVC PIPE FOR <br />USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS. <br />C. ACRYLONITRILE BUTADIENE STYRENE (ABS) PIPE - NOM 6 IN. DIAM (OR SMALLER) SCHEDULE 40 SOLID -CORE <br />OR CELLULAR CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) <br />PIPING SYSTEMS <br />D. FLAME RETARDANT POLYPROPYLENE (FRPP) PIPE - NOM 6 IN. DIAM (OR SMALLER) SCHEDULE 40 FRPP PIPE <br />FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEM. <br />E. POLYVINYLIDENE FLUORIDE (PVDF) PIPE - NOM 4 IN. DIAM (OR SMALLER) PVDF PIPE FOR USE IN CLOSED <br />(PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEM. <br />WHEN MAX 6 IN. DIAM PIPE IS USED, T RATING IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL. WHEN NOM 8 <br />IN. OR 10 IN. DIAM PIPE IS USED, T RATING IS 0 HR. <br />3. FIRESTOP DEVICE* - FIRESTOP COLLAR - FIRESTOP COLLAR SHALL BE INSTALLED IN ACCORDANCE WITH THE <br />ACCOMPANYING INSTALLATION INSTRUCTIONS. COLLAR TO BE INSTALLED AND LATCHED AROUND THE PIPE AND <br />SECURED TO BOTH SIDES OF THE WALL USING THE ANCHOR HOOKS PROVIDED WITH THE COLLAR. (MINIMUM TWO <br />ANCHOR HOOKS FOR 1-1/2 AND 2 IN. DIAM PIPES, THREE ANCHOR HOOKS FOR 3 AND 4 IN. DIAM PIPES, FOUR <br />ANCHOR HOOKS FOR 6 IN. DIAM PIPES, TEN ANCHOR HOOKS FOR 8 IN. DIAM PIPES AND TWELVE ANCHOR HOOKS <br />FOR 10 IN. DIAM PIPES). THE ANCHOR HOOKS ARE TO BE SECURED TO THE SURFACE OF WALL WITH 3/16 IN. DIAM <br />BY 2-1/2 IN. LONG STEEL TOGGLE BOLTS ALONG WITH WASHERS. AS AN ALTERNATE FOR PIPE SIZES OF NOM 4 IN. <br />DIAM OR LESS, MIN NO. 10 BY 1-1/2 IN. LONG DRYWALL OR LAMINATE SCREWS WITH MIN 3/4 IN. STEEL WASHERS <br />MAY BE USED. WHEN THE DRYWALL OR LAMINATE SCREW IS USED, T RATING SHALL NOT EXCEED 1 HR. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - CP 643 50/1.5"N, CP 643 63/2"N, CP 643 90/3"N, CP 643 110/4"N, <br />CP 643 160/6"N, CP 644 200/8" ANDCP 644 250/10" FIRESTOP COLLARS <br />4. FILL, VOID OR CAVITY MATERIAL* - SEALANT - (NOT SHOWN) - MIN 1/2 IN. THICKNESS OF SEALANT APPLIED <br />WITHIN THE ANNULAR SPACE FOR NOM 8 IN. AND 10 IN. DIAM PIPES, FLUSH WITH EACH SIDE OF WALL. SEALANT IN <br />ANNULAR SPACE IS OPTIONAL FOR MAX 6 IN. DIAM PIPES. A MIN 1/4 IN. THICKNESS OF SEALANT IS REQUIRED <br />WITHIN THE ANNULAR SPACE, FLUSH WITH EACH SIDE OF WALL, TO ATTAIN THE L RATINGS FOR MAX 6 IN. DIAM <br />PIPES. <br />2 RATED PENETRATION DETA <br />A-8.3 ' <br />SYSTEM NO.WW-D-0045 <br />NOVEMBER 25, 2003 <br />ASSEMBLY RATINGS - 1, 2 AND 3 HR (SEE ITEM 1) <br />NOMINAL JOINT WIDTH - 2 IN. <br />CLASS II MOVEMENT CAPABILITIES - 12.5% COMPRESSION OR EXTENSION <br />I! <br />1. WALL ASSEMBLY - NONBEARING 1, 2 OR 3 HR FIRE RATED GYPSUM BOARD/STEEL STUD ASSEMBLY <br />CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U400-SERIES <br />WALL <br />OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING <br />CONSTRUCTION FEATURES: <br />A. STUDS - MIN 1-1/2 IN. (38 MM) WIDE STEEL STUDS SPACED MAX 24 IN. (610 MM) OC. <br />B. GYPSUM BOARD* - THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE <br />AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U400 SERIES DESIGN IN THE UL FI <br />RE <br />RESISTANCE DIRECTORY. <br />THE HOURLY ASSEMBLY RATING OF THE JOINT SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE <br />WALL ASSEMBLY IN WHICH IT IS INSTALLED. <br />2. JOINT SYSTEM - MAX WIDTH OF JOINT (AT TIME OF INSTALLATION OF JOINT SYSTEM) IS 2 IN. (51 MM) <br />THE JOINT SYSTEM IS DESIGNED TO ACCOMMODATE A MAX 12.5 PERCENT COMPRESSION OR EXTENSION <br />FROM ITS INSTALLED WIDTH. THE JOINT SYSTEM SHALL CONSIST OF THE FOLLOWING: <br />A. FORMING MATERIAL* - MIN 4.0 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION INSTALLED IN JOINT <br />OPENING AS A PERMANENT FORM. PIECES OF BATT CUT TO MIN WIDTH OF 1-3/4, 3, OR 4-1/4 IN. (44,76 OR <br />108 MM) FOR 1, 2 AND 3 HR RATED ASSEMBLIES, RESPECTIVELY. PIECES OF BATT INSTALLED EDGE -FIRST <br />INTO JOINT OPENING, PARALLEL WITH JOINT DIRECTION, SUCH THAT BATT SECTIONS ARE COMPRESSED <br />MIN 50 PERCENT IN THICKNESS AND SUCH THAT THE COMPRESSED BATT SECTIONS ARE RECESSED FROM <br />BOTH SURFACES OF WALL TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL. <br />FIBREX INSULATIONS, INC. - FBX SAFING INSULATION <br />ROCK WOOL MANUFACTURING CO. - DELTA BOARD <br />ROXUL INC. - SAFE <br />B. FILL,VOID OR CAVITY MATERIAL* - MIN 1/2 IN. (13 MM) THICKNESS OF FILL MATERIAL APPLIED <br />WITHIN THE JOINT, FLUSH WITH BOTH SURFACES OF WALL. <br />3M COMPANY - FD-150+ <br />*BEARING THE UL CLASSIFICATION MARKING <br />UL SYSTEM NO. W-L-1054 <br />METAL PIPE THROUGH GYPSUM WALL ASSEMBLY <br />F RATING = 1-HR. OR 2-HR. <br />T-RATING = 0-HR. <br />L-RATING AT AMBIENT = LESS THAN 1 CFM/SQ. FT. <br />L-RATING AT 400' = LESS THAN 4 CFM/SQ. FT. <br />AFRO VIEW <br />SECTION -A <br />1. GYPSUM WALL ASSEMBLY (1-HR. OR 2-HR. FIRE -RATING) (2-HR. SHOWN) <br />2. PENETRATING ITEM TO BE ONE OF THE FOLLOWING. - <br />A. MAXIMUM 20" DIAMETER STEEL PIPE (SCHEDULE 10 OR HEAVIER) <br />B. MAXIMUM 6" DIAMETER COOPER PIPE. <br />C. MAXIMUM 6" DIAMETER STEEL CONDUIT. <br />E. MAXIMUM 4" DIAMETER STEEL EMT. <br />3. A. MINIMUM 5/8" DEPTH HILTI FS-ONE FIRESTOP SEALANT = <br />1 HR. FIRE -RATING. <br />B. MINIMUM 1-1/4" DEPTH HILTI FS-ONE FIRESTOP SEALANT = <br />2HR. FIRE -RATING. <br />4. MINIMUM 1/2" BEAD HILTI FS-ONE FIRESTOP SEALANT AT POINT OF CONTACT. <br />NOTES: 1. MAXIMUM DIAMETER OF OPENING = 22-1/4" <br />2. ANNULAR SPACE = MINIMUM 0", MAX. 2-1/4" <br />INSTALLATION INSTRUCTIONS FOR UL No. wl 1054 <br />STEP 1- PENETRATION: ALL SURFACES MUST BE CLEAN, SOUND DRY AND FROST FREE PRIOR TO <br />APPLICATION OF FIRES TOPING MATERIALS. <br />STEP 2- FIRESTOP SEALANT: APPLY A MINIMUM J" OR 1-1/4" DEPTH OF FS-ONE IN THE ANNULAR <br />SPACE AROUND THE PENETRATING ITEM. TOOL EXCESS SEALANT BEYOND <br />PERIMETER OF THE OPENING '" ONTO WALL SURFACE. LEAVE COMPLETED <br />SEAL UNDISTURBED FOR <br />3 RATED PENETRATION DETAIL <br />A-8.3 N.T.S. <br />SYSTEM NO. BW-S-0008 <br />JANUARY 31, 2006 <br />ASSEMBLY RATINGS - 1 AND 2 HR (SEE ITEM 2) <br />L RATING AT AMBIENT - LESS THAN 1 CFM/LIN FT <br />L RATING AT 400' F - LESS THAN 1 CFM/LIN FT <br />JOINT WIDTH - 2 IN. MAX <br />1. FLOOR ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT <br />(100-150 PCF OR 1600 2400 KG/M3) STRUCTURAL CONCRETE. FLOOR MAY ALSO BE CONSTRUCTED OF <br />ANY 6 IN. (152 MM) THICK UL CLASSIFIED HOLLOW CORE PRECAST CONCRETE UNITS*. <br />SEE PRECAST CONCRETE UNITS CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF <br />MANUFACTURERS. <br />2. WALL ASSEMBLY - THE 1 OR 2 HR FIRE -RATED GYPSUM BOARD/STEEL STUD WALL ASSEMBLY <br />SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U400 <br />OR V400 SERIES WALL AND PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. IN ADDITION, <br />THE WALL MAY INCORPORATE A HEAD -OF -WALL JOINT SYSTEM CONSTRUCTED AS SPECIFIED IN THE <br />HW SERIES JOINT SYSTEMS IN THE UL FIRE RESISTANCE DIRECTORY. THE WALL SHALL INCLUDE THE <br />FOLLOWING CONSTRUCTION FEATURES: <br />A. STEEL FLOOR RUNNER - FLOOR RUNNERS OF WALL ASSEMBLY SHALL CONSIST OF MIN NO. 25 <br />GAUGE GALV STEEL CHANNELS SIZED TO ACCOMMODATE STEEL STUDS (ITEM 2C). FLOOR RUNNERS <br />TO BE PROVIDED WITH FLANGES A MIN OF 1/4 IN. (6 MM) GREATER THAN THE JOINT WIDTH. RUNNERS <br />SECURED WITH STEEL FASTENERS SPACED 12 IN. (305 MM) OC. <br />B. STUDS - STEEL STUDS TO BE MIN 3-1/2 IN. (89 MM) WIDE. STUDS CUT 1/2 TO 3/4 IN. (13 TO 19 MM) <br />LESS IN LENGTH THAN ASSEMBLY HEIGHT WITH BOTTOM NESTING IN, RESTING ON AND FASTENED TO <br />FLOOR RUNNER WITH SHEET METAL SCREWS. STUD SPACING NOT TO EXCEED 24 IN. (610 MM) OC. <br />C. GYPSUM BOARD* - GYPSUM BOARD INSTALLED TO A MIN TOTAL THICKNESS OF 5/8 OR 1-1/4 IN. (16 <br />OR 32 MM) ON EACH SIDE OF WALL FOR A 1 OR 2 HR RATED WALL, RESPECTIVELY. WALL TO BE <br />CONSTRUCTED AS SPECIFIED IN THE INDIVIDUAL U400 OR V400 SERIES DESIGN IN THE UL FIRE <br />RESISTANCE DIRECTORY, EXCEPT THAT A MAX 2 IN. (51 MM) GAP SHALL BE MAINTAINED BETWEEN <br />THE BOTTOM OF GYPSUM BOARD AND TOP OF CONCRETE FLOOR. <br />THE HOURLY FIRE RATING OF THE JOINT SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE <br />WALL. <br />3. JOINT SYSTEM - MAX SEPARATION BETWEEN TOP OF FLOOR AND BOTTOM OF GYPSUM BOARD IS 2 <br />IN. (51 MM). THE JOINT SYSTEM CONSISTS OF FORMING MATERIAL AND A FILL MATERIAL, AS FOLLOWS: <br />A. PACKING MATERIAL - MIN 5/8 AND 1-1/4 IN. 16 AND 32 MM THICKNESS OF MIN 4 PCF 64 KG/ ( ) ( M3) <br />MINERAL WOOL BATT INSULATION FOR 1 AND 2 HR RATED ASSEMBLIES, RESPECTIVELY. PACKING <br />MATERIAL TO BE FIRMLY PACKED INTO GAP BETWEEN THE BOTTOM OF THE GYPSUM BOARD AND THE <br />TOP OF THE CONCRETE FLOOR ON EACH SIDE OF THE WALL, FLUSH WITH EACH SURFACE OF THE <br />WALL. <br />B. FILL, VOID OR CAVITY MATERIAL* - MIN 1/16 IN. (1.6 MM) DRY THICKNESS (1/8 IN. OR 3.2 MM WET <br />THICKNESS) OF FILL MATERIAL SPRAYED OR BRUSHED ON EACH SIDE OF THE WALL TO COMPLETELY <br />COVER MINERAL WOOL BETWEEN THE BOTTOM OF THE GYPSUM BOARD AND THE TOP OF THE <br />CONCRETE FLOOR. <br />3M COMPANY - FIREDAMTM SPRAY 200 <br />*BEARING THE UL CLASSIFICATION MARK <br />4 RATED PENETRATION DETAIL <br />A-8.3 N.T.S. <br />CANADIAN GYPSUM COMPANY - 1/2 IN. THICK TYPE C, IP-X2 OR <br />2 4 <br />IPC-AR; WRC, 5/8 IN. THICK TYPE AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, <br />SCX, SHX, WRX OR WRC; 3/4 IN. THICK TYPES IP-X3 OR ULTRACODE <br />UNITED STATES GYPSUM CO - 1/2 IN. THICK TYPE C, IP-X2, IPC-AR <br />OR WRC; 5/8 IN. THICK TYPE SCX, SHX, WRX, IP-X1, AR, C, WRC, <br />FRX-G, IP-AR, IP-X2, IPC-AR ; 3/4 IN. THICK TYPES IP-X3 OR <br />ULTRACODE <br />USG MEXICO S A DE C V - 1/2 IN. THICK TYPE C, IP-X2, IPC-AR OR <br />WRC; 5/8 IN. THICK TYPE AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, <br />SHX, WRX, WRC OR; 3/4 IN. THICK TYPES IP-X3 OR ULTRACODE <br />FOR NUMBER OF LAYERS <br />WHEN ITEM 6B, STEEL FRAMING MEMBERS*, IS USED, <br />3 3A 4 AND HOURLY RATINGS <br />NONBEARING WALL RATING IS LIMITED TO 1 HR. MIN. STUD DEPTH <br />SEE ITEM 4 <br />IS 3-1/2 IN., MIN. THICKNESS OF INSULATION (ITEM 3) IS 3 IN., AND <br />TWO LAYERS OF GYPSUM BOARD PANELS (1/2 IN. OR 5/8 IN. <br />1. FLOOR AND CEILING RUNNERS - (NOT SHOWN) - CHANNEL SHAPED, FABRICATED FROM MIN 25 MSG <br />THICK) SHALL BE ATTACHED TO FURRING CHANNELS AS <br />CORROSION -PROTECTED STEEL, MIN WIDTH TO ACCOMMODATE STUD SIZE, WITH MIN 1 IN. LONG LEGS, <br />DESCRIBED IN ITEM 5. ONE LAYER OF GYPSUM BOARD PANELS <br />ATTACHED TO FLOOR AND CEILING WITH FASTENERS 24 IN. OC MAX. <br />(1/2 IN. OR 5/8 IN. THICK) ATTACHED TO OPPOSITE SIDE OF STUD <br />WITHOUT FURRING CHANNELS AS DESCRIBED IN ITEM 5. <br />2. STEEL STUDS - CHANNEL SHAPED, FABRICATED FROM MIN 25 MSG CORROSION -PROTECTED STEEL, <br />4A. GYPSUM BOARD* - (AS AN ALTERNATE TO ITEM 4) - 5/8 IN. <br />MIN WIDTH AS INDICATED UNDER ITEM 4, MIN 1-1/4 IN. FLANGES AND 1/4 IN. RETURN, SPACED A MAX OF 24 <br />THICK, 2 FT. WIDE, TONGUE AND GROOVE EDGE, APPLIED <br />IN. OC. STUDS TO BE CUT 3/8 TO 3/4 IN. LESS THAN ASSEMBLY HEIGHT. <br />HORIZONTALLY AS THE OUTER LAYER TO ONE SIDE OF THE <br />ASSEMBLY. SECURED AS DESCRIBED IN ITEM 5. JOINT COVERING <br />3. BATTS AND BLANKETS* - (REQUIRED AS INDICATED UNDER ITEM 4) - MINERAL WOOL BATTS, FRICTION <br />(ITEM 7) NOT REQUIRED. <br />FITTED BETWEEN STUDS AND RUNNERS. MIN NOM THICKNESS AS INDICATED UNDER ITEM 4. SEE BATTS <br />AND BLANKETS (BKNV OR BZJZ) CATEGORIES FOR NAMES OF CLASSIFIED COMPANIES. <br />CANADIAN GYPSUM COMPANY - TYPE SHX. <br />3A. BATTS AND BLANKETS* - (OPTIONAL) - PLACED IN STUD CAVITIES, ANY GLASS FIBER OR MINERAL <br />UNITED STATES GYPSUM CO - TYPE SHX. <br />WOOL INSULATION BEARING THE UL CLASSIFICATION MARKING AS TO SURFACE BURNING <br />USG MEXICO S A DE C V - TYPE SHX. <br />CHARACTERISTICS AND/OR FIRE RESISTANCE. SEE BATTS AND BLANKETS (BKNV OR BZJZ) CATEGORIES <br />FOR NAMES OF CLASSIFIED COMPANIES. <br />5. FASTENERS - (NOT SHOWN) - TYPE S OR S-12 STEEL SCREWS <br />USED TO ATTACH PANELS TO STUDS (ITEM 2) OR FURRING <br />4. GYPSUM BOARD* - GYPSUM PANELS WITH BEVELED, SQUARE OR TAPERED EDGES, APPLIED <br />CHANNELS (ITEM 6). SINGLE LAYER SYSTEMS: 1 IN. LONG FOR 1/2 <br />VERTICALLY OR HORIZONTALLY. VERTICAL JOINTS CENTERED OVER STUDS AND STAGGERED ONE STUD <br />AND 5/8 IN. THICK PANELS OR 1-1/4 IN. LONG FOR 3/4 IN. THICK <br />CAVITY ON OPPOSITE SIDES OF STUDS. VERTICAL JOINTS IN ADJACENT LAYERS (MULTILAYER SYSTEMS) <br />PANELS, SPACED 8 IN. OC WHEN PANELS ARE APPLIED <br />STAGGERED ONE STUD CAVITY. HORIZONTAL JOINTS NEED NOT BE BACKED BY STEEL FRAMING. <br />HORIZONTALLY, OR 8 IN. OC ALONG VERTICAL AND BOTTOM <br />HORIZONTAL EDGE JOINTS AND HORIZONTAL BUTT JOINTS ON OPPOSITE SIDES OF STUDS NEED NOT BE <br />EDGES AND 12 IN. OC IN THE FIELD WHEN PANELS ARE APPLIED <br />STAGGERED. HORIZONTAL EDGE JOINTS AND HORIZONTAL BUTT JOINTS IN ADJACENT LAYERS <br />VERTICALLY. TWO LAYER SYSTEMS: FIRST LAYER- 1 IN. LONG FOR <br />(MULTILAYER SYSTEMS) STAGGERED A MIN OF 12 IN. THE THICKNESS AND NUMBER OF LAYERS FOR THE 1 <br />1/2 AND 5/8 IN. THICK PANELS OR 1-1/4 IN. LONG FOR 3/4 IN. THICK <br />HR, 2 HR, 3 HR AND 4 HR RATINGS ARE AS FOLLOWS: <br />PANELS, SPACED 16 IN. OC. SECOND LAYER- 1-5/8 IN. LONG FOR 1/2 <br />WALLBOARD PROTECTION ON EACH SIDE OF WALL <br />IN., 5/8 IN. THICK PANELS OR 2-1/4 IN. LONG FOR 3/4 IN. THICK <br />RATING MIN STUD DEPTH NO. OF LAYERS & THKNS OF PANEL MIN THKNS OF INSULATION (ITEM 3) <br />PANELS, SPACED 16 IN. OC WITH SCREWS OFFSET 8 IN. FROM <br />1 LAYER, 5/8 IN. THICK OPTIONAL <br />1 3--� <br />FIRST LAYER. THREE -LAYER SYSTEMS: FIRST LAYER- 1 IN. LONG <br />1 2 1 LAYER, 1/2 IN. THICK 1-1/2 IN. <br />FOR 1/2 IN., 5/8 IN. THICK PANELS, SPACED 24 IN. OC. SECOND <br />1 A 1 LAYER, 3/4 IN. THICK OPTIONAL <br />LAYER- 1-5/8 IN. LONG FOR 1/2 IN., 5/8 IN. THICK PANELS, SPACED <br />2 <br />24 IN. OC. THIRD LAYER- 2-1/4 IN. LONG FOR 1/2 IN., 5/8 IN. THICK <br />1 2 LAYERS, 1/2 IN. THICK OPTIONAL <br />A <br />PANELS OR 2-5/8 IN. LONG FOR 5/8 IN. THICK PANELS, SPACED 12 <br />2 2 LAYERS, 5/8 IN. THICK OPTIONAL <br />IN. OC. SCREWS OFFSET MIN 6 IN. FROM LAYER BELOW. <br />2 3-7 1 LAYER, 3/4 IN. THICK 3 IN. <br />FOUR -LAYER SYSTEMS: FIRST LAYER- 1 IN. LONG FOR 1/2 IN., 5/8 <br />3 151-198 3 LAYERS, 1/2 IN. THICK OPTIONAL <br />IN. THICK PANELS, SPACED 24 IN. OC. SECOND LAYER- 1-5/8 IN. <br />3 A 2 LAYERS, 3/4 IN. THICK OPTIONAL <br />LONG FOR 1/2 IN., 5/8 IN. THICK PANELS, SPACED 24 IN. OC. THIRD <br />3 A 3 LAYERS, 5/8 IN. THICK OPTIONAL <br />LAYER- 2-1/4 IN. LONG FOR 1/2 IN. THICK PANELS OR 2-5/8 IN. LONG <br />4 A 4 LAYERS, 5/8 IN. THICK OPTIONAL <br />FOR 5/8 IN. THICK PANELS, SPACED 24 IN. OC. FOURTH LAYER- <br />4 1 4 LAYERS, 1/2 IN. THICK OPTIONAL <br />2-5/8 IN. LONG FOR 1/2 IN. THICK PANELS OR 3 IN. LONG FOR 5/8 IN. <br />4 2 9 2 LAYERS, 3/2 IN. THICK 2 IN <br />THICK PANELS, SPACED 12 IN. OC. SCREWS OFFSET MIN 6 IN. <br />FROM LAYER BELOW. <br />6. FURRING CHANNELS - (OPTIONAL, NOT SHOWN, FOR SINGLE OR <br />6A. STEEL FRAMING MEMBERS (NOT SHOWN)* - <br />(OPTIONAL ON ONE OR BOTH SIDES, NOT SHOWN, FOR <br />SINGLE OR DOUBLE LAYER SYSTEMS) - AS AN <br />ALTERNATE TO ITEM 6, FURRING CHANNELS AND STEEL <br />FRAMING MEMBERS AS DESCRIBED BELOW: <br />A. FURRING CHANNELS - FORMED OF NO. 25 MSG GALV <br />STEEL. 2-3/8 IN. WIDE BY 7/8 IN. DEEP, SPACED MAX. 24 IN. <br />OC PERPENDICULAR TO STUDS. CHANNELS SECURED TO <br />STUDS AS DESCRIBED IN ITEM B. GYPSUM BOARD <br />ATTACHED TO FURRING CHANNELS AS DESCRIBED IN <br />ITEM 5. NOT FOR USE WITH ITEM 4A. <br />B. STEEL FRAMING MEMBERS* - USED TO ATTACH <br />FURRING CHANNELS (ITEM 6AA) TO STUDS (ITEM 2). <br />CLIPS SPACED MAX. 48 IN. OC., AND SECURED TO STUDS <br />WITH NO. 8 X 1-1/2 IN. MINIMUM SELF -DRILLING, S-12 <br />STEEL SCREW THROUGH THE CENTER GROMMET. <br />FURRING CHANNELS ARE FRICTION FITTED INTO CLIPS. <br />PAC INTERNATIONAL INC - TYPE RSIC-1. <br />6B. STEEL FRAMING MEMBERS (OPTIONAL, NOT SHOWN)* <br />- AS AN ALTERNATE TO ITEM 6, FURRING CHANNELS AND <br />STEEL FRAMING MEMBERS ON ONLY ONE SIDE OF STUDS <br />AS DESCRIBED BELOW: <br />A. FURRING CHANNELS'- FORMED OF NO. 25 MSG GALV <br />STEEL, SPACED 24 IN. OC PERPENDICULAR TO STUDS. <br />CHANNELS SECURED TO STUDS AS DESCRIBED IN ITEM <br />B. BATTS AND BLANKETS PLACED IN STUD CAVITY AS <br />DESCRIBED IN ITEM 4. TWO LA <br />YERS OF GYPSUM BOARD <br />ATTACHED TO FURRING CHANNELS AS DESCRIBED IN <br />ITEM 4. NOT FOR USE WITH ITEM 4A. <br />B. STEEL FRAMING MEMBERS* - USED TO ATTACH <br />FURRING CHANNELS (ITEM 6BA) TO ONE SIDE OF STUDS <br />(ITEM 2) ONLY. CLIPS SPACED 48 IN. OC., AND SECURED <br />TO STUDS WITH TWO NO. 8 X 2-1/2 IN. COARSE DRYWALL <br />SCREWS, ONE THROUGH THE HOLE AT EACH END OF THE <br />CLIP. FURRING CHANNELS ARE FRICTION FITTED INTO <br />CLIPS. <br />KINETICS NOISE CONTROL INC - TYPE ISOMAX <br />7. JOINT TAPE AND COMPOUND - VINYL OR CASEIN, DRY <br />OR PREMIXED JOINT COMPOUND APPLIED IN TWO COATS <br />TO JOINTS AND SCREW HEADS OF OUTER LAYERS. <br />PAPER TAPE, NOM 2 IN. WIDE, EMBEDDED IN FIRST LAYER <br />OF COMPOUND OVER ALL JOINTS OF OUTER LAYER <br />PANELS. PAPER TAPE AND JOINT COMPOUND MAY BE <br />OMITTED WHEN GYPSUM PANELS ARE SUPPLIED WITH A <br />SQUARE EDGE. <br />8. SIDING, BRICK OR STUCCO - (OPTIONAL, NOT SHOWN) - <br />ALUMINUM, VINYL OR STEEL SIDING, BRICK VENEER OR <br />STUCCO, MEETING THE REQUIREMENTS OF LOCAL CODE <br />AGENCIES, INSTALLED OVER GYPSUM PANELS. BRICK <br />VENEER ATTACHED TO STUDS WITH CORRUGATED <br />METAL WALL TIES ATTACHED TO EACH STUD WITH STEEL <br />SCREWS, NOT MORE THAN EACH SIXTH COURSE OF <br />BRICK. <br />'signTec <br />Pni t U, <br />--mationa <br />Associates, Inc. AA26001933 <br />Architecture * Planning * Interior Design <br />14125 N.W. 80th Ave. Suite 303 <br />Miami Lakes, FI, 33016 <br />T.786-235-9097 <br />F. 305-362-4420 <br />dtiinfo@dtiarchitect,corn <br />V"vw.dtiarchitect. cam <br />Revisions: <br />Date Description <br />10.30.20 ISSUED FOR BID <br />a. <br />O <br />d0' <br />Z <br />O <br />N <br />�Q <br />M <br />�C) <br />W <br />2W <br />Z <br />iw <br />LL <br />�v <br />X <br />L <br />to <br />LV <br />im <br />O <br />m <br />o <br />0 <br />Q <br />w <br />Z�Ja. <br />W <br />W <br />V� <br />p <br />C <br />W <br />a <br />x <br />p <br />am <br />Uj <br />W <br />n <br />V <br />Z <br />Cn <br />M <br />Co <br />Ip <br />a <br />Q <br />J <br />Z <br />aa. <br />H <br />� <br />O <br />es0� <br />2 <br />wLL. <br />1' <br />Uj <br />O <br />a <br />cc <br />O <br />QVW <br />M� <br />�W <br />yr>0 <br />Z <br />Q <br />>- <br />= <br />IL <br />= <br />N <br />° OW <br />IL <br />_ <br />C. <br />N <br />Job Number: <br />19093.01 <br />File name: <br />Issued Date: <br />10.30.20 <br />Drawn by: <br />J.0 <br />Checked by: <br />C.P <br />I SHEET NAME <br />uL <br />DETAILS <br />s RATED PENETRATION DETA <br />A-8.3 N.T.S. <br />J2 <br />TED PENETRATION DETAIL. <br />DOUBLE LAYER SYSTEMS) - RESILIENT FURRING CHANNELS <br />7 FABRICATED FROM MIN 25 MSG CORROSION -PROTECTED STEEL, <br />DESIGN NO. U 419 <br />SPACED VERTICALLY A MAX OF 24 IN. OC. FLANGE PORTION <br />A_8.3 ATTACHED TO EACH INTERSECTING STUD WITH 1/2 IN. LONG TYPE <br />SCALE: N.T.S. NONBEARING WALL RATINGS - 1,2,3 OR 4 HR (SEE ITEMS 3 & 4) S-12 STEEL SCREWS. NOT FOR USE WITH ITEM 4A. <br />9. CAULKING AND SEALANTS* - (OPTIONAL, NOT SHOWN) - <br />A BEAD OF ACOUSTICAL SEALANT APPLIED AROUND THE <br />PARTITION PERIMETER FOR SOUND CONTROL. <br />UNITED STATES GYPSUM CO - TYPE AS <br />SHEET Nt7MBER <br />A-8.3 <br />