LANDLORD'S WORK <br />CHIPOTLE MEXICAN GRILL WORK LETTER <br />LANDLORD, AT ITS SOLE COST AND EXPENSE, SHALL: <br />1. ELECTRICAL SERVICE: FURNISH AND INSTALL ONE CODE -COMPLIANT 400AMP, 120/208 VOLT, <br />3-PHASE, 4-WIRE METERED SERVICE CAPABLE OF SUPPLYING 120 KVA BROUGHT TO 400 AMP <br />FUSED DISCONNECT SWITCH (TO BE NEMA 3R RAIN TIGHT IN EXTERIOR INSTALLATIONS) OR 400AMP <br />CIRCUIT BREAKER. ANY RELATED ELECTRIC UTILITY COMPANY CHARGES SHALL BE PAID BY LANDLORD. <br />LANDLORD SHALL PROVIDE ONE SET 400A COPPER THHN CONDUCTORS, TO BE 4-500 KCMIL, #1/0 <br />G IN 3-1/2" C. FOR CONDUCTOR LENGTHS UP TO 250 FEET OR 4-600 KCMIL, #1/0 G IN 4" C. <br />FOR CONDUCTOR LENGTHS OVER 250 FEET, FROM MAIN DISCONNECT TO TENANT'S PANEL BOARD <br />LOCATION WITHIN THE PREMISES AS DETERMINED BY TENANT IN ACCORDANCE WITH TENANT'S PLANS <br />FOR THE PREMISES. LANDLORD SHALL CLEARLY LABEL TENANT'S SERVICE METER WITH TENANT'S <br />NAM E. <br />2. ELECTRICAL CONDUITS IN EXPOSED CEILING - ALL LANDLORD'S BASE BUILDING WIRING RUNNING <br />THROUGH TENANT'S EXPOSED CEILING SHALL BE ENCASED IN EMT OR IMC CONDUIT, RUN TIGHT TO <br />THE DECK AND BE EITHER PARALLEL OR PERPENDICULAR TO THE MAIN ENTRY STOREFRONT. THERE <br />SHALL BE NO DIAGONAL RUNS OR AND ALL CONDUITS SHALL BE IN STRAIGHT LINES. <br />3. FIRE ALARM: IF REQUIRED BY CODE FOR TENANT'S INTENDED USE, THE LANDLORD SHALL FURNISH <br />AND INSTALL ONE MAIN FIRE ALARM CONTROL PANEL FOR THE SHELL BUILDING WITH SUFFICIENT <br />CAPACITY TO SERVE THE TENANT'S NEEDS (TO BE LOCATED IN A SHARED DEDICATED COMMON AREA <br />WITHIN THE SHELL BUILDING OR AT A LOCATION OTHERWISE APPROVED BY TENANT). LANDLORD'S <br />MAIN FACP SHALL BE CAPABLE OF ACCOMMODATING AND CONNECTING TO THE TENANT'S FIRE ALARM <br />SYSTEM AS REQUIRED BY THE LOCAL JURISDICTION FOR TENANT'S USE. LANDLORD SHALL PROVIDE <br />A 1 " MIN. EMT CONDUIT (WITH PULL STRING) TO BE ROUTED FROM THE MAIN FACP TO THE <br />TENANT'S LEASED PREMISES AS SHOWN IN LANDLORD'S PLANS AND AGREED TO BETWEEN LANDLORD <br />AND TENANT. LANDLORD SHALL PROVIDE TENANT WITH MONITORING COMPANY CONTACT INFORMATION <br />OR CODES AS NEEDED TO COMPLETE INSTALLATION OF TENANT'S FIRE ALARM SYSTEM. <br />4. NATURAL GAS: FURNISH AND INSTALL A MINIMUM OF 1600MBH NATURAL GAS SERVICE WITH A <br />DELIVERY PRESSURE OF 7" WATER COLUMN ROUTED TO A LOCATION WITHIN THE LEASED PREMISES <br />AS SHOWN IN LANDLORD'S PLANS AND AGREED TO BETWEEN LANDLORD AND TENANT IN <br />ACCORDANCE WITH TENANT'S PLANS FOR THE PREMISES. LANDLORD TO PROVIDE PROOF OF <br />DELIVERY PRESSURE (GAUGE) AT POSSESSION AND REGULATE PRESSURE IF REQUIRED. GAS PIPING <br />SHALL BE APPROPRIATELY SIZED FROM LANDLORD METER LOCATION TO A POINT OF DELIVERY WITHIN <br />THE TENANT'S PREMISES AS AGREED TO BY LANDLORD AND TENANT. TENANT TO APPLY WITH THE <br />GAS COMPANY FOR SERVICE AND SPECIFY ITS DESIGN CRITERIA. ALL RELATED NATURAL GAS UTILITY <br />COMPANY CHARGES SHALL BE PAID BY LANDLORD. <br />5. WATER: FURNISH AND INSTALL A SEPARATELY METERED AND INSULATED 1.5" OR GREATER DEDICATED <br />DOMESTIC COPPER WATER SUPPLY LINE SUPPLYING MINIMUM OF 45 GALLONS PER MIN AT 60 PSI, <br />ROUTED TO A LOCATION WITHIN THE PREMISES AS DETERMINED BY TENANT IN ACCORDANCE WITH <br />TENANT'S PLANS FOR THE PREMISES SUBJECT TO FLUCTUATION OF THE UTILITY SERVICE PROVIDER. <br />LANDLORD SHALL PROVIDE PROOF OF DELIVERY PRESSURE (GAUGE) OR FLOW RATE AT POSSESSION <br />AND PROVIDE AND INSTALL A BOOSTER PUMP AT LANDLORD'S EXPENSE IF WATER PRESSURE IS <br />UNABLE TO BE PROVIDED AT MINIMUM OF 60 PSI. ALL RELATED TAP, IMPACT, SYSTEM <br />DEVELOPMENT, FIXTURE AND/ OR ANY SIMILAR CHARGES OR FEES SHALL BE PAID BY LANDLORD. <br />6. TELEPHONE/ IT: LANDLORD SHALL PROVIDE THE FOLLOWING: <br />a. A 2" CONDUIT WITH PULL STRING ROUTED FROM THE PROPERTY'S JOINT TELEPHONE POINT OF <br />DEMARCATION TO THE LEASED PREMISES AS SHOWN IN LANDLORD'S PLANS AND AGREED TO BY <br />LANDLORD AND TENANT. <br />b. IF EXISTING FACILITIES FROM CURRENT TELECOM PROVIDER (S) ARE FULL, LANDLORD AGREES TO <br />PAY FOR THE EXPANSION OF SEGREGATED FACILITIES FOR TENANT'S USE. <br />c. APPROPRIATE INFRASTRUCTURE FROM COMMON SERVICE ENTRANCE TO TENANT'S LEASED <br />PREMISES IN ORDER FOR TENANT TO PROVISION HIGH SPEED BROADBAND ACCESS, PER FCC <br />GUIDELINES (25M/3M). <br />7. SEWER: FURNISH AND INSTALL TWO (2) FOUR -INCH MINIMUM PVC SANITARY SEWER LINES WITH <br />MINIMUM INVERT ELEVATION OF 42 INCHES, ONE LINE LEADING TO A CODE -COMPLIANT GREASE <br />INTERCEPTOR (WHICH LANDLORD SHALL INSTALL WITH A MINIMUM CAPACITY OF 1,500 GALLONS OR <br />SUFFICIENT TO MEET LOCAL CODE FOR TENANT'S EXCLUSIVE USE) WITH INVERT ELEVATION AS <br />NECESSARY TO ACCOMMODATE GREASE INTERCEPTOR INSTALLATION REQUIREMENTS OF TENANT, AND <br />ONE LINE BYPASSING THE GREASE INTERCEPTOR WITH MINIMUM INVERT ELEVATION OF 42 INCHES <br />THAT CONNECTS TO THE MAIN SANITARY SEWER SYSTEM FOR THE BUILDING OR THE LOCAL <br />MUNICIPAL SYSTEM. BOTH SEWER LINES SHALL BE BROUGHT TO A LOCATION WITHIN THE PREMISES, <br />AS DETERMINED BY TENANT IN ACCORDANCE WITH TENANT'S PLANS FOR THE PREMISES. <br />8. ROOF SCREENING: FURNISH AND INSTALL ALL REQUIRED SCREENING FOR TENANT'S STANDARD <br />ROOFTOP -MOUNTED EQUIPMENT SUFFICIENT TO MEET APPLICABLE LOCAL COVENANTS, CODES AND <br />ORDINANCES FOR TENANT'S INTENDED USE. NO ROOF MOUNTS SHALL BE INSTALLED WHICH SHALL <br />INVALIDATE THE LANDLORD'S ROOF WARRANTIES WITHOUT LANDLORD APPROVAL. <br />9. ROOF DRAINS AND SCUPPERS: LANDLORD TO PROVIDE AND INSTALL ROOF DRAINS AND SCUPPERS <br />FOR SHELL BUILDING SO AS NOT TO CONFLICT WITH TENANT'S INTENDED EXITS AS LOCATED ON <br />TENANT'S APPROVED FLOOR PLAN. INTERIOR DRAIN PIPING SHALL BE INSULATED. <br />10. ROOF INSULATION: FURNISH AND INSTALL EXTERIOR ROOF INSULATION TO MEET LOCAL CODES FOR <br />TENANT'S INTENDED USE. LANDLORD TO PROVIDE TENANT THE NAME OF LANDLORD'S ROOFING <br />CONTRACTOR AND WARRANTY INFORMATION WHEN REQUESTED. <br />11. ROOF ACCESS: FURNISH AND INSTALL A PERMANENT, CODE COMPLIANT AND OSHA -APPROVED ROOF <br />ACCESS SYSTEM FOR TENANT'S USE (INCLUDING EXTENDABLE ROOF HATCH POLE AS APPLICABLE TO <br />THE DESIGN OF THE ROOF LADDER). LANDLORD SHALL SUPPLY TENANT WITH A KEY AND /OR <br />24-HOUR ACCESS TO SUCH ROOF ACCESS SYSTEM IF APPLICABLE. <br />12. FIRE SPRINKLER: IF REQUIRED BY CODE, LANDLORD SHALL FURNISH AND INSTALL A FIRE SPRINKLER <br />SYSTEM TO MEET APPLICABLE GOVERNMENTAL ORDINANCES FOR THE INTENDED USE OF TENANT AS <br />ANTICIPATED BY THE LEASE. SUBJECT TO PERMITTING AGENCY AGREEMENT AND APPROVAL, <br />LANDLORD TO COORDINATE MAIN AND BRANCH LINE LOCATIONS SO AS NOT TO CONFLICT WITH <br />TENANT'S FUTURE ROOF MOUNTED EQUIPMENT, CURBS, AND PENETRATIONS. SPRINKLER SYSTEM <br />RISER ASSEMBLY TO BE LOCATED IN A DEDICATED COMMON AREA WITHIN THE SHELL BUILDING AS <br />APPROVED BY TENANT. MODIFICATIONS TO SAID SYSTEM SHALL BE AT TENANT'S EXPENSE. ALL <br />RELATED TAP, IMPACT, SYSTEM DEVELOPMENT, FIXTURE AND/OR ANY SIMILAR CHARGES OR FEES <br />SHALL BE PAID BY LANDLORD. <br />13. TRASH AND WASTE, PROVIDE A CONVENIENT WELL LIT (ADEQUATE WATTAGE TO PROVIDE AN AVERAGE <br />MAINTAINED ILLUMINATION LEVEL OF NOT LESS THAN FIVE (5) FOOT CANDLES) AREA LOCATED WITHIN <br />REASONABLE PROXIMITY TO THE PREMISES (THE LOCATION OF SUCH AREA IS TO BE SHOWN ON AN <br />EXHIBIT TO BE ATTACHED TO THE LEASE) FOR A CODE COMPLIANT TRASH AND WASTE ENCLOSURE <br />TO BE CONSTRUCTED BY LANDLORD. SAID ENCLOSURE SHALL BE CONSTRUCTED IN ACCORDANCE <br />WITH APPLICABLE LAWS AND COMPLY WITH ANY ACCESS, HEIGHT, DRAINAGE AND/OR OTHER <br />REQUIREMENTS OF THE JURISDICTIONAL ZONING, SEWER AND WASTE REMOVAL AUTHORITIES, AS <br />WELL AS ANY ACCESS, VERTICAL CLEARANCE (MINIMUM 20'-6") AND/OR OTHER REQUIREMENTS OF <br />THE VENDOR(S) PROVIDING WASTE REMOVAL SERVICES FOR TENANT'S TRASH AND WASTE. SUCH <br />AREA AND ENCLOSURE SHALL BE CONSTRUCTED BY LANDLORD.AS MAY BE REQUIRED BY APPLICABLE <br />LAW. <br />14. CANOPIES: FURNISH AND INSTALL ALL CANOPIES PER TENANT'S PROTOTYPICAL PLANS AND PROVIDED <br />BY AMERICAN PRODUCTS INC. (API) OR EQUIVALENT. INSTALLATION WILL INCLUDE EXTERIOR BUILDING <br />LIGHTING INTEGRAL TO THE FRONT CANOPY. <br />15. STOREFRONT: FURNISH AND INSTALL SHERWIN WILLIAMS 7757 HIGH REFLECTIVE WHITE ANODIZED <br />ALUMINUM STOREFRONT AS AGREED TO BETWEEN LANDLORD AND TENANT OR EQUIVALENT GLAZING <br />SYSTEM BY KAWNEER ALUMINUM WITH CLEAR INSULATED LOW E GLASS (TO MEET LOCAL <br />REQUIREMENTS) AND WIDE STILE, SINGLE ACTING, INSULATED DOUBLE ENTRY DOORS (6'-0" X <br />7'-0") AND ONE (1) WIDE STILE, SINGLE -ACTING, INSULATED DOOR (3 '-O" X 7' -0") FOR <br />EGRESS OR PATIO ACCESS. ALL HARDWARE FOR ALL EXTERIOR DOORS SHALL BE IN ACCORDANCE <br />WITH TENANT'S SPECIFICATION FOR THE PROJECT; INCLUDING BUT NOT LIMITED TO: DOOR HINGES, <br />PANIC HARDWARE, THRESHOLD, SWEEPS, STOPS, AND CYLINDER CORE. IF AN IMPACT -RATED GLAZING <br />SYSTEM IS REQUIRED BY CODE, LANDLORD SHALL PROVIDE SUCH SYSTEM. SAFETY GLAZING WILL BE <br />INSTALLED AS REQUIRED PER LOCAL ADOPTED CODES. <br />16. WALLS: <br />FURNISH AND INSTALL A MINIMUM 6" STEEL <br />STUDS, AT 16" ON CENTER, AND 5/8" GYPSUM <br />BOARD <br />DEMISING WALL ASSEMBLY <br />TO MEET LOCAL <br />CODE, ALL PERIMETER WALLS TO ROOF DECK <br />TAPED <br />(FIRE -TAPED IF REQUIRED) <br />SKIMMED, FILLED <br />(ALL PENETRATIONS FIRE -SEALED IF REQUIRED), <br />AND SANDED TO SMOOTH FINISH <br />AND PREPARED <br />TO RECEIVE PAINT. IN ADDITION, ALL EXTERIOR <br />WALLS <br />SHALL HAVE STEEL STUDS AND/OR FURRING <br />WITH INSULATION THAT MEETS ALL LOCAL <br />CODES. <br />LANDLORD WILL PROVIDE A <br />$4000 CREDIT TO <br />TENANT FOR EXTERIOR WALLS. <br />17. REAR DOOR: FURNISH AND INSTALL A 42" STOREFRONT REAR DOOR WITH HARDWARE AS SHOWN IN <br />LANDLORD'S ARCHITECTURAL PLANS AND AGREED TO BY LANDLORD AND TENANT IN ACCORDANCE <br />WITH TENANT'S PLANS AND SPECIFICATIONS FOR THE PREMISES; INCLUDING BUT NOT LIMITED TO <br />HINGES, THRESHOLD, PANIC DEVICES, PEEP HOLE, SWEEP, STOP, AND CYLINDER. THE FINAL <br />LOCATION OF THE REAR DOOR SHALL BE AS AGREED TO BY LANDLORD AND TENANT. <br />18. FLOOR: LANDLORD AGREES TO COMPACT THE EXPOSED SUB -GRADE OF THE PREMISES FLOOR TO A <br />CONDITION AND ELEVATION BETWEEN 4" AND 5" BELOW FINISHED FLOOR ACCEPTABLE TO TENANT <br />AND GIVE TENANT A CREDIT OF $5 PSF FOR THE CONCRETE SLAB. COMPACTION WILL BE AS <br />FOLLOWS: <br />a. LANDLORD SHALL COMPLETE COMPACTION OF THE PREMISES IN ACCORDANCE WITH THE <br />APPROPRIATE ENGINEERING STANDARDS AND BUILDING CODE REQUIREMENTS, SO THAT THE <br />BUILDING PAD SHALL BE GRADED WITHIN 1 /10 OF A FOOT OF THE FINISHED FLOOR GRADE <br />ELEVATION OF TENANT'S BUILDING [BASED UPON FINAL GRADING PLAN MINUS THE THICKNESS <br />OF THE SUBGRADE AND FINISH MATERIALS], BUT IN NO EVENT LESS THAN NINETY-FIVE <br />PERCENT (95%) OF THE MODIFIED PROCTOR SOIL TEST FOR WATER CONTENT AND COMPACTION <br />LEVELS ("MODIFIED PROCTOR"), SO AS TO ENABLE TENANT TO CONSTRUCT ITS IMPROVEMENTS IN <br />ACCORDANCE WITH ITS PLANS, WITH SPREAD FOOTINGS AND WITHOUT NECESSITY OF PILINGS OR <br />OTHER EXTRAORDINARY FOUNDATION WORK. THE PREMISES SOIL SHALL HAVE A MINIMUM <br />BEARING CAPACITY OF 2,500 POUNDS PER SQUARE FOOT. <br />19. MECHANICAL EQUIPMENT: LANDLORD AGREES THAT TENANT SHALL HAVE RIGHT TO INSTALL TENANT'S <br />MECHANICAL EQUIPMENT AND ASSOCIATED CURBS PER TENANT'S PLANS UPON ROOF OR AT <br />ANOTHER FUNCTIONALLY APPROPRIATE LOCATION ON OR ABOUT PREMISES AS IS NECESSARY AND <br />TYPICAL FOR RESTAURANT USE. TENANT WILL NOT MAKE MODIFICATIONS TO THE ROOF THAT WILL <br />INVALIDATE LL'S ROOF WARRANTY. TENANT WILL USE LL'S ROOFING CONTRACTOR FOR ITS <br />MODIFICATIONS TO THE ROOF SYSTEM. THE LANDLORDS ROOF MUST BE ABLE TO ACCOMMODATE <br />THE FOLLOWING: <br />i. HVAC RTUS 2,000 LBS. EACH <br />ii. MAKEUP AIR UNIT 800 LBS. <br />iii. GREASE EXHAUST FAN: 300 LBS. <br />iv. GREASE EXHAUST HOOD: 1,000 LBS. <br />v. WALK-IN CONDENSING UNIT 300 LBS. <br />vi. ICE MACHINE CONDENSING UNIT 100 LBS. <br />vii. RESTROOM FAN 100 LBS. <br />20. PATIO: FURNISH AND INSTALL THE CONCRETE SLAB ON A SINGLE PLANE FOR THE PATIO IN <br />ACCORDANCE WITH LOCAL CODE AS SHOWN ON LANDLORD'S PLANS. WHEN APPLICABLE TENANT WILL <br />HAVE THE RIGHT TO INSTALL ADDITIONAL POLE MOUNTED LIGHTS AT THE PATIO. THE LANDLORD WILL <br />COORDINATE THE LOCATION OF THESE LIGHTS WITH THE TENANT ENSURING APPROPRIATE CONDUIT <br />WITH PULL STRING ARE SUPPLIED FOR FUTURE POWER BY TENANT. PATIO AREA WILL SLOPE AWAY <br />FROM THE BUILDING WITH GRADE NO LESS THAN 1.5 % AND NO MORE THAN 2% WITH CONTROL <br />JOINTS EVERY TWELVE (12) FEET EACH DIRECTION. <br />21. STAGING AREA: LANDLORD SHALL DESIGNATE AND ALLOW TO BE FENCED A CONSTRUCTION STAGING <br />AREA OR OTHER SUITABLE ARRANGEMENTS AS MAY BE ACCEPTABLE, ADJACENT TO TENANT'S <br />PREMISE AND SHALL PERMIT TENANT'S CONTRACTOR AT ITS EXPENSE TO PLACE A TEMPORARY <br />TRAILER ON SITE FOR THE PURPOSE OF HOUSING TEMPORARY CONSTRUCTION OFFICE ACTIVITIES <br />AND STORAGE FACILITIES INCLUDING SPACE FOR A 40 YARD DUMPSTER AND ONE TEMPORARY <br />STORAGE CONTAINER TO BE USED DURING THE COURSE OF TENANT'S CONSTRUCTION ACTIVITIES. <br />ANY DAMAGE TO THE PREMISES BY TENANT OR ITS CONTRACTORS TO BE REPAIR BY TENANT AT <br />TENANT'S EXPENSE. <br />22. TEMPORARY SIGNS: LANDLORD SHALL PERMIT TENANT TO PLACE TEMPORARY SIGNAGE OR BANNERS <br />UPON THE BUILDING OR SITE FENCING TO INDICATE THE TENANT'S IMPENDING OCCUPANCY OF THE <br />PREMISES, DURING THE PERIOD FROM THE COMMENCEMENT OF CONSTRUCTION OF THE LANDLORD'S <br />BUILDING SHELL UNTIL OPENING OF THE RESTAURANT AND GRAND OPENING SIGNAGE FROM THE <br />TENANT'S GRAND OPENING UNTIL 30 DAYS AFTER GRAND OPENING. ALL SIGNAGE SHALL BE IN <br />CONFORMANCE WITH JURISDICTIONAL REQUIREMENTS AND SUBJECT TO LANDLORD'S APPROVAL. <br />23. DIRECTIONAL SIGNAGE: LANDLORD SHALL PROVIDE AN AREA FOR TENANT'S INSTALLATION OF PICKUP <br />PARKING SIGNS, AT A LOCATION MUTUALLY APPROVED BY LANDLORD AND TENANT. <br />24. MONUMENT/PYLON SIGNAGE: LANDLORD SHALL FURNISH AND INSTALL MONUMENT SIGNAGE FOR <br />TENANT'S INSTALLATION OF TENANT'S SIGN PANELS. LANDLORD SHALL PROVIDE THE MONUMENT SIGN <br />STRUCTURE (FRAME, FOOTINGS, AND FOUNDATIONS AS REQUIRED), APPLICABLE SIGN FINISHES <br />(INCLUDING MONUMENT BASE MATERIALS), AND POWER FOR THE SIGN. TENANT SHALL OBTAIN <br />LANDLORD AND LOCAL MUNICIPAL APPROVAL FOR TENANT'S SIGN PANELS. <br />25. OTHER SITE WORK: LANDLORD SHALL BE RESPONSIBLE FOR ALL OTHER SITE WORK WITHIN THE <br />PREMISES BUT OUTSIDE OF THE BUILDING INCLUDING BUT NOT LIMITED TO: CURB AND GUTTER, <br />STONE AND ASPHALT PAVING, CONCRETE TRASH ENCLOSURE PAD & APRON, PARKING LOT STRIPING, <br />OVERALL SITE LIGHTING INCLUDING BUT NOT LIMITED TO PARKING LOT LIGHTING ILLUMINATING THE <br />ENTIRE SITE AND LANDSCAPING IN ACCORDANCE WITH LANDLORD'S PLANS AS APPROVED BY TENANT. <br />26. SPECIAL PROVISIONS: <br />a. LANDLORD SHALL TREAT FOR AND EXTERMINATE ANY INFESTATION OF RODENTS, TERMITES, <br />CARPENTER ANTS OR OTHER INSECTS OR GROWTHS. <br />b. LANDLORD SHALL PROVIDE FOR REPAIR OF DAMAGE CAUSED BY ANY SUCH INFESTATION. <br />27. SITE ELECTRIC DISTRIBUTION: LL SHALL FURNISH AND INSTALL THREE UNDERGROUND ELECTRICAL <br />CONDUITS, LABELED WITH PULL STRINGS FROM TENANT'S SPACE TO EACH OF THE THREE <br />DRIVE-THRU EQUIPMENT LOCATIONS AS PROVIDED BY TENANT AND AS SHOWN IN LANDLORD'S <br />PLANS. <br />a. ONE (1) 1" CONDUIT FROM MOBILE ORDER PICKUP AHEAD TO ABOVE ELECTRICAL PANELS. <br />b. ONE (1) 1" CONDUIT FROM THE CLEARANCE BAR TO ABOVE ELECTRICAL PANELS. <br />c. ONE (1) 1" CONDUIT FROM ALL DIRECTIONAL SIGNS TO ABOVE ELECTRICAL PANELS. NOTE: UP <br />TO 3 DIRECTIONAL SIGNS CAN BE SERVED BY A SINGLE CIRCUIT; ADDITIONAL SIGNS REQUIRE A <br />NEW DEDICATED CIRCUIT AND CONDUIT. <br />28. TRAFFIC SIGNAGE: LANDLORD SHALL PROVIDE PARKING LOT STRIPING AND DIRECTIONAL ARROWS PER <br />ALL APPLICABLE LOCAL CODES. <br />29. SITE CONCRETE: LANDLORD SHALL PROVIDE PAD CONSTRUCTED OF 6" THICK REINFORCED (WITH <br />WIRE MESH) CONCRETE. THE WIDTH OF THE PAD SHALL BE THE WIDTH OF THE DRIVE THROUGH <br />LANE OR NO LESS THAN 12' WIDE WITH A LENGTH EXTENDING FROM 12' PRIOR TO THE <br />CENTERLINE OF THE SPEAKER POST TO 12' PAST THE CENTERLINE OF THE DRIVE THROUGH PICKUP <br />WINDOW. <br />30. DRIVE THROUGH WINDOW: LANDLORD SHALL FURNISH AND INSTALL THE TENANT SPECIFIED DRIVE <br />THROUGH SERVICE WINDOW WITH ALL CONNECTIONS FULLY OPERATIONS PER MANUFACTURER'S <br />SPECIFICATIONS AND PER ALL NOTATIONS ON TENANT'S CONSTRUCTION DOCUMENTS, INCLUDING BUT <br />NOT LIMITED TO: ELECTRICAL CONNECTION, TRANSOMS AND SIDELIGHTS, BUMP OUT AND EXTERIOR <br />SHELF, AIR CURTAIN/ FLY FAN PER APPLICABLE LOCAL CODES AND TENANT'S CONSTRUCTION <br />DOCUMENTS. HEIGHT OF SERVICE WINDOW MUST BE 36" ABOVE THE INTERIOR FINISHED FLOOR AND <br />42" ABOVE THE DRIVE THROUGH LANE ASPHALT. <br />31. PICK UP WINDOW LIGHTING: LANDLORD SHALL FURNISH AND INSTALL (2) EXTERIOR, LIGHTS LOCATED <br />ADJACENT TO THE DRIVE -THROUGH WINDOW AND CONSISTENT WITH THE BASE BUILDING EXTERIOR <br />LIGHTING. ILLUMINATION LEVELS WHEN MEASURED AT GRADE AROUND BUILDING PERIMETER SHALL BE <br />NO LESS THAN 1.5 FOOT-CANDLES. <br />esignTec <br />pternationall <br />Associates, Inc. AA26001933 <br />Architecture • Planning • Interior Design <br />14125 N.W. 80th Ave. Suite 303 <br />Miami Lakes, FI. 33016 <br />T. 786-235-9097 <br />F. 305-362-4420 <br />dtiinto@dtiarchitect.com <br />wwwAtiarchitect_com <br />Revisions: <br />Date Description <br />10.30.20 ISSUED FOR BID <br />V_ <br />CD <br />N <br />M <br />M <br />a0~a <br />U <br />"O <br />W <br />�W <br />Z <br />W <br />W_ <br />LL <br />42 <br />W <br />a <br />d. <br />U) <br />W <br />� <br />- <br />m <br />04 <br />o <br />OW <br />a <br />wa <br />Z <br />� <br />J <br />a <br />W <br />vH <br />Q <br />0 <br />W <br />as <br />Z <br />Z�ti a� <br />QOW �� <br />J=v z CV) <br />'yQ ao <br />J Z O <br />Q 0 <br />H2O a <br />W2 <br />at O p� <br />OVW M� <br />Z Q = <br />U O=W �W <br />�N <br />�N <br />Job Number: <br />19093.01 <br />File name: <br />Issued Date: <br />10.30.20 <br />Drawn by: <br />J.0 <br />Checked by: <br />C.P <br />SHEET NAME <br />WORK <br />LETTER <br />REQ. <br />SHEET NUMBER <br />A=0.3 <br />