4
<br />PAMENT CARE AREA SYMBOL LEGEND
<br />4�> GENERAL CARE - CATEGORY 2
<br />NOTES:
<br />1. THERE ARE NO CRITICAL OR WET PATIENT AREAS IN THE SCOPE OF
<br />WORK.
<br />2. GENERAL PATIENT CARE AREAS REQUIRE A WRING METHOD WTH A
<br />REDUNDANT GROUND AS PER ARTICLE 517.13 OF THE NEC.
<br />GROUNDING 0 FALL RECEPTACLES, LIGHTING AND FIXED EQUIPMENT IN
<br />PATIENT CARE AREAS SHALL COMPLY WTH NEC ARTICLE 517.13 (A)
<br />AND (B)
<br />TESTING, INSPECTIONS -
<br />AND CERTIFICATIONS:
<br />A. EQUIPOTENTIAL GROUNDING TEST FOR PATIENT CARE AREAS
<br />NFPA 99, 2018 EDITION, SECTION 6.3.3 REQUIRES TESTING OF NEW CONSTRUCTION
<br />AND EXISTING CONSTRUCTION AND REPEATED WIEN MAJOR RENOVATIONS OCCUR.
<br />MOST EXISTING FACIU11ES HAVE NO RECORDS OF EXISTING CONDITIONS, HOWEVER,
<br />LOGS SHOULD BE CHECKED ANNUALLY BY AHCA. THEREFORE, ALL PATIENT AREAS
<br />WTHIN ANY SCOPE OF WORK WLL NEED TO BE TESTED BY THE CONTRACTOR. (ALSO
<br />SEE NEC 517-13, 14 & 16).
<br />B. WHAT NEEDS TO BE TESTED? ONLY METAL CONDUCTIVE SURFACES LIKELY TO BECOME
<br />ENERGIZED WTHIN THE PATIENT VICINITY. PATIENT VICINITY IS DEFINED AS:
<br />1. AN AREA MERE PATIENTS ARE NORMALLY CARED FOR.
<br />2. THE SPACE NTH SURFACES LIKELY TO BE CONTACTED BY PATIENT OR ATTENDANT
<br />TOUCHING THE PATIENT. (BEDS, HEADWALLS, A/C UNITS, SINK, TRIM, ETC.)
<br />3. IN A PATIENT ROOM BASICALLY THE ENTIRE ROOM INCLUDING TOILET/SHOWER ROOM.
<br />PATIENTS SHOULD BE IN WHEELCHAIRS OR SITTING IN CHAIRS.
<br />C.
<br />1.
<br />2.
<br />D.
<br />2.
<br />a.
<br />b.
<br />C.
<br />d.
<br />e.
<br />f.
<br />3.
<br />4.
<br />E.
<br />b.
<br />C.
<br />F.
<br />1.
<br />2.
<br />G.
<br />1.
<br />2.
<br />3.
<br />4.
<br />60-0w 69-Ow
<br />PATIENT BED
<br />31-6"
<br />6'-On
<br />7'-6- VERTICALLT
<br />ABOVE FLOOR I
<br />TYPICAL PATIENT ROOM
<br />PATIENT VICINITY DISTANCES
<br />GROUND TEST DOES NOT INCLUDE:
<br />SMALL WALL MOUNTED CONDUCTIVE SURFACES, TOWEL AND SOAP DISPENSERS,
<br />MIRRORS, BED PANS, ETC.
<br />LARGE METAL SURFACES NOT LIKELY TO BECOME ENERGIZED, WNDOW FRAMES, DOOR
<br />FRAMES, FLOOR DRAINS AND MOVABLE CABINETS.
<br />TEST METHOD:
<br />BOTH VOLTAGE AND IMPEDANCE MEASUREMENTS MUST BE MADE.
<br />ALL MEASUREMENTS MUST BE TAKEN TO A REFERENCE POINT OR IN NEAR AREA
<br />BEING TESTED.
<br />GROUND BAR IN A PANEL SERVING AN AREA.
<br />GROUND JACK IF ONE EXISTING.
<br />ESTABLISHED GROUND BUS.
<br />AN ALL METAL COLD WATER PIPE.
<br />BE CAREFUL OF WASTE PIPE OR SPRINKLER PIPE BECAUSE OF NO -HUB AND
<br />VITAULIC FITTINGS.
<br />GROUNDING CONTACT OR A RECEPTACLE THAT IS POWERED FROM A DIFFERENT
<br />CIRCUIT FROM THE RECEPTACLE UNDER TEST.
<br />VOLTAGE MEASUREMENTS ARE TO BE MADE BETWEEN REFERENCE POINT AND
<br />APPROPRIATE CONDUCTIVE SURFACES INCLUDING RECEPTACLE GROUND CONTACTS.
<br />IMPEDANCE MEASUREMENTS ARE TO BE MADE ONLY BETWEEN REFERENCE POINT AND
<br />RECEPTACLE GROUND CONTACTS.
<br />REQUIRED RESULTS:
<br />NEW/EXISTING CONSTRUCTION
<br />VOLTAGE - MAXIMUM 20MV +/-20% (24 TO 20MV)
<br />IMPEDANCE - MAXIMUM 0.1 OHM +/-20% (0.12 TO 0.1 OHM)
<br />IMPEDANCE (ISOLATED GROUND) - MAXIMUM 0.2 OHM +/- 20% (0.28 TO 0.12 OHM)
<br />GENERAL COMMENTS:
<br />THE IMPEDANCE MEASUREMENTS FOR NEW AND EXISTING CONSTRUCTION SHALL BE
<br />THE RATIO OF 60HZ VOLTAGE DEVELOPED BETWEEN A POINT UNDER TEST AND A
<br />REFERENCE POINT TO 60HZ CURRENT APPLIED TO THE POINT UNDER TEST. IF
<br />EXISTING CONSTRUCTION 60HZ OR DC MAY BE USED, AND THE TEST MUST NOT
<br />ENDANGER PATIENT.
<br />ALSO, TESTS MUST INCLUDE CORRECT POLARITY OF HOT AND NEUTRAL AND
<br />GROUNDING BLADE RETENTION FORCE (40Z. MIN.)
<br />JEST EQUIPMENT:
<br />USE A MILLIVOLT METER DESIGNED FOR THIS PURPOSE NTH 1 K OHM INPUT
<br />RESISTANCE (+/-10%) AT FREQUENCIES OF 1000HZ OR LESS.
<br />USE A HIGH Z MV METER WTH EXTERNAL FREQUENCY SHAPING NETWORK.
<br />RECEPTACLE POLARITY TESTER.
<br />RETEN11ON FORCE TESTER OR MANUFACTURER'S DATA VERIFYING COMPLIANCE
<br />THROUGH U.L, NEMA OR OTHER TESTS.
<br />ELECTRICAL SPECIFICA11ONS
<br />GENERAL PROVISIONS
<br />A. PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT FOR A COMPLETE
<br />AND PROPERLY OPERATING ELECTRICAL SYSTEM. INCLUDE NECESSARY
<br />FEES AND PERMITS WITHIN BASE BID.
<br />ARCHITECTURAL, MECHANICAL, PLUMBING AND FIRE PROTECTION
<br />DRAWNGS ARE CONSIDERED PART OF THESE CONSTRUCTION
<br />DOCUMENTS FOR COORDINATION, EQUIPMENT CONNECTION, HEIGHTS
<br />AND LOCATIONS.
<br />B. CODES AND STANDARDS: ALL ELECTRICAL WORK SHALL BE IN STRICT
<br />COMPLIANCE WTH THE PROVISIONS OF THE LOCAL GOVERNMENT
<br />AUTHORITY, THE NATIONAL ELECTRIC CODE 2017 EDITION; SEVENTH
<br />ED11ION (2020) FLORIDA BUILDING CODE, THE FLORIDA FIRE
<br />PREVENTION CODE 2020 EDITION, NATIONAL FIRE ALARM CODE NFPA
<br />72 2016 EDITION AND THE CODES AND STANDARDS REFERENCED
<br />THEREIN. ALL MATERIALS SHALL BE NEW AND FREE FROM DEFECTS,
<br />AND SHALL BEAR THE UNDERWRITER'S LABEL.
<br />C. CONTRACTOR SHALL THOROUGHLY INVESTIGATE SITE BEFORE BIDDING.
<br />NO CHANGES WLL BE ALLOWED IN CONTRACT PRICE FOR WORK
<br />REQUIRED TO COMPLY WTH EXISTING CONDITIONS.
<br />D. ALL ELECTRICAL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE
<br />MANNER.
<br />E. CONTRACTOR SHALL SCHEDULE AH DOWN -TIME NTH THE OWNER
<br />PRIOR TO BEGINNING THE WORK. PREMIUM /OVERTIME RATES MAY BE
<br />REQUIRED AND MUST BE INCLUDED IN BASE BID.
<br />F. CONTRACTOR SHALL THOROUGHLY REVIEW CONSTRUCTION DOCUMENTS
<br />AND WALK SITE. MEN CONFLICTS ARISE WTHIN CONSTRUCTION
<br />DOCUMENTS, CONTRACTOR SHALL NOTIFY ENGINEER PRIOR TO
<br />SUBMITTING A BID. SUBMISSION OF A BID SHALL INDICATE THAT
<br />CONTRACTOR THOROUGHLY REVIEWED CONSTRUCTION DOCUMENTS AND
<br />WALKED THE SITE PRIOR TO BID SUBMISSION.
<br />MEN ENGINEER IS NOT AVAILABLE, OR TIME DOES NOT
<br />PERMI TCON TRACTOR SHALL INCLUDE THE MOST STRINGENT (COSTLY)
<br />REQUIREMENTS WTHIN BASE BID.
<br />G. CONTRACTOR SHALL COORDINATE WTH UTILITY COMPANY AND
<br />TELECOMMUNICATION COMPANY FOR LOCATIONS, REQUIREMENTS AND
<br />CONDUITS ROUTING PRIOR TO COMMENCEMENT OF WORK OR ROUGH -IN.
<br />H. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
<br />MANUFACTURERS, SUB- CONTRACTORS, VENDORS AND SUPPLIERS, WTH
<br />A COMPLETE SET OF THESE DOCUMENTS PRIOR TO SUBMITTING A BID.
<br />1. GUARANTEE ALL ELECTRICAL SYSTEM MATERIALS AND WORKMANSHIP
<br />TO BE FREE FROM DEFECTS FOR A PERIOD OF ONE (1) YEAR FROM
<br />THE DATE OF FINAL ACCEPTANCE AND PROPERLY CORRECT LATENT
<br />DEFECTS ARISING WTHIN THIS PERIOD UPON NOTIFICATION BY THE
<br />OWNER'S REPRESENTATIVE WTHOUT ADD11IONAL COMPENSATION.
<br />J. DAILY REMOVE REFUSE AND DEBRIS ACCUMULATING FROM ELECTRICAL
<br />CONSTRUCTION AND PRIOR TO ACCEPTANCE OF THIS WORK, LEAVE THE
<br />PREMISES "BROOM CLEAN" INSOFAR AS AFFECTED BY ELECTRICAL
<br />WORK.
<br />K. ELECTRICAL CONTRACTOR SHALL EXAMINE ARCHITECTURAL,
<br />MECHANICAL, PLUMBING AND FIRE PROTECTION DRAWNGS FOR
<br />ES11MATING AND CONSTRUCTION OF THIS PROJECT. SUBMISSION OF A
<br />PROPOSAL SHALL BE CONSTRUED AS EVIDENCE THAT SUCH
<br />EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR,
<br />EQUIPMENT OR MATERIALS REQUIRED FOR CONNECTING AND
<br />ENERGIZING EQUIPMENT SHOWN ON THOSE DRAWNGS WLL NOT BE
<br />RECOGNIZED. ELECTRICAL CONTRACTOR SHALL COMMUNICATE
<br />DISCREPANCIES TO ENGINEER PRIOR SUBMITTING A BID.
<br />L. EQUIPMENT AND DESIGN OF SYSTEMS INDICATED ON THE DESIGN
<br />DRAWNGS AND WTHIN THESE SPECIFICATIONS SHALL BE CONSIDERED
<br />AS "SPECIFIED STANDARD" OF QUALITY. NO SUBSTITUTIONS SHALL BE
<br />MADE WTHOUT WRITTEN APPROVAL OF THE ENGINEER AT LEAST 10
<br />DAYS PRIOR TO BID DATE.
<br />ANY DEVIATION FROM SPECIFIED EQUIPMENT THAT AFFECT THE
<br />INSTALLATION, OPERATION, PERFORMANCE, QUALITY OR LONGEVITY OF
<br />THE ELECTRICAL SYSTEMS AS DEFINED HEREIN, SHALL BE REPLACED
<br />BY THE ELECTRICAL CONTRACTOR NTH NO ADDITIONAL COST TO THE
<br />CLIENT, IN ADDITION, ELECTRICAL CONTRACTOR SHALL PROVIDE THE
<br />ENGINEERING WTH PHOTOMETRIC FLOOR PLANS FOR ANY LIGHTING
<br />FIXTURES CHANGES FOR APPROVAL AT LEAST 10 DAYS PRIOR TO BID
<br />DATE.
<br />BASIC MATERIALS AND METHODS
<br />A. RACEWAYS AND FITTINGS: ALL RACEWAYS AND FITTINGS SHALL BE
<br />GALVANIZED RIGID STEEL OR INTERMEDIATE METAL CONDUIT WTH
<br />LOCKNUTS AND BUSHINGS, NTH THE EXCEPTION THAT WERE
<br />SPECIFICALLY ALLOWED BY THE NATIONAL ELECTRICAL CODE AND
<br />APPLICABLE LOCAL CODES. ELECTRICAL METALLIC TUBING (E.M.T) MAY
<br />BE USED FOR ALL INTERIOR EXPOSED AND CONCEALED WORK WHERE
<br />IT IS NOT SUBJECT TO PHYSICAL DAMAGE OR CORROSION. FITTINGS
<br />SHALL BE STEEL SET SCREW TYPE. PVC SCHEDULE 40 WTH TAR
<br />COATED GALVANIZED RIGID STEEL ELBOWS SHALL BE USED FOR BELOW
<br />GRADE INSTALLATIONS. MC CABLE SHALL BE ALLOWED MEN
<br />APPROVED BY TENANT AND LANDLORD AND IT SHALL BE INSTALLED
<br />AS PER ARTICLE 330 OF THE NEC, NO BX CABLE ALLOWED. INSTALL
<br />EXPANSION FITTINGS IN RACEWAYS EVERY 200' LINEAR RUN OR
<br />WHEREVER STRUCTURAL EXPANSION JOINTS ARE CROSSED.
<br />FOR MEDICAL, DENTAL AND SIMILAR OFFICES AS DEFINED BY NEC
<br />ARTICLE 517, NO NON-METALIC RACEWAYS SHALL BE USED ANYWHERE
<br />AND ONLY MC CABLE LISTED FOR HEALTHCARE USE MAY BE USED FOR
<br />RECEPTACLE CIRCUITS, FIXED EQUIPMENT CIRCUITS, SWTCH LEGS AND
<br />LIGHT FIXTURE MIPS.
<br />B. PROVIDE PULL STRING IN ALL EMPTY CONDUITS.
<br />C. FINAL CONNECTIONS TO MOTORS OR EQUIPMENT SUBJECT TO
<br />VIBRATION SHALL BE MADE UP WTH GREENFIELD IN DRY LOCATIONS
<br />AND WTH JACKETED, LIQUID -TIGHT, FLEXIBLE, GALVANIZED STEEL
<br />CONDUIT IN WET OR DAMP LOCATIONS.
<br />D. CONDUCTORS: FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE
<br />THWN-2 COPPER (MINIMUM SIZE #12 UNLESS OTHERWSE NOTED). PER
<br />NEC 110.14 (c)(1)(a)Ab) CONDUCTOR AMPACITY BASED ON 60*C
<br />COLUMN FOR CIRCUITS RATED 100 AMPS OR LESS, OR #1 AWG OR
<br />LESS CONDUCTORS AND 75*C COLUMN FOR CIRCUITS RATED OVER 100
<br />AMPS, OR LARGER THAN #1 AWG CONDUCTORS PER TABLE NEC
<br />310.15(B)(16). NO ALUMINUM SHALL BE PERMITTED UNLESS
<br />SPECIFICALLY NOTED OTHERNSE. INSTALL ALL WRING IN CONDUIT OR
<br />APPROVED RACEWAYS UNLESS OTHERWSE INDICATED. PROVIDE #10
<br />AWG FOR BRANCH CIRCUITS OVER 100 FEET IN LENGTH TO ACCOUNT
<br />FOR VOLTAGE DROP. PROVIDE #10 GROUND TO CORRESPOND. ALL
<br />BRANCH CIRCUITS SHALL CARRY AN EQUIPMENT GROUNDING
<br />CONDUCTOR, AND BE WIRED WTH COLOR -CODED WIRE WTH SAME
<br />COLOR USED FOR A PHASE THROUGHOUT. COLOR -CODE SHALL BE AS
<br />FOH OWS:
<br />120/208 VOLT -
<br />PHASE A - BLACK
<br />PHASE 8 - RED
<br />PHASE C - BLUE
<br />NEUTRAL - WHITE
<br />GROUND - GREEN.
<br />PUSH -IN WIRE CONNECTORS ARE NOT PERMITTED.
<br />E. LOCATE ALL DEVICES AND EQUIPMENT MERE SHOYM ON DRAWNGS. ALL
<br />DIMENSIONS SHOINN ON THE DRAWNGS ARE FROM FINISHED FLOOR TO THE
<br />CENTER OF THE DEVICE UNLESS OTHERWSE INDICATED. STANDARD
<br />MOUNTING HEIGHTS ARE AS FOLLOWS:
<br />DEVICES HEIGHT AFF AT DEVICE CENTER
<br />ELECTRICAL OUTLETS 18,
<br />ELECTRICAL OUTLETS ABOVE COUNTER 42"
<br />TELEPHONE 18w
<br />WALL TELEPHONE 46"
<br />LIGHT SWTCHES 42"
<br />FIRE ALARM DEVICES 80" TO BOTTOM OF GLASS
<br />EXIT SIGNS AS NECESSARY
<br />SPECIAL DEVICES AS NECESSARY
<br />NOTE: ELECTRICAL CONTRACTOR SHALL FIELD VERIFY AND COORDINATE WTH
<br />PROJECT SUPERINTENDENT FOR OVER COUNTER OUTLETS MOUNTING
<br />HEIGHT AND DIREC11ON (VERTICAL OR HORIZONTAL) PRIOR TO ROUGH -IN.
<br />F. DISCONNECT SWTCHES: HEAVY DUTY, FUSED OR NON -FUSED AS CALLED
<br />FOR ON DRAWNGS. PROVIDE SOLID NEUTRAL CONNEC11ON MERE
<br />REQUIRED. USE NEMA-1 INDOORS AND NEMA-3R OUTDOORS. ALL
<br />DISCONNECT SWTCHES SHALL BE PROVIDED NTH GROUND KIT.
<br />G. PROVIDE PANELBOARDS OF THE DEAD FRONT TYPE, NO LESS THAN 20
<br />INCHES WDE AND 5 3/4 INCHES DEEP WTH QUANTITY OF BRANCH
<br />CIRCUITS/CIRCUIT BREAKERS AS INDICATED ON THE PANELBOARD
<br />SCHEDULE NTH THE VOLTAGE, PHASE AND AMPERE RATING AS REQUIRED.
<br />ALL PANELBOARDS SHALL HAVE PHASE SEQUENCE CIRCUITS AND BOLT -ON
<br />CIRCUIT BREAKERS. MAIN BREAKERS SHALL BE MOLDED CASE. CIRCUIT
<br />BREAKERS FEEDING HVAC LOADS SHALL BE HACR TYPE THAT SERVE AS
<br />DISCONNECTING MEANS FOR EQUIPMENT SHALL BE PROVIDED WTH
<br />PERMANENTLY INSTALLED LOCK -OFF KIT. TYPEWRITTEN PANEL DIRECTORIES
<br />SHALL BE PROVIDED AT COMPLETION OF THE PROJECT.
<br />H. ELECTRICAL CONTRACTOR SHALL REVIEW ONE LINE POWER RISER DIAGRAM
<br />IN CONJUNCTION NTH SWTCHGEAR MANUFACTURER REPRESENTATIVE TO
<br />CROSS REFERENCE POWER RISER WTH PANEL SCHEDULES AND VERIFY
<br />VOLTAGES, AMPS, LUGS SIZES/NUMBER AND CABINETS DIMENSIONS PRIOR
<br />TO SUBMITTING A BID.
<br />1. EXERCISE CARE IN CONNECTING THE VARIOUS ELECTRICAL LOADS TO THE
<br />PANELS IN ORDER TO ARRIVE AT A REASONABLE BALANCE BETWEEN
<br />LOADS IN EACH PHASE AT EACH PANEL MAKE TESTS AND ADJUST
<br />LOADS AT EACH PANEL TO RESULT IN REASONABLY BALANCED LOAD
<br />CONDITION. SATISFACTORY TO THE U11LITY COMPANY. ENGINEER, OYMER
<br />AND INSPECTION AGENCIES. DOCUMENT ALL SAID LOAD ADJUSTMENTS.
<br />J. MANUFACTURERS: BASE OF DESIGN IS SQUARE D, EQUAL PRODUCTS BY
<br />GENERAL ELECTRIC, SIEMENS OR CUTLER HAMMER WLL BE CONSIDERED.
<br />K. MATERIALS SHALL BE NEW AND UNUSED AND THE CATALOGUED PRODUCTS
<br />OF MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH
<br />MATERIALS. THE MATERIALS SHALL BE OF THE MANUFACTURER'S LATEST
<br />STANDARD DESIGN THAT COMPLIES WTH THE SPECIFICATION REQUIREMENTS.
<br />ALL MATERIALS SHALL BE PROVIDED WTH UL LABELS.
<br />M. LIGHTING
<br />M.1. LIGHTING FIXTURES SHALL BE AS SHOYM ON THE DRAWNG AND SHALL
<br />BE FURNISHED WTH LAMPS INSTALIfD.
<br />M.2. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING
<br />CEILING TYPES PRIOR TO ORDERING LIGHT FIXTURES.
<br />M.3. LIGHT FIXTURES SHALL BE SUPPORTED NTH #12 GAUGE WRE FROM
<br />BUILDING STRUCTURE AND NOT FROM CEILING GRID. SECURE TWO
<br />OPPOSITE CORNERS TO STRUCTURE.
<br />M.4. LUMINAIRES MUST NOT BE INSTALLED LESS THAN 1 2/2 INCHES
<br />BELOW METAL ROOF DECKING.
<br />N. ALL GROUNDING SHALL CONFORM TO ARTICLE 250 OF THE NEC
<br />REQUIREMENTS. IN ADDITION THERETO AS IMPOSED BY THE DRAWNGS AND
<br />THE LOCAL CODE ENFORCEMENT AUTHORITIES HAVING JURISDICTION.
<br />0. SUBMITTALS: SUBMIT ELECTRONIC SUBMITTALS VIA E-MAIL FORMATTED AS
<br />PDF FILE.
<br />P. CONDUIT PENETRATIONS THROUGH FIRE RATED PARTITIONS SHALL BE
<br />SEALED USING AN UL APPROVED SYSTEM. REFER TO ARCHITECTURAL
<br />FLOOR PLAN FOR LOCA11ON OF FIRE RATED PARTITIONS. PROVIDE
<br />ACOUSTICAL FOAM SEALANT AT ALL DEVICES ON DEMISING PARTITIONS. IF
<br />PARTITION IS FIRE RATED, PROVIDE FIREPROOF COMPOUND ON BACK AND
<br />SIDES OF THE BOX. MERE TELEPHONE AND ELECTRICAL OUTLETS APPEAR
<br />ON PLANS AS BACK TO BACK, OUTLETS SHALL BE STAGGERED TO REDUCE
<br />NOISE TRANSMISSION. WERE WALLS AND PARTITIONS ARE REQUIRED TO
<br />HAVE A MINIMUM OF 1-HOUR FIRE -RESISTANCE RATING, BOXES SHALL BE
<br />SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES OR
<br />PROTECTED WTH UL LISTED PUTTY PADS.
<br />Q. ELECTRICAL CONTRACTOR SHALL REVIEW THE ARCHITECTURAL DRAWNGS
<br />FOR DEVICES EXACT LOCATIONS, MOUNTING HEIGHTS AND QUANTITIES
<br />PRIOR TO BID AND PRIOR TO ROUGH -IN. NOTIFY THE ENGINEER
<br />IMMEDIATELY IF ANY DISCREPANCIES ARE FOUND.
<br />R. REVIEW AND COORDINATE WTH MECHANICAL CONTRACTOR DRAWNGS FOR
<br />EQUIPMENT, CONDUIT, DEVICES, ETC. REQUIRED FOR A COMPLETE AND
<br />OPERATING HVAC SYSTEM. LOW VOLTAGE CONTROL WRING FURNISHED AND
<br />INSTALLED BY DIVISION 15. CHECK ALL MOTORS AND ROTATING EQUIPMENT
<br />FOR PROPER ROTATION.
<br />S. FINAL QUANTITY OF EXIT AND EMERGENCY LIGHTS TO BE DETERMINED BY
<br />FIRE MARSHALL INCLUDE CONTINGENCY FOR 6 ADDITIONAL EXIT LIGHTS AND
<br />6 ADDITIONAL EMERGENCY LIGHTS IN BASE BID.
<br />T. PROVIDE BACK BOXES AND RACEWAY FOR DOOR ACCESS CARD READERS
<br />AND ELECTRIC STRIKES AS PER SECURITY CONTRACTOR DIRECTIONS.
<br />PROVIDE 120VAC TO EACH ELECTRIC STRIKE DOOR LOCATION AND TO
<br />ACCESS CONTROL SYSTEM PANEL ACCESS CONTROL SYSTEM MUST
<br />DEACTIVATE OR OPEN ANY DOOR LOCKING MECHANISM AND REMAIN IN
<br />FAIL SAFE POSITION WHENEVER FIRE ALARM SYSTEM IS ACTIVATED OR
<br />BUILDING POWER FAILS. PROVIDE "PUSH-TO-EXIr PUSHBUTTON AND
<br />MOTION DETECTOR AT EACH ACCESS DOOR LOCATION. INTERLOCK NTH
<br />FIRE ALARM SYSTEM. ANY CARD READERS PREVENTING FREE EGRESS
<br />SHALL BE IN ACCORDANCE NTH SECTION 1010.1.9.9 OF CHAPTER 10 OF
<br />THE FLORIDA BUILDING CODE.
<br />U. ELECTRICAL CONTRACTOR MAY COMBINE CIRCUITS IN A COMMON RACEWAY
<br />AS LONG AS CONDUCTORS ARE DERATED AS PER NEC TABLE 310-15.
<br />SHARED NEUTRAL SHALL NOT BE ALLOWED UNLESS OTHERNSE INDICATED.
<br />CIRCUITS SHARING A COMMON NEUTRAL MUST HAVE COMMON TRIP CIRCUIT
<br />BREAKERS TO ALLOW ALL TO BE TURNED OFF SIMULTANEOUSLY, AS PER
<br />NEC 210.4(B).
<br />V. ELECTRICAL CONTRACTOR SHALL INCLUDE CORE DRILLING, CUTTING AND
<br />PATCHING FOR THE INSTALLATION OF HIS/HER WORK WTHIN BASE BID.
<br />W. CLEAN ALL NEW AND EXISTING LIGHT FIXTURES, LAMPS AND LENSES AND
<br />PANELBOARD INTERIORS PRIOR TO FINAL ACCEPTANCE.
<br />X. PROVIDE DISK FILE ON CAD 2015 OR NEWER RELEASE WTH ACCURATE
<br />ELECTRICAL RECORD DRAWNGS AT THE COMPLETION OF THE PROJECT.
<br />Y. CONTRACTOR REPRESENTS THAT HIS BID IS BASED UPON THE
<br />MANUFACTURER'S MATERIALS AND EQUIPMENT DESCRIBED IN THE
<br />CONTRACT DOCUMENTS.
<br />Z. ELECTRICAL CONTRACTOR SHALL FILL UTILITY SERVICE INFORMATION LOAD
<br />FORMS AND BUILDING DEPARTMENT ELECTRICAL PERMIT FORMS.
<br />AA. ELECTRICAL CONTRACTOR SHALL INSTRUCT OWNER REPRESENTATIVE
<br />REGARDING EQUIPMENT OPERA11ON AND MAINTENANCE AT COMPLETION OF
<br />WORK. PROVIDE OWNER NTH ALL MANUALS PERTAINING TO THE PROJECT.
<br />AB. LOW VOLTAGE CABLES FOR SECURITY SYSTEM, AV SYSTEM, TELEPHONE
<br />SYSTEM AND DATA SYSTEM ARE NOT PART OF THIS ENGINEER'S SCOPE OF
<br />WORK. ELECTRICAL CONTRACTOR SHALL COORDINATE NTH LOW VOLTAGE
<br />VENDOR(S) FOR BOXES AND RACEWAYS LOCATIONS, SIZES AND ROUTING
<br />PRIOR TO ROUGH -IN.
<br />AC. MINIMUM EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A PERIOD OF
<br />1 1/2 HOURS IN THE EVENT OF FAILURE OR NORMAL LIGHTING, WTHIN THE
<br />WORK AREAS. EMERGENCY LIGHTING FACIU11ES SHALL BE ARRANGED TO
<br />PROVIDE INITIAL ILLUMINATION THAT IS AT LEAST AN AVERAGE OF 1
<br />FOOTCANDLE (10 LUX) AND A MINIMUM AT ANY POINT OF 0.1 FOOTCANDLE
<br />(1 LUX) MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL
<br />'Elm,
<br />ENERGY CONSERVAT'ION
<br />CODE COMPLIANCE
<br />1. THIS DESIGN COMPLIES WTH F.B.C. ENERGY CONSERVATION SEVENTH EDITION
<br />(2020) CHAPTER 4, SECTION C405 FOR ELECTRICAL POWER AND LIGHTING
<br />SYSTEMS.
<br />2. THIS DESIGN COMPLIES WTH 7TH EDITION (2020) OF F.B.C. ENERGY CONSERVATION
<br />CHAPTER 4 ARTICLE C405.5.3 FOR FEEDER AND BRANCH CIRCUIT VOLTAGE DROP.
<br />3. WTHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF
<br />THE ACTUAL INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER, INCLUDING:
<br />a. A SINGLE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND
<br />b. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION.
<br />(REF. FBC-EC C405.5.4.1 - 7TH EDITION).
<br />4. AN OPERATING MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING
<br />OWNER. THE MANUALS SHALL INCLUDE� AT A MINIMUM, THE FOLLOWNG.
<br />a. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH
<br />PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
<br />b. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF
<br />EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS
<br />SHALL BE CLEARLY IDENTIFIED.
<br />c. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
<br />(REF: FBC-EC 405.5.4.2 - 7TH EDITION).
<br />LIGHTING COMMISSIONING
<br />LIGHTING SYSTEM FUNCTIONAL TESTING
<br />CONTROLS FOR AUTOMATIC UGFITING SYSTEMS SHALL COMPLY WTH SECTION C408.3.
<br />FUNCTIONAL TESTING
<br />TESTING SHALL ENSURE THAT CONTROL HARDWARE AND SOFTWARE ARE CALIBRATED,
<br />ADJUSTED, PROGRAMMED AND IN PROPER WORKING CONDIT10N IN ACCORDANCE WTH
<br />THE CONSTRUCTION DOCUMENTS AND MANUFACTURER'S INSTALLATION INSTRUCTIONS.
<br />FUNCTIONAL TESTING SHALL BE PERFORMED BY CONTRACTOR AND MANUFACTURER'S
<br />REPRESENTATIVE IN THE PRESENCE OF THE CLIENT REPRESENTATIVE AT THE
<br />COMPLETION OF THE PROJECT. SCHEDULE A SECOND TESTING WTH ONSIER
<br />REPRESENTATIVE AFTER FACILITY HAS BEEN IN OPERATION FOR TWO OR THREE
<br />MONTHS. MERE REQUIRED BY THE CODE OFFICIAL, AN APPROVED PARTY
<br />INDEPENDENT FROM THE DESIGN OR CONSTRUCTION OF THE PROJECT SHALL BE
<br />RESPONSIBLE FOR THE FUNCTIONAL TESTING AND SHALL PROVIDE DOCUMENTATION TO
<br />THE CODE OFFICIAL CERTIFYING THAT THE INSTALLED LIGHTING CONTROLS MET THE
<br />PROVISIONS OF SECTION C405.
<br />FOR OCCUPANT SENSORS, TIME SWTCHES, PROGRAMMABLE SCHEDULE CONTROL
<br />PHOTOSENSORS OR DAY LIGHTING CONTROLS THE FOLLOWNG PROCEDURES SHALL BE
<br />PERFORMED.
<br />1. CONFIRM THAT THE PLACEMENT, SENSITIVITY AND TIME-OUT ADJUSTMENTS FOR
<br />OCCUPANT SENSORS YIELD ACCEPTABLE PERFORMANCE.
<br />2. CONFIRM THAT THE TIME SWTCHES AND PROGRAMMABLE SCHEDULE CONTROLS
<br />ARE PROGRAMMED TO TURN THE LIGHTS OFF.
<br />3. CONFIRM THAT THE PLACEMENT AND SENSITIVITY ADJUSTMENTS FOR
<br />PHOTOSENSOR CONTROLS REDUCE ELECTRIC LIGHT BASED ON THE AMOUNT OF
<br />USABLE DAYLIGHT IN THE SPACE AS SPECIFIED.
<br />EXISTING CONDITIONS GENERAL NOTES
<br />1. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING
<br />AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS,
<br />SO AS TO BECOME FAMILIAR WTH EXISTING CONDITIONS AND
<br />DIFFICULTIES THAT WLL AFFECT EXECUTION OF THE WORK.
<br />SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT
<br />SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR,
<br />EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES
<br />ENCOUNTERED WLL NOT BE RECOGNIZED.
<br />2. ELECTRICAL CONTRACTOR SHALL TRACE LIGHTING AND POWER BRANCH
<br />CIRCUITS TO IDENTIFY CIRCUITS SERVING AREA WTHIN SCOPE OF
<br />WORK. PROVIDE UPDATED TYPEWRITTEN PANEL SCHEDULES AT
<br />COMPLETION OF WORK.
<br />3. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS AND CEILINGS TO
<br />BE REMOVED. REMOVE EXISTING POWER, LIGHTING, SYSTEMS, MATERIAL
<br />AND EQUIPMENT WHICH ARE MADE OBSOLETE OR MICH INTERFERE
<br />WTH THE CONSTRUCTION OF THE PROJECT.
<br />3.o. REINSTALL ANY SUCH POWER, LIGHTING, SYSTEMS, MATERIALS AND
<br />EQUIPMENT MICH ARE REQUIRED TO REMAIN ACTIVE FOR THE
<br />FACILITY TO BE FULLY FUNCTIONAL
<br />4. EXISTING OUTLET BOXES AND CONDUIT MICH ARE LOCATED PROPERLY
<br />FOR NEW WORK MAY BE REUSED FOR NEW DEVICES AND WRE.
<br />5. ALL CONDUIT AND WIRE REMOVED SHALL BE TAKEN BACK TO THE
<br />SOURCE OF SUPPLY.
<br />6. ALL UNUSED RACEWAYS WTHIN ACCESSIBLE SPACES SHALL BE
<br />COMPLETELY REMOVED. REMOVE ALSO ASSOCIATED CONDUCTORS,
<br />JUNCTION BOXES, FASTENERS AND SUPPORTS.
<br />7. REMOVE CONDUCTORS FROM EXISTING FLOOR BOXES BEING DEMOLISHED
<br />TO SOURCE OF SUPPLY. PATCH SURFACES AS DIRECTED BY GENERAL
<br />CONTRACTOR.
<br />8. WHERE EXISTING EQUIPMENT OR MATERIALS ARE REMOVED OR
<br />CHANGED, ALL BRANCH CONDUITS, MICH NO LONGER ARE IN SERVICE,
<br />SHALL BE REMOVED AS DIRECTED BY THE ARCHITECT. IF, IN THE
<br />COURSE OF THE WORK, OUTLETS ARE COVERED UP OR OTHERWSE
<br />RENDERED INACCESSIBLE, ALL WRING TO SAME SHALL BE REMOVED TO
<br />THE SOURCE. IF A CIRCUIT THAT MUST REMAIN IN SERVICE IS
<br />INTERRUPTED THEREBY, IT SHALL BE RECONNECTED BY THE MOST
<br />INCONSPICUOUS MEANS SO AS TO REMAIN OPERATIONAL, NTH SAME
<br />CAPACITY AS BEFORE. ALL BUILDING SURFACES DAMAGED, AND
<br />OPENINGS LEFT BY REMOVAL OF BOXES, PIPING OR OTHER EQUIPMENT
<br />SHALL BE REPAIRED BY THE CONTRACTOR. ALL HOLES LEFT IN
<br />JUNCTION BOXES, SWTCHES, PANELS, ETC. SHALL BE CLOSED.
<br />9. MERE NEW OPENINGS ARE CUT AND CONCEALED CONDUITS, ETC., ARE
<br />ENCOUNTERED, THEY SHALL BE REMOVED OR RELOCATED AS
<br />REQUIRED. MERE CONDUIT TO BE REMOVED STUBS THROUGH FLOORS,
<br />WALLS, AND CEILINGS, SUCH CONDUIT SHALL BE REMOVED TO THE
<br />POINT MERE THE FINISH SURFACES CAN BE PATCHED ADEQUATELY
<br />SO THAT NO EVIDENCE OF THE FORMER INSTALLATION REMAINS.
<br />10. ALL REUSABLE DEVICES, FIXTURES AND EQUIPMENT SHALL BECOME THE
<br />PROPERTY OF THE OWNER. ALL OTHER SALVAGE AND DEBRIS SHALL
<br />BE REMOVED FROM THE PREMISES DAILY.
<br />11. ABANDONED LOW VOLTAGE CABLES WTHIN CEILING SPACES SHALL BE
<br />REMOVED AS PER ARTICLE 725.25 OF THE NFPA-70.
<br />ELECTRICAL OUTLETS AND BOXES NOTES
<br />1. AN OUTLET BOX OF THE APPROPRIATE SIZE AND TYPE SHALL BE PROVIDED
<br />FOR ALL LIGHTING FIXTURES, SWTCHES, RECEPTACLES, ETC.
<br />2. ALL SWITCHES AND RECEPTACLES SHALL BE SPECIFICATION GRADE 20A
<br />MINIMUM UNLESS OTHERWSE NOTED. COORDINATE COLOR WTH ARCHITECT
<br />PRIOR TO ORDERING.
<br />3. ALL RECEPTACLES LOCATED OUTDOOR SHALL BE WEATHER RESISTANT.
<br />COVERS SHALL BE "MILE -IN -USE" TYPE. COVER SHALL BE IDENTIFIED AND
<br />LISTED AS "EXTRA-DUT'r.
<br />4. PROVIDE 4 11/16"x 4 11/16"x 2 1/8' SQUARE BOX AND 1" CONDUIT
<br />STUB -UP TO ACCESSIBLE CEILING FOR TELEPHONE AND DATA OUTLETS.
<br />TERMINATE CONDUITS 6" ABOVE CEILING IN ACCESSIBLE SPACE WTH 90*
<br />BEND INSULATED BUSHINGS AND PULL STRING. COORDINATE WTH TENANTS
<br />DATA/TELEPHONE CONTRACTOR FOR FURTHER ELECTRICAL AND RACEWAYS
<br />REQUIREMENTS PRIOR TO ROUGH -IN. CABLING BY OTHERS.
<br />5. ALL JUNCTION BOX COVERS SHALL BE MARKED NTH PANEL, CIRCUIT
<br />NUMBER AND VOLTAGE WTH PERMANENT BLACK MARKER.
<br />6. JUNCTION BOXES SHALL NOT BE MOUNTED TO THE PARTITION TOP PLATE.
<br />7. PROVIDE ACOUSTICAL FOAM AND SEALANT AT ALL DEVICES ON DEMISING
<br />PARTITIONS. IF PARTITION IS FIRE RATED, PROVIDE FIREPROOF COMPOUND
<br />ON BACK AND SIDES OF THE BOX.
<br />8. MERE TELEPHONE AND ELECTRICAL OUTLETS APPEAR ON PLANS AS BACK
<br />TO BACK, OUTLETS SHALL BE STAGGERED TO REDUCE NOISE TRANSMISSION.
<br />WERE WALLS AND PARTITIONS ARE REQUIRED TO HAVE A MINIMUM OF
<br />1-HOUR FIRE -RESISTANCE RATING, BOXES SHALL BE SEPARATED BY A
<br />MINIMUM HORIZONTAL DISTANCE OF 24" INCHES OR PROTECTED NTH UL
<br />LISTED PUTTY PADS.
<br />9. GROUNDING OF RECEPTACLES AND FIXED EQUIPMENT IN PATIENT CARE
<br />AREAS SHALL COMPLY WTH NEC ARTICLE 517,13 (A) AND (B).
<br />10. GFC1 RECEPTACLES FOR ALL APPLIANCES MUST BE READILY ACCESSIBLE. IF
<br />RECEPTACLE CANNOT BE MADE ACCESSIBLE, PROVIDE GFCl CIRCUIT
<br />BREAKER.
<br />WIRE SIZE REOUIRED FOR
<br />BRANCH CIRCUITS AT LESS
<br />THAN 3% VOLTAGE DROP
<br />I FT
<br />TO
<br />50 FT
<br />51 FT
<br />m
<br />75 FT
<br />76 FT
<br />TO
<br />100 FT
<br />101 FT
<br />70
<br />125 FT
<br />12SEFT
<br />TO
<br />I FT
<br />151 FT
<br />70
<br />200 FT
<br />120V
<br />20A
<br />#12
<br />#10
<br />#8
<br />#13
<br />#6
<br />#6
<br />30A
<br />110
<br />#B
<br />#6
<br />#6
<br />#6
<br />#4
<br />40A
<br />#B
<br />#6
<br />#6
<br />#4
<br />#4
<br />#3
<br />F50A
<br />#8
<br />0
<br />0
<br />0
<br />0
<br />9
<br />208V
<br />10
<br />20A
<br />f12
<br />#12
<br />#12
<br />#10
<br />#10
<br />#8
<br />30A
<br />#10
<br />#10
<br />#10
<br />#8
<br />#8
<br />#6
<br />40A
<br />#8
<br />#B
<br />#B
<br />#8
<br />#6
<br />#6
<br />50A
<br />#B
<br />#8
<br />#B
<br />#6
<br />#6
<br />#4
<br />60A
<br />#6
<br />#6
<br />#6
<br />#6
<br />#4
<br />#4
<br />70A
<br />14
<br />#4
<br />#4
<br />14
<br />#4
<br />#3
<br />80A
<br />#3
<br />#3
<br />#3
<br />#3
<br />#2
<br />#1
<br />90A
<br />#2
<br />#2
<br />#2
<br />#2
<br />#2
<br />#1
<br />100A
<br />#1
<br />#1
<br />#1
<br />#1
<br />NO
<br />NO
<br />208V
<br />30
<br />I
<br />20A
<br />#12
<br />#12
<br />#12
<br />#10
<br />#10
<br />#8
<br />30A
<br />#10
<br />#10
<br />#10
<br />#8
<br />#8
<br />#6
<br />40A
<br />#8
<br />#8
<br />#8
<br />#8
<br />#6
<br />#6
<br />50A
<br />#8
<br />#8
<br />#8
<br />#6
<br />#6
<br />#4
<br />60A
<br />#6
<br />#6
<br />#6
<br />#6
<br />#6
<br />#4
<br />70A
<br />#4
<br />14
<br />14
<br />J4
<br />f4
<br />#4
<br />80A
<br />#3
<br />#3
<br />#3
<br />#3
<br />#2
<br />#1
<br />90A
<br />#2
<br />#2
<br />#2
<br />J2
<br />#2
<br />#1
<br />100A
<br />#1
<br />0
<br />#1
<br />#1
<br />#170-1
<br />#1/01
<br />CALCULATED USING COPPER WIRE AT 750 C.
<br />TABLE ABOVE FOR REFERENCE ASSUMING FULLY RATED
<br />CIRCUIT AT 80% OF AMPACITY.
<br />NO MORE THAN 2% VOLTAGE DROP MAXIMUM FOR
<br />FEEDERS. AS PER FBC ENERGY CONSERVATION, CHAPTER
<br />4 ARTICLE C405.7.3.1.
<br />NO MORE THAN 3% VOLTAGE DROP MAXIMUM FOR BRANCH
<br />FEEDERS. AS PER FBC ENERGY CONSERVATION, CHAPTER
<br />4 ARTICLE C405.7.3.2.
<br />WERE UNGROUNDED CONDUCTORS ARE INCREASED IN
<br />SIZE, EQUIPMENT GROUNDING CONDUCTORS SHALL BE
<br />INCREASED IN SIZE PROPORTIONATELY ACCORDING TO THE
<br />CIRCULAR MILL AREA OF THE UNGROUNDED CONDUCTORS.
<br />ELECTRICAL SYMBOL LEGEND
<br />(NOT ALL SYMBOLS USED ON THIS PROJECT)
<br />RECESSED LUMINAIRE
<br />EMERGENCY RECESSED LUMINAIRE. CONNECT AS 24-HOUR
<br />NIGHTLIGHT UNLESS OTHERWSE NOTED.
<br />0 rX) LED, INCANDESCENT, COMPACT FLUORESCENT FIXTURE - CEILING
<br />MOUNTED, WALL MOUNTED
<br />I& 4P EXIT SIGN FIXTURE, SHADED QUADRANT INDICATES FACE, WTH
<br />ARROWS AS SHOWN ON PLAN - CEILING MOUNTED, WALL MOUNTED
<br />$ $2 $3 $4
<br />H
<br />sm smp sw
<br />w 9
<br />19
<br />(000
<br />IG
<br />GW ($G
<br />oc
<br />El [A
<br />RN fm
<br />we--%
<br />121010
<br />=P cm mmj
<br />1-POLE, 2-POLE, 3-WAY, 4-WAY SWTCH
<br />DIMMER SWTCH, LUTRON, VERIFY LAMP TYPE
<br />(LED/INCANDESCENT/FLUORESCENT) PRIOR TO ORDER
<br />MANUAL MOTOR STARTER TOGGLE SWTCH AS NOTED; *P"
<br />INDICATES PILOT LIGHT; -WP- INDICATES WEATHERPROOF
<br />OCCUPANCY SENSORS
<br />POWER PACK
<br />DUPLEX RECEPTACLE AT 18-, ABOVE COUNTER AT 42% ISOLATED
<br />GROUND TYPE
<br />GROUND FAULT AT 42" TYPE SELF TESTING DUPLEX RECEPTACLE
<br />CEILING MOUNTED DUPLEX RECEPTACLE
<br />(2) DUPLEX RECEPTACLES IN SINGLE OUTLET BOX WTH
<br />SINGLE COVER PLATE AT 18% ABOVE COUNTER AT 42-
<br />TELEPHONE/DATA OUTLET, PROMDE 4 11/16"x 4 11/16"x 2 1/8"
<br />SQUARE BOX AND 1" CONDUIT TO ACCESSIBLE CEILING.
<br />CONFIRM WTH VENDOR PRIOR TO ROUGH -IN
<br />SPECIAL RECEPTACLE, PUSHBUTTON AS NOTED,
<br />TELEPOWER POLE
<br />FLOOR MOUNTED DUPLEX RECEPTACLE, FLOOR MOUNTED
<br />TELEPHONE/DATA OUTLET
<br />FINAL CONNECTION TO EQUIPMENT
<br />JUNCT10N BOXES, MOTOR CONNEC11ON
<br />DISCONNECT SWTCH, STARTER OR CONTACTOR,
<br />COMBINATION STARTER/DISCONNECT
<br />120/208V PANELBOARD
<br />277/480V PANELBOARD
<br />TELEPHONE TERMINAL BOARD
<br />ELECTRIC DOOR STRIKE/CARD READER
<br />TV OUTLET, PROVIDE 4 11/16*x 4 11/16"x 2 1/8"
<br />SQUARE BOX AND 1* CONDUIT TO ACCESSIBLE CEILING.
<br />COORDINATE MOUNTING HEIGHT PRIOR TO ROUGH -IN.
<br />BRANCH CIRCUIT CONDUIT CONCEALED ABOVE CEILING OR IN
<br />WALL, SLASH MARKS INDICATE NUMBER OF CONDUCTORS,
<br />LONGER SLASH IS NEUTRAL, (GROUND WIRE NOT SHOWN);
<br />2 #12 - 1 #12 GROUND MINIMUM (UNLESS OTHERWSE NOTED
<br />OR MARKED); LONGER SLASH WTH HATCH MARK INDICATES
<br />ISOLATED GROUND. ISOLATED GROUND CONDUCTOR SHALL BE
<br />GREEN WTH A YELLOW STRIPE. QUANTITY OF ARROWS
<br />INDICATE QUANTITY OF HOMERUNS TO PANELBOARD.
<br />PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN ALL BRANCH
<br />CIRCUITS. CIRCUITS SHARING A COMMON NEUTRAL MUST HAVE
<br />A COMMON TIE HANDLE ON THE CIRCUIT BREAKERS TO
<br />ALLOW ALL TO BE TURNED OFF SIMULTANEOUSLY.
<br />BRANCH CIRCUIT CONDUIT CONCEALED BELOW SLAB OR
<br />UNDERGROUND. CIRCUITS SHARING A COMMON NEUTRAL MUST
<br />HAVE A COMMON TIE HANDLE ON THE CIRCUIT BREAKERS TO
<br />ALLOW ALL TO BE TURNED OFF SIMULTANEOUSLY.
<br />SUBSCRIPT LEGEND
<br />E EXISTING DEVICE/UGHT AND ASSOCIATED CIRCUIT WRING TO REMAIN. PROVIDE
<br />ALL NECESSARY EXTENSION OF CONDUIT AND WRING AS REQUIRED, IN ORDER
<br />TO MAINTAIN CIRCUIT CONTINUITY TO EXISTING EQUIPMENT TO REMAIN.
<br />ERL EXISTING DEVICE/LIGHT TO BE RELOCATED. JUNCTION AND EXTEND EXISTING
<br />CONDUIT AND WRING TO NEW LOCATION AS REQUIRED.
<br />RL NEW LOCATION OF EXISTING DEVICEAIGHT. PROVIDE EXTENSION OF EXISTING
<br />CONDUIT AND WRING AS REQUIRED. (PROVIDE NEW SWTCHING AS INDICATED)
<br />R EXISTING DEVICE/LICNT TO BE REMOVED. MERE EXISTING EQUIPMENT TO
<br />REMAIN IS FED VIA EXISTING EQUIPMENT TO BE REMOVED, PROVIDE ALL
<br />NECESSARY EXTENSION OF CONDUIT AND WRING AS REQUIRED IN ORDER TO
<br />MAINTAIN CIRCUIT CONTINUITY TO EXISTING EQUIPMENT.
<br />N DEVICE/UGHT TO MATCH EXISTING BUILDING STANDARDS.
<br />f9REF9GHTERS RADIO NOTE
<br />BASE BID:
<br />CONTRACTOR SHALL PROCURE THE SERVICES OF A THIRD PARTY VENDOR
<br />TO TEST THE PUBLIC SAFETY RF RADIO COVERAGE, WTHIN THE PROJECT
<br />SCOPE OF WORK, AND DETERMINE WHETHER A NEW DAS SYSTEM IS
<br />REQUIRED PER FLORIDA FIRE PREVENTION CODE 7TH EDITION CHAPTER 11
<br />SECTION 11.10.1 AND NFPA 72 2016 EDITION CHAPTER 24 SECTION 24.9.
<br />CONTRACTOR SHALL SUBMIT TEST REPORTS AND RECOMMENDATIONS TO
<br />THE FIRE MARSHALL AS REQUESTED BY BUILDING PERMIT COMMENTS.
<br />BID ALIERNAIE:
<br />CONTRACTOR TO PROVIDE PRICING FOR A COMPLETE IN-BULDING RF RADIO
<br />COVERAGE SYSTEM FOR THE PUBLIC SAFETY RADIO AS SET FORTH IN
<br />FLORIDA FIRE PREVENTION CODE 7TH EDITION CHAPTER 11 SECTION 11.10.1
<br />AND NFPA 72 2016 ED11ION CHAPTER 24 SECTION 24.9 AND SHALL BE
<br />VERIFIED AS COMPLIANT PER THE CODES ABOVE AND THE AHJ. THE
<br />SYSTEM SHALL BE INSTALLED BY A TURN -KEY FIRM SPECIALIZING IN THE
<br />TRADE, TO INCLUDE NECESSARY SHOP DRAWNGS, FREQUENCY ENHANCING
<br />EQUIPMENT, INSTALLATION, TESTING, AND MONITORING TO SATISFY CODE
<br />AND AHJ REQUIREMENTS. CHANGE ORDERS FOR ADDITIONAL EQUIPMENT
<br />SHALL NOT BE PERMITTED. CONTRACTOR PROVIDING THIS PRICING SHALL
<br />BE INDEPENDENT OF THE THIRD PARTY VENDOR THAT PERFORMED THE
<br />PUBLIC SAFETY RADIO TEST AS PART OF BASE BID.
<br />MEP CONSULTING
<br />ENGINEERS
<br />SINCE 1977
<br />FL REG NO. 3089
<br />2016 ALDEN RD.
<br />ORLANDO, FL
<br />32803
<br />(407) 246-1688
<br />WWW.PEIFLA.COM
<br />PEI PROIECT it
<br />22121
<br />CAMPBELL + VAN DUSEN
<br />IIARCH IT ECTU RE IIN_E�IQF DE31ro-N
<br />www.CVDstudio.com
<br />CAMPBELL + VAN DUSEN Design Studio, LLC.
<br />255 South Orange Avenue Suite # 1240
<br />Orlando, Florida 32801
<br />Phone: 407.930.6016
<br />FL. Lic. No. AA26003339
<br />ARCHITECT OF RECORD
<br />FRANK W. CAMPBELL AIA
<br />FL LIC NO. AROO 16053
<br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
<br />SEALED AND DATED BY THE ARCHITECT OF RECORD
<br />I I 111111,f
<br />�PA)V
<br />C,
<br />S N S 4,., % op
<br />4Z-
<br />\V
<br />z C, a 140. SAIlro-w %
<br />CC
<br />sTxTS OF
<br />'P % PL ovkO.*6
<br />C2
<br />%%
<br />Bryan G. Spangler, PE,
<br />FL Reg. No. 64601
<br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED,
<br />SEALED AND DATED BY THE ENGINEER OF RECORD
<br />-1
<br />LL_
<br />(/i
<br />_j
<br />CL
<br />LLJ
<br />U
<br /><
<br />C/)
<br />LU
<br />LLJ
<br />>
<br />_j
<br />0
<br />CIO
<br />+
<br />L0
<br />-'0
<br />0e
<br /><
<br />LU
<br />LU
<br />0
<br />>
<br />-0 1-
<br />C)
<br />Lu
<br />'0 Lo
<br />w
<br /><
<br />3:
<br />or-11) lcyt)l
<br />CL
<br />rL_U_4
<br />CONSTRUCTION DOCUMENTS
<br />03.24.2023
<br />00
<br />PRINCIPAL IN CHARGE
<br />F. CAMPBELL
<br />. ..................................................................
<br />PROJECT MANAGER
<br />M. TORRES
<br />....................................................................
<br />ADVENT HEALTH
<br />WELL 65+
<br />ZEPHYRHILLS
<br />22-0328-01
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />El I
<br />
|