1 <br />E3.1 <br />LIGHTING RENOVATION PLAN <br />1/8" = V-0. <br />GENERAL LIGHTNG NOTES <br />1. PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL <br />LIGHTING CIRCUIT TO EMERGENCY EGRESS LIGHTS. <br />RUN 3 #12 - 1 #12 GND - 3/4-C TO INCLUDE <br />UNSWITCHED CONDUCTOR. <br />2. PULL UNSWITCHED HOT CONDUCTOR FROM LOCAL <br />LIGHTING CIRCUIT TO EXIT SIGNS. RUN 2 #12 - 1 <br />#12 GND - 3/4-C. <br />3. LIGHT FIXTURES BEING REUSED SHALL BE REPAIRED, <br />CLEANED AND RELAMPED. <br />4. SWITCHES SHALL BE GANGED WHEN THEY APPEAR <br />ADJACENT TO ONE ANOTHER ON PLANS WHEREVER <br />PRACTICABLE. PROVIDE MULTI -GANG JUNCTION <br />BOX AND COVER PLATE AS REQUIRED. <br />5. DASHED ARCS INDICATE CONTINUATION OF BRANCH <br />CIRCUIT BUT NOT SWITCH CONTROL. <br />6. UNLESS OTHERWISE NOTED, ALL FIXTURES AND <br />DEVICES SHOWN ON THIS PLAN ARE NEW. ALL <br />NEW FIXTURES AND SWITCHES SHALL MATCH <br />EXISTING BUILDING STANDARD. <br />7. VERIFY THAT DIMMER MATCHES LAMP TYPE PRIOR <br />TO ORDER. <br />8. ELECTRICAL CONTRACTOR SHALL PROVIDE A <br />LUMINAIRE DISCONNECT CONNECTOR FOR ALL <br />FLUORESCENT FIXTURES, AS REQUIRED BY N.E.C. <br />410.130(g)3 2011. UL LISTED CONNECTORS ARE <br />MANUFACTURER BY IDEAL, THOMAS AND BETTS AND <br />WAGO, ANY UL LISTED CONNECTOR WILL BE <br />ACCEPTABLE. INSTALL PER MANUFACTURERS <br />SPECIFICATIONS. <br />LIGHTING PLAN NOTES <br />FEED FIXTURES FROM EXISTING, LOCAL <br />LIGHTING CIRCUIT. FIELD VERIFY EXACT <br />CIRCUIT NUMBER. TYPICAL ALL EXIT SIGNS. <br />RUN 2#12 1#12 GND - 3/4- C. <br />PROVIDE A NEW EXTERIOR GRADE BUILDING <br />WALL MOUNTED LED LIGHT FIXTURE - MATCH <br />EXISTING. CONNECT ALL BUILDING MOUNTED <br />LIGHTS TO PANEL VIA TIME CLOCK WITH <br />PHOTOCELL. REFER TO EXTERIOR <br />LIGHTING/SIGNAGE WIRING DIAGRAM. <br />---- Do <br />�-OF <br />rio <br />2 <br />E3.1 <br />POWER RENOVATION PLAN <br />1/811 = i I -oil <br />GENERAL POWER NOTES <br />1. INDICATED CIRCUIT NUMBERS ARE SUGGESTED <br />FROM EXISTING SPARE BREAKERS AND SPACES <br />IN EXISTING PANELS. CONTRACTOR MAY USE <br />DIFFERENT CIRCUIT NUMBERS TO MATCH FIELD <br />CONDITIONS. <br />2. <br />ELECTRICAL CONTRACTOR SHALL COORDINATE <br />WITH INTERIOR DESIGN PACKAGE FOR ALL <br />MILLWORK AND WALL DESIGNS PRIOR TO <br />3. COMMENCING WORK. <br />EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN <br />FROM FIELD INVESTIGATION AND /OR ORIGINAL <br />DOCUMENTS AND SHOWN FOR THE CONVENIENCE <br />OF THE ELECTRICAL CONTRACTOR AND SHALL <br />NOT BE CONSIDERED "AS -BUILT" CONDITION. <br />4. BEFORE CONSTRUCTION BEGINS, ELECTRICAL <br />CONTRACTOR SHALL FIELD VERIFY ALL BRANCH <br />CIRCUITS. <br />PROVIDE TYPED, UPDATED PANEL SCHEDULES <br />UPON COMPLETION OF WORK. <br />54' BACK BOX <br />CONFIGURATION A - <br />DIAGNOSTIC UNIT LOCATION <br />POWER PLAN NOTES <br />CONNECT ELECTRIC WATER HEATER. PROVIDE <br />30A, 3P, 240V, N-1, NON -FUSED DISCONNECT <br />SWITCH. COORDINATE WITH PLUMBING <br />CONTRACTOR. RUN 3#10, 1#10 GND - 3/4" <br />C. <br />PROVIDE FLUSH MOUNTED FLOOR BOX WITH <br />120V QUAD RECEPTACLE AND TELE/DATA <br />OUTLETS, WALKER OMNIBOX SERIES <br />(#880S2-TWO GANG) OR APPROVED EQUAL. <br />SAWCUT FLOOR AS REQUIRED. RUN 2#12, <br />1#12 FOR 120V POWER. RUN 1-1/4- <br />CONDUIT WITH PULLSTRING FOR LOW VOLTAGE <br />CABLING. PROVIDE ALL ACCESSORIES <br />REQUIRED FOR A COMPLETE SYSTEM. <br />COORDINATE EXACT LOCATION, FINISHES, <br />COVERPLATES AND TYPE OF LOW VOLTAGE <br />OUTLETS WITH OWNER. <br />NEW CARD READER AND ELECTRIC STRIKE. <br />PROVIDE 3/4- RACEWAY TO ACCESSIBLE <br />CEILING FOR LOW VOLTAGE POWER. <br />COORDINATE WITH CARD READER VENDOR. <br />TENANT SECURITY SYSTEM SHALL BE <br />CONNECTED TO BUILDING FIRE ALARM SYSTEM <br />TO RELEASE ALL LOCKS UPON ACTIVATION. <br />PROVIDE ALL CONNEC11ONS AND ACCESSORIES <br />REQUIRED FOR A FULLY OPERATIONAL SYSTEM. <br />ANY CARD READERS INSTALLED IN SUCH A <br />WAY THAT THEY PREVENT FREE EGRESS <br />SHALL BE IN COMPLIANCE NTH SECTION <br />7.2.1.6.2 FOR ACCESS CONTROLLED EGRESS <br />DOOR ASSEMBLIES (NFPA 101) <br />PROVIDE RECESSED 2-GANG BOX AT HEIGHT <br />SHOWN ON WELLNESS SUITE J-BOX LOCAT10N <br />DETAIL FOR A/V CABLING. TYPICAL FOR ALL <br />ALL WELLNESS SUITES, BROKER ROOMS AND <br />STAFF LOUNGE. ARLINGTON MODEL #TVBS810. <br />PROVIDE JUNC11ON BOXES AND 120V CIRCUIT <br />FOR DOOR OPENER. COORDINATE EXACT <br />REQUIREMENTS WITH VENDOR. <br />PROVIDE 8'H X 4'W X 3/4-D PLYWOOD BACK <br />BOARD ON WALL FOR TELECOMMUNICATION <br />EQUIPMENT. PAINT NTH GRAY FIRE <br />RETARDENT PAINT. INSTALL DOUBLE DUPLEX <br />RECEPTACLE MOUNTED 0 42" AFF. RUN 2" <br />E.C. TO EXISTING MAIN TELEPHONE TERMINAL <br />BOARD. PROVIDE #6 GROUND NTH BUS BAR <br />CONNECTED TO BUILDING GROUND LUG. <br />--- Do <br />CONNECT 120V POWER TO NEW EXHAUST FAN. <br />PROVIDE MOTOR -RATED SWITCH. COORDINATE <br />WITH MECHANICAL CONTRACTOR. FAN HAS <br />M01ION SENSOR CONTROL. <br />CONNECT SPLIT SYSTEM. PROVIDE 30A, 2P, <br />240V, N-3R FUSED DISCONNECT SWITCH ON <br />ROOF. FUSE PER MANUFACTURER'S <br />NAMEPLATE. COORDINATE WITH MECHANICAL <br />CONTRACTOR. ELECTRICAL POWER IS <br />THROUGH CONDENSING UNIT THEN TO INDOOR <br />UNIT. <br />RUN 2 #10 - 1 #10 GND - 3/4-C TO <br />CONDENSING UNIT AND 2 #10 - 1 #10 GND - <br />3/4-C TO INDOOR UNIT. <br />PROVIDE 30A, 2P, 240V, N-1, FUSED <br />DISCONNECT SWITCH AT INDOOR UNI FU <br />AS MANUFACTURER'S NAMEPLATE. '7 <br />PROVIDE A 120V STAND ALONE DUCT <br />MOUNTED SMOKE DETECTOR IN SUPPLY SIDE <br />DUCTWORK OF EXISTING UNIT. PROVIDE <br />RELAY, CONTROL MODULE, AND REMOTE TEST <br />STATION NTH AUDIBLE AND VISUAL <br />NOTIFICATION. CONNECTION TO EXISTING UNIT <br />TO SHUT -DOWN UPON ACTIVATION. <br />COORDINATE WITH MECHANICAL CONTRACTOR. <br />PROVIDE RECESSED, FLANGELESS BOX WITH <br />DUPLEX RECEPTACLE AT HEIGHT SHOWN ON <br />WELLNESS SUITE J-BOX LOCATION DETAIL. <br />ARLINGTON MODEL #TVBS810. <br />CONNECT 120V POWER TO NEW EXHAUST FAN. <br />PROVIDE MOTOR -RATED SWITCH. COORDINATE <br />N CARE MEA SYMBOL LEGEND <br />0\,ADer,WERPOKP,CMEARAISAtE@6RyNffC IN <br />DNT Or NEW PANELS. <br />:ONDUIT (2)4"C. TO NEW COMM <br />E ARE NO CRITICAL OR WET PATIENT AREAS IN THE <br />'E OF WORK. <br />2. <br />GENERAL PATIENT CARE AREAS REQUIRE A WIRING METHOD <br />WITH A REDUNDANT GROUND AS PER ARTICLE 517.13 OF <br />THE NEC. <br />GROUNDING 0 FALL RECEPTACLES, LIGHTING AND FIXED <br />EQUIPMENT IN PATIENT CARE AREAS SHALL COMPLY WITH <br />IV <br />CAMPBELL + VAN DUSEN <br />1ARCH17ECTU RE lr�_ERIDF DE.311Z�t4 <br />www.CVDstudio.com <br />CAMPBELL + VAN DUSEN Design Studio, LLC. <br />255 South Orange Avenue Suite # 1240 <br />Orlando, Florida 32801 <br />Phone: 407.930.6016 <br />FL. Lic. No. AA26003339 <br />ARCHITECT OF RECORD <br />FRANK W. CAMPBELL AIA <br />FLLIC NO. AR0016053 <br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED, <br />SEALED AND DATED BY THE ARCHITECT OF RECORD <br />S PA <br />IV, <br />Sp <br />No. 6460 <br />Z STATE OF cr <br />oe <br />0 %."ZORIO'?" <br />.......... <br />IONAt-e\ <br />""11111111%00 <br />Bryan G. Spangler, PE, <br />FL Reg. No. 64601 <br />COPY OF THIS PLAN IS NOT VALID UNLESS SIGNED, <br />SEALED AND DATED BY THE ENGINEER OF RECORD <br />_j <br />H <br />V� <br />ry <br />0 <br />11-- <br />LIJ <br />r_4 <br />C) <br />< <br />0 <br />C/') <br />U_j <br />LLJ <br />> <br />_j <br />+ <br />Lr) <br />_j <br />U <br />7' <br />0.o� <br />< <br />LU <br />LLj <br />0 <br />> <br />-0 It <br />0 <br />LU <br />'0 Lo <br />Oe <br />< <br />3�: <br />Iro-0-- <br />CL <br />rL-U4 <br />(1y"') <br />CONSTRUCTION DOCUMENTS <br />03.24.2023 <br />PRINCIPAL IN CHARGE <br />F . CAMPBELL <br />.................................................................... <br />PROJECT MANAGER <br />M. TORRES <br />.......... ... I ...................................................... <br />ADVENT HEALTH <br />WELL 65+ <br />ZEPHYRHILLS <br />22-0328-01 <br />9. EXISTING BRANCH CIRCUITS HAVE BEEN TAKEN <br />FROM FIELD INVESTIGATION AND/OR ORIGINAL <br />DOCUMENTS AND SHOWN FOR THE CONVENIENCE OF <br />THE ELECTRICAL CONTRACTOR AND SHALL NOT BE <br />34"' C; OF OUITLE7 BOX <br />CONSULTING <br />ELECTRICAL <br />CONSIDERED "AS -BUILT" CONDITION. BEFORE <br />F <br />ENGINEERS <br />CONSTRUCTION BEGINS, ELECTRICAL CONTRACTOR <br />SINCE 1977 <br />RENOVATION PLANS <br />SHALL FIELD VERIFY ALL BRANCH CIRCUITS. <br />CONFIGURATION 11 <br />FL REG NO. 308 <br />91 <br />10. CONTRACTOR SHALL INCLUDE COMMISSIONING OF <br />LCD BOX LOCATION <br />LIGHTING CONTROL SYSTEM BY MANUFACTURER IN <br />2016 ALDEN RD. <br />BASE BID. <br />ORLANDO, FL <br />32803 <br />11. VERIFY CEILING TYPES BEFORE ORDERING LIGHT <br />WEU.W=88 <br />StM <br />J—WX <br />LOCARM <br />(407) 246-1688 <br />FIXTURES. <br />SCALF-- WW <br />WWW.PEIFLA.COM <br />Ell <br />NOTE: <br />'A' <br />PEI PROJECT t. <br />CONFIGURATION REFERS TO Kl��D NOTE <br />22121 <br />CONFIGURA11ON 'B' REFERS TO K&D NOTE <br />