Laserfiche WebLink
_ _ _ <br />1 or 2 Hour Fire Rated Through <br />G\a.ys i fi o <br />V <br />Penetration Firestop for Single <br />Metal Pipe through <br />sys 1 e� <br />Gypsum Walls using <br />FYRE-SHIELD. <br />W L 1097 <br />F-Rating = 1 and 2 Hr. <br />T-Rating = 0 11r. <br />D O <br />3735 Green Rd. <br />Beachwood, OH, 44122 <br />Drawing not to scale <br />ID Pre -Rated Gypsum Wallboard/Stud Wall Assembly <br />20 Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe. <br />B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe. <br />C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit. <br />D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing. <br />E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe. <br />The annular space shall be min. 1/4" to max. 5/8" within the firestop system. <br />0 FYRE-SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant <br />to be installed such that a min. 1/4" crown is formed around the <br />penetrating item. <br />Project: The Tremco produce used above have been The above described assembly has been <br />tested in accordance with the rollowing; <br />reared and is based on both pout and muci- <br />ASTM E514 (UL1479) Stmderd'rest Method <br />Location:for Through Penetration Fireutopping. petal perform criteria. Tremco shnnut <br />be liable for myy damages, direct or mn- <br />Installer. sequentinl, resulting from use of this material <br />Date: 4/23/97 Drawing: 'r W-1097 or design. Tremm aha11 only be responsible <br />for replacing material found to be defective. <br />Signature: Approved by: J. Pitcole <br />2 Ilour Fire Rated Through <br />sip �� <br />Penetration Firestop for Single ° lJUL �lJ <br />Metal Pipe through Concrete 3735 Green Rd. <br />® Floors or Block Walls using Beachwood, OH, 44122 <br />system TRLMstop Acrylic. <br />C A J 1205 F-Rating = 2 Hr. Drawing not to scale <br />T-Rating = 0 Hr. <br />L-Rating at Ambient - Less Than I CFM/sq. ft. <br />L-Rating at 400 F - Less Than I CFM/sq. ft. <br />DI Pre -Rated Concrete Floors or Block Walls = Min. 4-1/2" thickness. <br />The annular space range shall be min. 0" to max. 7/8" for this firestop system. <br />20 Metallic Pipe: > Steel Pipe - 12" diam. (or smaller) sch. 40 (or heavier) steel <br />> Conduit - Nom. 4" diam. (or smaller) steel conduit, or EMT. <br />> Copper Pipe - 3" diam. (or smaller) Regular (or heavier) copper. <br />> Cast Iron Pipe - 12" diam. (or smaller) cast or ductile iron. <br />> Copper Tubing - 3" diam. (or smaller) Type L (or heavier) copper. <br />0 Packing Material -Min. 4" thickness of mineral wool (min. 4.0 per) insulation, <br />firmly packed into opening as a permanent form. <br />TREMstop Acrylic - Min. 1/2" sealant applied within annulus, and a minimum 1/4" <br />sealant applied at point contact, at the floor surface for floors, <br />or both surfaces for walls. <br />Project: The Tremco products used above have been Mesh- deaeribed maanbly has been <br />tested to accordance with the following; tested and is based - both past and mlid- <br />I.ocatlon: • ASTM ES 14 (T)Ll479) Standard Test Method paled performence criteria. T-o shall not <br />for Through Penetration Firestopping. be liable for my deranges, direct or con - <br />Installer: ecqucntial, vaulting from use of this nwtcriel <br />-1205 or design. Tremor shall only be respomiblc <br />Date: 1/15A17 Drawing: TR <br />for rcplacing material fund to be defective. <br />Signature: Approved by: J. Pitcole <br />FIRE STOPPING DETAILS <br />SCALE: N.T.S. <br />FIRE ALARM SYSTEM NOTES <br />1. THE EXTENT OF THE FIRE ALARM SYSTEM WORK IS INDICATED BY THE DRAWINGS AND <br />SCHEDULES. <br />2. THE FIRE ALARM RISER IS A DIAGRAMMATIC GUIDE FOR THE INSTALLATION OF THE FIRE ALARM <br />EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE <br />OPERATING SYSTEM. <br />3. ALL FIRE ALARM SYSTEM COMPONENTS SHALL BE UL LISTED AND LABELED. <br />4. SIGNALING CIRCUITS SHALL BE POWER LIMITED PER NEC 760-11. <br />5. CABLE PENETRATION INTO OR THROUGH PLENUM AREAS USED FOR TRANSFER OF <br />ENVIRONMENTAL AIR SHALL BE TEFLON INSULATED TYPE OR OF AN APPROVED TYPE IN ACCORDANCE <br />WITS SECTION 800-3(D) OF THE NATIONAL ELECTRIC CODE. <br />6. ALL WIRING MUST CONFORM WITH NEC ARTICLE 760 AND LOCAL CODES. ALL EQUIPMENT SHALL <br />BE UL LISTED. <br />7. ALL INSTALLATION MATERIAL SUCH AS CONDUIT FITTINGS, BOXES, SUPPORTS, HANDERS, ETC. <br />ARE TO BE PROVIDED AND INCLUDED. <br />8. ALL INITIATING AND INDICATING CIRCUITS MUST BE SUPERVISED. <br />9. CIRCUIT POLARITY MUST BE OBSERVED. <br />10. WIRE RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF ALL EQUIPMENT TO BE <br />DETERMINED IN THE FIELD, BUT SHALL CONFORM WITH THE BASIC LAYOUT AS SHOWN ON DRAWINGS <br />TO PREVENT CIRCUIT OVERLOAD. <br />11. SMOKE DETECTORS SHALL NOT BE LOCATED IN DIRECT AIR STREAM FROM SUPPLY AIR <br />OUTLETS. MAINTAIN A MINIMUM CLEAR DISTANCE OF 36". OFFSET/ADJUST LOCATIONS AS REQUIRED. <br />12. MINIMUM CONDUIT SIZE WILL BE 3/4" UNLESS NOTED OTHERWISE CONDUIT SHALL BE NO <br />MORE THAN 40% FILLED. <br />13. DO NOT MARK ID NUMBERS ON DEVICES. LABEL BASE ONLY. <br />14. POWER UP & POWER DOWN ON PANEL MUST BE DONE IN PROPER SEQUENCE. <br />POWER DOWN <br />A - DISCONNECT BATTERY. <br />B - TURN OFF AC POWER PRIMARY & SECONDARY. <br />POWER UP <br />A - TURN ON AC POWER PRIMARY & SECONDARY. <br />B - RECONNECT BATTERIES. <br />15. AHU SHUTDOWN IS BY THE RELAYS LOCATED IN THE DUCT DETECTORS. THIS MUST BE USED <br />IN THE NORMALLY CLOSED POSITION SO THAT A LOSS OF CONTINUITY BETWEEN THE RELAY CONTACT <br />AND THE UNIT WILL CAUSE AHU SHUTDOWN. RELAY CONTACTS ARE RATED AT 2 AMPS 120 VAC, <br />24 VDC. UNDER NO CIRCUMSTANCES COULD THIS BE EXCEEDED. FAN SHUTDOWN RELAYS MUST BE <br />LOCATED WITHIN 3' OF STARTER COIL PER NFPA 72. <br />16. PROVIDE DETAILED INSTALLATION SHOP DRAWINGS SHOWING NEW EQUIPMENT, DEVICE <br />LOCATIONS AND CONNECTION WIRING NECESSARY FOR THE NEW SYSTEM EXPANSION. <br />17. ELECTRICAL CONTRACTOR MUST SET ADDRESSES FOR ADDRESSABLE DEVICES PRIOR TO <br />INSTALLING THE DEVICE. <br />18. DAMPER MOTOR AND FAN SHUTDOWN CONNECTIONS ARE TO BE COORDINATED IN FIELD <br />WITH HVAC CONTRACTOR. <br />19. STROBES ARE TO BE WALL MOUNTED PER ADA REQUIREMENTS. EXACT LOCATION OF <br />THESE DEVICES TO BE DETERMINED IN FIELD. MOUNT STROBES 80" AFF TO TOP OF LENS, OR <br />6" BELOW CEILING TO TOP OF LENS, WHICHEVER IS LOWER. <br />20. MANUAL PULL STATIONS SHALL BE MOUNTED SO THAT THE OPERATING LEVER IS <br />BETWEEN 42" AND 48" ABOVE THE FINISHED FLOOR <br />21. FIRE ALARM TERMINAL CABINET MUST BE CONNECTED TO THE SYSTEM GROUND OR <br />COLD -WATER GROUND VIA 1 GREEN #10 THHN OR EQUIVALENT. <br />22. ANY SURFACE MOUNTED FIRE ALARM DEVICES, i.e., PULL STATION, STROBES, <br />SPEAKER/STROBE SHALL BE MOUNTED IN "SYSTEMS" BOXES PROVIDED BY THE MANUFACTURER <br />DO NOT USE 1900 TYPE ELECTRICAL BOXES PAINTED RED. <br />23. PROVIDE AND INSTALL ALL DEVICES AS INDICATED IN THE FLOOR PLANS AND/OR RISER <br />DIAGRAM AND/OR SPECIFICATIONS AND/OR ELEVATOR RECALL DETAIL, <br />24. THE BOTTOM OF THE VISIBLE APPLIANCE SHALL NOT BE LESS THAN 80" ABOVE THE <br />FINISHED FLOOR. <br />25. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY UNAUTHORIZED <br />EXTERNAL DEVICE. FIRE ALARM SYSTEM SHOWN IN THIS SET OF DOCUMENTS IS FOR DESIGN <br />INTENT ONLY, <br />26. ELECTRICAL CONTRACTOR IS FULLY RESPONSIBLE TO PROVIDE INSTALLATION DRAWINGS, <br />ALONG WITH SHOP DRAWINGS, SHOWING ACTUAL LOCATION OF DEVICES, DEVICE NUMBERS, <br />BATTERY CALCULATIONS, INSTALLATION RISER DIAGRAMS, AND ANY OTHER DOCUMENTATION <br />NEEDED AND REQUESTED BY THE FIRE DEPARTMENT. <br />27. IN CASE INSTALLATION DRAWINGS NEED TO BE SIGNED & SEALED BY A PROFESSIONAL <br />LICENSED ENGINEER, SUCH ENGINEER MUST BE HIRED SEPARATELY BY THE CONTRACTOR, AT <br />ITS OWN COST TO PERFORM SUCH TASK. <br />28. THESE DRAWINGS ARE ACCEPTED BY THE FIRE DEPARTMENT AS A CONCEPTUAL DESIGN <br />ONLY. FIRE ALARM CONTRACTOR'S WORKNG PLANS AS PER F.S.S.633.70(4) MUST BE <br />SUBMITTED TO AND APPROVED BY THE LOCAL FIRE DEPARTMENT BEFORE ANY FIRE ALARM <br />SYSTEM IS INSTALLED OR REMODELED. <br />ALL WORK SHALL COMPLY WITH ALL <br />PREVAILING (,ODES, FLORID,A BUILDING <br />CODE, NATIONAL ELECTRIC CODE AND <br />CITY OF ZEPHY 1-111 LS ORDINANCES <br />REVIEW 1).4TT. <br />CITY OF ZEPtl1, <br />StALMING OFF] <br />A/C SUPPLY <br />DIFFUSER <br />CEILING MOUNTED <br />SMOKE/HEAT �3' (MIN) <br />DETECTOR <br />SYNCHRONIZE MORE THAIS <br />TWO APPLIANCES IN ANY <br />FIELD OF VIEW, SPACED A <br />MINIMUM OF 55' FROM EACH <br />OTHER IN ROOMS 80' x 80' <br />OR GREATER. <br />NFPA 72 2002 EDITION <br />(SECTION 7.5.4.4.2(3)) <br />80" AFF <br />OR 6" BELOW CEILING <br />(WHICHEVER IS LOWER <br />TO BOTTOM OF VISUAL) <br />FINISHED <br />FLOOR <br />AUDIO/VISUAL <br />& VISUAL -ONLY <br />DEVICES <br />MANUAL <br />PULL <br />STATION <br />FIRE <br />PHONE <br />JACK o <br />48" AFF <br />TO HANDLE <br />5' MAX <br />NOTE: MEASUREMENTS <br />SHOWN ARE TTHE <br />CLOSEST OF THE <br />E <br />DETECTOR. <br />ACCEPTED HERE -' <br />12" (MAX) <br />NEVER <br />HERE <br />WALL MOUNTED <br />SMOKE/HEAT <br />DETECTOR <br />SIDE WALL <br />FINISHED <br />WALL <br />FIRE ALARM TYPICAL DEVICE MOUNTING LOCATIONS <br />FIRE ALARM SYSTEM LEGEND <br />SYMBOL <br />DESCRIPTION <br />MOUNTING <br />REMARKS <br />OPHOTOELEC <br />D <br />TYPE <br />CEILING <br />SMOKE DETECTOR <br />SS <br />DUCT SMOKE <br />CEILING <br />PROVIDE ON ALL SUPPLY <br />R �J <br />DETECTOR <br />AND RETURN AIR DUCTS <br />* <br />SL <br />STROBE LIGHT <br />WALL <br />MINIMUM 75 CANDELA PER FACBC <br />TRANSPARENT PROTECTIVE COVER <br />MANUAL PULL <br />PROVIDE WITH PLEXIGLASS <br />F <br />STATION <br />WALL <br />COVER. "STOPPER III" <br />W/ VISUAL <br />MINIMUM 75 CANDELA PER FACBC <br />U <br />AHORN LARM <br />WALL <br />TRANSPARENT PROTECTIVE COVER <br />FAP <br />FIRE ALARM <br />WALL <br />PANEL <br />WIRE LEGEND: <br />DESCRIPTION <br />2 <br />CONDUCTOR <br />#18 <br />AWG <br />TWISTED PAIR <br />2 <br />CONDUCTOR <br />#14 <br />AWG <br />FPL <br />2 <br />CONDUCTOR <br />#14 <br />AWG <br />FPL <br />2 <br />CONDUCTOR <br />#14 <br />AWG <br />FPL <br />2 <br />CONDUCTOR <br />#18 <br />AWG <br />FPL <br />2 <br />CONDUCTOR <br />#18 <br />AWG <br />FPL <br />2 <br />CONDUCTOR <br />#16 <br />AWG <br />TWISTED/SHIELDED FPL PAIR <br />T <br />T <br />T <br />T <br />L L U (2) U <br />BACKDOOR REC JAN STO STO <br />1001 F115 l08 102A <br />DUCT DUCT DUCT DUCT <br />COORDINATE WITH MECHANICAL DRAWINGS FOR <br />FIRE ALARM CONNECTIONS TO ALL AIR <br />HANDLING UNITS' SHUTDOWNg UP,N FIRE <br />CONDITIONS. PROVIDE ALL REQUIRED RELAYS, <br />JUNCTON BOXES CONTROL WIRING, ETC., FOR S L S L S L S L S L <br />A FULLY FUNCTIONAL SYSTEM. _ <br />BREAK OPEN TOILET TOILET TOILET <br />116 1 FT-" I FT14 113 112 <br />3/4"C <br />TYPICAL <br />REQUIRED USE <br />CONNECTION TO ADDRESSABLE DEVICES <br />CONNECTION TO HORN CIRCUIT <br />CONNECTION TO STROBE CIRCUITS <br />UNSWITCHED 24V DC POWER <br />SWITCHED 24V DC POWER <br />MONITOR MODULES <br />NETWORK CONNECTION DEVICES <br />VENDOR IT I- TRAINING J CORRIDOR <br />110 1 F 109 102 <br />S L S L [II] DLL° �I S i� S L <br />L- TRAINING -� I CORRIDOR '� RECEPTION <br />102 100 <br />#10 TO ELEC BUILDING <br />GROUND <br />FIRE ALARM RISER DIAGRAM <br />1 NTS <br />SEE FLOOR PLANS FOR EXACT QUANTITY AND <br />LOCATION OF DEVICES <br />RECEPTION DESK <br />NEW FIRE I "EXISTING <br />ALARM FIRELITE" <br />TERMINAL FIRE ALARM <br />CABINET I PANEL <br />FIRE <br />COMMAND <br />ROOM <br />VENDOR IT ROOM <br />L_---_J <br />EXPAND EXISTING "FIRELITE" MS9050UD FIRE ALARM <br />PANEL TO ACCOMMODATE NEW DEVICES UNDER THIS <br />PROJECT. PROVIDE ALL REQUIRED NAC PANELS AND <br />POWER SUPPLIES AS NEEDED FOR CONTINUOUS <br />SERVICE. <br />CONTACT "AFA PROTECTIVE SYSTEMS, INC" <br />877-AFA-1873 CURRENTLY SERVING THIS SYSTEM FOR <br />ANY ADDITIONAL INFORMATION NEEDED. <br />� L7MANA� <br />Project <br />HUMANA- ZEPHYRHILLS, <br />FLORIDA - GUIDANCE <br />CENTER <br />7920 GALL BLVD. <br />ZEPHYRHILLS, FLORIDA 33541 <br />Prepared for <br />HUMANA INC. <br />Contract No: 12.01622.00 <br />HOK <br />One Tampa City Center, Suite 1800 <br />Tampa, FL 33602 USA <br />t +1 813 229 0300 f +1 813 223 7116 <br />FL Reg: AAC001139 <br />All reproduction & intellectual property rights reserved ® 2012 <br />In Association with <br />Alm <br />SDM Consulting Engineers <br />MEP Engineer <br />135 Almeria Ave. <br />Coral Gables, FL 33134 <br />305.446.2788 <br />www.sdmcorp.com <br />Key Plan <br />C' <br />Professional Seal. <br />I JtJ�� <br />ERNESTO ALOMA <br />P.E. 53823 <br />JOSE I. MARTINEZ <br />P.E. 53779 <br />No. <br />Issue Description <br />YYYY-MM-DD <br />01 <br />50% CONSTRUCTION DOCUMENTS 06.15.2012 <br />02 <br />BID SET <br />06.29.2012 <br />03 <br />ISSUE FOR PERMIT <br />07.27.2012 <br />No. <br />Revision Description <br />YYYY-MM-DD <br />1 <br />ADDENDUM 1 <br />2012-07-09 <br />2 <br />ADDENDUM 2 <br />2012-07-19 <br />Drawn by SDM Reviewed by SDM <br />Project No 12.01622.00 <br />Sheet Title: <br />FIRE ALARM <br />RISER DIAGRAM <br />Original drawing is 36 x 24 Do not scale contents of this drawing <br />Sheet Number <br />E501 <br />