<br />1 or 2 Hour Fire Rated Through
<br />Penetration Firestop for Single
<br />Metal Pipe through
<br />Gypsum Walls using
<br />FYRE-SHIELD.
<br />wL 1 097
<br />F-Rating = 1 and 2 Hr.
<br />T-Rating = 0 1Ir.
<br />O Q
<br />e.
<br />3735 Green Rd.
<br />Beachwood, Of 1, 44122
<br />Drawing not to scale
<br />1Q Pre -Rated Gypsum Wallboard/Stud Wall Assembly
<br />Q2 Metallic Pipe - A) Steel Pipe - 8" diam. (or smaller) Sch. 40 (or heavier) steel pipe.
<br />B) Iron Pipe - 8" diam. (or smaller) cast or ductile iron pipe.
<br />C) Conduit - 4" diam. (or smaller) EMT or rigid steel conduit.
<br />D) Copper Tubing - 4" diam. (or smaller) Type L (or heavier) copper tubing.
<br />E) Copper Pipe - 4" diam. (or smaller) Regular (or heavier) copper pipe.
<br />The annular space shall be min. 1/4" to max. 5/8" within the firestop system.
<br />30 F•YRF,-SHIELD - Min. 1/2" thickness of sealant applied within opening. Additional sealant
<br />to be installed such that a min. 1/4" crown is formed around the
<br />penetrating item.
<br />Pro eet: The Tremor p odabove have used abhave been
<br />J reared in accordance witb the following; The above described assembly ttbeen
<br />ASTVt E914 (tJL1479) standard Teat Method pealed and is based un both past anand lei-
<br />I.00atlOn; paled parfortnance criteria. Tremor shall sh all not
<br />for Through Peaevatius Firestopping,
<br />be liable for any damages, director con -
<br />Installer: sequential, nnsulting from me of thin material
<br />Date: 4/23/97 Drawing: TW-1097 or design. Tremco shall only be responsible
<br />Signature: for replacing material found to be defective.
<br />Sri Approved by: J. Pitcole
<br />2 Hour Fire Rated Through tiij rJ�ass l r,"a Penetration Firestop for Single ° 0
<br />Metal Pipe through Concrete 3735 Green Rd.
<br />® Floors or Block Walls using Beachwood, OH, 44122
<br />`P t eo TREMstop Acrylic.
<br />C A J 1205 F-Rating - 2 Hr. Drawing not to scale
<br />T-Rating = 0 Hr.
<br />L-Rating at Ambient - Less Than I CFM/sq. ft.
<br />L-Rating at 400 F - Less Than 1 CFM/sq. ft.
<br />10 Pre -Rated Concrete Floors or Block Walls = Min. 4-1/2" thickness.
<br />The annular space range shall be min. 0" to max. 7/8" for this Firestop system.
<br />20 Metallic Pipe: > Steel Pipe - 12" diam. (or smaller) sch. 40 (or heavier) steel
<br />> Conduit - Nom. 4" diam. (or smaller) steel conduit, or EMT.
<br />> Copper Pipe - 3" diam. (or smaller) Regular (or heavier) copper.
<br />> Cast Iron Pipe - 12" diam. (or smaller) cast or ductile iron.
<br />> Copper Tubing - 3" diam. (or smaller) Type L (or heavier) copper.
<br />0 Packing Material -Min. 4" thickness of mineral wool (min. 4.0 pcO insulation,
<br />firmly packed into opening as a permanent form.
<br />® TREMstop Acrylic -Min. 1 /2" sealant applied within annulus, and a minimum 1/4"
<br />sealant applied at point contact; at the floor surface for floors,
<br />or both surfaces for walls.
<br />Project: The Tretm:o products uxed above have been The above described assembly has been
<br />tested in accordance with the roaowmg; tested and is based on both past and antici-
<br />T.ocation: • ASTM ES 14 (UL 1479) standard Test Method pated performance criteria. Tremw shall not
<br />for Through Peneuation Firtrempping. be liable for my damages, direct or con -
<br />Installer: sotluental, resulting from use of this malorial
<br />Date: 1 /15/97 1 Drawing: TR-1205 or desiym. Inmeo shall only beresponsible
<br />Signature: for replacing rnatcrtal found to be defective.
<br />Approved by: 1 Pitcole
<br />FIRE STOPPING DETAILS
<br />SCALE: N.T.S.
<br />FIRE ALARM SYSTEM NOTES
<br />1. THE EXTENT OF THE FIRE ALARM SYSTEM WORK IS INDICATED BY THE DRAWINGS AND
<br />SCHEDULES.
<br />2. THE FIRE ALARM RISER IS A DIAGRAMMATIC GUIDE FOR THE INSTALLATION OF THE FIRE ALARM
<br />EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A COMPLETE
<br />OPERATING SYSTEM.
<br />3. ALL FIRE ALARM SYSTEM COMPONENTS SHALL BE UL LISTED AND LABELED.
<br />4. SIGNALING CIRCUITS SHALL BE POWER LIMITED PER NEC 760-11.
<br />5. CABLE PENETRATION INTO OR THROUGH PLENUM AREAS USED FOR TRANSFER OF
<br />ENVIRONMENTAL AIR SHALL BE TEFLON INSULATED TYPE OR OF AN APPROVED TYPE IN ACCORDANCE
<br />WITS SECTION 800-3(D) OF THE NATIONAL ELECTRIC CODE.
<br />6. ALL WIRING MUST CONFORM WITH NEC ARTICLE 760 AND LOCAL CODES. ALL EQUIPMENT SHALL
<br />BE UL LISTED.
<br />7. ALL INSTALLATION MATERIAL SUCH AS CONDUIT FITTINGS, BOXES, SUPPORTS, HANDERS, ETC.
<br />ARE TO BE PROVIDED AND INCLUDED.
<br />8. ALL INITIATING AND INDICATING CIRCUITS MUST BE SUPERVISED.
<br />9. CIRCUIT POLARITY MUST BE OBSERVED.
<br />10. WIRE RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF ALL EQUIPMENT TO BE
<br />DETERMINED IN THE FIELD, BUT SHALL CONFORM WITH THE BASIC LAYOUT AS SHOWN ON DRAWINGS
<br />TO PREVENT CIRCUIT OVERLOAD.
<br />11. SMOKE DETECTORS SHALL NOT BE LOCATED IN DIRECT AIR STREAM FROM SUPPLY AIR
<br />OUTLETS. MAINTAIN A MINIMUM CLEAR DISTANCE OF 36". OFFSET/ADJUST LOCATIONS AS REQUIRED.
<br />12. MINIMUM CONDUIT SIZE WILL BE 3/4" UNLESS NOTED OTHERWISE CONDUIT SHALL BE NO
<br />MORE THAN 40% FILLED.
<br />13. DO NOT MARK ID NUMBERS ON DEVICES. LABEL BASE ONLY.
<br />14. POWER UP & POWER DOWN ON PANEL MUST BE DONE IN PROPER SEQUENCE.
<br />POWER DOWN
<br />A - DISCONNECT BATTERY.
<br />B - TURN OFF AC POWER PRIMARY & SECONDARY.
<br />POWER UP
<br />A - TURN ON AC POWER PRIMARY & SECONDARY.
<br />B - RECONNECT BATTERIES.
<br />15. AHU SHUTDOWN IS BY THE RELAYS LOCATED IN THE DUCT DETECTORS. THIS MUST BE USED
<br />IN THE NORMALLY CLOSED POSITION SO THAT A LOSS OF CONTINUITY BETWEEN THE RELAY CONTACT
<br />AND THE UNIT WILL CAUSE AHU SHUTDOWN. RELAY CONTACTS ARE RATED AT 2 AMPS 120 VAC,
<br />24 VDC. UNDER NO CIRCUMSTANCES COULD THIS BE EXCEEDED. FAN SHUTDOWN RELAYS MUST BE
<br />LOCATED WITHIN 3' OF STARTER COIL PER NFPA 72.
<br />16. PROVIDE DETAILED INSTALLATION SHOP DRAWINGS SHOWING NEW EQUIPMENT, DEVICE
<br />LOCATIONS AND CONNECTION WIRING NECESSARY FOR THE NEW SYSTEM EXPANSION.
<br />17. ELECTRICAL CONTRACTOR MUST SET ADDRESSES FOR ADDRESSABLE DEVICES PRIOR TO
<br />INSTALLING THE DEVICE.
<br />18. DAMPER MOTOR AND FAN SHUTDOWN CONNECTIONS ARE TO BE COORDINATED IN FIELD
<br />WITH HVAC CONTRACTOR.
<br />19. STROBES ARE TO BE WALL MOUNTED PER ADA REQUIREMENTS. EXACT LOCATION OF
<br />THESE DEVICES TO BE DETERMINED IN FIELD. MOUNT STROBES 80" AFF TO TOP OF LENS, OR
<br />6" BELOW CEILING TO TOP OF LENS, WHICHEVER IS LOWER.
<br />20. MANUAL PULL STATIONS SHALL BE MOUNTED SO THAT THE OPERATING LEVER IS
<br />BETWEEN 42" AND 48" ABOVE THE FINISHED FLOOR
<br />21. FIRE ALARM TERMINAL CABINET MUST BE CONNECTED TO THE SYSTEM GROUND OR
<br />COLD -WATER GROUND VIA 1 GREEN #10 THHN OR EQUIVALENT.
<br />22. ANY SURFACE MOUNTED FIRE ALARM DEVICES, i.e., PULL STATION, STROBES,
<br />SPEAKER/STROBE SHALL BE MOUNTED IN "SYSTEMS" BOXES PROVIDED BY THE MANUFACTURER
<br />DO NOT USE 1900 TYPE ELECTRICAL BOXES PAINTED RED.
<br />23. PROVIDE AND INSTALL ALL DEVICES AS INDICATED IN THE FLOOR PLANS AND/OR RISER
<br />DIAGRAM AND/OR SPECIFICATIONS AND/OR ELEVATOR RECALL DETAIL.
<br />24. THE BOTTOM OF THE VISIBLE APPLIANCE SHALL NOT BE LESS THAN 80" ABOVE THE
<br />FINISHED FLOOR.
<br />25. THE FIRE ALARM CONTROL PANEL SHALL NOT BE USED TO POWER ANY UNAUTHORIZED
<br />EXTERNAL DEVICE. FIRE ALARM SYSTEM SHOWN IN THIS SET OF DOCUMENTS IS FOR DESIGN
<br />INTENT ONLY.
<br />26. ELECTRICAL CONTRACTOR IS FULLY RESPONSIBLE TO PROVIDE INSTALLATION DRAWINGS,
<br />ALONG WITH SHOP DRAWINGS, SHOWING ACTUAL LOCATION OF DEVICES, DEVICE NUMBERS,
<br />BATTERY CALCULATIONS, INSTALLATION RISER DIAGRAMS, AND ANY OTHER DOCUMENTATION
<br />NEEDED AND REQUESTED BY THE FIRE DEPARTMENT.
<br />27. IN CASE INSTALLATION DRAWINGS NEED TO BE SIGNED & SEALED BY A PROFESSIONAL
<br />LICENSED ENGINEER, SUCH ENGINEER MUST BE HIRED SEPARATELY BY THE CONTRACTOR, AT
<br />ITS OWN COST TO PERFORM SUCH TASK.
<br />28. THESE DRAWINGS ARE ACCEPTED BY THE FIRE DEPARTMENT AS A CONCEPTUAL DESIGN
<br />ONLY. FIRE ALARM CONTRACTOR'S WORKNG PLANS AS PER F.S.S.633.70(4) MUST BE
<br />SUBMITTED TO AND APPROVED BY THE LOCAL FIRE DEPARTMENT BEFORE ANY FIRE ALARM
<br />SYSTEM IS INSTALLED OR REMODELED.
<br />REVIEW! [)ATE:
<br />CITY OF ZEPH)
<br />9I IILIANG OFF
<br />ALL WOR1:IIALICO\IPtL�' �1 L'l l i ALL
<br />mNk
<br />p�I�,VAII-INC, CODI�.S. I:CTRI CODI" AND
<br />CODE.NATIONAi LJ.
<br />CIT1r C?F ZEI'IIYRIIII_L � OP.DINANCI�.S
<br />DUCT DUCT DUCT DUCT
<br />COORDINATE WITH MECHANICAL DRAWINGS FOR
<br />FIRE ALARM CONNECTIONS TO ALL AIR
<br />HANDLING UNITS' SHUTDOWNS UPON FIRE
<br />JUONCDTONNBOXESROCONTROL WIIRING EETC., FOd
<br />A FULLY FUNCTIONAL SYSTEM.
<br />A/C SUPPLY
<br />DIFFUSER
<br />CEILING MOUNTED
<br />SMOKE/HEAT �3' (MIN)
<br />DETECTOR
<br />AUDIO/VISUAL
<br />•
<br />& VISUAL -ONLY
<br />DEVICES
<br />SYNCHRONIZE MORE THA
<br />TWO APPLIANCES IN ANY
<br />FIELD OF VIEW, SPACED A
<br />MINIMUM OF 55' FROM EACH
<br />OTHER IN ROOMS 80' x 80'
<br />OR GREATER.
<br />NFPA 72 2002 EDITION
<br />(SECTION 7.5.4.4.2(3))
<br />80" AFF
<br />OR 6" BELOW CEILING
<br />MANUAL
<br />(WHICHEVER IS LOWER
<br />PULL
<br />TO BOTTOM OF VISUAL)
<br />STATION
<br />FIRE
<br />PHONE
<br />JACK o
<br />FINISHED
<br />FLOOR
<br />5' MAX
<br />48" AFF
<br />TO HANDLE
<br />NOTE: MEASUREMENTS
<br />-4"
<br />SHOWN ARE TO THE
<br />CLOSEST OF THE
<br />EILING
<br />DETECTOR.
<br />ACCEPTED HERE
<br />12" (MAX)
<br />IVER
<br />SME/HEAT
<br />DETECTOR
<br />____1
<br />SIDE WALL
<br />FINISHED
<br />WALL
<br />FIRE ALARM TYPICAL DEVICE MOUNTING LOCATIONS
<br />FIRE ALARM SYSTEM LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />REMARKS
<br />OPHOTOELEC
<br />D
<br />TYPE
<br />CEILING
<br />SMOKE DETECTOR
<br />S
<br />DUCT SMOKE
<br />CEILING
<br />PROVIDE ON ALL SUPPLY
<br />R
<br />DETECTOR
<br />AND RETURN AIR DUCTS
<br />*
<br />SL
<br />STROBE LIGHT
<br />WALL
<br />MINIMUM 75 CANDELA PER FACBC
<br />TRANSPARENT PROTECTIVE COVER
<br />MANUAL PULL
<br />PROVIDE WITH PLEXIGLASS
<br />F
<br />STATION
<br />WALL
<br />COVER. "STOPPER III"
<br />W/ VISUAL
<br />75 CANDELA PER FACBC
<br />H I
<br />AHORN LARM
<br />WALL
<br />TRANSPARENT
<br />TRANSPARENT PROTECTIVE COVER
<br />FAP
<br />FIRE ALARM
<br />WALL
<br />PANEL
<br />WIRE LEGEND:
<br />DESCRIPTION
<br />2
<br />CONDUCTOR
<br />#18
<br />AWG
<br />TWISTED PAIR
<br />2
<br />CONDUCTOR
<br />#14
<br />AWG
<br />FPL
<br />2
<br />CONDUCTOR
<br />#14
<br />AWG
<br />FPL
<br />2
<br />CONDUCTOR
<br />#14
<br />AWG
<br />FPL
<br />2
<br />CONDUCTOR
<br />#18
<br />AWG
<br />FPL
<br />2
<br />CONDUCTOR
<br />#18
<br />AWG
<br />FPL
<br />2
<br />CONDUCTOR
<br />#16
<br />AWG
<br />TWISTED/SHIELDED FPL PAIR
<br />3/4"C
<br />TYPICAL
<br />REQUIRED USE
<br />CONNECTION TO ADDRESSABLE DEVICES
<br />CONNECTION TO HORN CIRCUIT
<br />CONNECTION TO STROBE CIRCUITS
<br />UNSWITCHED 24V DC POWER
<br />SWITCHED 24V DC POWER
<br />MONITOR MODULES
<br />NETWORK CONNECTION DEVICES
<br />u u U U U U U U U U U U U
<br />BACKDOOR REC JAN STO STO VENDOR IT TRAINING CORRIDOR
<br />Fl-00-1 FTF51i08 102A 110 109 102
<br />SL
<br />SL
<br />ISLI
<br />ISL I
<br />ISL
<br />BREAK
<br />116
<br />OPEN
<br />11 1-1
<br />TOILET
<br />114
<br />TOILET
<br />FF3
<br />TOILET
<br />112
<br />s L I s L s >L�la DLZ s L
<br />1- TRAINING I CORRIDOR -J RECEPTION
<br />102 F100
<br />#10 TO ELEC BUILDING
<br />GROUND
<br />FIRE ALARM RISER DIAGRAM
<br />NTS
<br />SEE FLOOR PLANS FOR EXACT QUANTITY AND
<br />LOCATION OF DEVICES
<br />RECEPTION DESK
<br />AN NI
<br />NEW FIRE I "EXISTING
<br />ALARM FIRELITE"
<br />TERMINAL I FIRE ALARM
<br />CABINET I PANEL
<br />FIRE
<br />COMMAND
<br />ROOM
<br />I
<br />VENDOR IT ROOM I I
<br />L---__J
<br />EXPAND EXISTING "FIREUTE" MS905OUD FIRE ALARM
<br />PANEL TO ACCOMMODATE NEW DEVICES UNDER THIS
<br />PROJECT. PROVIDE ALL REQUIRED NAC PANELS AND
<br />POWER SUPPLIES AS NEEDED FOR CONTINUOUS
<br />SERVICE.
<br />CONTACT "AFA PROTECTIVE SYSTEMS, INC"
<br />877-AFA-1873 CURRENTLY SERVING THIS SYSTEM FOR
<br />ANY ADDITIONAL INFORMATION NEEDED.
<br />H`UMANA.
<br />Project
<br />HUMANA- ZEPHYRHILLS,
<br />FLORIDA - GUIDANCE
<br />CENTER
<br />7920 GALL BLVD.
<br />ZEPHYRHILLS, FLORIDA 33541
<br />Prepared for
<br />HUMANA INC.
<br />Contract No: 12.01622.00
<br />HOK
<br />One Tampa City Center, Suite 1800
<br />Tampa, FL 33602 USA
<br />t +1 813 229 0300 f +1 813 223 7116
<br />FL Reg: AAC001139
<br />All reproduction & intellectual property rights reserved Q 2012
<br />In Association with
<br />SDM Consulting Engineers
<br />MEP Engineer
<br />135 Almeria Ave.
<br />Coral Gables, FL 33134
<br />305.446.2788
<br />www.sdmcorp.com
<br />Key Plan
<br />C'
<br />Professional Seals
<br />ERNES TO ALOMA JOSE I. MARTINEZ
<br />P.E. 53823 P.E. 53779
<br />No. Issue Description YYYY-MM-DD
<br />01 50% CONSTRUCTION DOCUMENTS 06.15.2012
<br />02 BID SET 06.29.2012
<br />03 ISSUE FOR PERMIT 07.27.2012
<br />No. Revision Description YYYY-MM-DD
<br />1 ADDENDUM 1 2012-07-09
<br />2 ADDENDUM 2 2012-07-19
<br />Drawn by SDM Reviewed by SDM
<br />Project No 12.01622.00
<br />Sheet Title:
<br />FIRE ALARM
<br />RISER DIAGRAM
<br />Original drawing is 38 x 24 Do not scale contents of this drawing