ELECTRICAL SPECIFICATION:
<br />1, ALL WORK SHALL BE IN STRICT ACCORDANCE WITH THE LATEST EDITION OF N,E,C, AND
<br />ALL LOCAL CODES AND ORDINANCES,
<br />2, IT EEIS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION,
<br />COMPLETETELECTRI❑CALRSYSTEMI AND PROVIDE ALL NECESSARY INSTALL ALL
<br />COMPONENTS
<br />FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER,
<br />3, ALL MATERIALS SHALL BE NEW AND SHALL BEAR UNDERWRITERS'
<br />LABEL WHERE APPLICABLE,
<br />4, ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST-CLASS
<br />WORKMANLIKE MANNER THE COMPLETED SYSTEM IS TO BE FULLY OPERABLE AND ACCEPTABLE
<br />OF THIS SYSTEM BY THE OWNER MUST BE A CONDITION OF THE SUB CONTRACT,
<br />5, ALL WORK TO BE COORDINATED WITH OTHER TRADES TO AVOID INTERFERENCE WITH THE
<br />PROGESSS OF CONSTRUCTION,
<br />6, ELECTRICAL CONTRACTOR TO GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM
<br />DEFECTS FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR FROM DATE OF ACCEPTANCE,
<br />7, CORRECTION OF ANY DEFECTS TO BE COMPLETED WITHOUT ADDITIONAL CHARGE AND TO
<br />INCLUDE REPLACEMENT OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY
<br />HAVE BEEN DAMAGED THEREBY,
<br />8. ELECTRICAL CONTRACTOR TO PAY FOR ALL PERMITS, FEES, INSPECTION AND TESTING
<br />CONNECTED WITH HIS WORK,
<br />9, MINIMUM WIRE SIZE SHALL BE #12 AWG, EXCLUDING CONTROL WIRING UNLESS OTHERWISE NOTED
<br />SMALLERDMAYOBE SOE D BALLOTHOSEW#8HAND LARGER TOSBEASTRANDED, CONTRACTOSASHALL
<br />INCREASE CONDUIT SIZE BY ONE (1) FOR EVERY 75 FEET OF RUN AND SHALL BE RESPONSIBLE
<br />FOR INSTALLATION OF PROPER WIRE AND CONDUIT SIZE.
<br />10, ALL UNDERGROUND RACEWAYS SHALL BE GALVANIZED RIGID STEEL CONDUIT OR SCHEDULE
<br />40 PVC, ALL OTHER RACEWAYS TO COMPLY WITH GOVERNING CODES,
<br />11, OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALUMINUM WITH THREADED
<br />AREAS, ALLT BOXES SHALL BEI❑RECESSEDB (FLUSH) INI WALLS SOR UCEILING WHEONEVERC POSSIBLE,
<br />12, DISCONNECTS SWITCHES SHALL BE H,P, RATED, GENERAL DUTY, QUICK -MAKE, QUICK -BREAK TYPE,
<br />ENCLOSURES SHALL BE AS REQUIRED BY N,E,C, AND LOCATION (WEATHERPROOF,
<br />EXPLOS❑N PROOF, ETC,),
<br />13, ALL GENERAL PURPOSE SWITCHES AND RECEPTACLES SHALL BE THE PORDUCT OF A SINGLE
<br />REQUIRED UDEVICES COLOR OF
<br />FIXTURES
<br />ACOLOR RAND STYLE BE DICTATED BY OWNER ALL OTHER
<br />14, ALL RACEWAYS AND PIPES, SPACED IN OR THROUGH ANY CONCRETE SLAB, SHALL BE SPACED A
<br />MINIMUM OF THREE TIMES THE DIAMETER OF THE LARGEST RACEWAY,
<br />15, ALL ELECTRICAL RACEWAYS (METALLIC AND NON-METALLIC) AND CONDUITS SHALL HAVE AN
<br />EQUIPMENT GROUND CONDUCTOR SIZED IN ACCORDANCE WITH THE LATEST EDITION OF N,E,C,
<br />16, LOAD DATA IS BASED ON INFORMATION GIVEN ENGINER AT THE TIME OF DESIGN, VERIFY ALL
<br />EQUIPMENT NAMEPLATE RATINGS BEFORE ORDERING,
<br />17, CIRCUITS SHOWN ON PLANS ARE TO DETERMINE LOAD DATA AND PANEL SIZES, THE ELECTRICAL
<br />CONTRACTOR IS TO PR❑VIDE CIRCUITS AND ROUTING OF CONDUITS TO SUIT JOB CONDITIONS,
<br />18, FURNISH AND INSTALL DISCONNECT SWITCHES, WIRING, AND CONNECTION OF AIR CONDITIONING
<br />SYSTEM AS SHOWN ON PLANS, ELECTRICAL CONTRACTOR SHALL VERIFY AND C❑ORDINATE WITH
<br />MECHANICAL CONTRACTOR REGARDING SUPPLY AND INSTALLATION OF REQUIRED CONTROLS,
<br />19, ALL SWITCH GEAR SHALL BE THE PRODUCT OF A SINGLE MANUFACTURER SYSTEM DESIGN
<br />IS BASED ON WESTINGH❑USE/CHALLANGER, HOWEVER, COMPARABLE EQUIPMENT BY SQUARE 'D", GE,
<br />AND ITE WILL BE ACCEPTABLE, TANDEM AND HALF -SPACE CIRCUIT BREAKERS SHALL NOT BE USED,
<br />20, ALL UNDERGROUND PVC CONDUIT RUNS SHALL HAVE RIGID STEEL ELBOWS AND RIGID STEEL
<br />SECTIONS AT SLAB PENETRATIONS WHERE SUBJECT TO POSSIBLE DAMAGE, WHERE RIDIG STEEL IS
<br />USED IT SHALL BE COMPLETELY COATED WITH AN ALKAKI AND RUST -RESISTANT BITUMASTIC PAINT,
<br />KIPPER N❑,#50 AND THE THREADS SHALL BE COATED WITH ZINC CHROMATE,
<br />21, THE ELECTRICAL CONTRACTOR SHALL MEET AND COORDINATE WITH THE LOCAL POWER COMPANY AT
<br />RELATED WORKKRWITHCTHETUTILITY COMPANY'S RESN� S BIL CONTRACTOR
<br />ES TO ❑MEET THE OWNER'S SCHEDULE,
<br />22, ALL ELECTRICAL CONDUCTORS SHALL BE INSTALLED IN AN APPROVED RACEWAY MAXIMUM NUMBER
<br />OF 120 VOLT CIRCUITS ALLOWED IN A COMMON CONDUIT SHALL BE SIX (6), ELECTRICAL CONTRACTOR
<br />SHALL STRICTLY CONFORM TO THE N,E,C, REQUIREMENTS OF RATING FOR CONDUCTOR AMPACITY
<br />AND CONDUIT FILL,
<br />23, ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR SEALING ALL CONDUIT PENETRATIONS MADE
<br />THROUGH FIRE RATED WALLS, CEILING, SLABS, ETC,, PENETRATION SEALS SHALL BE PER U,L,
<br />ASSEMBLY STANDARDS,
<br />24, LOCAL POWER COMPANY SHALL PROVIDE ELECTRICAL SERVICE C❑NNECTI❑N AND VERIFICATION OF
<br />SAID SERVICE L❑CATION.
<br />25, IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY THE LOCATION OF THE
<br />TRANSFORMER PROVIDED BY THE LOCAL POWER COMPANY AND POINT OF SAID CONNECTION PRIOR
<br />TO SUBMITTING THEIR BID,
<br />26, SMOKE DETECTORS SHALL HAVE ELECTRICAL INTERLOCK PER SECTION 9052 F,B,C,, SO THAT IF ONE
<br />DETECTOR IS TRIGGERED ALL OTHER SMOKE DETECTORS ARE ACTIVATED,
<br />27, NO ELECTRICAL SHALL BE BACKED UP (IF APPICABLE) IN ANY FIREWALLS,
<br />DETECTOR IS TRIGGERED ALL OTHER SMOKE DETECTORS ARE ACTIVATED,
<br />28, ALL RECEPTACLES LOCATED IN BEDROOMS TO HAVE ARC FAULT CURRENT INTERRUPTERS,
<br />29, THE ELECTRICAL CONTRACTOR SHALL INSTALL BOTH THE ELECTRODE GROUNDING CONDUCTOR TO THE
<br />C❑ljD WATER PIPE AND THE ELECTRODE GROUND CONDUCTOR TO THE CONCRETE F❑❑TER PER NFPA
<br />70 ARTICLE 250-81C, AND ALL LOCAL CODES AND REGULATIONS.
<br />30, CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS:
<br />NEUTRAL - WHITE ABC TOP PHASE A - BLACK LEF`f TO RIGHT, FRONT
<br />GR❑UNDBC❑NREDGREEN TO BACK
<br />31, THE OWNER RESERVESTHERIGHT TO DRAW
<br />THE DRAWINGS FROM TIMETOTTO TIME( TO INDICATE
<br />H �N%
<br />IfflEkI SER E ,qI R�VA G�ST p, CSU AL LRNNYH L RN G AV RAW N I VE A AD TI� ❑ DEDUC I N❑ FIC
<br />AMOUNT OF MONEY TO THE CONTRACT PRICE, THE CONTRACTOR SHALL NOT PROCEED WITH THE
<br />REVISED WORK WITH❑UT PRIOR WRITTEN APPROVAL BY THE OWNER OF THE COST OF THE REVISED WORK,
<br />32, IF ELECTRICAL CONTRACTOR, HAS QUESTIONS, OR IN THEIR OPINION FIND ❑MISSIONS OR
<br />ERRORS ON ELECTRICAL DOCUMENTS IT IS THERE RESPONSIBILITY TO BRING THIS TO THE
<br />ATTENTION OF THE ENGINEER/❑WNE� IMMEDIATELY,
<br />EQUIPMENT C❑NNECTI❑N NOTES:
<br />1, ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE EQUIPMENT SUPPLIER FOR EXACT REQUIREMENTS AND/OR
<br />EQUIPMENT TO BE INSTALLED, PRIOR TO R❑UGH-IN, VERIFY L❑CATION, CONNECTION PINT AND MOUNTING
<br />HEIGHTS, CONTACT ENGINEER FOR DIRECTIVES IF CONFLICT OCCURS, ELECTRICAL CONTRACTOR
<br />SHALL MAKE ALL CONNECTIONS REQUIRED AND ENSURE PROPER OPERATION OF EQUIPMENT, THE SCHEDULE
<br />IS INFORMAI❑N ONLY, VERIFY ALL INFORMATION WITH SUPPLIER'S PLANS,
<br />2, ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO PR❑VIDE CORRECT, ACCURATE ELECTRICAL SERVICE TO
<br />ALL LIGHTING AND POWER CIRCUITRY, INCLUDING FEEDERS TO UTILITY AND LOCAL TRANSFORMERS, AND ALL
<br />SWITCHES AND PANELB❑ARDS, CONTRACTORS SHALL BE RESPONSIBLE FOR SHORT CIRCUIT AND VOLTAGE DROP
<br />MAKE NECESSARY FIELD CHANGES BASED ON THESE CALULATI❑NS, CONTACT ENGINEER IMMEDIATELY WHERE
<br />THERE IS A CHANGE TO THE CONSTRUCTION DOCUMENTS,
<br />ELECTRICAL FIXTURE SCHEDULE
<br />LIGHTING
<br />POWER
<br />SYMBOL
<br />DESCRIPTION
<br />SYMBOL
<br />DESCRIPTION
<br />CEILING MOUNTED
<br />120V DUPLEX RECEPTACLE
<br />-'
<br />LIGHT FIXTURE
<br />MOUNTED 18' AFF
<br />WALL MOUNTED
<br />„GFI
<br />120V DUPLEX RECEPTACLE
<br />LIGHT FIXTURE
<br />P
<br />GROUND TINTERRUPTER
<br />FAULT
<br />P
<br />EXTERIOR
<br />N
<br />HGIR(EA
<br />OUAFF RECEPTACLE
<br />MNTDUPLEX'
<br />Z{
<br />FXTUEEWTHER)
<br />842
<br />WP
<br />LIGHTING
<br />�},GFI
<br />842
<br />120V DUPLEX RECEPTACLE
<br />MOUNTED 42' AFF
<br />FIXTURE(WEATHER)
<br />GROUND FAULT INTERRUPTER
<br />EXTERIOR WALL MOUNTED
<br />120V DUPLEX RECEPTACLE
<br />WALLPAK LIGHTING FIXTURE
<br />AFI
<br />MOUNTED 18' AFF
<br />FAULT INTERRUPTER
<br />(WEATHER)
<br />ARC
<br />250W, METAL HALIDE LOBAY
<br />ENDURALUME V
<br />240V RECEPTACLE
<br />OREQUAL
<br />MOUNTED 18' AFF
<br />EMERGENCY LIGHTING
<br />RECHARGABLE BATTERY
<br />BATHROOM EXHAUST FAN
<br />CEILING MOUNTED
<br />FEED FROM LIGHT CKT,
<br />EMERGENCY LIGHTING
<br />BATHROOM EXHAUST FAN
<br />RECHARGABLE BATTERY
<br />w/LIGHT FIXTURE
<br />FEED FROM LIGHT CKT,
<br />EXIT
<br />EXIT EXIT
<br />EXIT LIGHTING w/❑PT
<br />DIRECTIONAL SYMBOL
<br />®
<br />ELECTRICAL PANEL
<br />A� L T
<br />LOCATION
<br />EXIT
<br />CH
<br />LIGHTSWITCH
<br />TELEPHONE TERIMAL CABINET
<br />AFF
<br />3
<br />TWO-WAY LIGHTSWITCH
<br />®
<br />CEILING MOUNTED
<br />FL❑URSCENT LIGHT FIXTURE
<br />MOUNTED 42' AFF
<br />Ar-� 1;5=L
<br />c�f"jT►'-��-5� S7 � 1�.t� -�;� i2.19 ►� �ti: i �-'S7'I'" �' /
<br />25' 5,
<br />�x%%111l1111 E L 7- °°
<br />����,• • •� C ENS'•.
<br />• 08
<br />i I
<br />00
<br />'Vt;j%A L
<br />ELECTRICAL
<br />RICK GOLLHARDT - DRAFTSMAN
<br />813-781-3651
<br />rgolliordt@tampaba-y.rr.com
<br />I hereby certify that I have reviewed this plan and found it to be in
<br />compliance with ASCE 7-10 and the Florida Building Code 6th Edition 2017
<br />David W, Smith, P,E, #53608
<br />#53608
<br />D.W.SMITH,M.S.,P.E.#53608 LIGHTING
<br />FLORIDA PROFESSIONAL ENGINEER LICENSE NUMBER 53608
<br />PROJECTS ENGINEERING CONSULTANT
<br />9909 WALLASTON DRIVE-DADE CITY,FLORIDA 33525 SCALE
<br />PHONE, 352-521-0865 FAX, 352-521-0867 E-MAIL, dwsf Ipeeearthl Ink. net DO NOT SCAT
<br />DESIGN/DRAWN
<br />R. GOLLHARE
<br />29 AUG 2018
<br />CHECKED
<br />D.W.S.
<br />SHEET OF
<br />8OF9
<br />JOB NO.
<br />2018-50
<br />
|