Laserfiche WebLink
AUXILIARY DRAIN VALVE <br />(NOT TO SCALE) <br />GLOBE VALVE OR EQUAL <br />(1" NPT MINIMUM) <br />0'-6" NIPPLE AND <br />CAP (NO PLUGS) <br />If ," fl II <br />END OF BRANCHLINE NOTE <br />RUN (OR EQUAL) AUX. DRAIN VALVES TO BE PROVIDED <br />ON 'TRAPPED' PIPING SECTIONS <br />CONTAINING MORE THAN 5 GALLONS <br />OF WATER. (PER NFPA 13) <br />INSPECTOR'S TEST <br />WET SYSTEM ASSEMBLY <br />(NOT TO SCALE) <br />ROOF DECK <br />DETAIL KEY NOTES <br />1. <br />1 " SCHED. 40 FROM SYSTEM. <br />J <br />2. <br />1" SCHED. 40 PIPE NIPPLE. <br />Of <br />3. <br />1" COMBINATION INSPECTOR'S TEST AND <br />0 <br />DRAIN VALVE WITH INTEGRAL PRESSURE <br />RELIEF VALVE. <br />w <br />F_ <br />4. <br />PIPE ESCUTCHEONS AND WATERPROOF <br />W <br />PENETRATION. <br />5. <br />1" GALVANIZED SCHED. 40 PIPE NIPPLE. <br />6. <br />45' ELBOW WITH REDUCING BUSHING AND <br />5.6K STANDARD COVERAGE SPRINKLER HEAD <br />WITH FRAME ARMS BROKEN OFF. <br />7. <br />SPLASH BLOCK. <br />8. <br />SIGHT GLASS. <br />o` <br />0 <br />a.l <br />1�1►1f`yGl��7 <br />PIPE SUPPORT - TYPE S16 <br />'SAMMY SUPER SCREW' W/ RING HANGER <br />(NOT TO SCALE) <br />'Z' PURLIN <br />PROVIDE HEX NUT FOR <br />PULL-OUT RESISTANCE <br />"SAMMY SUPER SCREW" MODEL <br />SDWR - INSTALLED WITH <br />RECOMMENDED NUT DRIVER <br />PLATED FERROUS <br />-THREAD ROD <br />MINIMUM SIZE <br />)UIREMENTS BELOW <br />+ PIPE <br />(4" MAX.) <br />ALL THREAD ROD SIZES <br />PIPE SIZES 1" - 4" -- ROD SIZE = 3/8" <br />um <br />SAMMY SUPER SCREW MODELS <br />SWDR 1" & SWDR 1%" ARE FM <br />APPROVED FOR PIPE SIZES UP TO 4" <br />TYPICAL GOOSENECK ARMOVER <br />(NOT TO SCALE) <br />SEE PLAN FOR ACTUAL <br />ARMOVER DIMENSIONS <br />L SEE PLAN VIEW FOR --_e_ _ ._ --_—__—_—___— <br />RELATIVE BRANCH LINE <br />AND MAIN ELEVATIONS <br />BRANCH LINE <br />TEE OR 90' ELL <br />SCH 40 DROP NIPPLE <br />CUT LONG, FIELD CUT TO <br />FINAL CEILING ELEVATION <br />CEILING ELEVATION <br />PIPE SUPPORT - TYPE S01 <br />TOP BEAM CLAMP W/ RING HANGER <br />(NOT TO SCALE) <br />STEEL BAR JOIST <br />OR BEAM <br />PLATED FERROUS <br />.-THREAD ROD <br />MINIMUM SIZE <br />)UIREMENTS BELOW <br />PIPE <br />ALL THREAD ROD SIZES <br />PIPE SIZES 1" - 4" -- ROD SIZE = 3/8" <br />PIPE SIZES 5" - 8" -- ROD SIZE = 1/2" <br />PIPE SUPPORT - TYPE T03 <br />TRAPEZE USING TBCs W/ RING HANGERS <br />(NOT TO SCALE) <br />UL LISTED TOP BEAM <br />CLAMP W/ LOCK NUT <br />-TYPICAL - <br />STEEL BAR <br />JOIST OR BEAM <br />INVERTED TBC <br />TO PREVENT <br />SLIPPING <br />TRAPEZE MEMBER <br />SEE CHART BELOW <br />PIPE <br />SIZE <br />"A' <br />MAX. <br />TRAPEZE <br />MEMBER <br />UL LISTED SWIVEL <br />RING HANGER (TWO <br />TYPICAL). WHEN <br />SUPPORTING PIPE <br />SIZES LARGER THAN <br />TRAPEZE MEMBER <br />PIPE SIZE, PROVIDE <br />' <br />HANGER RINGS. HEAVY DUTY" <br />ALL THREAD <br />PIPE SIZES <br />PIPE SIZES <br />+ <br />ROD <br />1" - <br />5" - <br />CAD PLATED FERROUS <br />ALL -THREAD ROD SEE <br />MINIMUM SIZE <br />REQUIREMENTS BELOW <br />UL LISTED SWIVEL <br />RING HANGER <br />PIPE <br />SIZES <br />4" -- ROD SIZE = 3/8" <br />8" -- ROD SIZE = 1/2" <br />1 <br />8'-0" <br />2" SCH. 40 PIPE <br />1 1/4 <br />8'-0" <br />2" SCH. 40 PIPE <br />1 1/2 <br />8'-0" <br />2" SCH. 40 PIPE <br />2 <br />8'-0" <br />2" SCH. 40 PIPE <br />2 1/2 <br />7'-0" <br />2" SCH. 40 PIPE <br />2 1/2 <br />8'-0" <br />2 1/2" SCH. 40 PIPE <br />3 <br />6'-0' <br />2" SCH. 40 PIPE <br />3 <br />W-0" <br />2 1/2" SCH 40 PIPE <br />4 <br />5'-0' <br />2' SCH. 40 PIPE <br />4 <br />8'-0" <br />2 1/2" SCH 40 PIPE <br />6 <br />3'-O" <br />2" SCH. 40 PIPE <br />s <br />5'-0" <br />2 1/2' SCH. 40 PIPE <br />6 <br />7'-0" <br />2 1/2' SCH. 40 PIPE <br />6 <br />10'-0" <br />3" SCH. 40 PIPE <br />PIPE SUPPORT <br />TRAPEZE USING TBCs W/ RING HANGERS <br />(NOT TO SCALE) <br />IV PURLIN <br />"SAMMY SUPER SCREW" MODEL <br />SDWR - INSTALLED WITH <br />RECOMMENDED NUT DRIVER <br />FOR PIPE SIZES 4" AND <br />SMALLER. <br />INVERTED TBC <br />TO PREVENT <br />SLIPPING <br />TRAPEZE MEMBER <br />SEE CHART BELOW <br />PIPE <br />SIZE <br />"A" <br />MAX. <br />TRAPEZE <br />MEMBER <br />4 <br />5'-0" <br />2" SCH. 40 PIPE <br />4 <br />8'-0" <br />2 1/2' SCH 40 PIPE <br />6 <br />3'-0" <br />2" SCH. 40 PIPE <br />6 <br />5'-0- <br />2 1/2' SCH. 40 PIPE <br />6 <br />7'-0' <br />2 1/2' SCH. 40 PIPE <br />6 <br />10'-0" <br />3" SCH. 40 PIPE <br />1/2" BOLT AND <br />WASHER ARRANGEMENT <br />1/2" EYE ROD 1/2' CAD -PLATED COUPLING <br />1/2" CAD PLATED FERROUS <br />ALL -THREAD ROD <br />NOTE: <br />I USE EYE ROD <br />ATTACHMENT TO <br />+ + + PURLINS FOR PIPES <br />6" AND LARGER IN <br />DIAMETER. <br />CAD PLATED FERROUS <br />ALL -THREAD ROD SEE <br />MINIMUM SIZE <br />REQUIREMENTS BELOW <br />UL LISTED SWIVEL <br />RING HANGER <br />+ PIPE <br />ALL THREAD ROD SIZES <br />PIPE SIZES 1" - 4" -- ROD SIZE = 3/8" <br />PIPE SIZES 5" - 8" -- ROD SIZE = 1/2" <br />AUTOMATIC AIR VENT <br />(NOT TO SCALE) <br />AUTOMATIC AIR VENTING NOTES <br />1). ONLY A SINGLE AIR VENT IS <br />REQUIRED PER NFPA 13. <br />2). THE VENT SHALL BE INSTALLED <br />NEAR A HIGH POINT IN THE <br />SYSTEM. (EX. TOP OF A <br />VERTICAL RISER, ELEVATED <br />BRANCHLINE, AND UNDER ROOF <br />PEAKS.) <br />RECOMMENDED INSTALLATION: <br />1). SHOULD BE INSTALLED OFF THI <br />TOP OF HORIZONTAL PIPING. <br />2). DO NOT INSTALL AIR VENT OFF <br />THE BOTTOM OR SIDE OF <br />HORIZONTAL PIPING. <br />3). SHOULD BE INSTALLED NEAR <br />THE END OF SYSTEM BRANCH <br />LINES, WHENEVER POSSIBLE. <br />4). SHOULD BE INSTALLED OVER <br />AREAS WITHOUT CEILINGS, <br />ABOVE LAY -IN CEILINGS, OR <br />ABOVE AN ACCESS PANEL. <br />3/4" NPT OUTLET. <br />AGF MODEL 7900V STANDARD DRAIN <br />IS SHOWN. LINE MAY BE <br />INSTALLED. <br />SPRINKLER BRANCHLINE <br />PIPE. SEE PLANS FOR SIZE <br />STABLE <br />:E VALVE WITH <br />CONNECTION <br />SCOPE OF WORK <br />ADD AUTOMATIC FIRE PROTECTION SYSTEM DESIGNED IN COMPLIANCE WITH THE HATCHER ENGINEERING FOR DRAWINGS AND <br />APPLICABLE STANDARDS LISTED WITHIN THESE DOCUMENTS. <br />ACCEPTANCE TEST CRITERIA <br />SHALL COMPLY WITH NFPA-13. SPRINKLER SYSTEM SHALL BE PROPERLY INSPECTED AND MAINTAINED IN ACCORDANCE WITH NFPA-25 <br />STANDARD FOR INSPECTION, TESTING, AND MAINTENANCE OF WATER BASED SYSTEM. <br />HAZARD CLASSIFICATION <br />CLASSIFICATION: PER FOR DOCUMENTS. <br />APPLICABLE NFPA STANDARDS TO BE APPLIED <br />FLORIDA BUILDING CODE (7TH EDITION), FLORIDA FIRE PREVENTION CODE (7TH EDITION), AND THE FOLLOWING CODES AS ADOPTED BY THE <br />FLORIDA FIRE PREVENTION CODE: <br />NFPA 13 (2016 EDITION) <br />NFPA 25 (2017 EDITION) <br />STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS <br />THERE IS A LIVE AND DEAD LOAD ALLOWANCE FOR FIRE PROTECTION SYSTEM RUNNING IN THE CEILING OF THE STRUCTURE. REFER TO <br />STRUCTURAL FOR FURTHER INFORMATION. <br />FIRE ALARM SYSTEM <br />REFER TO ELECTRICAL DOCUMENTS FOR ALARMING REQUIREMENTS. <br />FLOW TEST DATA: <br />CURRENT FLOW TEST IS PROVIDED ON THE HYDRAULIC REFERENCE SITE PLAN. <br />VALVING AND ALARM REQUIREMENTS TO MINIMIZE POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF WATER: <br />THE FIRE SUPPRESSION SYSTEM FOR THIS FACILITY IS SUPERVISED AND REPORTS SYSTEM STATUS (WATER FLOW, TAMPER SWITCHES, <br />PRESSURE SWITCHES, ETC) TO A MONITORED ALARM PANEL. <br />BACKFLOW PREVENTION AND METERING SPECIFICATIONS <br />THE BACKFLOW PREVENTION DEVICE ASSEMBLY AND METERING EQUIPMENT IS EXISTING TO REMAIN. <br />QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD AND INTERIOR FIRE PROTECTION COMPONENTS <br />ALL NEW INTERIOR FIRE PROTECTION EQUIPMENT SHALL BE UL LISTED AND/OR FM APPROVED. <br />1 <br />3- 41'-1" 40 <br />31/2�- 4{1-3 40 1 <br />2fi 0a. pa Galvalume <br />.5'-0 511C <br />LIRE SPRINKLER RISER DETAIL <br />6" DI STUB —UP X 6" STEEL RISER <br />1 � ad <br />F <br />V, <br />A <br />nw0 <br />MATERIAL DESCRIPTION <br />ITEM DESCRIPTION <br />1 6' 120 VAC ELECTRIC BELL W/ WEATHERPROOF BOX <br />2 6" VANE -TYPE WATER FLOW SWITCH <br />3 6' RISER CHECK VALVE <br />4 6' GROOVED BUTTERFLY VALVE <br />5 2' ANGLE VALVE (MAIN DRAIN LINE) <br />RISER GENERAL NOTES: <br />1). ALL OUTSIDE STEEL PIPING EXTENDING THROUGH THE <br />EXTERIOR WALL SHALL BE GALVANIZED WITH GALVANIZED <br />FITTINGS. <br />2). ALL GROOVED COUPLINGS SHALL BE OF THE "RIGID" TYPE. <br />3). ALL DIMENSIONS SHOWN ARE CENTER -TO -CENTER <br />DIMENSIONS AND SHALL BE FIELD VERIFIED BEFORE <br />FABRICATION AND INSTALLATION. <br />4). ALL ELECTRICAL WIRING SHALL BE PERFORMED BY OTHERS. <br />5). INSTALL ELECTRIC BELL ON OUTSIDE WALL <br />6). PIPE DIMENSIONS SHOWN ARE FOR THE VALVES AND <br />DEVICES SPECIFIED USING STANDARD GROOVED FITTINGS. <br />O m HYDRAULIC NODE POINT <br />2' MAIN DRAIN SHALL BE <br />PIPED TO OUTSIDE BUILDING <br />WALL. SUPPLY GALVANIZED <br />PIPING THROUGH WALL WITH <br />2" PIPE ESCUTCHEONS BOTH <br />SIDES OF WALL <br />1 <br />I <br />� <br />� <br />I <br />u�' I <br />FINISHED FLOOR <br />$p <br />OI <br />�z <br />I�B <br />W <br />w <br />�Z <br />W I <br />Ix <br />is <br />I� 1 <br />�I <br />1 <br />( <br />AS <br />1 <br />ELL AT BASE OF RISER SHALL BE <br />- <br />RESTRAINED PER NFPA 24 <br />SCALE: 1/2" = V-0 <br />Qt" <br />12 <br />FIRE SPRINKLER SECTION <br />SCALE: N.T.S. <br />A <br />�H400O <br />C4 <br />N <br />p cp <br />w q0 �W <br />p►����11 <br />Fs� r-III co <br />F� 0 r_� <br />A <br />d <br />C\Z <br />� <br />W <br />O <br />w <br />F� <br />I-+-i <br />I� <br />co <br />F- 4 co <br />co <br />1-i4 <br />O <br />� � <br />U� w o <br />x <br />rW p <br />0 <br />3 <br />03 <br />ca <br />A co Lv <br />0 <br />--I <br />Nco <br />Z <br />U <br />O <br />v <br />co <br />0 <br />W <br />O <br />N <br />lro E <br />PERMIT No:N / A <br />CONTRACT No:C24-014 <br />APPROVAL: JMD <br />DRAWN BY: JMD <br />SCALE: AS NOTED <br />DATE: 3/1 /24 <br />FIRE PROTECTION <br />FLOOR PLAN <br />SEE HEAD SCHEDULE FOR <br />FIRE SPRINKLER FINISH <br />AND HEAD TYPE <br />FP- 2 <br />--- <br />